X3-Hybrid Series

User Manual
5.0kW - 15.0kW

EN
Copyright Declaration
The copy right of this manual belongs to SolaX Power Network Technology(Zhe jiang) Co. , Ltd.
ADD: No. 288 Shizhu Road, Tonglu Economic Development Zone, (SolaX Power Co. , Ltd. ) . Any corporation or individual should not plagiarize, partially or fully
Tonglu City, Zhejiang Province, China. copy (including software, etc. ) , and no reproduction or distribution of it in any form or by any
means. All rights reserved. SołaX Power Network Technology (Zhe jiang) Co. , Ltd. reserves the
Tel: + 0571- 5626 0011 right of nal interpretation. The contents are subject to change without prior notice.
E-mail: info@solaxpower.com
614.00498.02
Contents

Contents
1 Note on this Manual ................................................. 03
1.1 Scope of Validity .................................................................... 03
1.2 Target Group .......................................................................... 03
1.3 Symbols Used .......................................................................... 03
1.3.1 Important Safety Instructions............................................ 04
1.3.2ExplanationofSymbols...................................................... 09
 1.3.3 CE Directives........................................................................ 11

2 Introduction...................................................................... 12
2.1 Basic Features.........................................................................12
2.2 Electrical Block Diagram of The System.........................12
2.3 Work Modes .............................................................................. 15
2.4 Dimension................................................................................17
2.5 Terminals of Inverter .............................................................18

3 Technical Data .................................................................... 19


3.1 DC Input . ................................................................................... 19
3.2 AC Output/Input................................................................... 19
3.3 Battery ........................................................................................ 20
3.4 Efficiency, Safety and Protection ..................................... 20
3.5 EPS(Off-grid) Output ........................................................... 21
3.6 General Data ............................................................................ 21

4 Installation .............................................................................. 22
4.1 Check for Transport Damage ...................................................... 22
4.2 Packing List .................................................................................................. 22
4.3 Installation Precautions ..................................................................... 24
4.4 Tool Preparation ...................................................................................... 25
4.5 Installation Site Conditions ............................................................ 27
4.5.1 Installation Carrier Requirements ............................................. 27
4.5.2 Installation Requirements............................................................... 27
4.5.3 Installation Space Requirements................................................. 28
4.6 Mounting ...................................................................................................... 29

01
Contents Notes on this Manual

5 Electrical Connections ........................................................... 32 1 Notes on this Manual


5.1 PV Connection ......................................................................................... 32
5.2 Grid Port and EPS(Off-grid) Output Connection .......... 36 1.1 Scope of Validity
5.3 EPS(Off-grid) Block Diagram ......................................................... 37 This manual is an integral part of X3-Hybrid G4, it describes the
5.4 Battery Connection .............................................................................. 46 assembly, installation, commissioning, maintenance and failure of
5.5 Communication Connection ....................................................... 50 the product. Please read it carefully before operating.
5.5.1 Introduction to DRM Communication..................................... 50 X3-Hybrid-5.0-D X3-Hybrid-5.0-M X3-Hybrid-10.0-D X3-Hybrid-10.0-M
5.5.2 Introduction to Meter/CT Communication........................... 51
X3-Hybrid-6.0-D X3-Hybrid-6.0-M X3-Hybrid-12.0-D X3-Hybrid-12.0-M
5.5.3 Parallel Communication................................................................. 54
5.5.4 COM Communication...................................................................... 60 X3-Hybrid-8.0-D X3-Hybrid-8.0-M X3-Hybrid-15.0-D X3-Hybrid-15.0-M
5.5.5 Communication Connection Steps........................................... 62 Note: "X3-Hybrid" Series refers to the energy storage inverter that
5.6 Grounding (Mandatory) ....................................................................71 supports photovoltaic grid-connected.
5.7 Monitoring Connection .................................................................... 74
“5.0"means 5.0kW.
5.8 Check All Below Steps Before Starting Inverter .............. 76
“D" means "DC switch", "M" means externally connected.
5.9 Inverter Operation ................................................................................. 77
X3-Matebox, built-in DC switch, BAT circuit breaker, AC and EPS
(Off-grid)circuit breaker, which can reduce the cost of customers
6 Firmware upgrading...........................................................................................79 on accessory. And pre-installed wiring cables and device can get
grid of the complicated wiring work.
X3-Hybrid-15.0 complies with Thailand’s PEA/MEA grid-connected
7 Setting ......................................................................................... 83 regulations.
7.1 Control Panel ............................................................................ 83 Keep this manual available at any time.
7.2 Menu Structure ...................................................................... . 84
7.3 LCD Operation .......................................................................................... 85 1.2 Target Group
This manual is for quali ed electricians.The tasks described in this
manual only can be performed by quali ed electricians.
8 Troubleshooting ............................................................ 111 1.3 Symbols Used
8.1 Trouble Shooting ..................................................................111
The following types of safety instructions and general information
8.2 Routine Maintenance ......................................................... 117 appear in this document as described below:
Danger!
“Danger" refers to a dangerous situation that, if not
9 Decommissioning ........................................................ 118 avoided, will result in a high level of risk such as serious
9.1 Disassemble the Inverter ...................................................118 injury or even death.
9.2 Packaging ................................................................................118
9.3 Storage and Transportation ..............................................118 Warning!
9.4 Waste Disposal .......................................................................................118 “Warning" indicates a dangerous situation, which,
if not avoided, may result in serious injury or death.

Caution!
10 Disclaimer ....................................................................................... 119 “Caution” indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.

02 03
Safety Safety

Note! Warning!
“Note” provides tips that are valuable for the optimal
operation of our product. Before performing maintenance, cleaning or operation on
the circuit connected to the inverter, authorized
maintenance personnel must first disconnect the AC and
DC power supplies of the inverter.

Warning!
Danger!
The inverter can not be operated when it is running.
Danger to life due to high voltages in the inverter!
The personnel responsible for the installation, electrical
connection, debugging, maintenance and fault handling Warning!
operation of this product need to be trained, master the Risk of electric shock!
correct operation method, have the corresponding
electrician qualification and safety operation knowledge.

Strictly follow relevant safety specifications for product installation


and testing. During installation, operation or maintenance, please
Caution! read carefully and follow the instructions and precautions on the
When the inverter is working, it is strictly forbidden to inverter or user manual. If the operation is incorrect, it may cause
touch the shell. The temperature of the shell is high and personal and property losses. Please keep the user manual properly
there is a risk of scalding. after use.

This inverter can only use the accessories sold and recommended by
Caution! SolaX, otherwise it may cause fire, electric shock or casualties.
Without the authorization of our company, you may not open the
Radiation may be harmful to health! inverter cover or replace the inverter parts, otherwise the warranty
Do not stay for a long time and keep at least 20 cm away promise of the inverter will be invalid.
from the inverter.
The use and operation of the inverter must be carried out in
Note! accordance with the instructions in this manual, otherwise this
protection will fail and the warranty of the inverter will also fail.
Ground PV system. During working, the inverter surface temperature may exceed 60 °C ,
Finish PV modules and photovoltaic system grounding in please make sure the inverter cools down before touching, and
accordance with local requirements to achieve optimal make sure children can not touch.
protection of systems and personnel.
When exposed to sunlight, photovoltaic arrays generate dangerous
high DC voltages. Please follow our instructions, otherwise it will be
Warning! life-threatening.

Ensure that the input DC voltage is below the inverter limit. All DC and AC power sources must be disconnected from the
Excessive DC voltage and current may cause permanent inverter for at least 5 minutes before any wiring or electrical
damage or other losses to the inverter, which is not operation is performed on the inverter to ensure complete isolation
covered by the warranty. of the inverter and avoid electric shock.

04 05
Safety Safety

A photovoltaic module used on the inverter must have a IEC61730A If the building installed with external light protection device is far
rating, and the total open circuit voltage of the photovoltaic string / away from the inverter location, in order to protect the inverter from
array is lower than the maximum rated DC input voltage of the
inverter. Any damage caused by photovoltaic over voltage is not
electrical and mechanical damage, the inverter should also install an
covered by warranty. external lightning protection equipment.

Installation position should be away from wet environment and In order to protect DC system, two-stage surge protection equipment
corrosive substances. is needed between DC cable of inverter and photovoltaic equipment
module.
After the inverter and power grid cut off the PV power supply, there
will be a certain amount of residual current in a short time, be
cautious or it may lead to serious personal injury and even high risk In order to protect the AC system, the level 2 surge protection
of death. Use a multimeter (impedance at least1 MΩ) to measure the equipment should be installed at the AC output, located between
voltage between the UDC and the UDC- to ensure that the inverter the inverter and the grid. Installation requirements must comply with
port is discharged below the safe voltage before starting operation IEC61643-21 standard.
(35 VDC).
All DC cables shall be installed in a distance as short as possible, and
the positive and negative cables of the same input need to be
Ø Surge protection devices (SPDs) for PV installation bundled together to avoid causing loops in the system. Minimum
distance installation and binding requirements also apply to auxiliary
Warning! grounding and shielding grounding conductors.
Over-voltage protection with surge arresters should be
provided when the PV power system is installed.
The grid connected inverter is fitted with SPDs in both
PV input side and MAINS side. Ø Anti-lslanding Effect
The islanding effect means that when the power grid is cut off, the
Direct or indirect lightning strikes can cause failures. Surge is the main grid-connected power generation system fails to detect the power
cause of lightning damage to most devices. Surge voltage may occur outage and still supplies power to the power grid. This is very dangerous
at photovoltaic input or AC output, especially in remote mountain for the maintenance personnel and the power grid on the transmission
areas where long distance cable is supplied. line.

Please consult professionals before installing SPDs. X3-Hybrid G4 series inverter’s use active frequency offset method to
prevent islanding effect.
The external lightning protection device can reduce the in uence of
direct lightning strike, and the lightning protection device can release
surge current to the earth.

06 07
Safety Safety

Ø PE Connection and Leakage Current 1.3.2 Explanation of Symbols


• All inverter’s incorporate a certified internal Residual Current Monitoring This section gives an explanation of all the symbols shown on the inverter
(RCM) in order to protect against possible electrocution and fire hazard and on the type label.
in case of a malfunction in the PV array, cables or inverter.
There are 2 trip thresholds for the RCM as required for certification Symbols on the Inverter
(IEC 62109-2:2011).
The default value for electrocution protection is 30mA, and for slow
rising current is 300mA.

• The inverter, with built-in RCM, will exclude possibility of DC residual Operating Display
current to 6mA,thus in the system an external RCD (type A) can be used
(≥30mA).
Battery status
Warning!
High leakage Current! An error has occurred, please inform your installer immediately
Earth connection essential before connecting supply.

• A faulty ground connection can result in equipment failure, personal


Symbols on the Type Label
and death injuries, and electromagnetic interference.
• Ensure correct according to grounding to IEC62109 and conductor
Symbols
diameter according to STANDARD specification.
• Do not connect the grounding end of the equipment in series to CE mark.
prevent multi-point grounding. The inverter complies with the requirements of the
• Electrical appliances must be installed in accordance with the wiring applicable CE guidelines.
rules of each country.
Type Approved
Safety
Regular Production

For United Kingdom Sur veillance

www.tuv.com
TUV certified.
ID 1111227431

• The installation that connects the equipment to the supply terminals


shall comply with the requirements of BS 7671.
• Electrical installation of PV system shall comply with requirements of
RCM remark.
BS 7671 and IEC 60364-7-712.
• All protective devices cannot be changed.
• User shall ensure that equipment is so installed, designed and UKCA mark.
operated to maintain at all times compliance with the requirements of The inverter complies with the requirements of the
ESQCR22(1)(a). applicable UKCA guidelines.

Ø Battery Safety Instructions UKNI mark.


The inverter complies with the requirements of the
SolaX X3-Hybrid G4 Series inverter should pair with high voltage battery, applicable UKNI guidelines.
for the speci c parameters such as battery type, nominal voltage and
nominal capacity etc., please refer to section 3.3.

Please refer to the matching battery speci cation for details.

08 09
Safety Safety

1.3.3 EC Directives
SAA certification.
This chapter describes the requirements of the European low voltage
regulations, including safety instructions and system licensing
Beware of hot surface. conditions, the user must comply with these regulations when
The inverter can become hot during operation. Avoid installing, operating, and maintaining the inverter, otherwise it will
contact during operation. cause personal injury or death, and the inverter will cause damage.

Danger of high voltages. Please read the manual carefully when operating the inverter .If you do
Danger to life due to high voltages in the inverter! not understand "danger", "warning", "caution" and the description in the
manual, please contact the manufacturer or service agent before installing
and operating the inverter.
Danger.
Risk of electric shock! Grid-connected inverter comply with low voltage directive (LVD)
2014/35/EU and Electromagnetic compatibility directive (EMC)
2014/30/EU.Detection of components is based on:
Observe enclosed documentation. EN 62109-1:2010 ;
EN 62109-2:2011;
IEC 62109-1(ed.1) ;
The inverter can not be disposed together with the IEC62109-2(ed.1) ;
household waste. Disposal information can be found in the EN 61000-6-3: 2007+A:2011;
enclosed documentation. EN 61000-6-1: 2007 ;
EN 61000-6-2: 2005 ;
Do not operate this inverter until it is isolated from battery,
mains and on-site PV generation suppliers.
For installation in photovoltaic module system, it is necessary to
make sure that the whole system complies with the requirements of
Danger to life due to high voltage. There is residual voltage EC(2014/35/EU, 2014/30/EU, etc.) before starting the module (i.e. to
existing in the inverter after powering off, which needs 5 min start the operation).The assembly shall be installed in accordance
to discharge. Wait 5 min before you open the upper lid or with the statutory wiring rules .Install and configure the system in
the DC lid. accordance with safety rules, including the use of specified wiring
methods. The installation of the system can only be done by
professional assemblers who are familiar with safety requirements
and EMC. The assembler shall ensure that the system complies with
the relevant national laws.

The individual subassembly of the system shall be interconnected by


means of the wiring methods outlined in national/international such as
the national electric code (NFPA) No. 70 or VDE regulation 0107.

10 11
Installation Introduction

2 Introduction Diagram B: N line and PE line separate wiring, M series inverter ;


(For most countries)
2.1 Basic Features
PV 1
X3-Hybrid G4 series is a high-quality inverter that can convert solar PV 2
energy into alternating current and store energy into batteries. X3-Hybrid G4
The inverter can be used to optimize self-consumption, stored in CT
batteries for future use or fed into the public grid. The way it works Main Breaker/RCD
depends on user preferences. It can provide emergency power during BAT Grid EPS(Off-grid)
power outages. N

X3-Matebox
2.2 Electrical Block Diagram of The System E-BAR Grid
X3-Hybrid G4 series has two wiring schemes, one is for M series
inverter connected to X3-Matebox, and the other is for D series
inverter.

Breaker
Breaker
There are different ways of wiring in different countries, one is to
connect N line with PE line, the other is to separate the line from the Battery
EPS(Off-grid) loads Loads
PE line wiring, see below;
N-BAR for EPS(Off-grid) loads N-BAR for loads
Diagram A: N line and PE line separate wiring , D series inverter ;
(For most countries)
Diagram C: N line and PE line together, D series inverter;
PV 1 ( Applicable to Australia)
PV 2
X3-Hybrid G4
PV 1
CT
PV 2
Breaker Main Breaker/RCD X3-Hybrid G4
EPS(Off-grid) CT
BAT Grid
N Breaker CT 1 Main Breaker/RCD

BAT Grid EPS(Off-grid) CT 2


CT 3
N
Breaker
E-BAR Grid

RCD Breaker
E-BAR Grid
N
Breaker
Breaker

RCD

Battery
Distribution Box

Breaker
Breaker
EPS(Off-grid) loads Loads
Battery Distribution Box
N-BAR for EPS(Off-grid) loads N-BAR for loads EPS(Off-grid) loads Loads

N-BAR for EPS(Off-grid) loads N-BAR for loads

12 13
Introduction Introduction

Diagram D: N line and PE line together, M series inverter; 2.3 Work Modes
( Applicable to Australia)
X3-Hybrid G4 series, can be based on different needs, there are a variety
of models.
PV 1 Self Use
PV 2 The self-use mode is suitable for areas with low
X3-Hybrid G4 feed-in subsidies and high electricity prices.
CT
① When the power of PV is sufficient
Main Breaker/RCD
CT 1 Active Charging or Discharge time period: PV will
BAT Grid EPS(Off-grid) power the loads rstly, and surplus power will
CT 2
CT 3 charge to the battery.
N
N If the battery is fully charged, then sell the surplus
E-BAR power to the grid;( The inverter will limit the
E-BAR output if Feed-in limit or zero feed-in is needed )
X3-Matebox Grid

① (PV>Load, PV →Load→Battery → Grid)

② When the power of PV is insufficient
Active Charging time period: PV will power the

Breaker
Breaker

loads rstly ,the remaining power will be taken


from the grid , the battery will not discharge at
this time.
Battery EPS(Off-grid) loads Loads
(PV<Load, PV + Grid → Load)
Active Discharge time period: PV+BAT will power
N-BAR for EPS(Off-grid) loads N-BAR for loads the loads together. If the power is still not enough,
the remaining power will be taken from the grid.
(PV<Load, PV + Battery + Grid → Load)

③ Without PV power
Active Charging time period: The grid supplies the
loads and also can charge the battery;
(PV=0, Grid → Load + Battery)
Note! Active Discharge time period: The battery will
The RCD on the gure represents a leakage protection power the home loads rstly. If the battery power
device with a circuit breaker function. ②
is not enough ,the remaining power will be taken
① from the grid. The inverter will enter into the
standby state.
• When power cuts suddenly, the inverter connects the N
(PV=0, Battery+Grid → Load )
line of EPS(Off-grid) load with the ground through relay,
providing a xed zero potential for EPS(Off-grid) load and Battery min SOC can be set: 10%-100%;
ensuring the safety of electricity use by users. Charge battery to min SOC can be set:10%-100%.

• Please control the inverter load and make sure it is Feed-in priority
"output value" in "within " EPS(Off-grid) mode, otherwise
The Feed-in priority mode is suitable for areas with
the inverter will stop and alarm overload fault". high feed-in subsidies, but has feed-in power
limitation.
• Please confirm with the grid operator whether there are ① ①When the power of PV is sufficient
special regulations for grid connection. Active Charging time period: First, PV supply
power to the load, then charge the battery to the

set capacity, and then sell the power to the grid.

If the local grid company limits the grid-connected
power of the inverter, the excess energy continues
to charge the battery.
(PV> Load, PV → Load → Battery→ Grid → Battery)

14 15
Introduction Introduction

Feed-in priority EPS(Off-grid) mode


Active Discharge time period: PV will power the The EPS(Off-grid) is used when the power grid is off.
loads rstly,and surplus power will feed-in to the System will provides emergency power
grid. through PV and batteries to supply power to the
(PV> Load, PV → Load → Grid ) household loads.

(Battery must be installed for this mode)
②When the power of PV is insufficient ①When the power of PV is sufficient

Active Charging time period: PV will power the PV will power the loads rstly, and surplus power
loads rstly, the remaining power will be taken will charge to the battery.
② ①
from the grid. The battery will not discharge. ③
(PV>Load, PV → Load → Battery)
(PV< Load, PV + Grid → Load) ② ②When the power of PV is insufficient
The remaining power will be taken from the battery.
Discharge time period: PV+BAT will power the (PV<Load, PV → Load → Battery)
loads together. ③ Without PV power
If the power is still not enough, the remaining The battery will power the emergency loads until
power will be taken from the grid. the battery reached the min SOC, then the inverter
(PV< Load, PV + Battery + Grid → Load) will enter into the idle mode.
(PV=0, Battery → Load)
③Without PV power EPS(off-grid) SOC-min condition is adjustable within
Active Charging time period: The grid will power the range of 10%-25%.
the home loads and also charge the battery;
(PV=0 , Grid → Load + Battery) Note: in the case of grid connection, all working modes work normally when the battery
SOC >5%. When the battery charge rate is below 5%, the PV or Grid will first charge the
Active Discharge time period: The battery will battery SOC11%, and then return to the working mode selected by the user.
power the home loads rstly. If the battery power

is not enough, the remaining power will be taken

from the grid. The inverter will enter into the
standby state.
(PV=0, Battery+Grid → Load)

Battery min SOC can be set: 10%-100%; 2.4 Dimension


Charge battery to min SOC can be set:10%-100%.

Backup mode 503mm 199mm

The back-up mode is suitable for areas with


frequent power outages.
Same working logic with “Self-use” mode. This
① mode will maintain the battery capacity at a

503mm
relatively high level. (Users' setting) to ensure

that the emergency loads can be used when the
grid is off. Customers no need to worry about the
battery capacity.

Battery min SOC can be set:30%-100%.


Charge battery to min SOC can be set:30%-100%.

16 17
Introduction Technical Data

2.5 Terminals of Inverter 3 Technical Data


B C D E F G H 3.1 DC Input(apply to version D/M)
A
Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0

Max. recommended DC power [W] A:4000/B:4000 A:5000/B:5000 A:7000/B:5000 A:9000/B:6000 A:11000/B:7000 A:11000/B:7000

Max. DC voltage [V] 1000 1000 1000 1000 1000 1000


Nominal DC operating voltage [V] 640 640 640 640 640 640
SHUT

Operating voltage typical [V] 180-950 180-950 180-950 180-950 180-950 180-950

Upgrade/Dongle
Max. input current [A] 14/14 14/14 26/14 26/14 26/14 26/14

EPS(Off-grid) Max. short circuit current [A] 16/16 16/16 30/16 30/16 30/16 30/16
Start output voltage [V] 200 200 200 200 200 200
No. of MPP trackers 2 2 2 2 2 2
Strings per MPP tracker A:1/B:1 A:1/B:1 A:2/B:1 A:2/B:1 A:2/B:1 A:2/B:1

I M
J K L

Object Description 3.2 AC Output/Input(apply to version D/M)


A DC switch
Model X3-Hybrid-6.0 X3-Hybrid-8.0-M
X3-Hybrid-5.0 X3-Hybrid-6.0-M X3-Hybrid-8.0 X3-Hybrid-10.0-M
X3-Hybrid-10.0 X3-Hybrid-12.0-M
X3-Hybrid-12.0 X3-Hybrid-15.0-M
X3-Hybrid-15.0
B PV connection port X3-Hybrid-5.0-M

AC Output
C Battery connection port
Nominal AC power[ W ] 5000 6000 8000 10000 12000 15000(PEA 14000)
D USB port for upgrading Max. apparent AC power [ VA] 5500 6600 8800 11000 13200 15000

E Ethernet port Rated AC voltage [V] 415/240; 400/230; 380/220


Rated grid frequency [Hz] 50/60
F Battery communication
Max. AC current [A] 8.1 9.7 12.9 16.1 19.3 24.1
G Meter/CT Port
Displacement power factor 1 (0.8 leading...0.8 lagging)
H Grid connection port Total harmonic distortion(THDi) < 3%

Ground connection port AC Input


I
Rated AC power [W] 10000 12000 16000 20000 20000 20000
J Fans(only for X3-Hybrid-12.0-D/M and X3-Hybrid-15.0-D/M )
Rated grid voltage(range) [V] 415/240; 400/230; 380/220
K External monitoring connection port Rated grid frequency [Hz] 50/60

CAN are reserved ports / SHUT is a reserved port/ Max. AC current [A] 16.1 19.3 25.8 32.0 32.0 32.0
L
DRM Port(only for Australia)
M EPS(Off-grid) Output(main load connection port)

Warning!
Qualified electrician required for the installation.

18 19
Technical Data Technical Data

3.3 Battery(apply to version D/M) 3.5 EPS(Off-grid) Output(apply to version D/M)


Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0-M
X3-Hybrid-5.0-MX3-Hybrid-6.0-M X3-Hybrid-8.0 X3-Hybrid-10.0-M
X3-Hybrid-10.0 X3-Hybrid-12.0
X3-Hybrid-12.0-MX3-Hybrid-15.0
X3-Hybrid-15.0-M Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0
X3-Hybrid-5.0-MX3-Hybrid-6.0-M X3-Hybrid-8.0-MX3-Hybrid-10.0 X3-Hybrid-12.0
X3-Hybrid-10.0-M X3-Hybrid-15.0
X3-Hybrid-12.0-M X3-Hybrid-15.0-M

Battery type Lithium batteries EPS(Off-grid) rated power[VA] 5000 6000 8000 10000 12000 15000
Battery Full Voltage [V] 180-650 EPS(Off-grid) rated voltage [V] 400V/230VAC
Maximum charge/discharge flow [A] 30A Frequency[ Hz] 50/60
Communication interface CAN/RS485 EPS(Off-grid) rated current [A] 7.2 8.7 11.6 14.5 17.5 21.8
Reverse connection protection Yes EPS(Off-grid) Peak Power [VA] 7500, 60s 9000, 60S 12000, 60S 15000, 60S 15000, 60S 16500, 60S
Switching time [s] <10ms
Total harmonic distortion (THDv) <3 %

3.4 Efficiency, Safety and Protection(apply to version D/M)

Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0


X3-Hybrid-8.0-M X3-Hybrid-10.0
X3-Hybrid-10.0-MX3-Hybrid-12.0 X3-Hybrid-15.0
X3-Hybrid-5.0-MX3-Hybrid-6.0-M X3-Hybrid-12.0-M X3-Hybrid-15.0-M
3.6 Generic Data(apply to version D/M)
MPPT efficiency 99.9% 99.9% 99.9% 99.9% 99.9% 99.9%
European efficiency 97.7% 97.7% 97.7% 97.7% 97.7% 97.7% Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0
X3-Hybrid-5.0-MX3-Hybrid-6.0-M X3-Hybrid-8.0-MX3-Hybrid-10.0 X3-Hybrid-12.0
X3-Hybrid-10.0-M X3-Hybrid-15.0
X3-Hybrid-12.0-M X3-Hybrid-15.0-M

Maximum efficiency 98.2% 98.2% 98.2% 98.2% 98.2% 98.2% Dimensions (W/H/D)[mm] 503*503*199
Max. battery charge efficiency Dimensions of Packing (W/H/D)[mm] 560*625*322
(PV to BAT )(@ full load) 98.5% 98.5% 98.5% 98.5% 98.5% 98.5%
Net weight [kg] 30 30 30 30 30 30
Max. battery discharge efficiency Gross weight* [kg] 34 34 34 34 34 34
(BAT to AC)(@ full load) 97.5% 97.5% 97.5% 97.5% 97.5% 97.5%
Heat dissipation treatment Natural Cooling Smart Cooling
Security & Protection <45
Noise emission(typical) [dB] <40
DC SPD Protection Integrated
Storage temperature range [°C] -40~+70
AC SPD Protection Integrated
Operating temperature range[°C] -35~+60 (derating at 45)
Over/under voltage protection YES
Humidity [%] 0%~100%
Grid protection YES
Altitude [m] <3000
DC injection monitoring YES
Ingress Protection IP65
Back feed current monitoring YES
Protective Class I
Residual current detection YES
Cold standby consumption <5W
Anti-islanding protection YES
Over voltage category III(MAINS), II(PV, Battery)
Over load protection YES
Pollution Degree III
Over heat protection YES
Installation mode Wall mounted
Array insulation resistance detection YES
Inverter Topology Non-isolated
Communication interface Meter/ CT, external control RS485, Pocket series (optional), DRM, USB

* The specific gross weight is subject to the actual situation of the whole machine, which may be a little different due
to the influence of the external environment.

20 21
Installation Installation

4 Installation
Number Quantity Description
A 1 X3-Hybrid G4 series inverter.
4.1 Check for Transport Damage
B 1 Bracket
Ensure that the inverter is in good condition via transportation. If there
C☆ 1 Waterproof connector
is any visible damage such as cracks, please contact the dealer ☆
immediately. D 6 PV terminal (positive*3 , negative*3 )
E☆ 6 PV pin angle(positive*3 , negative*3 )

4.2 Packing List F☆ 12 10AWG European terminals


G☆ 1 OT terminal(inverter grounding)
Open the package and check the materials and accessories
H 5 (Expansion bolt, Gasket, Self-tapping bolt)
according to the following list.
I 1 M5 inner hexagon bolt
J 3 Communication line adapter (COM/Meter/BMS)
K 2 Battery connection terminals(positive*1, negative*1 )
L 5 RJ 45 terminals
A B C D M* 1 Manual
N 1 Quick Installation Guide
O 1 Warranty Card
P 1 Pocket WiFi
E F G H Q 1 Meter ( optional )
R 1 CT ( optional )

Note: The M series inverter in the accessory package does not include the “ C” \“ D” \“ E” \“ F”
and ”G“ accessories. The M series inverter must be used with X3-Matebox.

I J K “L ” The inverter in Australia needs to be connected to DRM, which is 1 more


L communication line adapter than that in other countries.

X3-Hybrid Series
User Manual
5.0kW - 15.0kW

X3-Hybrid Series 5.0KW-15.0KW

EN

M N O P

Q R

22 23
Installation Installation

4.3 Installation Precautions 4.4 Tool preparation


The protection level of X3-Hybrid G4 series inverter is IP 65, so that the
inverter can be installed outdoors. Tool equipment
Check the installation environment and pay attention to the following
conditions when installing: Type Name Image Name Image
• Do not expose to strong light. Bit Φ10 DC Voltage
• Do not touch flammable building materials. Range ≥1100 V DC
• Do not approach flammable and explosive gases or liquids (e.g. where Hammer Multimeter
chemicals are stored). drill
• Do not touch cold air directly.
• Do not approach TV antenna or cable.
• Do not place in areas above 3000 meters above sea level. Crosshead M5
Socket
• Do not install in precipitation or high humidity, which may cause Torque wrench set
corrosion or damage Internal devices. screwdriver (Hexagon)
• Keep the system out of reach of children.
If the inverter is installed in a narrow area, be sure to reserve appropriate 0.5mm²~6mm²
Diagonal

Machine Installation Tools


space for heat dissipation. OT
The ambient temperature of the installation site is -35°C~60°C. terminals poliers
The maximum angle range of wall tilt ±5°. press clamp
Avoid direct sunlight, rain and snow weather.
Multifunction
Utility knife terminal
crimping
tool (RJ45)

wire stripper Marker


No direct sunlight No Rain Exposure No snow Lay up

Rubber Tape
hammer measure

Hexagon
Crimping
Stay away from Stay away from keys
combustibles
Direct Sunlight Rain Exposure Snow Lay up
antenna cables Tool

Euro
terminal
crimping Spirit level
tool
Individual
Protection Dustproof Protective
Tools Cover glasses

24 25
Installation Installation

4.5 Installation Site Conditions

Tool equipment 4.5.1 Installation Carrier Requirements


Do not install the inverter near flammable materials.
Type Name Image Name Image
Please install the inverter on a solid object that can withstand the weight
requirements of the inverter and energy storage system.
Individual Please be careful not to install the inverter in the plasterboard wall or
Safety Safety
Protection
Tool
gloves shoes similar to the residential places with poor sound insulation, so as not to
work with noise and interfere with the residents' life in the morning.

Type Name Image Requirement 4.5.2 Installation Requirements


Install the inverter at a maximum back tilt of 5 degrees, the inverter can
Equipment Breaker not be tilted forward, inverted, excessive back tilted or side tilted.
Grid port and EPS(Off-grid) port wiring
Preparation section (4.5.2)

Dedicated PV wire, line number


#12 AWG withstand voltage 1000V,
PV end
wire temperature resistance 105℃ fire
resistance grade VW-1

EPS
(Off-grid) Five-core cable
end wire ≤5°

Cable
Preparation
Grid end
Five-core cable
wire

Communi- Twisted pair with shield


cation lines

Battery
Conventional wire
Cable

PE Cable Conventional wire

26 27
Installation Installation

4.5.3 Installation Space Requirements 4.6 Mounting


Reserve enough space when installing inverter (at least 300mm) for heat
dissipation. Ø Preparation

Please prepare the following tools before installation.


≥300mm Reserved space dimensions of
installation

Position Min Distance


≥300mm ≥300mm Left 300mm
Right 300mm
Up 300mm Installation tools: screwdriver, wrench, Φ10 drill, rubber hammer, socket
Down 500mm wrench set and Hexagon keys.

≥300mm Ø Step 1: Fix the wall bracket to the wall

First find the expansion screw and the wall bracket in the accessory bag,
as shown below:
For multi-inverter installation scenarios, the inline installation method is
recommended; when the space is insufficient, the recommended method of It consists of four parts
installation in the form of "products"; it is not recommended to install multiple
inverters in stacks. If you choose stack installation, please refer to the installation
separation distance below.

Expansion bolts, Tapping screws, nut, Gasket Gasket Bracket


≥300mm ≥300mm

a) Use a marker to mark drilling holes of the bracket on the wall.


≥300mm ≥300mm ≥300mm b) Drill holes at marked spots with depth of 65mm.

≥1000mm ≥1000mm

≥300mm ≥300mm ≥300mm

≥500mm ≥500mm

28 29
Installation Installation

Ø Step 3: Tighten the inverter and bracket


m
80.00 m e ) Hang the buckle on the inverter to the corresponding position of the
backplane;
f ) Use the inner hexagonal wrench to tighten the inner hexagonal screw
on the right side of the inverter.

Φ10 Drill
(Depth: 80 mm)
b)
Ø Step 2: hang the inverter on the bracket
c) Insert expansion bolt into the hole, use rubber hammer to knock the
expansion screw bolt into the wall;
d) The bracket is aligned with the screw uses the inner hexagonal wrench to
e)
screw the tapping screw until the expansion bolt "bang" is heard.

Expansion bolts, Tapping screws,

Hammer
c)

f)

Inner hexagonal wrench


nut, Gasket, (Torque:1.2±0.1 N· m)

d)

30 31
Electrical Connections Electrical Connections

5 Electrical Connections Ø Connection step


The PV port wiring of X3-Hybrid G4 M series inverter has been
5.1 PV Connection completed. For speci c installation details, please refer to the
X3-Hybrid G4 series inverter have two PV inputs. Please select X3-Matebox Quick Installation Guide, the D series needs to be
photovoltaic modules with good performance and quality assurance. wired.
The open circuit voltage of the module array should be less than the
maximum PV input voltage specified by the inverter, and the working Step 1. Turn off the DC switch, connect the PV module, prepare a 12AWG
voltage should be within the MPPT voltage range. PV cable, and find the PV (+) terminal and PV (-) terminal in the package.

Table 1: Maximum input voltage limit(apply to version D/M)


Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0

Max. DC input voltage 1000V Positive PV pin

Negative PV pin
Warning! Positive terminal
The voltage of photovoltaic modules is very high, and is PV cable PV pin Negative terminal
dangerous voltage. When wiring, please follow the safe
electricity regulations.
Step 2. Use a wire stripper to strip the 7mm insulation layer of the wire end.

Note!
Please do not make PV positive or negative ground!

Note! mm
The following PV module requirements need to be applied 7.0
Wire stripper
to each input range:
1. Same model
2. Same quantity Step 3. Tighten the cable with the insulation layer stripped and insert it into
3. The same queue the metal terminal (see Figure 1), make sure all wires are inserted Into the
4. The same angle metal terminal (see Figure 2).

Note!

x
X3-Hybrid G4 series inverters do not support the following
PV module connection modes.
+ + +
- PV1
-
+ + PV2 Positive PV pin
- - - Negative PV pin
PV Inverter Figure 1


X3-Hybrid G4 series inverter support the following PV
module connection modes.
+ + +
- - PV1 Positive metal terminal
Negative metal terminal
+
+- PV2
- Figure 2
PV Inverter

32 33
Electrical Connections Electrical Connections

Step 4. Tighten the PV pin needle and the wiring harness to make the The following is the location of the inverter's positive and negative
connection tight without looseness. (PV-/PV+) ports.
Note: Before inserting the PV terminal, please turn on the switch of
the PV module and use a multimeter to measure the positive and
negative poles of the PV terminal port to prevent reverse
connection.

Crimping Tool

Multimeter
DC Voltage
Range ≥1100 V DC

Step 5. The PV joint is divided into 2 parts - the plug and the fastening head.
Insert the cable through the fastening head and the opposite plug.
Note that the red and black lines correspond to differentof plugs. Finally,
force the cable pair into the plug, will a "click" sound,which indicates that
the connection is complete. PV1+ Dongle/Up grade

PV1+
PV 2+
Positive terminal PV1-
PV1-
PV 2-

Schematic diagram of the inverter PV connected.

Negative terminal

Step 6. Tighten the fastening head and into insert the corresponding
positive and negative (PV-/PV+) ports of the inverter.

PV+

Positive

PV-

Dongle/

Negative

34 35
Electrical Connections Electrical Connections

5.2 Grid Port and EPS(Off-grid) Output Connection 5.3 EPS(Off-grid) Block Diagram
X3-Hybrid G4 series inverter are three-phase inverter. Suitable for rated X3-Hybrid G4 series inverter has an EPS(Off-grid) function. When the
voltage 380/400/415V, frequency 50/60Hz. Other technical requests should grid is connected, the inverter outputs go through the Grid port, and
comply with the requirement of the local public grid. when the grid is disconnected, the inverter outputs go through the
EPS(Off-grid) port.
The EPS(Off-grid) function can be connected to part of the load, Please
refer to the following diagram for the wiring.
Ø Grid port connection If you want to save installation time, you will need an accessory. If you
need a solution, please contact our sales staff.
Grid Cable and Micro-breaker recommended
(apply to version D/M)
Ø EPS(Off-grid) wiring diagram
Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0

Cable (copper) 4~6mm² 4~6mm² 5~6mm²


For to different local wiring rules, please refer to the diagram below
4~6mm² 5~6mm² 5~6mm²
Please select the appropriate wiring method according to local wiring
Micro-Breaker 20A 20A 32A 40A 40A 40A
rules.

EPS(Off-grid) Cable and Micro-breaker recommended Diagram A: N line and PE line separate wiring , D series inverters ;
(apply to version D/M)
(For most countries)
Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0

Cable (copper) 4~6mm² 4~6mm² 4~6mm² 4~6mm² 4~6mm² 4~6mm²


Micro-Breaker 16A 16A 20A 25A 32A 40A PV 1
PV 2
X3-Hybrid G4
CT
The load should not be directly connected to the inverter. Breaker Main Breaker/RCD

BAT Grid EPS(Off-grid)


N

Breaker
E-BAR Grid

RCD

Breaker
Breaker
Battery
Distribution Box
EPS(Off-grid) loads Loads

Figure: Wrong connection of load and inverter


N-BAR for EPS(Off-grid) loads N-BAR for loads

36 37
Electrical Connections Electrical Connections

Diagram B: N line and PE line separate wiring, M series inverters ; Diagram D: N line and PE line together, all load connection EPS(Off-grid)
(For most countries) scheme; ( Applicable to Australia)

PV 1
PV 2 PV 1
X3-Hybrid G4
PV 2
CT
X3-Hybrid G4
Main Breaker/RCD CT

BAT Grid EPS(Off-grid) Main Breaker/RCD


CT 1
N
BAT Grid EPS(Off-grid)
CT 2
X3-Matebox CT 3 N
N
E-BAR Grid E-BAR
E-BAR
X3-Matebox Grid

Breaker
Breaker

Breaker
Breaker
Battery Loads
EPS(Off-grid) loads
Battery EPS(Off-grid) loads Loads

N-BAR for EPS(Off-grid) loads N-BAR for loads


N-BAR for EPS(Off-grid) loads N-BAR for loads

Diagram C: N line and PE line together, D series inverters;


( Applicable to Australia)

PV 1
X3-Matebox is a convenient wiring accessory. Please refer to 
PV 2
X3-Hybrid G4 X3-Matebox for details. If you need to purchase X3-Matebox, please
CT contact us.
Breaker CT 1 Main Breaker/RCD

BAT Grid EPS(Off-grid) CT 2 The RCD on the gure represents a leakage protection
CT 3
N
device with a circuit breaker function.
To use X3-Matebox's Diagram B and Diagram D, you
need to set "X3-Matebox" to "Enable" in "Settings";
E-BAR Grid
Breaker
N
The Australian customer must shorten the N lines of the
Grid and the EPS(Off-grid) in the X3-Matebox.
RCD If your local wiring method does not follow the above
operation guide, especially the neutral wire, ground wire,
RCD wire, please contact our company before operation.
Breaker
Breaker

Battery Distribution Box


EPS(Off-grid) loads Loads

N-BAR for EPS(Off-grid) loads N-BAR for loads

38 39
Electrical Connections Electrical Connections

Ø EPS(Off-grid) load requirements Ø Grid and EPS(Off-grid) connection steps

Warning! Connection requirements


Ensure that the EPS(Off-grid) load rated power is within the
Note: Check the grid voltage and compare the voltage range
EPS(Off-grid) rated output power range, otherwise, the
(see technical data).
inverter will report an "overload" warning.
Disconnect the circuit board from all power sources to prevent electric
shock.
When “overload” occurs, adjust the load power to make sure it
is within the EPS(Off-grid) rated output power range, and the
The Grid and the EPS(Off-grid) ports of X3-Hybrid G4 M series inverter
inverter will automatically return to normal.
have been connected, for specific installation details, please refer to the
X3-Matebox Quick Installation Guide. And the D series needs to be
For non-linear loads, ensure that the inrush current power is
wired according to the following steps.
within the EPS(Off-grid) rated output power range.
When the configuration current is less than the maximum DC
input current, the capacity and voltage of lithium and lead
Step 1. Prepare a Grid cable (five-core wire) and an EPS(Off-grid) cable
acid will decrease linearly.
(four-core wire), and then find the European terminal and waterproof
The following table shows some common loads for your reference. cover in the accessory bag.
m
2m 2m
m
L=1 L=1
Note: Please check with the manufacturer for high-power inductive loads. L L

Power Instance
Common 10AWG Grid(Five-Core Cable) 10AWG EPS(Off-grid)(Four-Core Cable)
Content
equipment Equipment
Start Rated Start Rated

100W 100VA 100VA


Resistive load X1 X1 (W) (W)
Incandescent Incandescent
lamp lamp

10AWG Euro Terminal*10 Waterproof cover

Inductive load X 3~5 X2 450-750VA 300VA


150W (W) (W)
Fan Fridge Fridge

40 41
Electrical Connection Electrical Connection

Step 2. First remove the waterproof housing plug, and then the Grid and Step 3. Remove the 12mm insulation layer at the end of the wire. Insert
EPS(Off-grid) cables through the waterproof housing corresponding to the European-style terminals respectively, and make sure that the stripped
the Grid and EPS(Off-grid) ports. ends are inserted into the European-style terminal, and finally use
crimping pliers to press tightly.

Diagonal pliers

L L= 12 m m

m
2m
L L=1

Crimping Tool

※Note: Please press European


terminal into a 3.3.*3.3mm square.

Grid

EPS(Off-grid) Grid

d)
EPS(Off-gri

42 43
Electrical Connection Electrical Connection

Step 4. Find the location of the AC interface on the inverter, insert the Step 6. Tighten the waterproof fastening head.
crimped terminals into the UW10 terminals L1, L2,L3,N, and PE according
to the wire sequence, and use a flat-blade screwdriver to tighten the
screws. (Torque: 1.5±0.1N·m)

Torque screwdriver
( Torque: 1.5±0.1N·m)

Step 5. Install the AC waterproof cover, and tighten the screws on the four
sides of the waterproof cover with an Hexagon keys.

Hexagon keys
( Torque: 0.8±0.1N·m)

44 45
Electrical Connection Electrical Connection

5.4 Battery Connection Ø Battery connection steps


Ø Connection requirements Batter y por t connec tion line of the X3-H ybrid G4 M series
X3-Hybrid G4 series inverter charge and discharge system can be inverter is on the X3-Matebox,for specific installation details, please
equipped with high voltage lithium battery . refer to the X3-Matebox Quick Installation Guide It is necessary to
Please note that the maximum voltage of the battery should not wire the D series according to the following steps.
exceed 650 V, battery communication should be compatible with the Step 1. Prepare 8 AWG battery power line, find the DC plug (+), DC plug (-)
X3-Hybrid G4 inverter. in the accessory bag.

Ø Battery Breaker 8 AWG

Before connecting the battery, a non-polar DC MCB must be installed to


ensure safety.
Before maintenance, the inverter need to be safely disconnected.
Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0 Power line BAT plug (+) BAT plug (-)
Nominal voltage of DC breaker should be larger than maximum
Voltage
voltage of battery. Step 2. Strip the insulation layer (length: 15mm) at one end of the power line.
Current[A] 32A

Note: The above situation applies to the D/M version.


m
Ø Battery connection diagram 0m
15.
Diagonal pliers
com

Upgrade/Dongle
Step 3. Insert the stripped cables into the DC plug (-) and DC Plug (+)
EPS(Off-grid)

respectively.

Non-polar
DC MCB
Communication line connection

Power line connection


CAN/RS485
- +

DC plug (-) DC plug (+)

... ...

Spring

High voltage lithium battery


Note: Cavity
When using SolaX battery, it is recommended to use the number of
battery control (T-BAT-5.8) is 1, the number of battery modules
(HV11550) is 1-3; the number of battery control (Mc0600) is 1, the
number of battery modules (HV10230) is 2-4.
The cable must pass through here
46 47
Electrical Connection Electrical Connection

Step 4. Press down on the spring by hand, you can hear a click sound, Ø Communication connection
then push the ends together, and tighten the screw joints.
BMS port definition
The communication interface between the inverter and the battery uses
the waterproof connector with RJ 45.
Spring
Spring
1) White with orange stripes
2) Orange
1 2 3 4 5 6 7 8
3) White with green stripes
4) Blue
5) White with blue stripes
Click ! 6) Green
7) White with brown stripes
8) Brown

1 2 3 4 5 6 7 8

X X X BMS_CANH BMS_CANL x BMS_485A BMS_485B

Note!
After the BMS communication between the battery
and the inverter is finished, the battery will work
normally.
Step 5. Insert the battery power lines into the corresponding BAT port (+), (-)
of the inverter.

Dongle/Up grade

Do ng le/ Up gra
de

Note: BAT port, not PV port!


Note: The positive and negative
wires of the battery are not
allowed to be reversed!

48 49
Electrical Connection Electrical Connection

5.5 Communication Connection 5.5.2 Introduction to meter/CT Communication

5.5.1 Introduction to DRM communication (AS4777 regulatory requirements) X3-Hybrid G4 inverter should work with an electric meter or current
sensor (CT for short) to monitor household electricity usage. The electricity
meter or CT can transmit the relevant electricity data to the inverter or
DRM requirements: platform, which is convenient for users to read at anytime.
Mode Requirement
Users can choose to use electric meters or CTs according to their needs.
DRM0 Operation disconnect device
Please note that the meter/CT brand required by SolaX must be used.
DRM1 Do not consume power
DRM2 Do not consume more than 50% of rated power
Note!
Do not consume more than 75% of rated power AND The meter or CT must be connected to the inverter, otherwise
DRM3 the inverter will shut down and alarm SolaX "meter failure"alarm.
Source reactive power if capable
Smart meters must be authorized by SolaX, third party or
Increase power consumption other companies, Unauthorized meter may be incompatible
DRM4 (subject to constraints from other active DRMs) with the inverter.

DRM5 Do not generate power SolaX will not be responsible for the impact caused by the use
of other appliances.
DRM6 Do not generate more than 50% of rated power

Do not generate more than 75% of rated power AND Ø Electric meter connection diagram
DRM7
Sink reactive power if capable
com

Increase power generation


DRM8 (subject to constraints from other active DRMs)
Upgrade/Dongle

EPS(Off-grid)

1 1 2 3 4 5 6 7 8
DRM4/8 Load
8 DRM1/5 DRM2/6 DRM3/7 +3.3V DRM0 GND GND
in out

L1
L2
L3
Note! N
PE
Currently only PIN6 (DRM0) and PIN1 (DRM1/5) are functional, other Household Meter
Meter1
PIN functions are under development. Grid (three-phase meter)
in out
If the user has other power generation
equipment (such as inverter) at home and
wants to monitor both, X3-Hybrid G4 inverter
provides Meter2 communication function to Other power
Meter2
monitor the power generation equipment. (three-phase meter) generation equipment
For more information, please contact SolaX.

Note: If you want to connect the meter, please ground the GND terminal of the Meter1.

50 51
Electrical Connection Electrical Connection

Ø CT Connection Note for CT connection:

The current sensor measures the current on the live wire between the Note!
inverter and the public grid. • Do not place the CT on the N wire or ground wire.
• Do not put CT on the N line and L line at the same time.
• Do not place the CT on the side where the arrow points to
CT connection diagram the inverter.
• Do not place the CT on non-insulated wires.
• The cable length between CT and inverter should not
com exceed 100 meters.
• After CT is connected, prevent the CT clip from falling off.
Upgrade/Dongle
It is recommended to wrap the CT clip around in circles with
insulating tape.

Grid Loads
1 2 3 4 5 6 7 8

L1 CT1-1 CT1-2 CT1-3


L2 1 1 2 3 4 5 6 7 8
L3
N

Household Meter 8 CT1-1 CT2-1 CT3-1 485A 485B CT3-2 CT2-2 CT1-2

Note:The arrow on the CT Meter/CT port is at the


must point at the public bottom of the inverter.
grid.

Public Grid L Line


electricity
CT
Note!
Meter/CT
Only one of the Meter and CT connections can be selected.
Meter cable goes to pin terminal 4 and 5; CT1 cable to PIN
Terminal 4 and 5; CT2 cable to PIN Terminal 1 and 8; CT3 cable is
connected to terminals 3 and 6.

LCD settings
To select CT, you need to enter Use setting, then enter CT/Meter
Setting.

CT/Meter Setting
>Select
CT

52 53
Electrical Connection Electrical Connection

5.5.3 Parallel Connection Ø Work Modes in parallel system


X3-Hybrid G4 Series Inverter provides the parallel connection function There are three work modes in parallel system, and your acknowledge
which should make 6 inverters maximumly connected in one system. In of different inverter’s work modes will help you understand parallel system
this system, one inverter will be set as the “Master inverter” which will better, therefore please read it carefully before operating.
control every other inverters. This system needs to be equipped with an
X3-Parallel Box or X3-EPS Parallel Box, and communicate with the Only if no one inverter is set as a “Master”, all inverters are in
Free mode
"Master Inverter", and all other slave inverters are connected to the free mode in the system.
"Master Inverter" in parallel via CAN cable.
When one inverter is set as a “Master”, this inverter enters
If users want to use the parallel function, please contact SolaX for consultation Master mode master mode.
and purchase X3-Parallel Box or X3-EPS Parallel products. Master mode can be changed to free mode.

Once one inverter is set as a “Master”, all other inverters will


Ø System Diagram
Slave mode enter slave mode automatically. slave mode can not be
changed from other modes by LCD setting.
PE
Battery

X3-Hybrid G4 Inverter
-

Critical Load
three-phase
CAN R S T N R S T N

N T S R
+

EPS
Slave

Ø Wiring Operation and LCD Setting


Grid
PV+ PV-

single-phase
Critical Load
L N Note: Before operation, please make sure that the inverter
......

meets the following three conditions,


CAN CAN PE

... ...
1. The software version of all inverters is the same;
2. The power range of all inverter models is the same;
3. The type and quantity of batteries connected to all
PE
X3-Hybrid G4 Inverter
Battery

inverters are the same;


R S T N CAN

single-phase
Critical Load
-

L N

Otherwise, this function cannot be used.


+

Master
EPS
Grid
CAN R S T N

N
S
T

S
T
R

R
PV+ PV-

Note: There are two CAN ports on the inverter. The CAN
X3-Parallel Box

EPS Load
COM

port of the inverter set as the "host" is connected. The CAN


port on the left on the bottom frame of the inverter must
R S T N
Meter

Grid

be connected to the COM port of the X3-Parallel Box, and


Normal Load Normal Load
three-phase single-phase
L N

the CAN port on the right is connected "Slave".


R S T N

Step1: Connect all inverters’ communication together by connecting CAT7


network cables between CAN ports.
SOLAX
Meter
485

- Use standard CAT7 network cables for CAN-CAN connection and CAT5
cable for CAN(left)-COM(X3-Paralle Box) connection.
N
S
T
R

Grid

- Insert one side of CAT7 cable into the rst inverter’s CAN(right) port and
the other side into the next inverter’s CAN port.

54 55
Electrical Connection Electrical Connection

- Insert one side of CAT5 cable into the COM port of meter, and the other For example, the wiring diagram of the X3-Parallel box power line.
side into the CAN (left)port the master inverter.

- Insert one side of CAT5 cable Meter, and the other side into the Meter
port the master inverter.
GRID LOAD
N T S R

X3-Hybrid G4 Inverter

Master
X3-Hybrid G4 Inverter

slave1
...... X3-Hybrid G4 Inverter

slave8
X3-Hybrid G4 Inverter

slave9
SOLAX
Meter CAN CAN(right) CAN CAN(right) CAN CAN(right) CAN CAN(right) CAN
Meter (left) (left) (left) (left) (left)
CAT5
CAT7 CAT7 CAT7 CAT7
X3-Parallel
Box COM CAT5

......
n=10
EPS
Ø CAN PIN Definition

1 1 2 3 4 5 6 7 8 X3-Parallel Box
485A 485B VCC CANH CANL GND SYN1 SYN2
Step 3: Turn on the power of the entire system, nd the inverter connected
to the meter, enter the setting page of the inverter LCD screen, click on the
Step 2: Connect the power cable between X3-Parallel Box parallel settings, and select "master control"; then enter the
(X3-EPS Parallel Box) and inverter (R/S/T/N/PE). "resistance switch" and set it to " ON";
Finally, nd the last slave in the parallel system and enter the setting page
If the user purchased the X3-Parallel Box product, please refer to the of the inverter LCD screen and set the "resistance switch" to "ON".
X3-Parallel Box user manual for installation and connection.
Setting Parallel Setting
If the user purchased the X3-EPS Parallel Box product, please refer to the Battery >Setting
X3-EPS Parallel Box user manual for installation and connection. Parallel Setting
Reset Master

Important Warning! Parallel Setting


The hybrid parallel system is extremely complex and a >Resistance Switch
large amount cables need to be connected, therefore it
is strongly required that every cable must be connected ON
according to correct line sequence(R-R, S-S, T-T, N-N),
otherwise any small misoperation may cause the system Master Terminal Slave
X3-Parallel Box Meter
running failed.
... ...

Upgrade/Dongle
CAN1 CAN2 Upgrade/Dongle

CAT5

CAT5 CAT7 CAT7

56 57
Electrical Connection Electrical Connection

Ø How to Remove parallel system Ø Parallel Control Function


Master inverter has an absolute lead in the parallel system to control all
If one inverter wants to exit from this parallel system, please do the steps as
slave inverter’s energy management and dispatch control. Once master
below:
inverter has some error and stop working, all slave inverter will be stop
- step1: Disconnect all the network cables on the CAN port.
simultaneously. But master inverter is independent of all slave inverter
- step2: Disconnect all power cables (R/S/T/N/PE) connected to X3-Parallel Box
to work and will not be affected by slave inverter’s fault.
or X3-EPS Parallel Box.
- step3: Enter setting page and click parallel setting, and choose “Free”.
Overall system will be running according to master inverter’s setting
parameters, and most setting parameters of slave inverter will be kept
Note! but not be cancelled.
- If a slave inverter is set to “Free” mode but not disconnect the Once slave inverter exit from system and be running as an
network cable, this inverter will return to “slave”mode independent unit, its all setting will be re-excuted.
automatically.
- If a slave inverter is disconnected with other inverter but not The rest of this section covers several important parallel control
be set to “Free” mode, this inverter will stop working and functions, and the next page table shows which LCD options are
maintain “waiting” status. controlled by master inverter and which can work independently.

Off mode setting:
Off mode can only be set by master inverter ( long press ESC button on LCD ) .
Ø LCD display
Safety setting:
Main display: System safety protection is cancelled by master inverter’s safety. slave
Once inverter enters parallel system, the “today yield” will be replaced by “ inverter protection mechanism will only be triggered by master
Inverter Class”, and parallel relevant fault has a higher priority than other inverter’s instructions.
faults and will be showed rstly on main display.
Self-use setting:
Power 5688W Power 5688W Power 5688W If system is running as self-use mode, please note the Feedin Power Limit
Today 20.5KWh Parallel Master Parallel Slave1 set of master inverter is for the overall system and the corresponding set
Battery 67% Battery 67% Battery 67% of slave inverter is invalid.
Normal Normal Normal
Power Factor setting:
All sets about power factor are all for the overall system and the
Status display: corresponding sets of slave inverter are invalid.
User can obtain all the status data from master inverter. System power and
individual slave inverter power can be obtain in status display of master Remote control setting:
inverter. The remote demand instructions received by master inverter will be
interpreted as the demand instructions to overall system.
Menu Parallel Status Parallel Status
Status >All 2 >Grid
>Parallel Status Slave1 Solar
History Slave2 Load

Means the total number of online inverters

58 59
Electrical Connection Electrical Connection

5.5.4 COM Communication Inverter communication control external equipment:

COM communication interface is mainly provided for customization


the second step of development use.The inverter supports the control
of external equipment or external equipment control through
communication.

For example, the inverter adjusts the working mode


of the heat pump and so on.

Ø Application occasion
COM is a standard communication interface, through which the
monitoring data of the inverter can be directly obtained. Also, external Adapter
Box
communication devices can be connected to carry out the secondary
development of the inverter. For specific technical docking, please
contact SolaX.

External communication equipment controls the inverter:

Ø COM PIN Definition

1 1 2 3 4 5 6 7 8

8 Drycontact_A(in) Drycontact_B(in) +13V 485A 485B GND Drycontact_A(out) Drycontact_B(out)

Note!
Date Read Customers can communicate or control the inverter and external
devices through the COM interface. Professional users can use
pins 4 and 5 to realize data acquisition and external control
functions. The communication protocol is Modbus RTU. For
details, please contact SolaX. If the user wants to use the inverter
dry contact to control external equipment (such as a heat pump),
it can be used with SolaX's Adapter Box. For details, please refer to
Date Read the Quick Installation Manual of the Adapter Box.
Date Write
Smart control device
(developing)

60 61
Electrical Connection Electrical Connection

5.5.5 Communication Connection Steps


Step 1. Prepare a communication cable, and then find the communication
adapter in the accessory bag. Diagonal pliers

m
Communication cable Waterproof connector with RJ 45 RJ 45 terminal 0m
.0
CAN 15
Step 2 . The inverter CAN/DRM/SHUT port communication line connection, CAN
need to remove the inverter cover plate. DRM
Shut down

Step 4. Insert the prepared communication cables into the RJ45 terminals
in sequence, and then use network cable crimping pliers to
press them tightly.

Torque screwdriver
( Torque: 1.2±0.1N·m)

com
Grid
Multifunction terminal
crimping tool (RJ45)
CAN CAN LCD DRM

Upgrade/Dongle

EPS(Off-grid)

1) White with orange stripes


2) Orange
1 2 3 4 5 6 7 8
3) White with green stripes
4) Blue
Step 3. Insert the communication cable through the communication 5) White with blue stripes
adapter, and peel off the outer insulation layer of 15 mm. 6) Green
7) White with brown stripes
8) Brown

Diagonal pliers

m
Meter/CT/BMS/COM 00m
15.

62 63
Electrical Connection Electrical Connection

Ø DRM communication cable


The DRM pin is defined as follows:

1 2 3 4 5 6 7 8

1 1 2 3 4 5 6 7 8

8 DRM1/5 DRM2/6 DRM3/7 DRM4/8 +3.3V DRM0 GND GND

Note!
At present, there are only PIN6 (DRM0) and PINI (DRM1 /5), and
oher PIN functions are under development.

Ø BMS communication cable

The BMS pin is defined as follows:

1 2 3 4 5 6 7 8

1 1 2 3 4 5 6 7 8

8 X X X BMS_CANH BMS_CANL x BMS_485A BMS_485B

Note!
The communication port on the lithium battery must be
consistent with the definition of pins 4, 5, 7, and 8 above;

64 65
Electrical Connection Electrical Connection

Ø METER/CT communication cable 2) One side of the finished cable, Waterproof connector with RJ45 is
inserted into the inverter, and one side of the RJ45 terminal is inserted
METER/CT pin is defined as follow: into the CT connection.

1 2 3 4 5 6 7 8

1 1 2 3 4 5 6 7 8 Upgrade/Dongle

EPS(Off-grid)

8 CT1-1 CT2-1 CT3-1 485A 485B CT3-2 CT2-2 CT1-2

Note!
Only one of the Meter and CT connections can be selected.
Meter cable goes to pin terminal 4 and 5; CT1 cable to PIN
Terminal 4 and 5; CT2 cable to PIN Terminal 1 and 8; CT3 cable is
connected to terminals 3 and 6.

1) Users can customize the length of the CT communication cable. The


accessory package provides 1*RJ45 and 1*waterproof connector with
RJ45 terminals.
When the CT cable is completed, connect the A terminal to the
"CT/METER" port of the inverter and tighten the waterproof screw, and Distribution box
connect the B terminal to the RJ45 coupler.

Note!
A When installing, pay attention to water resistance. All the
connected parts of CT must be put into the distribution cabinet.
B

66 67
Electrical Connection Electrical Connection

Step 5. Connect the DRM / CAN / SHUT communication cable, and Step 6. Lock the cover plate and tighten the fastening head.
insert the cable into the corresponding port.

Upgrade/Dongle

EPS(Off-grid)

CAN CAN DRM SHUT

Upgrade/Dongle

Torque screwdriver
( Torque: 1.2±0.1N·m)

CAN CAN DRM SHUT

CAN CAN DRM SHUT CAN CAN DRM SHUT

68 69
Electrical Connection Electrical Connection

Step 7: Finally, find the corresponding COM, BMS, Meter, CT, CAN, DRM, 5.6 Grounding Connection (Mandatory)
SHUT poets on the inverter and insert the communication cable into the
corresponding ports. The user must make two ground connections: one shell grounding,
and one equipotential grounding. This prevents electric shock.

COM
Note: If the PV end of the inverter is not connected with earth, the
inverter will turn on a red light Inspect and report ISO Fault. This
inverter complies with IEC 62109-2 clause 13.9 for earth fault alarm
monitoring.

Ground wire port of X3-Hybrid G4 M series inverter has been


connected, and the D series needs to be wired according to the
following steps.

Upgrade/Dongle
Ø Ground connection steps
EPS(Off-grid)

Step 1. Prepare a one-core cable (12AWG), and then find the ground
terminal in the accessories.

12AWG

One-core cable (12 AWG) OT terminal Hexagon socket screws


CAN CAN DRM SHUT

Step 2. Strip the grounding cable insulation(length”L2), insert the


striped cable into the ring terminal, and then clamp it.

L1
m
3m
L 1+
L2=
Diagonal plier

70 71
Electrical Connection Electrical Connection

C Step 4. Find the ground connection port on the inverter, and screw the
Step 3. Insert the striped cable into OT terminal and tighten the terminal ground wire on the inverter with an M5 Hexagon keys.
with a terminal crimping tool.

Grid

CAN CAN LCD DRM

Upgrade/Dongle

EPS

Leaking cable

Crimping Tool

Hexagon keys
Torque: 0.8±0.2N·m

72 73
Electrical Connection Electrical Connection

5.7 Monitoring Connection (Accessories) Step 2. Plug Pocket WiFi into the DONGLE port.

The inverter provides a DONGLE port, which can transmit data of the
inverter to the monitoring website via Pocket WiFi, Pocket 4G
and Pocket LAN. (If necessary, purchase products from SolaX)

Upgra de/Do ngle

Ø DONGLE connection diagram

SolaX Cloud

Upgrade/Dong le

Router

Ø Wireless monitoring accessories connection steps


DONGLE port connection line of the X3-Hybrid G4 M series inverter is on
the X3-Matebox, for specific installation details, please refer to the
X3-Matebox Quick Installation Guide It is necessary to wire the D
series according to the following steps.
Step 1. First find the DONGLE port of the inverter.

Up gra de/ Do ngl e

Please check the Pocket WiFi user manual/Pocket LAN user manual
/4G user manual.

Dongle/Up grade

74 75
Electrical Connection Electrical Connection

5.8 Check All Below Steps Before Starting Inverter 5.9 Inverter Operation
Ø Before operation, check the inverter according to the
Ø After the inverter is checked, then conduct the following following steps
steps a) Check that the inverter is well xed on the wall.
Make sure that the inverter is fixed on the wall. b) Ensure that all ground wires are well tightened.
c) Ensure that all DC and AC circuit breakers are disconnected.
Ensure that all ground wires are grounded. d) Ensure that all ground wires are well tightened.
Confirm that all DC lines and AC lines are connected. e) The AC output terminal is correctly connected to the mains.
Make sure the CT are connected. f ) Ensure that all photovoltaic panels and inverters are properly
connected. Unused DC connectors should be blocked with caps.
Make sure the battery is well connected.
Turn on the Load switch and EPS(Off-grid) switch.
Ø Start the inverter
Turn on the battery switch.
Long press the “Enter “key for 5 seconds to exit the Off mode. Steps to start the inverter
(The mode is factory defaulted as Off Mode) - Turn on the AC switch between the X3-Hybrid G4 and the power grid.
- (Optional) Remove the locking screw from the DC switch.
- Turn on the DC switch between the PV string and the X3-Hybrid G4 if
there is any.
- Turn on the DC switch at the bottom of the X3-Hybrid G4 .
When the photovoltaic panel generates enough power, the inverter
will start automatically.
PV 1
- If the battery port of the X3-Hybrid G4 is connected to a battery, turn
PV 2
X3-Hybrid G4 on the auxiliary power switch of the battery and then the battery
CT switch.
Breaker Main Breaker/RCD
Check the status of the LED and LCD screen, the LED is blue, and the
LCD displays the main interface.
BAT Grid EPS(Off-grid) If the LED is not blue, please check the following:
N
- All connections are correct.
- All external disconnect switches are closed.
- The DC switch of the inverter is set to the "ON" position.
Breaker
E-BAR Grid

RCD The following are 3 different states of inverter operation, which


means that the inverter starts successfully.
Breaker
Breaker

Battery Distribution Box Waiting: When the DC output voltage of the photovoltaic panel is higher
than 160V (lowest starting voltage) and lower than 180V (lowest working
EPS(Off-grid) loads Loads
voltage), the inverter waits for checking.

N-BAR for EPS(Off-grid) loads N-BAR for loads


Checking: The inverter will automatically detect the DC input. When the
DC input voltage of the photovoltaic panel is higher than 200V and the
Note: The RCD on the gure represents a leakage protection device with photovoltaic panel has enough energy to start the inverter, the inverter
a circuit breaker function. will enter the checking state.

76 77
Electrical Connection Firmware Upgrading

Normal: When the inverter is working normally, the green light is always on. 6 Firmware Upgrade
At the same time, the power is fed back to the grid, and the LCD displays
the output power. Ø Upgrade notes
Please read the following precautions before upgrading.

Warning!
If it is the rst time to boot, please follow the prompts to enter the setting
- In order to upgrade the firmware smoothly, if the DSP
interface.
and ARM firmware need to be upgraded, please note that
ARM firmware must be upgraded first, then DSP firmware!
- Please make sure that the category format is correct, do
not modify the firmware file name, Otherwise, the inverter
Warning!
may not work!
The input terminal of the inverter can be opened only when all
the installation work of the inverter has been completed. All
electrical connections must be performed by professionals in Warning!
accordance with local regulations. - For X3-Hybrid G4, ensure that the PV input voltage is
greater than 180V (upgrade on sunny days). please
ensure that the battery SOC is greater than 20% or the
battery input voltage is greater than 180V. Otherwise, it
Note! may cause serious failure during the upgrade process!
If it is the first time to operate the inverter, the system will
automatically display setup guide. Please follow the setup guide
to complete the basic inverter settings. Caution!
- If the ARM firmware upgrade fails or stops, please do
not unplug the U disk power off the inverter and
restart it. Then repeat the upgrade steps.

Caution!
- If the DSP firmware upgrade fails or stops, please check
whether the power is off. If it is normal, plug in the U disk
again and repeat the upgrade.

Ø Upgrade preparation

1) Please check the inverter version and prepare a U disk (USB 2.0/3.0) and
personal computer before upgrading.

Caution!
- Please make sure that the size of the U disk is smaller than
32G, and the format is FAT 16 or FAT 32.

78 79
Firmware Upgrading Firmware Upgrading

2) Please contact our service support through service@solaxpower.com to


obtain the firmware, and store the firmware in the U disk according to the
following path.
/Up gra de

Update: Upg rade /Don gle


For ARM le: “update \ARM\618.00406.00_HYB_3P_ARM_V1.01.0710_usb”;
For DSP le: “update\DSP\618.00405.00_HYB_3P_DSP_V1.01.0710_usb”;
U Disk
Ø Upgrade steps
Step 1. Please save the "Upgrade" firmware in your U disk first, and press
the "Enter" button on the inverter screen for 5 seconds to enter the OFF
mode.

/Upgrade

Long press for 5


seconds Step 3. LCD operation, enter the upgrade interface "update", as shown
below (a): Please press the up and down keys to select ARM, then press
down to set "OK", press the enter key to enter the software version
Step 2. Find the "Upgrade" port of the inverter, unplug the monitoring
interface;
module (Pocket WiFi/ Pocket 4G/Pocket 4G) by hand, and insert the USB
flash drive. Upgrade Selection Upgrade(ARM)
>ARM Cancel
DSP >OK

(a) (b)

Step 4. Please confirm the new firmware version again and select the
firmware to upgrade. The upgrade takes about 20 seconds.
(d) When it is completed, the LCD screen returns to the "Update" page.

Update(ARM) Update(ARM) Update


>618.00406.00_Hybrid_ Upgrading---------25% >ARM
X3G4_ARM_V1.01 DSP
0710.usb

(c) (d) (e)

80 81
Firmware Upgrading Setting

Step 5. For DSP: Please wait for 10 seconds. When "Update" page shown 7 Setting
as below, press down to select "DSP" and then press Enter. Please confirm
the firmware version again and press Enter to upgrade. The upgrade
takes about 2 minutes.

Update Update(DSP) Update(DSP)


7.1 Control Panel
ARM >618.00360.00_Hybrid_ connect
>DSP X3G4_DSP_V1.01_07
10.usb

( f) (g) (h)

Update(DSP) Update(DSP)

DSP Erasing--------- Upgrading---------25%

(i) (j)

Step 6. After the upgrade is completed, the LCD screen displays" Upgrade
Successful" .
Upgrade(DSP)

Upgrade Successful Name Description


LCD Display inverter information on the LCD display.
(k) Screen
Blue light: The inverter is in normal state or EPS(Off-grid) mode.
Step 7. Plug off the U disk, press "Esc" to return to the main interface, and Blue ashing: The inverter is in the waiting, checking state
long press the enter key to exit the mode. or the system switch is off.
Off: The inverter is in a fault state.
LED Green: The battery communication is normal but the battery
Caution! Indicator MCB is disconnected, and the battery communication is
light normal and working normally.
- Please strictly follow each step from step 1-6, don't Green ashing: The battery communication is normal and
miss it. in an idle state.
- Please confirm the ARM/DSP firmware version on the Off: The battery does not communicate with the inverter.
USB flash drive. Red light on: The inverter is in a fault state.
Off: The inverter has no error.
ESC button: Return from the current interface or function.
Tip: If the display screen is stuck on "X3-Hybrid G4" after the upgrade,
Up button: Move the cursor to the upper part or increase the
please turn off the photovoltaic power supply and restart, and the inverter Key value.
will restart and return to normal. If not, Function
Down button: Move the cursor down or decrease the value.
please contact our service @solaxpower. com for help.
Enter button: Con rm selection.

82 83
Setting Setting

7.2 Screen Menu Structure 7.3 LCD Operation


1
System ON/OFF The main inter face is the default inter face, the inver ter will
automatically return to this interface when the system started up
successfully or not operated for a period of time.
Self Use
The information of the interface is as below. “Power” means the
Work Mode

2 Feed-in priority
instant output power; “ Today” means the power generated within
Backup mode Date&Time
Forced discharge the day. “Battery” means the left capacity of battery energy.
Manual Language
Forced charge
EPS(Off-grid) mode
Stopcharge&discharge
Self-use mode Power 0W
PV1 Feed-in Priority Today 0.0KWh
Battery 80%
System Status

PV2
Backup mode
3 Battery User settings Normal
Chrg & dischrg period
On-grid
Dry Contact
EPS(Off-grid)
User Password
Meter/CT
Safety Code

On-grid
Grid Parameters
Export Control
History Data

EPS(Off-grid)
Meter/CT Settings
4
Meter/CT-1
Self Test
Ø Menu interface
Meter/CT-2 Shadow Fix The menu interface is another interface for users to change settings
Error Logs Modbus or obtain information.
Matebox Setting
- When the LCD displays the main interface, click "OK" to enter this
interface.
Power Factor
- The user can select up and down the menu, and press the "OK" key
Pu Function to con rm.
settings

5
Advanced settings FVRT Function

Power limit

DRM Function Menu


Main Breaker Limit >System ON/OFF
Battery Heating Work Mode
System Status
Inverter EPS(Off-grid) Setting
6
About

Battery PhasePowerBalance

Internal Code Reset


Advance Password

COM Port Select


Manufactory settings
RlyEPSN Setting

Note:"  "This part of the content cannot be set by the end user.
Please contact the installer or SolaX if necessary.

84 85
Setting Setting

Ø Menu main Ø Mode Selection

Self Use
System ON/OFF

Mode Select
Feed-in priority
Work Mode
Backup mode
System Status
Manual
History Data
Mode selection, there are 4 working modes to choose from.
Settings
Name Description
About The self-use mode is suitable for areas with low feed-in subsidies
and high electricity prices.
① When the power of PV is sufficient
Active Charging or Discharge time period: PV will power the loads
rstly, and surplus power will charge to the battery .If the battery
is fully charged, then sell the surplus power to the grid;
( The inverter will limit the output if Feed-in limit or zero feed-in is
needed )
(PV>Load, PV →Load→Battery → Grid)
② When the power of PV is insufficient
Active Charging time period: PV will power the loads rstly ,the
remaining power will be taken from the grid , the battery will not
Ø System ON/OFF discharge at this time.
Self Use
(PV<Load , PV + Grid → Load)
“ON" means the inverter is in working state, and the inverter is in the Active Discharge time period: PV+BAT will power the loads
default state. together. If the power is still not enough, the remaining power
will be taken from the grid.
"OFF" means that the inverter stops running and only the LCD screen (PV<Load, PV + Battery + Grid → Load)
is on. ③ Without PV power
Active Charging time period: The grid supplies the loads and also
can charge the battery;
(PV=0, Grid → Load + Battery)
Active Discharge time period: The battery will power the home
loads rstly. If the battery power is not enough ,the remaining
System
power will be taken from the grid. The inverter will enter into the
Switch idle mode.
(PV=0, Battery+Grid → Load )
>OFF< Battery min SOC can be set:10%-100%;
Charge battery to min SOC can be set:10%-100%.

The Feed-in priority mode is suitable for areas with high feed-in
subsidies, but has feed-in power limitation.
①When the power of PV is sufficient
Active Charging time period: First, PV supply power to the load,
Feed-in then charge the battery to the set capacity, and then sell the
priority power to the grid. If the local grid company limits the
grid-connected power of the inverter, the excess energy
continues to charge the battery
(PV>Load, PV → Load → Battery→ Grid → Battery)
Active Discharge time period: PV will power the loads rstly, and
surplus power will feed-in to the grid.
(PV<Load, PV → Load → Grid )
86 87
Setting Setting

②When the power of PV is insufficient Ø System Status


Active Charging time period: PV will power the loads rstly, the
remaining power will be taken from the grid. The battery will not
discharge. PV1 a)
(PV<Load, PV + Grid → Load)
Discharge time period: PV+BAT will power the loads together. If the PV2 b)

System Status
power is still not enough, the remaining power will be taken from the
grid. Battery c)
Feed-in (PV<Load, PV + Battery + Grid → Load)
priority ③Without PV power On-grid d)
Active Charging time period: The grid will power the home loads and
EPS(Off-grid) e)
also charge the battery;
(PV=0, Grid → Load + Battery) Meter/CT f)
Active Discharge time period: The battery will power the home loads
rstly. If the battery power is not enough, the remaining power will be
taken from the grid. The inverter will enter into the idle mode. System status contains six content: PV1/PV2/Battery/On-grid
(PV=0, Battery+Grid → Load)
(energy feed into or buy from the grid)and EPS(Off-grid) and so on.
Battery min SOC can be set:10%-100%.;
Charge battery to min SOC can be set:10%-100%. Press up and down to select, press "Enter" to con rm the selection,
and press "ESC" to return to the menu.
The Back-up mode is suitable for areas with frequent power outages.
Same working logic with “Self-use” mode. This mode will maintain the
battery capacity at a relatively high level. (Users' setting) to ensure that a/b ) PV1, PV2
Backup the emergency loads can be used when the grid is off. Customers no Here you can see the voltage, current and power of the pv1 and Pv2.
mode need to worry about the battery capacity. Photovoltaic panels respectively;
Battery min SOC can be set:30%-100%.
Charge battery to min SOC can be set:30%-100%.
The EPS(Off-grid) mode is used when the power grid is off. System will
provides emergency power through PV and batteries to supply power PV1 PV2
to the household loads. (Battery is necessary) >U 0.0V >U 0.0V
①When the power of PV is sufficient I 0.0A I 0.0A
PV will power the loads rstly, and surplus power will charge to the
EPS battery.(PV>Load , PV → Load → Battery)
(Off-grid) ②When the power of PV is insufficient
The remaining power will be taken from the battery.
(PV<Load, PV+ Battery → Load → Battery)
③Without PV power
c ) Battery
The battery will power the emergency loads until the battery reached This status shows the battery condition of the system. Including
the min SOC, then the inverter will enter into the idle mode. battery voltage and battery current, Battery power, battery
(PV=0 , Battery → Load) capacity, battery temperature, BMS connection status. The
EPS(off-grid) SOC-min condition is adjustable within the range of meaning of the sign of battery current and power: "+" means
1 0%-25%;
charging; "-" means discharging.
Note: in the case of grid connection, all working modes work normally when the
battery SOC >5%. When the battery charge rate is below 5%, the PV or Grid will first
charge the battery SOC11%, and then return to the working mode selected by the Battery
Manual mode, there are three options to choose from: forced charging, forced U 400.0V
discharge, stop charging and discharging (grid-connected 0 power). I -1.0A
P -400W

Work Select Work Select Work Select


>Manual >Manual >Manual
Forced Charge Forced Discharge Stop Cha&Discha

88 89
Setting Setting

d ) On-grid Ø History Data


Here you can see the voltage, current, frequency, and power of the
On-grid a)
grid.

History Data
EPS(Off-grid) b)

On-grid Meter/CT-1 c)
U 0.0V
I 0.0A Meter/CT-2 d)
P 0.0W
Error Logs e)

The history data contains five pieces of information: on-grid power of


the inverter, EPS(Off-grid) power generation, power of the meter /CT and error
e ) EPS(Off-grid) Error logs.
Here you can see the inverter of voltage, current, frequency and
power when EPS(Off-grid),
Press up and down to select, press Enter to confirm selection, and press
ESC to return to the menu.

EPS(Off-grid)
U a ) On-grid
I Here is a record of the power capacity of the inverter connected to the
P grid today and the total.

On-grid
Output Today
f ) Meter/CT Output Total
Here you can see the data showing the meter or the CT. Input Today

Meter/CT b ) EPS(Off-grid)
>Meter/CT1-A 0000Kw Here you can see the EPS(Off-grid) output of the inverter today and the
Meter/CT1-B 0000Kw total output.

EPS(Off-grid)
Today
Total
00.0KWh

90 91
Setting Setting

c ) Meter /CT-1 Ø User Settings


Here you can see the inverter's electricity sold, total electricity sold,
electricity bought from the grid and total electricity bought on that Date&Time a)
day.
Language b)
Meter CT-1
>FeedInToday: EPS(Off-grid) mode c)
00.0KWh d)
Self-use mode

User settings
Feed-in Priority mode e)

Backup mode f)

d ) Meter /CT-2 Chrg & dischrg period g)


Here you can see the total power output of the inverter for the day.
Dry Contact h)
Meter CT-2
>Output Today: User Password I)

00.0KWh
Here you can set the inverter time, language, working modeSOC,
charging and discharging time period and user password.

User Setting
Date Time
Language
e ) Error Logs EPS(Off-grid) mode
Here you can see the most recent six error messages.

Error logs a ) Date time


This interface is for users to set the system date and time.
>No error

Date time

>2019 - 11 - 15
10 : 19

b ) Language
This inverter provides multiple languages for customers to choose.

Language
>Select:
English

92 93
Setting Setting

c ) EPS(Off-grid) Mute e ) Feed-in Priority mode


Here you can choose whether the buzzer is turned on when the inverter In this mode, you can set the power reserve percentage of the minimum
is running in EPS(Off-grid) mode. Select Yes, the buzzer mutes, select NO, battery state, set whether the power can be taken from the mains side to
EPS(Off-grid) mode, the buzzer will sound once every 4s when the battery charge the battery, and set the amount of power to charge the battery.
is fully charged, the closer the battery is to the empty state, the higher the For example: set the reserved minimum SOC of the battery capacity to "10%",
buzzer will sound, to remind users to avoid battery loss . which means that when the battery has been discharged to 10% of the
battery capacity, the battery is not allowed to continue to discharge;

EPS(Off-grid) Mute Charge battery to is set to 90%, indicating that the mains is allowed to
> Mute:
charge the battery at 90%.
Yes
Feed-in Priority mode Feed-in Priorty mode
>Min SOC: >Charge battery to
d ) Self-use mode
In this mode, you can set the power reserve percentage of the minimum 10% 90%
battery state, set whether the power can be taken from the mains side to
charge the battery, and set the amount of power to charge the battery.
For example: set the reserved minimum SOC of the battery capacity to
"10%", which means that when the battery has been discharged to 10% of f ) Backup mode
the battery capacity, the battery is not allowed to continue to discharge; In this mode, you can set the power reserve percentage of the
When Charge from grid is set to "Enable", the utility power is allowed to minimum battery state, set whether the power can be taken from the
charge the battery; when set to “Disable”, the utility power is not allowed to mains side to charge the battery, and set the amount of power to
charge the battery; charge the battery.
Charge battery to is set to 90%, indicating that the mains is allowed to For example: set the reserved minimum SOC of the battery capacity to
charge the battery at 90%. "10%", which means that when the battery has been discharged to 10%
of the battery capacity, the battery is not allowed to continue to
discharge;

Self-use Mode Self-use Mode Charge battery to is set to 90%, indicating that the mains is allowed to
>Min SOC: >Charge from grid charge the battery at 90%.

10% Disable
Backup mode Backup mode
>Min SOC: >Charge battery to
Self-use Mode
>Charge battery to 10% 90%

90%

94 95
Setting Setting

g ) Charge and discharge time Ø Advance settings


Here you can set the charge and discharge time period.
If two charging and discharging periods are needed, turn on the charging
and discharging period 2 and set the period. Safety Code a)
FVRT Function l)
Chrg&Dischrg Period Chrg&Dischrg Period Grid Parameters b)
Power limit m)
>Charge Period >Charge Period Charge c)
DRM Function n)

Advanced settings
Start Time End Time Export Control d)
00:00 00:00 Main Breaker Limit o)

Advanced settings
Meter/CT Settings e) Battery Heating p)
Chrg&Dischrg Period2
Self Test f) EPS(Off-grid) Setting q)
> Function
Shadow Fix g) Phase Unbalanced r)
Enable Disable Modbus h) Reset s)
Chrg&Dischrg Period2 Chrg&Dischrg Period2 Matebox Setting i) Advance Password t)
>Allowed Disc Period > Allowed Disc Period j)
Power Factor
Start Time End Time
00:00 00:00 Pu Function k)

h ) Dry Contact
When the user uses the inverter communication control external device All advanced settings can be set here, such as battery, grid, EPS(Off-grid),
function, you can enter here to set the parameters of the external etc.
response control. For the setting method, please refer to the user manual "Advanced" setting is generally customization and resetting for battery
of the compatible external device. and grid. Each part has lower level parts.
If the user uses the inverter dry contacts to control external devices (such
as heat pumps) through the Adapter box, please refer to the Adapter box
quick installation manual to set the parameters here.
Advanced
Safety Code
Load Management
> Grid Parameters
> Mode Select

Disable
a ) Safety Code
I ) User Password Users can set safety standards according to different countries. There are
The default password for the end user is "0000", where you can reset the now 1 standards to choose from. (There may be changes in the future,
new password and press the up/down key to increase or decrease the please refer to the screen display)
value. Press "Enter" to confirm the value and jump to the next digit. When
all passwords have been entered and confirmed, press "OK" to set the
password successfully. Item Standard Country
1 ARN 4105 German

User Password

0 0 0 0

96 97
Setting Setting

c ) Charger
OverVoltage_L1 Tovp_L2 Here the user can set the parameters of charger on this page, the
UnderVoltage_L1 Tuvp_L2 inverter is compatible with both lithium battery. Users can set the
charge & discharge parameters.
OverFreq_L1 Tofp_L2 For the detailed parameters, please refer to below table.
UnderFreq_L1
Tufp_Fast
Vac 10min Avg
Grid Parameters

Reconnection Time Charger Charger


OverVoltage_L2 Charge Max Discharge Max

Grid Parameters
Checking Time
Current 25A Current 25A
UnderVoltage_L2 W(Gra)
OverFreq_L2 OFPL_StartPoint
UnderFreq_L2 OFPL_SetRate
OverFreq_L2
OFPL_DelayTime
UnderFreq_L2 d ) Export Control
UFPL_StartPoint
This feature allows the inverter to control the amount of electricity
Tovp_L1 UFPL_SetRate output to the grid.
Tuvp_L1 The factory value is the default and can be changed by the user. The
UFPL_DelayTime
user value set by setup must be less than the maximum. If the user
Tofp_L1 does not want to supply power to the grid, set it to 0.

b ) Grid Parameters
Here you can set the protection value of grid voltage and frequency. Export Control
The default value is the specified value under the current safety
regulations, and the user cannot change it. User value:
0W
The display content will be displayed according to the requirements
of local laws and regulations, which are constantly increasing. Please
refer to the contents displayed on the inverter screen.
e ) Meter/CT Settings
The user needs to select the CT or electricity meter to connect the
Grid Grid inverter here. Select the address of the meter. CT does not need to select
>OverVoltage_L1 >UnderVoltage_L1 the address.
0.0V 0.0V

Grid Grid CT/Meter Setting CT/Meter Setting


>OverFreq_L1 >UnderFreq_L1 >Select >Meter 1Addr:
xxxxxxxx
0.0Hz 0.0Hz Meter

Grid Grid
>Vac 10min Avg >OverVoltage_L2

0.0V 0.0V

98 99
Setting Setting

f ) Self Test (only for CEI 0-21) g ) Shadow Fix


The self test function allows users to test the following items. "Full test", Here, you can set the shadow tracking with four options, which are off,
"Ovp(59.S2) test"27. "Uvp (s1) test", "Uvp (27. s2) test", "Ofp (81> .S1) test", low, medium, and high.
"Ufp (81 <.S1) test", "Ufp (81> .S2) test", "Ufp (81 <.S2) test",
"Ovp10 (59. s1) test".
In the self-test interface, the user can select "all tests" or a single test item
for testing. Shadow Fix
Before testing, make sure that the inverter is connected to the grid. >Func Select
All tests take about 6 minutes. And it will display "Success" and then
"Delivery". >OFF<
For a single test item, it takes about a few seconds or minutes.
Click "Test Report" to view the test results of all items.
h ) Modbus
Here you select the baud rate of the external communication protocol,
the default location of 19200 and 485 addresses.
ALL Test
Test report
Uvp(27.S1) test Modbus RTU/485 Modbus RTU/485
Baud Rate: RS485 Addr:
>Ofp2(81>.S2)result >Ovp2(59.S2)result 115200
Ft: 51.50Hz Tt:1000ms Vt: 264.5V Tt: 300ms 1
Fs: 0.00Hz To: 998ms Vs: 0.0V To: 200ms
F0: 0.00Hz pass V0: 0.0V pass

>Ofp2(27.S2)result >Uvp2(27.S1)result
Vt: 92.0V Tt: 200ms Vt: 195.5V Tt: 400ms I ) Matebox Setting
Vs: 0.0V To: 196ms Vs: 0.0V To: 200ms If you want Matebox installed, you need to turn this feature on here.
V0: 0.2V pass V0: 0.0V pass

>Ofp2(81>S1)result >Ufp2(81<.S1)result
Ft: 50.50Hz Tt: 100ms Ft: 49.50Hz Tt: 100ms Matebox Setting
Fs: 0.00Hz To: 96ms Fs: 0.00Hz To: 98ms >Select
F0: 0.2Hz pass F0: 0.02Hz pass
Disable Enable
>Ufp2(81<.S2)result >Ovp10(59.S1)result
Ft: 47.50Hz Tt: 400ms Vt: 253.0V Tt: 600ms
Fs: 0.00Hz To: 3999ms Vs: 0.0V To: 598ms
F0: 0.02Hz pass V0: 0.0V pass

100 101
Setting Setting

j ) Power Factor (applicable to specific countries, please refer to local grid k ) PU Function (applicable to specific countries, please refer to local
requirements) grid requirements)
Power Factor Power Factor
The PU function is a volt-watt response mode required by certain
Mode Select Mode Select
national standards such as AS4777.2. This function can control the
> Off < > < active power of the inverter according to the grid voltage.
Over-Excited
Selecting "Enable" means that this function is turned on and is the
default value.
Power Factor Power Factor
Select "Disable" to deactivate the function.
Mode Select Mode Select

> Under-Excited < > Curve <
PU Function PU Function
Power Factor >PuFunction Response V2
Mode Select
Enable 220.0V
> Q(u) <
PU Function PU Function
Response V3 Response V4

Mode Comment 250.0V 265.0V


Off -
Over-Excited PF value PU Function
Under-Excited PF value 3Tau
P1_PF (EU50549 only)
P2_PF (EU50549 only) 6~180S
P3_PF (EU50549 only)
P4_PF (EU50549 only)
Power 1
Curve Power 2 l ) FVRT Function(apply to50549)
Power 3 Here you can set the high and low enable or disable.
Power 4
PFLockInPoint (EU50549 only)
PFLockOutPoint (EU50549 only)
FVRT Function
3Tau Function Control
VoltRATIO 1 ( AS4777.2 only) Disable Enable
Q( u ) VoltRATIO 4 ( AS4777.2 only)
QURESPONSEV1 (EU50549 only)
m ) Power limit
QURESPONSEV2 (EU50549 only)
Power limit function, the maximum power of the AC port can be set
QURESPONSEV3 ( (EU50549 only)
Q( u ) by percentage.
QURESPONSEV4 (EU50549 only)
K Value (CEI 0-21 only)
3Tau
Power Limit
QuDelayTimer >Proportion
Fixed Q Power Q Power 1.00

102 103
Setting Setting

● Reactive power control, reactive power standard curve cos φ = f(P) n ) DRM function (applied to NZS4777.2)
The DRM function is a demand response method required by the
For VDE ARN 4105, the curve cos = f(P) should refer to curve B. The set
NZS4777.2 standard and is only applicable to NZS4777.2.
default value is shown in curve B.
The default value is "enable". Select "Disable" to disable this function.
For e8001, the curve cos = f(P) should be curve A. The set default value is
shown in curve A. DRM Function
>Function Control
For CEI 0-21, the default value of PFLockInPoint is 1.05. When Vac> 1.05Vn,
Pac> 0.2 Pn, curve cos cp = f(P) corresponds to curve B. Enable
cos φ
leading
0.9/0.95*
over-excited

o ) Main Breaker Limit


Here you can set an open minimum current here.
1
0.2 0.5 1.0
under-excited

p/pEmax Main Breaker Limit


>Current
40A
0.9/0.95*
lagging
curve A

p ) Battery Heating
Upper limit cosφ If the user needs the battery heating function, you can set it to turn on
0.9 0.95 here, and set the time period that needs to be heated, and the two time
inductive
inductive

periods can be set. (Only for batteries with heating function)


Power Upper
0.7 0.8 0.2 0.5 1.0 Battery Heating Battery Heating
0.2 0.3
capacitive

f (P)
capacitive

Power Lower f (P) >Func Select: >Heating Period 1


Start Time
Enable Disable 00:00
0.9 0.95
Lower limit
curve A curve B Battery Heating Battery Heating
>Heating Period 1 >Heating Period 2
End Time Start Time
● Reactive power control, reactive power standard curve Q= f(V) 00:00 00:00

Q V2s=1.10Vn
Battery Heating
Qmax V1s=1.08Vn=QuVlowRate
>Heating Period 2
V2i=0.90Vn
End Time
V2i=0.92Vn=QuVlowRate
V1s V2s 00:00
V2i V1i V

-Qmax

104 105
Setting Setting

q ) EPS(Off-grid) Setting Ø Manufactory Setting


User can set the frequency selection in the EPS(Off-grid) mode here, and set the
minimum capacity reserved for battery discharge.

Manufactory settings
RlyEPSN Setting a)
EPS(Off-grid) Setting EPS(Off-grid) Setting EPS(Off-grid) Setting
> Frequency >Frequency > Min SoC

50Hz 60Hz 10%

COM Port Select b)


r ) Phase Unbalanced
This function controls the distribution of AC output power.
“Enable” means each phase will be divided according to the loads connected with
each phase. “Disable” means each phase power will be divided equally and “disable”
is the default setting value.
a ) RlyEPSN Setting
three phase three phase The user needs to set whether the inverter is installed in Australia or
inverter inverter
load1
3KW
load2
4KW
load3
5KW
load1
3KW
load2
4KW
load3
5KW
Europe. When the inverter is off the grid, the N line and PE line of the
Phase Unbalanced 3kw 4kw 5kw 4kw 4kw 4kw
circuit in Australia need to be connected; the N line and PE line of the
Function Control meter European circuit need to be separated .
meter
>Disable<
If 12kw AC power can be exported, each phase power will If 12kw AC power can be exported, each phase power will
be divided as above according to different loads connected
with each phase.
be divided equally as above and it is unrelated with the
loads connected with each phase.
RlyEPSN Setting RlyEPSN Setting
enable mode disable mode >function Control >function Control
s ) Reset Europe Australia
Users can reset the reset error log, meter power ,inverter power, and
restore factory settings here.

Reset Error Log Reset Meter/CT_1 Reset Meter/CT_2

>Reset >Reset >Reset b ) COM Port Select


Yes Yes Yes Here external communication protocol or external indoor screen of
the inverter can be set. When it is used for external communication
protocol, it can choose RS485 or MOBUS.
Reset INV Energy Factory Reset

>Reset >Reset
Yes RS485/MOBUS
Yes
>RS485
MOBUS
t )Advance Password
Here you can reset the advanced password. "Set OK!" is displayed on
success, and “Setup Failed!” Will also displayed on failure.

Advance Password Advance Password


Set OK! Setup failed

106 107
Setting Setting

Ø About a ) About
Here you can see some basic information of the inverter and battery.
such as the inverter and battery SN number, software version number,
and system run time.

About
Inverter SN >Inverter
Battery
Register SN
DSP
Inverter
ARM
On-grid Run Time
About
EPS(Off-grid) Run Time

Bat_PS1 SN

Bat_PS2 SN
Battery Inverter
Bat_PS4 SN
Inverter Inverter
BatteryM Version
>Inverter SN >Register
01234560123456 01234560123456
BatteryS Version

Inverter code
Internal Code Inverter Inverter
BMS Code >DSP >ARM
2.07 1.03

Inverter Inverter
> EPS(Off-grid) Runtime >On-grid runtime
Register1 SN: Represents the serial number of external monitoring 20.0H 45.9H
equipment, such as Pocket WiFi, Pocket LAN.

108 109
Setting Troubleshooting

Battery
8 Troubleshooting
Battery Battery
> BatBrand:BAK > Bat-M SN 8.1 Troubleshooting
6S012345012345
This section contains information and procedures for resolving
possible problems with X3-Hybird G4, and provides you with
Battery Battery troubleshooting tips to identify and solve most problems that may
> Bat-PS2 SN
occur in X3-Hybrid G4. This section will help you narrow down the
> Bat-PS1 SN
6S012345012345 6S012345012345 source of any problems you may encounter. Please read the
troubleshooting steps below.
Check the warning or fault information on the system control panel
Battery Battery or the fault code on the inverter information panel. If a message is
displayed, log it before doing anything further.
> Bat-PS3 SN > Bat-PS4 SN
Try the solutions indicated in the table below.
6S012345012345 6S012345012345

Battery Battery Number


> BatteryM Version > BatteryM Version Overcurrent fault.
2.01 2.01 • Wait for a while to check if you're back to normal.
IE 001 TZ Protect Fault • Disconnect PV+ PV- and batteries, reconnect.
• Or ask for help from the installer if itcan not return to normal.

• Check battery input voltage if it's within normal range


IE 002 Grid Lost Fult
• Or ask the installer for help.

Internal Code Power grid voltage overrun


• Wait a moment, if the utility returns to normal, the system will reconnect.
IE 003 Grid Volt Fault • Please check if the grid voltage is within normal range.
Internal Code Internal Code • Or ask the installer for help.

> Inverter code > BMS code Electricity frequency beyond range
IE 004 Grid Freq Fault • If the utility returns to normal, the system reconnects.
01 00 01 xx • Or ask the installer for help.

PV voltage out of range


Internal Code IE 005 PV Volt Fault • Check the output voltage of the PV panel
Internal Code • Or ask the installer for help.
> BAT-M > BAT-S1 • press the “ESC" key to restart the inverter.
2.01 1.01 50 IE 006 Bus Volt Fault • Check that the PV input open circuit voltage is in the normal range.
• Or ask the installer for help.
Battery voltage fault
IE 007 Bat Volt Fault • Check battery input voltage if it's within normal range
Internal Code Internal Code
> BAT-S2
1.01 50
... > BAT-S8
1.01 50 IE 008 AC10M Volt Fault
• Or ask the installer for help.
• The grid voltage was out of range in the last 10 minutes.
• The system will return to normal if the grid returns to normal.
• Or ask the installer for help.

110 111
Troubleshooting Troubleshooting

Number Number
DCI overcurrent protection fault.
ARM software version mismatch Fault
IE 009 DCI OCP Fault • Wait for a while to check if it's back to normal.
IE 022 ARM Unmatched • update the software and press the ESC" key to restart the inverter.
• Or ask the installer for help.
• Or ask for help from the installer if itcan not return to normal .
DCV EPS(Off-grid) overvoltage protection failure.
IE 010 DCV OVP Fault • Wait for a while to check if it's back to normal.
• Or ask the installer for help. Other device Fault
IE 023 Other Device Fault • update the software and press the ESC" key to restart the inverter.
Software Detection of Overcurrent Fault. • Or ask for help from the installer if itcan not return to normal .
• Wait for a while to check if it's back to normal.
IE 011 SW OCP Fault Mgr InterCom Fault
• Shut down photovoltaic, battery and grid connections
IE 025 InterComms Error • Shut down photovoltaic, battery and grid, reconnect.
• Or ask the installer for help.
• Or ask for help from the installer if itcan not return to normal .
Overcurrent protection fault.
• Check the impedance of DC input and AC output. • Internal communication errors
IE 012 RC OCP Fault • Wait for a while to check if it's back to normal.
IE 025 InterComms Error • Shut down photovoltaic, battery and grid connections.
• Or ask the installer for help. • Or ask for help from the installer if itcan not return to normal.
Insulation Fault
IE 013 Isolation Fault • Please check the wire insulation for damage.
Inverter EEPROM Fault.
• Wait for a while to check if it’s back to normal. • Shut down photovoltaic, battery and grid, reconnect.
• Or ask the installer for help. IE 026 Inv EEPROM Fault
• Or ask for help from the installer if it can not return to normal.
Temperature beyond limit
IE 014 Temp Over Fault • Check if ambient temperature exceeds the limit. Fault of Residual Current Device
• Or ask the installer for help. • Check the impedance of DC input and AC output.
IE 027 RCD Fault • Disconnect PV + PV - and batteries, reconnect.
EPS(Off-grid)mode current is too strong. • Or ask for help from the installer if itcan not return to normal.
• Ensure that the load power is within the EPS(Off-grid)power range.
IE 015 Bat Con Dir Fault • Check for any non-linear load connections on the EPS(Off-grid). Electrical relay failure
• Move this load to check for recovery. IE 028 Grid Relay Fault • Disconnect PV+ PV- grid and batteries and reconnect.
• Or ask for help from the installer if itcan not return to normal. • Or ask for help from the installer if itcan not return to normal.

EPS(Off-grid) over load fault.


• Shutdown the high-power device and press the “ESC" key to EPS(Off-grid)relay failure
IE 016 EPS(Off-grid) Overload Fault restart the inverter. IE 029 EPS(Off-grid) Relay Fault • Disconnect PV+ ,PV-, grid and batteries and reconnect.
•Or ask for help from the installer if it can not return to normal. • Or ask for help from the installer if itcan not return to normal.

On-grid mode overload PVdirectionfault


• Shutdownthehigh-power device and press the" ESC" key to IE 030 PV ConnDirFault • Check if the PV input lines are connected in the opposite direction.
IE 017 OverLoad Fault restart the inverter. • Or ask for help from the installer if itcannotreturntonormal.
•Or ask for help from the installer if it can not return to normal.
Charge relay fault
•Close the high-power device and press the "ESC" key to restart the
IE 031 ChargerRelayFault • Press the ESC" key to restart the inverter. .
inverter.
IE 018 BatPowerLow • Or ask for help from the installer if itcannotreturntonormal.
•Please charge the battery to a level higher than the protection
capacity or protection voltage
EPS(Off-grid) earth relay fault
Battery communication loss IE 032 EarthRaleyFault • Press the ESC" key to restart the inverter. .
• Check that the communication lines between the battery and • Or ask for help from the installer if itcannotreturntonormal.
IE 019 BMS Lost the inverter are properly connected.
• Or ask for help from the installer if it can not return to normal. Power type fault
IE 101 PowerTypeFault • Upgrade the software and press the ESC" key to restart the inverter.
Fan Fault • Or ask for help from the installer if itcannotreturntonormal.
• Check for any foreign matter that may have caused the fan not to
IE 020 Fan Fault function properly. EPS(Off-grid) port over current fault
• Or ask for help from the installer if it can not return to normal. • Check that the EPS(Off-grid) load does not exceed the system requirements,
IE 102 Port OC Warning and press the ESC" key to restart the inverter. .
Low temperature fault. • Or ask for help from the installer if itcannotreturntonormal.
IE 021 Low Temp • Check if the ambient temperature is too low.
• Or ask for help from the installer if it can not return to normal.

112 113
Troubleshooting Troubleshooting

Number Number

Manager EEEPROM Fault. Battery Unbalanced Failure


BE 009 BMS_CellImblance • Please contact the battery supplier.
.• Shut down photovoltaic ,battery and grid ,reconnect.
IE 103 Mgr EEPROM Fault
• Or seek help from the installer if it can not return to normal.
Battery hardware protection failure
BE 010 BMS_Hardware Protect • Please contact the battery supplier.
DSP version error.
IE 104 DSPunmatched • Check that the DSP1 version matches Battery circuit failure
• Or seek help from the installer if it can not return to normal. BE 011 BMS_Circuit_Fault • Restart the battery .
• Please contact the battery supplier.
NTC invalid
• Make sure the NTC is properly connected and the NTC is in good Battery insulation failure
IE 105 NTC Sample Invalid condition. BE 012 BMS_ISO_Fault • Check that the battery is properly grounded and restart the battery.
• Please confirm that the installation environment is normal • Please contact the battery supplier.
• Or ask for help from the installer, if itcannotreturnto normal.
Battery voltage sensor fault
Batterytemplow BE 013 BMS_VolSen_Fault • Please contact the battery supplier.
• Check the battery installation environment to ensure good heat
IE 106 Bat Temp Low dissipation. Temperature sensor failure
• Or ask for help from the installer, if itcannotreturnto normal. BE 014 BMS_TemppSen_Fault • Restart the battery .
• Please contact the battery supplier.
Batterytemphigh
• Check the battery installation environment to ensure good heat Battery current sensor fault
IE 107 Bat Temp High dissipation. BE 015 BMS_CurSensor Fault • Please contact the battery supplier.
• Or ask for help from the installer, if itcannotreturnto normal.
Battery relay failure
Meter error BE 016 BMS_Relay Fault • Please contact the battery supplier.
IE 109 Meter Fault •Please check that the instrument is working properly
• Or seek help from the installer if it can not return to normal. Battery type failure
BE 017 BMS_Type_Unmatch • Upgrade the battery BMS software.
Bypass relay fault • Please contact the battery supplier.
IE 110 BypassRaleyFault • Press the ESC" key to restart the inverter. .
• Or ask for help from the installer if itcannotreturntonormal. Battery version mismatch failure
BE 018 BMS_Ver_ Unmatch • Upgrade the battery BMS software.
Battery Error - External Communication Fault • Please contact the battery supplier.
BE 001 BMS_External_Err • Please contact the battery supplier.
Batterymanufacturer did not match the fault
BE 019 BMS_MFR_ Unmatch • Upgrade the battery BMS software.
Battery Error - Internal Communication Fault • Please contact the battery supplier.
BE 002 BMS_Internal_Err • Please contact the battery supplier.
Battery hardware and software mismatch failure
Over voltage in battery system BE 020 BMS_SW_ Unmatch • Upgrade the battery BMS software.
BE 003 BMS_OverVoltage • Please contact the battery supplier. • Please contact the battery supplier.

Low voltage in battery system Battery master slave control mismatches


BE 004 BMS_LowerVoltage • Please contact the battery supplier. BE 021 BMS_M&S_ Unmatch • Upgrade the battery BMS software.
• Please contact the battery supplier.
Battery fault - over charge fault
BE 005 BMS_ChargeOCP Battery charging request does not respond to a fault
• Please contact the battery supplier.
BE 022 BMS_CR_ NORespond • Upgrade the battery BMS software.
• Please contact the battery supplier.
Battery fault-discharge over current fault
BE 006 BMS_DischargeOCP • Please contact the battery supplier. Battery slave software protection failure
BE 023 BMS_SW_ Protect • Upgrade the battery BMS software.
Over temperature in battery system • Please contact the battery supplier.
BE 007 BMS_TemHigh • Please contact the battery supplier.
Battery fault-discharge over current fault
BE 024 BMS_536_Fault • Please contact the battery supplier.
Battery temperature sensor malfunction
BE 008 BMS_TempSensor Fault • Please contact the battery supplier.
Over temperature in battery system
BE 025 BMS_SelfcheckErr • Please contact the battery supplier.

114 115
Troubleshooting Troubleshooting

Number 8.2 Routine Maintenance


Battery temperature sensor malfunction
BE 026 BMS_TempdiffErr • Please contact the battery supplier.
Inverter do not require any maintenance or correction in most cases, but
if the inverter often loses power due to overheating, this can be
Battery Unbalanced Failure attributed to the following reason:
BE 027 BMS_BreakFault • Please contact the battery supplier.

Battery hardware protection failure


heat sink behind the inverter is covered with dirt.
BE 028 BMS_Flash_Fault • Please contact the battery supplier. If necessary, clean the cooling heat sink with a soft dry cloth or brush.
Only trained and authorized professionals familiar with safety
Battery precharge failure
BE 029 BMS_Precharge_Fault • Please contact the battery supplier. requirements can perform maintenance and maintenance work.

Battery air switch failure


BE 030 BMS_AirSwitch_Fault • Check that the battery breaker is off.
• Please contact the battery supplier.

Ø Safety inspections
If the information panel of your inverter does not show the fault light, check
the following list to ensure the current installation status, correct operation. Safety checks should be conducted at least every 12 months, please
contact the manufacturer to arrange for appropriate training, expertise,
------Is the inverter located in a clean, dry and well-ventilated place? and practical experience in performing these tests. (Please note that this
------Is the DC input circuit breaker open? action is not covered by warranty). These data should be recorded in the
------Is the specification and length of the cable adequate? device log. If the equipment is not running properly or any test fails, the
------Are the input and output connections and wiring in good condition? equipment must be repaired for details of safety inspections, refer to
------Is the configuration set correct for your particular installation? section 2 of this manual for safety instructions and europe commission
instructions.
Please contact SolaX customer service for further assistance. Please be prepared to describe
the details of your system installation and provide the inverter serial number.

Ø Regular maintenance

In the process of using frequency converter, the manager should check


and maintain the machine regularly. The specific operation is as follows.

1.check whether the heat sink is covered with dirt, clean the machine
and absorb dust if necessary. This work should be performed from time to
time.

2.check whether the frequency converter indicator is normal, check


whether the frequency converter button is normal, check whether the
frequency converter display is normal. This inspection should be
conducted at least every 6 months.

3.check the input and output lines for damage or aging. This inspection
should be conducted at least every 6 months.

4.Cleaning and safety inspection of PV modules shouldbe carried out at


least once every 6 months.

116 117
Decommissioning Disclaimer

9 Decommissioning 10 Disclaimer
The X3-Hybrid G4 series hybrid inverters are transported, used and
9.1 Disassemble the Inverter operated under limited condition, such as environmental, electrical etc.
SolaX shall not be liable to provide the service, technical support or
Remove DC input line and AC output line of inverter. compensation under conditions listed below, including but not limited
Wait for at least 5 minutes to power off. to:
Remove all cable connections from the inverter.
Remove inverter from finger support the bracket. Inverter is damaged or broken by force majeure (such as earthquake,
Remove the bracket if necessary. flooding, thunderstorm, lighting, fire hazard, volcanic eruption etc).
Inverter's warranty is expired and doesn't buy extended warranty.
Can't provide the inverter's SN, warranty card or invoice.
Inverter is damaged by man-made cause.Inverter is used or operated
against any items in local policy.
9.2 Packing
Inverter's installation, configuration, commissioning doesn't follow the
Load the inverter into the original package if possible. requirements mentioned in this manual.
Inverter is installed, refitted or operated in improper ways mentioned
If the original package can not be found, you can also use the in this manual without authority from SolaX.
following requirements of the carton packaging: Inverter is installed, operated under improper environment or
Bearing capacity of more than 30 kg. electrical condition mentioned in this manual without authority from
Easy to carry. SolaX.
Can completely seal the cover. Inverter is changed, updated or disassembled on hardware or
software without authority from SolaX.
Obtain the communication protocol from other illegal channels.
Build monitoring, control system without authority from SolaX.
9.3 Storage and Transportation
Connect to other brands batteries without authority from SolaX.
Store the inverter in a dry, temperature -40°C~70°C environment. Pay
SolaX will keep right to explain all the contents in this user manual.
attention to less than four machines on each stack board during
storage and transportation.

9.4 Waste Disposal


If it is necessary to scrap the inverter or other related parts, be sure to
send the waste inverter and packaging materials to the designated
location for recycling by the relevant department.

118 119