DESIGN CRITERIA

LOADINGS
A. DEAD LOAD
CONCRETE - 23.56 kN/m3
STEEL - 76.93 kN/m3
150MM THK. CHB WALL W/ PLASTER - 3.11 kN/m3
100MM THK. CHB WALL W/ PLASTER - 2.98 kN/m3
B. LIVE LOAD
ROOF - 1.00 kPa
CLASSROOM - 1.90 kPa
TOILETS - 2.40 kPa
CORRIDORS - 4.80 kPa
C. WIND LOAD (WL)
DESIGN WID PRESSURE (P) SHALL BE COMPUTED AS FOLLOWS
WHERE:
BASIC WIND SPEED V = 290 kph = 80.56 m/s, FIGURE 207A.5-1C NSCP 2015
IMPORTANCE FACTOR Iw = 1.00
EXPOSURE CATEGORY = EXPOSURE C
VELOCITY PRESSURE qz = 0.613 Kz Kzt Kd V2 I , EQ. 207B.3-1
Kd = WIND DIRECTIONALITY FACTOR, SECTION 207A.6 NSCP 2015
Kz = VELOCITY PRESSURE EXPOSURE COEFFICIENT, SECTION 207B.3.1
Kzt = TOPOGRAPHIC FACTOR, SECTION 207A.8.2 NSCP 2015
= (1 + K1 K2 K3)2
WHERE K1, K2, AND K3 ARE GIVEN IN FIG. 207A.8-1
DESIGN WIND PRESSURE P = q G Cp – qi (GCpi) , EQ. 207B.4-1
WHERE:
q = qz FOR WINDWARD WALL AT HEIGHT Z ABOVE THE GROUND
qh = qh FOR LEEWARD WALLS, SIDE WALLS, AND ROOFS, AT MEAN
DDDDDHEIGHT
qi = qh FOR WINDWARD WALLS, SIDE WALLS, LEEWARD WALLS, AND
DDDDDROOF OF ENCLOSED BUILDINGS AND FOR NEGATIVE INTERNAL
DDDDDPRESSURE EVALUATION IN PARTIALLY ENCLOSED BUILDINGS.
G = GUST-EFFECT FACTOR, SECTION 207A.9
Cp = EXTERNAL PRESSURE COEFFICIENT, FIG. 207B.4-1, 207B.4-2
DDDDDAND 207B.4-3
GCpi = INTERNAL PRESSURE COEFFICIENT, TABLE 207A.11-1
D. EARTHQUAKE
SEISMIC IMPORTANCE FACTOR, I = 1.5 TABLE 208-1, NSCP 2015
SOIL PROFILE TYPES, ISD = STIFF SOIL PROFILE TABLE 208-2, NSCP 2015
SEISMIC ZERO FACTOR, ZI = 0.4 (ZONE 4) TABLE 208-3, NSCP 2015
NEAR-SOURCE FACTOR, iNa = 1.0 TABLE 208-5, NSCP 2015
NEAR-SOURCE FACTOR, iNv = 1.0 TABLE 208-6, NSCP 2015
SEISMIC COEFFICIENT, iCa = 0.44Na TABLE 208-7, NSCP 2015
SEISMIC COEFFICIENT, iCv = 0.64Nv TABLE 208-8, NSCP 2015
DESIGN BASE SHEAR, iVii = (Cv I/RT)W EQUATION 208-8, NSCP 2015
≤ (2.5Ca I/R)W EQUATION 208-9
> (0.11Ca I W) EQUATION 208-10
> (0.8ZNv I/R)W EQUATION 208-11

Rii = 8.5 = NUMERICAL COEFFICIENT REPRESENTATIVE OF THE


IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIINHERENT OVER-STRENGTH AND GLOBAL
DUCTILITY OF IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIILATERAL-FORCE-
RESISTING SYSTEMS, AS SET FORTH IN
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIITABLE 208-11 OR TABLE 208-12.
Tii = Ct(hn)3/4 EQUATION 208-12, NSCP 2015
WHERE:
Ct = 0.0731 FOR REINFORCED CONCRETE MOMENT-RESISTING FRAMES
============AND ECCENTRICALLY BRACED FRAMESii
hn = HEIGHT IN METERS ABOVE THE BASE TO LEVEL
Project Name
DESIGN STRESSES
A. CONCRETE
COMPRESSIVE STRENGTH @ 28 DAYS f’c = 20.7 MPa (3000 psi)
B. REINFORCING BARS
a. FOR BARS 16MM DIA. AND GREATER fy = 275 MPa (40,000 psi)
b. FOR BARS LESS THAN 16MM DIA. fy = 230 MPa (33,000 psi)
C. STRUCTURAL STEEL ASTM-A36
FOR TRUSSES, BRACINGS, & STRUTS fy = 248 MPa (36,000 psi)
D. PURLINS
COLD FORMED LIGHT GAGE SHAPES fy = 248 MPa (36,000 psi)
E. MASONRY UNITS (CHB)
NON-LOAD BEARING CHB WALLS f’m = 3.45 MPa (500 psi)
F. WELDS-USED E-60xx ELECTRODE
G. STRUCTURAL BOLTS, ASTM-A307
a. Ft = 96.60 MPa (14,000 psi) b. Fv = 69 MPa (10,000 psi)

FOUNDATION
ASSUMED SOIL BEARING CAPACITY SHALL BE 96 KPa (2,000 psf)
1. IN CASE THE ACTUAL LOCATION OF THE STRUCTURE IS LESS THAN THE ASSUMED DISTANCE FROM THE SEISMIC SOURCE
OF 40 KM; NOTIFY THE DIRECTOR, BUREAU OF DESIGN FOR PROPER REVISION OF THE DESIGN. REFER TO THE SEISMIC
SOURCE MAP PROVIDED IN THE NATIONAL STRUCTURAL CODE OF THE PHILIPPINES OR PHIVOLCS SEISMIC SOURCE MAP.
2. SOIL TEST SHALL BE CONDUCTED PRIOR TO START OF CONSTRUCTION.
3. IN CASE THE ACTUAL SOIL BEARING CAPACITY IS FOUND LESS THAN THE ASSUMED, 96 kPa, NOTIFY THE DIRECTOR,
BUREAU OF DESIGN FOR PROPER REVISION OF FOUNDATION.
4. NO FOOTING SHALL REST ON FILL.
5. BOTTOM OF FOOTING SHALL BE AT LEAST 1.0 M BELOW NATURAL GRADE LINE.
6. SOIL BEARING CAPACITY SHALL BE INCREASED BY 33% WHEN IN COMBINATION WITH SEISMIC OR WIND LOAD.