Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Specifier's comments:
1 Anchor Design
1.1 Input data
Baseplate
CBFEM
: lx x ly x t = 350.0 mm x 360.0 mm x 12.0 mm;
CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Group anchor ID
1-4
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Group anchor ID
1-4
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
1.5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.256 0.050 2.000 7 OK
concrete 1.136 0.221 1.500 132 not recommended
a a
bN + bV <= 1
1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid baseplates as per current regulations (ETAG 001/Annex C, EOTA TR029,
etc.). This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the baseplate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the
minimum required baseplate thickness with CBFEM to limit the stress of the baseplate based on the assumptions explained above. The
proof if the rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The anchor design methods in PROFIS Engineering require rigid baseplates, as per current regulations (AS 5216:2021, ETAG 001/Annex
C, EOTA TR029 etc.). This means that the baseplate should be sufficiently rigid to prevent load re-distribution to the anchors due to
elastic/plastic displacements. The user accepts that the baseplate is considered close to rigid by engineering judgment."
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Hilti HST3 stud anchor with 120 mm embedment, M20 hef2, Steel galvanized, installation per ETA 98/0001, with annular gaps filled with Hilti
Filling Set or any suitable gap solutions
0.0
y
175.0 175.0
35.0
3 4
100.0
180.0
100.0
1 2
x
225.0
180.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
2 Baseplate design
2.2 Summary
Description Profile Stiffeners Baseplate Welds [%] Concrete
[%]
sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] Hole bearing
[%]
1 Combination 206.42 0.00 190.36 0.00 237.43 0.00 3 81 92
1
2.3 Baseplate plate classification
Results below are displayed for the decisive load combinations: Combination 1
Anchor tension forces Equivalent rigid baseplate (CBFEM) Component-based Finite Element Method
(CBFEM) baseplate
Anchor 1 13.513 kN 17.736 kN
Anchor 2 13.391 kN 16.509 kN
Anchor 3 14.312 kN 22.740 kN
Anchor 4 14.189 kN 21.474 kN
User accepted to consider the selected baseplate as rigid by his/her engineering judgement. This means the anchor design guidelines can be
applied.
2.4 Profile/Stiffeners/Plate
Profile and stiffeners are verified at the level of the steel to concrete connection. The connection design does not replace the steel design for
critical cross sections, which should be performed outside of PROFIS Engineering.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Results
Part Load Material sEd [N/mm²] ePl [%] fy [N/mm²] gM0 fy/gM0 elim [%] Status
combination [N/mm²]
Plate Combination S 275 237.43 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 150.47 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 148.03 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 206.42 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 119.73 0.00 275.00 1.00 275.00 5.00 OK
1
Stiffenera Combination S 275 190.36 0.00 275.00 1.00 275.00 5.00 OK
1
Stiffenerb Combination S 275 159.97 0.00 275.00 1.00 275.00 5.00 OK
1
275.00 N/mm²
0.00 N/mm²
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
5.00%
0.00%
2.4.2 Hole bearing
Decisive load combination: 1 - Combination 1
Plate hole bearing resistance, EN1993-1 - 8 section 3.6.1:
Equations
k1 ab fu d t
Fb,Rd =
gM2
VEd
Utilisation =
Fb,Rd
Variables
k1 ab fu [N/mm²] d [mm] t [mm] gM2
Anchor 1 2.50 1.00 430.00 20.0 12.0 1.25
Anchor 2 2.50 1.00 430.00 20.0 12.0 1.25
Anchor 3 2.50 0.53 430.00 20.0 12.0 1.25
Anchor 4 2.50 0.59 430.00 20.0 12.0 1.25
Results
VEd [kN] Fb,Rd [kN] Utilisation [%] Status
Anchor 1 3.340 206.400 2 OK
Anchor 2 1.495 206.400 1 OK
Anchor 3 3.003 109.623 3 OK
Anchor 4 1.435 121.220 2 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
2.5 Welds
Profiles are modelled without taking the corner radius into account. Special rules for welding (e.g. for cold-formed profiles ...) are not taken into
account by the software.
Equations
Results
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilisation [%] Utilisationc [%] Status
Member 1-tfl 1 255.41 404.71 309.60 81 27 OK
Member 1-bfl 1 264.13 404.71 309.60 78 26 OK
Member 1-w 1 189.22 404.71 309.60 47 31 OK
Member 1-w 2 257.54 404.71 309.60 64 44 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Equations
Results
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilisation [%] Utilisationc [%] Status
Stiffenera 150.62 404.71 309.60 38 14 OK
Stiffenera 1 154.27 404.71 309.60 39 18 OK
Stiffenerb 152.17 404.71 309.60 38 17 OK
Stiffenerb 1 150.33 404.71 309.60 38 14 OK
2.6 Concrete
Decisive load combination: 1 - Combination 1
According to EN1992-1-1 section 6.7(4), the concrete should have sufficient reinforcement to take into account the tensile forces that develop
due to the fixture attachment. The definition of the reinforcement in the concrete is not within the scope of PROFIS Engineering.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
0.00 N/mm²
2.6.2 Verification of compression in concrete under the baseplate around the profile as per EN1992-1 section 6.7 and EN1993-1-8,
section 6.2.5
Equations
fjd
bj kj acc fck
=
gc
N
s = Aeff
Utilisation =
s
fjd
Variables
N [kN] Aeff [mm²] bj kj acc fck [N/mm²] gc
84.587 9,709 0.67 1.00 0.85 25.00 1.50
Results
s [N/mm²] fjd [N/mm²] Utilisation [%] Status
8.71 9.49 92 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
13
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
2.8 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
baseplate may not behave rigidly. Please, have the results validated by a professional designer and/or structural engineer to ensure
suitability and adequacy for your specific jurisdiction and project requirements.
● The anchor is modelled considering stiffness values determined from load displacement curves tested in an independent laboratory.
Please note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution
results.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
14
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
3 Summary of results
Design of the baseplate, anchor, welds and other elements are based on CBFEM (component based finite element method) and Eurocode
regulations.
Load combination Max. utilisation Status
Anchors Combination 1 132% NOT OK
Baseplate Combination 1 87% OK
Welds Combination 1 81% OK
Stiffeners Combination 1 70% OK
Concrete Combination 1 92% OK
Profile Combination 1 76% OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
15
Hilti PROFIS Engineering 3.0.82
www.hilti.com.sg
Company: Page: 16
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 80637_Typical Connection_R1 Date: 27/12/2022
Fastening Point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
16