DESIGN NOTES FOR STRUCTURAL ANALYSIS

PROPOSED 2-STOREY 8-CLASSROOM SCHOOL BUILDING


PROJECT NAME
LOCATION GENERAL SANTOS CITY

A. REFERENCE CODES

1. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP 2015)


2. AMERICAN INSTITUTE FOR STEEL CONSTRUCTION (AISC 360-16) WITH
SUPPLEMENTARY SEISMIC PROVISIONS
3. AMERICAN CONCRETE INSTITUTE (ACI 318-14M)
4. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE-SEI 7-10)
5. UNIFORM BUILDING CODE (UBC 1997)

B. LOADING SPECIFICATIONS AND PROVISIONS

B.1. DEAD LOADS

LOADINGS VALUE UNIT


CONCRETE 23.54 kN/cu.m.
STEEL 76.93 kN/cu.m.
150mm THK. CHB WALL 2.73 kN/sq.m.
100mm THK. CHB WALL 2.11 kN/sq.m.
MECHANICAL, ELECTRICAL, PLUMBING,
1.00 kN/sq.m.
ELECTRICAL UTILITIES
PARTITION LOAD 1.00 kN/sq.m.
FLOOR FINISHES 1.10 kN/sq.m.

B.2. LIVE/OCCUPANCY LOADS

LOADINGS VALUE UNIT


ROOF 1.00 kN/sq.m.
CLASSROOM 1.90 kN/sq.m.
TOILETS 2.40 kN/sq.m.
CORRIDORS ABOVE GROUND FLOOR, STAIRS 3.80 kN/sq.m.
CORRIDORS ON GROUND FLOOR 4.80 kN/sq.m.

Construction of 2-Storey 8-Classroom School Building


Republic of the Philippines
General Santos City
Office Of the City Engineer

DESIGN NOTES FOR STRUCTURAL ANALYSIS

PROPOSED 2-STOREY 8-CLASSROOM SCHOOL BUILDING


PROJECT NAME
LOCATION GENERAL SANTOS CITY

B.3. WIND LOAD PROVISIONS (BASED ON ASCE 7-10)

SPECIFICATION DATA
BASIC WIND SPEED (kmph) 250
IMPORTANCE FACTOR 1.50
EXPOSURE CATEGORY D
BUILDING CLASSIFICATION CATEGORY Category IV
STRUCTURE TYPE BUILDING
BUILDING HEIGHT (m) 9.23
ENCLOSURE CLASSIFICATION ENCLOSED

B.4. SEISMIC LOAD PROVISIONS (BASED ON UBC 1997)

SPECIFICATION DATA
OCCUPANCY CATEGORY Category I
SEISMIC ZONE 0.40
IMPORTANCE FACTOR 1.5
DUCTILITY FACTOR 8.50
SOIL PROFILE TYPE 4
DISTANCE TO NEAREST FAULT LINE 17.30
SPECIFIED FAULT LINE MAKILALA-MALUNGON
NEAR SOURCE FACTOR, Na 1.0
NEAR SOURCE FACTOR, Nv 1.0
Ct VALUE 0.0853

SEISMIC SOURCE MAP OF SITE

Construction of 2-Storey 8-Classroom School Building


Republic of the Philippines
General Santos City
Office Of the City Engineer

DESIGN NOTES FOR STRUCTURAL ANALYSIS

PROPOSED 2-STOREY 8-CLASSROOM SCHOOL BUILDING


PROJECT NAME
LOCATION GENERAL SANTOS CITY

C. DESIGN STRESSES

MATERIAL VALUE UNIT


CONCRETE
COMPRESSIVE STRENGTH @ 28 DAYS 3000.00 psi
REINFORCING BARS
FOR BARS 16 mm DIAMETER AND GREATER 275.00 kN/sq.m.
FOR BARS LESS THAN 16 mm DIAMETER 275.00 kN/sq.m.
STRUCTURAL STEEL (ASTM-A36)
FOR TRUSSES, BRACINGS, AND STRUTS 248.00 kN/sq.m.
COLD FORMED LIGHT GAUGE SHAPES 248.00 kN/sq.m.
MASONRY UNITS
NON-LOAD BEARING CHB WALLS 3.45 kN/sq.m.
LOAD BEARING CHB WALLS 6.89 kN/sq.m.

D. FOUNDATION PROVISIONS

SOIL BEARING CAPACITY 95.00 kN/sq.m.


126.35 kN/sq.m. **(WITH SEISMIC AND WIND LOAD)

1. IN CASE THE ACTUAL LOCATION OF THE STRUCTURE IS LESS THAN THE


ASSUMED DISTANCE FROM THE SEISMIC SOURCE OF 17.3 km, NOTIFY THE
STRUCTURAL ENGINEER, OR ANY REPRESENTATIVE ENGINEER FROM
THE OFFICE OF THE CITY ENGINEER FOR PROPER REVISION OF THE
DESIGN. REFER TO THE SEISMIC SOURCE MAP PROVIDED IN THE NSCP
OR PHIVOLCS SEISMIC SOURCE MAP.

2. NO FOOTING SHALL REST ON FILL.

Construction of 2-Storey 8-Classroom School Building


Republic of the Philippines
General Santos City
Office Of the City Engineer

DESIGN NOTES FOR STRUCTURAL ANALYSIS

PROPOSED 2-STOREY 8-CLASSROOM SCHOOL BUILDING


PROJECT NAME
LOCATION GENERAL SANTOS CITY

3. BOTTOM OF FOOTING SHALL FOLLOW THE MINIMUM DEPTH FROM THE


NATURAL GRADE LINE, AS PER PLAN, UNLESS SPECIFIED OTHERWISE.

4. SOIL BEARING CAPACITY SHALL BE INCREASED BY 33% WHEN IN


COMBINATION WITH SEISMIC OR WIND LOAD.