Air Conditioning

Technical Data
Heat reclaim ventilation

EEDEN15-205

VAM-FA/FB
• Indoor Unit • VAM-FA/FB

TABLE OF CONTENTS
VAM-FA/FB

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Exchange efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

8 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

10 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

11 Air filter characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32


12 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

• Ventilation • VAM-FA/FB 1
• Indoor Unit • VAM-FA/FB

1 Features

t t i ai nl l BUc F ei / r tA o F ont - daM e neA HVentilation


IV with heat recovery as standard
• Energy saving ventilation using indoor heating, cooling and moisture • Wide range of units: air flow rate from 150 up to 2,000 m³/h
recovery
• High efficiency filters available in F6 ,F7, F8 grades
• Ideal solution for shops, restaurants or offices requiring maximum
• Shorter installation time thanks to easy adjustment of nominal air flow
floor space for furniture, decorations and fittings
rate, so less need for dampers compared with traditional installation.
• Free cooling possible when outdoor temperature is below indoor
• Specially developed heat exchange element with High Efficiency
1 temperature (eg. during nighttime)
Paper (HEP)
• Reduced energy consumption thanks to specially developed DC fan
• No drain piping needed
motor
• Can operate in over- and under pressure
• Prevent energy losses from over-ventilation while maintaining indoor
air quality with optional CO2 sensor • Total solution for fresh air with Daikin supply of both VAM / VKM and
electrical heaters
• Can be used as stand alone unit or integrated in the VRV system

2 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

2 Specifications

2-1 Technical Specifications


VAM150F
A
VAM250F
A
VAM350F
B
VAM500F
B
VAM650F
B
VAM800F
B
VAM1000
FB
VAM1500
FB
VAM2000
FB
3
Power input - 50Hz Heat exchange Nom. Ultra kW 0.116 0.141 0.132 0.178 0.196 0.373 0.375 0.828 0.852
mode high
High kW 0.100 0.112 0.107 0.135 0.129 0.270 0.275 0.668 0.695
Low kW 0.056 0.062 0.042 0.076 0.073 0.102 0.168 0.313 0.291
Bypass mode Nom. Ultra kW 0.116 0.141 0.132 0.178 0.196 0.373 0.375 0.828 0.852 2
high
High kW 0.100 0.112 0.107 0.135 0.129 0.270 0.275 0.668 0.695
Low kW 0.056 0.062 0.042 0.076 0.073 0.102 0.168 0.313 0.291
Power input - 60Hz Heat exchange Nom. Ultra kW 0.117 0.138 0.132 0.178 0.196 0.373 0.375 0.828 0.852
mode high
High kW 0.099 0.119 0.107 0.135 0.129 0.270 0.275 0.668 0.695
Low kW 0.056 0.062 0.042 0.076 0.073 0.102 0.168 0.313 0.291
Bypass mode Nom. Ultra kW 0.117 0.138 0.132 0.178 0.196 0.373 0.375 0.828 0.852
high
High kW 0.099 0.119 0.107 0.135 0.129 0.270 0.275 0.668 0.695
Low kW 0.056 0.062 0.042 0.076 0.073 0.102 0.168 0.313 0.291
Temperature Ultra high % 74 72 75 74 75
exchange efficiency - High % 74 72 75 74 75
50Hz
Low % 79 77 80 77 76 76.5 78
Temperature Ultra high % 74 72 75 74 75
exchange efficiency - High % 74 72 75 74 75
60Hz
Low % 80 77 80 77 76 76.5 78
Enthalpy exchange Cooling Ultra high % 58 61 58 60 61
efficiency - 50Hz High % 58 61 58 60 61
Low % 64 62 67 63 62 63 64 66
Heating Ultra high % 64 65 62 63 65 66
High % 64 65 62 63 65 66
Low % 69 68 70 67 66 67 68 70
Enthalpy exchange Cooling Ultra high % 58 61 58 60 61
efficiency - 60Hz High % 58 61 58 60 61
Low % 66 63 67 63 62 63 64 66
Heating Ultra high % 64 65 62 63 65 66
High % 64 65 62 63 65 66
Low % 71 69 70 67 66 67 68 70
Operation mode Heat exchange mode / Bypass mode / Fresh-up mode
Heat exchange system Air to air cross flow total heat (sensible + latent heat) exchange
Heat exchange element Specially processed non-flammable paper
Dimensions Unit Height mm 285 301 364 726
Width mm 776 828 1,004 1,512
Depth mm 525 816 868 1,156 868 1,156
Weight Unit kg 24 33 52 55 64 131 152
Casing Material Galvanised steel plate

• Ventilation • VAM-FA/FB 3
• Indoor Unit • VAM-FA/FB

2 Specifications

VAM150F VAM250F VAM350F VAM500F VAM650F VAM800F VAM1000 VAM1500 VAM2000


2-1 Technical Specifications A A B B B B FB FB FB
Fan Type Sirocco fan
Air flow rate - 50Hz Heat Ultra m³/h 150 250 350 500 650 800 1,000 1,500 2,000
exchan high
ge High m³/h 150 250 -
mode
2 Low m³/h 110 155 -
Bypass Ultra m³/h 150 250 350 500 650 800 1,000 1,500 2,000
mode high
High m³/h 150 250 -
Low m³/h 110 155 -
Air flow rate - 60Hz Heat Ultra m³/h 150 250 -
exchan high
ge High m³/h 150 250 -
mode
Low m³/h 110 145 -
Bypass Ultra m³/h 150 250 -
mode high
High m³/h 150 250 -
Low m³/h 110 145 -
External static Ultra high Pa 69 64 98 93 137 157 137
pressure - 50Hz High Pa 39 -
Low Pa 20 -
External static Ultra high Pa 98 -
pressure - 60Hz High Pa 54 -
Low Pa 24 20 -
Fan motor Quantity 2 4
Output 50 Hz W 30 80 106 210
60 Hz W 30 80 106 210
Sound pressure level - Heat exchange Ultra high dBA 27 / 28.5 28 / 29 32 33 34.5 36 39.5 40
50Hz mode High dBA 26 / 27.5 26 / 27 31.5 33 34.5 35 38
Low dBA 20.5 / 21 / 22 23.5 24.5 27 31 34 35
21.5
Bypass mode Ultra high dBA 27 / 28.5 28 / 29 32 33.5 34.5 36 40.5 40
High dBA 26.5 / 27 / 28 31 32.5 34 34.5 35.5 38
27.5
Low dBA 20.5 / 21 / 22 24.5 25.5 27 31 33.5 35
21.5
Sound pressure level - Heat exchange Ultra high dBA 28.5 29.5 34 34.5 35.5 37 41.5 42.5
60Hz mode High dBA 26.5 26 33 34 36 39 41
Low dBA 19 19.5 26 26.5 28 32 36 37
Bypass mode Ultra high dBA 28 29 34 34.5 35.5 37 41.5 42.5
High dBA 27 32.5 33.5 35 36 39 41
Low dBA 20 20.5 26.5 27.5 28.5 33 32 36 37
Operation range Min. °CDB -15
Max. °CDB 50
Relative humidity % 80% or less
On coil temperature Cooling Max. °CDB -
Heating Min. °CDB -
Connection duct diameter mm 100 150 200 250 350
Insulation material Self-extinguishable urethane foam
Standard Accessories : Installation and operation manual;

VAM150F VAM250F VAM350F VAM500F VAM650F VAM800F VAM1000 VAM1500 VAM2000


2-2 Electrical Specifications A A B B B B FB FB FB
Power supply Name VE
Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
Voltage range Min. % -10
Max. % 10

4 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

2 Specifications

2-2 Electrical Specifications


VAM150F
A
VAM250F
A
VAM350F
B
VAM500F
B
VAM650F
B
VAM800F
B
VAM1000
FB
VAM1500
FB
VAM2000
FB 3
Current Minimum circuit amps (MCA) A 0.9 1.3 1.6 2.5 3.0 5.0
Maximum fuse amps (MFA) A 15 16
Fan motor rated output kW 0.03x2 0.08x2 0.106x2 0.210x2 0.210x4
Full load amps Fan motor A 0.4 0.6 0.7 1.1 1.3 2.2
(FLA) Fan motor 2 A 0.4 0.6 0.7 1.1 1.3 2.2 2
Fan motor 3 A - 2.2
Fan motor 4 A - 2.2
Normal amps - 50Hz Heat Ultra A 0.67 0.72 0.60 0.81 0.93 1.69 1.71 3.76 3.87
exchan high
ge High A 0.57 0.49 0.62 1.23 1.25 3.04 3.16
mode
Low A 0.33 0.32 0.19 0.34 0.35 0.46 0.76 1.42 1.32
Bypass Ultra A 0.67 0.72 0.60 0.81 0.93 1.69 1.71 3.76 3.87
mode high
High A 0.57 0.49 0.62 1.23 1.25 3.04 3.16
Low A 0.33 0.32 0.19 0.34 0.35 0.46 0.76 1.42 1.32
Normal amps - 60Hz Heat Ultra A 0.66 0.64 0.60 0.81 0.93 1.69 1.71 3.76 3.87
exchan high
ge High A 0.59 0.56 0.49 0.62 1.23 1.25 3.04 3.16
mode
Low A 0.33 0.29 0.19 0.34 0.35 0.46 0.76 1.42 1.32
Bypass Ultra A 0.66 0.64 0.60 0.81 0.93 1.69 1.71 3.76 3.87
mode high
High A 0.59 0.56 0.49 0.62 1.23 1.25 3.04 3.16
Low A 0.33 0.29 0.19 0.34 0.35 0.46 0.76 1.42 1.32

Notes
Operation sound is measured at 1.5m below the center of the body.
Air flow rate can be changed to Low mode or High mode.
Normal amplitude, input and efficiency depend on the mentioned conditions.
Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and
peripheral noise.
The noise level at the air discharge port is about 8dB higher than the operating sound of the unit.
The specifications, designs and information here are subject to change without notice.
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000)
Select wire size based on the value of MCA
Instead of a fuse, use a circuit breaker
MCA = 1.25 x FLA (FM1) + FLA (FM2)
MCA represents maximum input current. MFA represents capacity which may accept MCA.
Next lower standard fuse rating minimum 16A
Specifications measured at fan curve 8 (factory settings)

• Ventilation • VAM-FA/FB 5
• Indoor Unit • VAM-FA/FB

3 Electrical data
3-1 Electrical Data

VAM350-2000FB

Unit model name Power supply FM


50Hz 60Hz MCA MFA kW FLA
VAM350FB 0.9 16 0.08 x 2 0.4 x 2

3 VAM500FB 1.3 16 0.08 x 2 0.6 x 2


VAM650FB 1.6 16 0.106 x 2 0.7 x 2
Power supply Power supply
VAM800FB Max.: 264V Max.: 242V 2.5 16 0.210 x 2 1.1 x 2
Min.: 198V Min.: 198V
VAM1000FB 3.0 16 0.210 x 2 1.3 x 2
VAM1500FB 5.0 16 0.210 x 2 2.2 x 4
VAM2000FB 5.0 16 0.210 x 2 2.2 x 4

LEGEND

MCA : minimum circuit Amps. (A)


MFA : maximum fuse Amps. (A) (see note 5)
kW : fan motor rated output (kW)
FLA : full load Amps. (A)
FM : Fan motor

NOTES

1. Voltage range:
The units are suitable for use on electrical systems where the voltage, supplied to unit terminals, is not below or above listed range limits.
2. The maximum allowable voltage variation between phases is 2%.
3. MCA = 1.25 x FLA (FM1) + FLA (FM2)
MCA represents maximum unit input current.
MFA represents acceptable capacity for MCA.
(Next lower standard fuse rating minimum 16A).
4. Select a wire size based on the MCA value.
5. Instead of a fuse, use a circuit breaker.

4D082062

6 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

4 Options
4-1 Options

VAM150-250FA 3
Model
Item VAM150FA VAM250FA

Remote control BRC301B61


Wired remote control BRC1D52 / BRC1E52Z / BRC1E52B (note 6)
Central remote control DCS302C51 (for general) DCS302C51 (For EC market)

Controlling device
Centralized controlling device Unied on/off controller
Schedule timer
DCS301B61 (for general) DCS301B51 (For EC market)
DST301B51 (for general) DST301B51 (For EC market) 4
Wiring adapter for electrical appendices KRP2A61 (for general) KRP2A51 (For EC market)
For humidier KRP50-2
PC board adapter
Installation box for adapter PCB KRP50-2A90 (Mounted electric component assy of HRV)
For heater control kit BRP4A50

Model name - -
Silencer
Additional function Nominal pipe diameter (mm) - -
Air lter for replacement YAFF323F15 YAFF323F25
High efciency lter YAFF323F15 YAFF323F25
- -
Duct adapter
Nominal pipe diameter (mm) - -
Duct adapter - -
Adapter for discharge - -
Interlock adapter for VRV

Indoor unit FXYC-K FXYK-K FXYF-K FXYS-K FXYH-K FXYA-K FXYL(M)-KJ FXYM-K(J)
Adapter for wiring KRP1B61 * KRP1B61 KRP1B2 * KRP1B61 KRP1B3 KRP1B61
KRP1B96 KRP1C98 KRP1B93
Installation box for adapter PCB ** - - - - -
Note 2,3 Note 4 Note 3

NOTES

1. Installation box marked with ** is required for each adapter marked with *.
2. Up to 2 adapters can be xed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 adapters can be xed for each indoor unit.
5. Flexible duct size *** is for the duct from HRV unit to branch duct (or air outlet).
6. *BRC1E52A contains languages English, German, French, Dutch, Spanish, Italian, Greek, Portuguese, Russian, Turkish and Polish.
BRC1E52B contains languages English, German, Albanian, Bulgarian, Croatian, Czech, Hungarian, Romanian, Serbian, Slovak and Slovenian.

3TW24921-1B

VAM350-2000FB
Model type: ceiling mounted duct connection

Model
Item
VAM350FB VAM500FB VAM650FB VAM800FB VAM1000FB VAM1500FB VAM2000FB
Remote control BRC301B61
BRC1D52
Wired remote control
BRC1E52A / BRC1E52B *
Central remote control DCS302C51
Controlling
Centralized controlling device 8QL¿HGRQRIIFRQWUROOHU DCS301B51
device
Schedule timer DST301B51
:LULQJDGDSWHUIRUHOHFWULFDODSSHQGLFHV .53$LQVWDOODWLRQER[.53%$
PC board adapter )RUKHDWHURIKXPLGL¿HUNLW BRP4A50A
)L[LQJSODWH - EKMPVAM **
Model name - KDDM24B50 KDDM24B100 KDDM24B100 KDDM24B100 .''0%[ .''0%[
Silencer
Nominal pipe diameter (mm) - Ø 200 Ø 200 Ø 250 Ø 250 Ø 250 Ø 250
Additional
(10 EKAFV50F6 EKAFV80F6 EKAFV100F6 (.$)9)[ (.$)9)[
IXQFWLRQ
$LU¿OWHU(1 (1) (.$)9) (.$)9) (.$)9) (.$)9)[ (.$)9)[
(1) EKAFV50F8 EKAFV80F8 EKAFV100F8 (.$)9)[ (.$)9)[
CO2VHQVRU BRYMA65 BRYMA65 BRYMA65 BRYMA100 BRYMA100 BRYMA200 BRYMA200

NOTES

1. %5&($FRQWDLQVODQJXDJHV(QJOLVK*HUPDQ)UHQFK'XWFK6SDQLVK,WDOLDQ*UHHN3RUWXJXHVH5XVVLDQ7XUNLVKDQG3ROLVK
 %5&(%FRQWDLQVODQJXDJHV(QJOLVK*HUPDQ$OEDQLDQ%XOJDULDQ&URDWLDQ&]HFK+XQJDULDQ5RPDQLDQ6HUELDQ6ORYDNDQG6ORYHQLDQ
2. )L[LQJSODWHPDUNHGZLWK LVQHFHVVDU\IRULQVWDOODWLRQRIRSWLRQ3&ERDUGVRQ9$0)%9$0)%
3. +XPLGL¿HU KHDWHUNLWFDQQRWEHFRPELQHG
4. ,I\RXRUGHULQVWDQFHRIWKH¿OWHUUHIHUHQFHV\RXFDQXVHLWIRUHLWKHU6XSSO\VLGHRU([KDXVW6LGH

3D082107D

• Ventilation • VAM-FA/FB 7
• Indoor Unit • VAM-FA/FB

5 Exchange efficiency
5-1 Exchange efficiency

VAM350-2000FB

VAM350FB VAM500FB VAM650FB

VAM800FB
VAM800FB VAM1000FB

VAM1500FB VAM2000FB

NOTE 7HPSHUDWXUHH[FKDQJHHI¿FLHQF\

1. $WKLJKIDQVSHHG (QWKDOS\H[FKDQJHHI¿FLHQF\ KHDWLQJ

(QWKDOS\H[FKDQJHHI¿FLHQF\ FRROLQJ

3D082313

8 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

6 Dimensional drawings
6-1 Dimensional Drawings

VAM150FA 3
Maintenance space for the heat exchange elements, the air
Switch box filters and fans

Ceiling hook
Inspection hole 4-14x40 oval hole
285 Ø 450

269 Supply air fan 6

120~250
600
Maintenance over 104 120.3
149

20
67

SA OA
124 164

124
Supply air to room Fresh air from outdoors

288
509

560
288

(Outdoor air)

164
RA EA
Return air from room Exhaust air to outdoors
8 Sealing Sealing
8

120 104 718

20
149
Damper plate
Exhaust air fan
(Maintenance cover) Exhaust spacer
(Switch box)
145 760 145

Ø200
Ø97

Heat exchange elements Air filters

NOTE
1 Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans.

3TW27874-1

VAM250FA
Maintenance space for the heat exchange elements, the air
Switch box filters and fans

Ceiling hook
Inspection hole
285 Ø 450 4-14x40 oval hole

269 Supply air fan


120~250
600

149 Maintenance over


104 120.3
20
67

SA
OA
124 164

124

Supply air to room Fresh air from outdoors


288
509

560
288

(Outdoor air)
164

RA EA
Return air from room Exhaust air to outdoors
8
Sealing Sealing
8

120 104
20

718
149
Damper plate
Exhaust air fan
(Maintenance cover)
(Switch box)
145 760 145
Ø200
Ø97

Heat exchange elements Air filters

NOTE
1 Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans.

3TW27884-1

• Ventilation • VAM-FA/FB 9
• Indoor Unit • VAM-FA/FB

6 Dimensional drawings
6-1 Dimensional Drawings

VAM350FB
Ceiling hook
4 – 12 x 40 oval hole

Sealing Exhaust air fan


Damper plate

6 RA
EA Return air from room
Exhaust air to outdoors

SA
OA Supply air to room
Fresh air from outdoors Supply air fan
(outdoor air) Switch box

Inspection hole

Maintenance space for the heat exchange


element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans. 3D081162

VAM500FB
Ceiling hook
4 – 12 x 40 oval hole

Sealing Exhaust air fan


Damper plate

RA
EA Return air from room
Exhaust air to outdoors

SA
OA Supply air to room
Fresh air from outdoors
(outdoor air) Switch box Supply air fan

Inspection hole

Maintenance space for the heat exchange


element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspectthe air lters, the exchange elements and fans. 3D081163

10 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

6 Dimensional drawings
6-1 Dimensional Drawings

VAM650FB
Ceiling hook
3
4 – 12 x 40 oval hole
Sealing
Damper plate

Exhaust air fan

RA 6
EA Return air from room
Exhaust air to outdoors

SA
OA Supply air to room
Fresh air from outdoors Supply air fan
(outdoor air)
Switch box

Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans. 3D081164

VAM800FB
Ceiling hook
4 – 12 x 40 oval hole
Sealing
Damper plate

Exhaust air fan


RA
EA Return air from room
Exhaust air to outdoors

SA
OA Supply air to room
Fresh air from outdoors Supply air fan
(outdoor air)
Switch box

Inspection hole

Maintenance space for the heat exchange


element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans. 3D081165

• Ventilation • VAM-FA/FB 11
• Indoor Unit • VAM-FA/FB

6 Dimensional drawings
6-1 Dimensional Drawings

VAM1000FB
Ceiling hook
4 – 12 x 40 oval hole
Sealing
Damper plate

Exhaust air fan


6 RA
Return air from room
EA
Exhaust air to outdoors

SA
Supply air to room
OA
Fresh air from outdoors Supply air fan
(outdoor air)
Switch box

Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans. 3D081166

VAM1500FB
Ceiling hook
4 – 14 x 40 oval hole
Sealing Exhaust air fan (2x)
Damper plate

EA RA
Exhaust air to outdoors Return air from room

OA SA
Fresh air from outdoors Supply air to room
(outdoor air)
Switch box Supply air fan (2x)

Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans. 3D081167

12 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

6 Dimensional drawings
6-1 Dimensional Drawings

VAM2000FB 3
Ceiling hook
Sealing 4 – 14 x 40 oval hole
Damper plate
Exhaust air fan (2x)

EA
RA 6
Exhaust air to outdoors Return air from room

SA
OA Supply air to room
Fresh air from outdoors
(outdoor air) Supply air fan (2x)

Switch box

Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans

Heat exchange element

Maintenance cover Air lters Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans. 3D081168

• Ventilation • VAM-FA/FB 13
• Indoor Unit • VAM-FA/FB

7 Centre of gravity
7-1 Centre of Gravity

VAM350-500FB

Design ref. AA AB AC
VAM350FB 24 51 10
VAM500FB 23 36 9

NOTES

1. The shown unit is VAM350FB


4D081262

VAM650-800FB

Design ref. AA AB AC
VAM650FB 20 42 6
VAM800FB 32 58 5

NOTES

1. The shown unit is VAM650FB


4D081263

14 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

7 Centre of gravity
7-1 Centre of Gravity

VAM1000FB 3

4D081264

VAM1500FB

4D081265

• Ventilation • VAM-FA/FB 15
• Indoor Unit • VAM-FA/FB

7 Centre of gravity
7-1 Centre of Gravity

VAM2000FB

4D081266

16 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase

9$0)$ 3

Power supply Wiring diagram


single phase
220-240/220V
8
50/60Hz
External output terminals

Adapter for wiring


(optionl accessories) (KRP50-2)

Switch box
Terminals for the
input from outside

Terminals for the


centralized control

Remote control
(optional accessories)

L - RED N - BLU M2F Motor (exhaust fan motor) Optional accessories


A1P Printed circuit board Q1L Q2L Thermo switch (MF1 2 built-in) Adapter for wiring (KRP50-2)
C1R C2R Capacitor (M1F M2F) R1T Thermistor (indoor air) Ry1 Magnetic relay (On/Off)
F1U Fuse (250V, 10A) R2T Thermistor (outdoor air) Ry2 Magnetic relay (humidifier operation)
K1R ~ K3R Magnetic relay (M1F) S1W Limit switch X9A 10A Connector (KRP50-20)
K4R ~ K6R Magnetic relay (M2F) T1R Transformer (supply 220-240V/22V) Remote control
K7R Magnetic relay (M1D) X1M Terminal (power supply) SS1 Selector switch (main/sub)
M1D Motor (damper motor) X2M Terminal (control) Optional connector
M1F Motor (air supply fan motor) X11A Connector (adapter power supply)

: Terminals Colors: BLK: Black GRN: Green

, : Connector BLU: Blue RED: Red


: Wire clamp BRN: Brown WHT: White
: Field wiring ORN: Orange YLW: Yellow
: Protective earth
2TW24836-1C
! Before obtaining access to terminal devices, all power supply circuits must be interrupted.

! Clean the heat exchange elements once every two years or more often and the air filter once a year or more often. (Before cleaning, make sure
that the unit is not operating.)

To prevent electric shock hazards, provide grounding work according to the installation manual.

• Ventilation • VAM-FA/FB 17
• Indoor Unit • VAM-FA/FB

8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase

VAM350-650FB

Measuring
points for
voltage
8 220-240V/220V
~
50/60Hz
Printed circuit board

Caution when performing service


inside the EL. Compo. box

WARNING Caution for ELECTRIC SHOCK

Indoor 1 Do not open the EL. Compo. box cover for 10 minutes
after the power supply is turned off.
2 After opening the EL. Compo. box, measure the points
VKRZQDWWKHULJKWZLWKDWHVWHUDQGFRQ¿UPWKDWWKH
voltage of the capacitor in the main circuit is less than
DC50V

See note 1

Control box
Wired remote control
(opt. accessory)

A1P Printed circuit board Field earth leak detector REMOTE CONTROL
Q1DI
C1 Capacitor (M1F) (Max. 300 mA) SS1 Selector switch
F1U Fuse T, 6.3A, 250V (A1P) R1T Thermistor (Indoor air) CONNECTOR FOR OPTION (See note 3)
F1U Fuse T, 5A, 250V (A1P) R2T Thermistor (Outdoor air) X14A Connector (CO2 sensor)
HAP Pilot lamp (Service monitor - green) R3T Thermistor (PTC) X24A Connector (Outside damper)
K1R Magnetic relay S1C Limit switch damper motor X26A Connector (Filter sign)
K2R Magnetic relay X1M Terminal (A1P) X33A Connector (Contact PCB)
L1R Reactor X2M Terminal (Outside input) (A1P) X35A Connector (Appendices PCB)
M1F Motor (Supply air fan) X3M Terminal (Power supply) X38A Connector (Multi tenant)
M2F Motor (Exhaust air fan) V1R Diode bridge X41A Connector (Humidity sensor 1)
M1D Motor (Damper) Z1F 1RLVH¿OWHU X42A Connector (Humidity sensor 2)
PS Switching power supply (A1P)

: Live : Connection Colors: Black White


: Neutral : Relay connector Blue Yellow
: Field wiring : Protective earth (screw) Orange Green
: Terminal strip : Noiseless earth Red
: Connector
3D080682B
NOTES

1 In case you use the central remote control, connect it to the unit in accordance with the attached manual.
2 When connecting the input wires from outside, fresh-up or on/off control operation can be selected. (Contact with a minimum applicable load of 12V DC, 1mA)
3 For details of connection see the attached manual of the option kit.
4 SS1 (A1P) has already been set to “nor.” at factory set. The unit will not run if the setting is changed.

18 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase

VAM800-1000FB 3
Caution when performing service inside the EL. Compo. box

WARNING Caution for ELECTRIC SHOCK


Measuring points
for voltage
1 Do not open the EL. Compo. box cover for 10 minutes after the power supply is turned
off. 8
2 After opening the EL. Compo. box, measure the points shown at the right with a tester
DQGFRQ¿UPWKDWWKHYROWDJHRIWKHFDSDFLWRULQWKHPDLQFLUFXLWLVOHVVWKDQ'&9
Printed circuit board

220-240V/220V
~
+]

Indoor

Control box

See note 1

Wired remote control


(opt. accessory)

A1P Printed circuit board M1D Motor (Damper) REMOTE CONTROL


A2P Printed circuit board assy (Fan) PS Switching power supply (A1P) SS1 Selector switch
A3P Printed circuit board assy (Fan) Field earth leak detector CONNECTOR FOR OPTION (See note 3)
Q1DI
C1 Capacitor (M1F) (Max. 300 mA) X14A Connector (CO2 sensor)
F1U )XVH7$9 $3 R1T Thermistor (Indoor air) X24A Connector (Outside damper)
F3U )XVH7$9 $3 R2T Thermistor (Outdoor air) X26A Connector (Filter sign)
HAP Pilot lamp (Service monitor - green) R3T Thermistor (PTC) X33A Connector (Contact PCB)
K1R Magnetic relay S1C Limit switch damper motor ;$ Connector (Appendices PCB)
K2R Magnetic relay X1M Terminal (A1P) X38A Connector (Multi tenant)
L1R Reactor X2M Terminal (Outside input) (A1P) X41A Connector (Humidity sensor 1)
L2R Reactor X3M Terminal (Power supply) X42A Connector (Humidity sensor 2)
M1F Motor (Supply air fan) V1R Diode bridge
M2F Motor (Exhaust air fan) Z1F 1RLVH¿OWHU

: Live : Connection Colors: Black White


: Neutral : Relay connector Blue Yellow
: Field wiring : Protective earth (screw) Orange Green
: Terminal strip : Noiseless earth Red
: Connector
2D080683A
NOTES

1 In case you use the central remote control, connect it to the unit in accordance with the attached manual.
2 When connecting the input wires from outside, fresh-up or on/off control operation can be selected. (Contact with a minimum applicable load of 12V DC, 1mA)
3 For details of connection see the attached manual of the option kit.
4 SS1 (A1P) has already been set to “nor.” qt factory set. The unit will not run if the setting is changed.

• Ventilation • VAM-FA/FB 19
• Indoor Unit • VAM-FA/FB

8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase

VAM1500-2000FB
Caution when performing service inside the EL. Compo. box

Measuring
WARNING Caution for ELECTRIC SHOCK points for
voltage

220-240V/220V
8 ~
Printed circuit board
50/60Hz
Indoor 1 Do not open the EL. Compo. box cover for 10 minutes
after the power supply is turned off.
2 After opening the EL. Compo. box, measure the points
shown at the right with a tester and conrm that the
voltage of the capacitor in the main circuit is less than
DC50V

See note 1

Wired remote control


(opt. accessory)

Control box

A1P Printed circuit board M4F Motor (Supply air fan) (Top) V1R Diode bridge
A2P - A4P Printed circuit board assy (Fan) M1D,M2D Motor (Damper) Z1F Noise lter
A5P Printed circuit board assy (Fan) PS Switching power supply (A1P) REMOTE CONTROL
C1 Capacitor (M1F) Q1DI, Field earth leak detector SS1 Selector switch
F1U Fuse T, 6.3A 250V (A1P) Q2DI (Max. 300 mA) CONNECTOR FOR OPTION (See note 3)
F3U Fuse T, 5A, 250V (A1P) R1T Thermistor (Indoor air) X14A Connector (CO2 sensor)
HAP Pilot lamp (Service monitor - green) R2T Thermistor (Outdoor air) X24A Connector (Outside damper)
K1R Magnetic relay R3T Thermistor (PTC) X26A Connector (Filter sign)
K2R, K5R Magnetic relay S1C, S2C Limit switch damper motor X33A Connector (Contact PCB)
L1R - L4R Reactor X1M Terminal (A1P) X35A Connector (Appendices PCB)
M1F Motor (Exhaust air fan) (Bottom) X2M Terminal (Outside input) (A1P) X41A Connector (Humidity sensor 1)
M2F Motor (Supply air fan) (Bottom) X3M Terminal (Power supply) X42A Connector (Humidity sensor 2)
M3F Motor (Exhaust air fan) (Top)

: Live : Connection Colors: Black White


: Neutral : Relay connector Blue Yellow
: Field wiring : Protective earth (screw) Orange Green
: Terminal strip : Noiseless earth Red
: Connector
2D080684A
NOTES

1 In case you use the central remote control, connect it to the unit in accordance with the attached manual.
2 When connecting the input wires from outside, fresh-up or on/off control operation can be selected. (Contact with a minimum applicable load of 12V DC, 1mA)
3 For details of connection see the attached manual of the option kit.
4 SS1 (A1P) has already been set to “nor.” at factory set. The unit will not run if the setting is changed.

20 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

9 Sound data
9-1 Sound Power Spectrum

VAM150FA VAM250FA 3
Power level data (in case of Total Heat Exchange mode) Power level data (in case of Total Heat Exchange mode)
(dB) (dB)
Power Hz Power Hz
Model 63 125 250 500 1000 2000 4000 8000 Model 63 125 250 500 1000 2000 4000 8000
supply NOTCH supply NOTCH
U-H 50 48 46 40.5 38.5 34 25.5 27 U-H 51.5 51 48 42 38.5 33.5 25.5 25.5
9
220V H 47 47 42 40 37.5 27.5 25 26.5 220V H 49.5 48.5 46 40 36.5 29 22 23.5

L 44 42 38.5 35.5 29.5 21.5 22.5 23.5 L 44.5 44 42 34 28 19.5 21 22

U-H 51 49 47 41.5 39.5 35 27 28.5 U-H 52 51.5 47 43 39.5 34 27 27

50Hz 230V H 47.5 47.5 42.5 39.5 37 28.5 26 27.5 50Hz 230V H 50.5 49.5 47 41 37.5 30 24.5 26

L 44 42 38.5 36 29.5 21.5 22.5 23.5 L 44.5 44.5 42 35 28 19.5 21 22


VAM150FA VAM250FA
U-H 53 50.5 46.5 42 40 36.5 30 31.5 U-H 51.5 52.5 48 44.5 41 36 29 29.5

240V H 49.5 49.5 45 42 39.5 31.5 29.5 31.5 240V H 52 52 48.8 40.5 37 32.5 28 30

L 44.5 42.5 39.5 36 30 22.5 23.5 25 L 45 44.5 43 34.5 28.5 21 22.5 23.5

U-H 52 51 46 42.5 39.5 33.5 24.5 27 U-H 51.5 52 49 43.5 39.5 34 25.5 25.5

60Hz 220V H 49 49 44.5 40.5 37 29.5 26 27.5 60Hz 220V H 49 50 45.5 40 38 30 24.5 26

L 41 42 39 35.5 29 21 21.5 23.5 L 44.5 41 39 34.5 30.5 20 20 22

NOTES NOTES

1. Operation sound is measured in an anechoic chamber. 1. Operation sound is measured in an anechoic chamber.
2. The operating sound level may become greater than this value depending on the 2. The operating sound level may become greater than this value depending on the
operating conditions, reected sound and peripheral noise. operating conditions, reected sound and peripheral noise.
3. Operation sound differs with operation and ambient conditions. 3. Operation sound differs with operation and ambient conditions.
4. The power IeveIs have been caIcuIated on the assumption that the measuring point were 4. The power IeveIs have been caIcuIated on the assumption that the measuring point were
right under the source of operating sound. right under the source of operating sound.
4D036765 4D036766

VAM350FB VAM500FB

Power level data (in case of Total Heat Exchange mode) Power level data (in case of Total Heat Exchange mode)

(dB) (dBA) (dB) (dBA)


Unit model Hz Unit model Hz
63 125 250 500 1000 2000 4000 8000 Total 63 125 250 500 1000 2000 4000 8000 Total
name Fan speed name Fan speed
U-H 57.5 53.0 49.5 45.0 42.5 39.5 31.5 25.5 48 U-H 57.0 54.0 51.0 48.0 45.0 37.5 27.5 25.5 50

VAM350FB H 58.5 51.0 46.5 43.5 40.5 35.0 26.0 26.5 46 VAM500FB H 54.0 51.5 49.0 46.0 42.5 36.0 26.5 26.0 48

L 58.5 45.5 41.5 38.0 33.5 24.0 25.0 27.0 41 L 50.5 47.5 44.0 39.0 33.5 25.0 23.0 24.5 41

NOTES NOTES

1. dBA = A-weighted sound power level (A-scale according to IEC). 1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m2 2. Reference acoustic intensity 0dB = 10E-6μW/m2
3. Measured according to ISO 3744. 3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating 4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is 5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound. immediately under the source of operating sound.

4D082464 4D082465

• Ventilation • VAM-FA/FB 21
• Indoor Unit • VAM-FA/FB

9 Sound data
9-1 Sound Power Spectrum

VAM650FB VAM800FB

Power level data (in case of Total Heat Exchange mode) Power level data (in case of Total Heat Exchange mode)

(dB) (dBA) (dB) (dBA)


Unit model Hz Unit model Hz
63 125 250 500 1000 2000 4000 8000 Total 63 125 250 500 1000 2000 4000 8000 Total
name Fan speed name Fan speed
9 U-H 62.0 58.0 52.5 48.5 45.5 41.5 34.0 26.0 51 U-H 58.0 58.0 52.5 49.5 48.5 41.5 33.5 26.0 53

VAM650FB H 61.0 56.5 51.0 47.0 44.5 39.0 30.0 26.0 50 VAM800FB H 58.5 57.0 51.5 49.5 47.0 40.5 31.0 27.5 52

L 53.5 50.5 46.0 42.0 37.5 32.0 24.0 25.5 44 L 54.5 54.5 47.5 44.5 43.0 35.5 24.5 23.5 47

NOTES NOTES

1. dBA = A-weighted sound power level (A-scale according to IEC). 1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m2 2. Reference acoustic intensity 0dB = 10E-6μW/m2
3. Measured according to ISO 3744. 3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating 4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is 5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound. immediately under the source of operating sound.

4D082466 4D082467

VAM1000FB VAM1500FB

Power level data (in case of Total Heat Exchange mode) Power level data (in case of Total Heat Exchange mode)

(dB) (dBA) (dB) (dBA)


Unit model Hz Unit model Hz
63 125 250 500 1000 2000 4000 8000 Total 63 125 250 500 1000 2000 4000 8000 Total
name Fan speed name Fan speed
U-H 62.0 58.5 54.0 50.5 49.0 42.0 36.5 28.0 53 U-H 60.5 61.0 55.5 52.5 50.5 46.0 39.5 29.5 55

VAM1000FB H 61.0 57.0 52.0 50.0 48.0 38.5 31.0 25.5 52 VAM1500FB H 60.5 60.0 53.5 51.5 49.5 44.5 37.0 31.0 54

L 58.0 55.0 49.0 45.5 43.5 36.5 27.5 24.0 48 L 58.5 58.0 51.0 49.0 47.0 39.5 30.5 31.0 51

NOTES NOTES

1. dBA = A-weighted sound power level (A-scale according to IEC). 1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m2 2. Reference acoustic intensity 0dB = 10E-6μW/m2
3. Measured according to ISO 3744. 3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating 4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is 5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound. immediately under the source of operating sound.

4D082468 4D082469

22 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

9 Sound data
9-1 Sound Power Spectrum

VAM2000FB 3
Power level data (in case of Total Heat Exchange mode)

(dB) (dBA)
Unit model Hz
63 125 250 500 1000 2000 4000 8000 Total
name Fan speed
U-H 65.0 61.5 57.0 54.0 53.0 45.0 39.5 32.5 57 9
VAM2000FB H 64.0 60.0 55.0 53.0 51.0 41.5 34.5 30.5 55

L 62.0 58.0 51.5 50.0 48.5 40.5 32.5 30.5 53

NOTES

1. dBA = A-weighted sound power level (A-scale according to IEC).


2. Reference acoustic intensity 0dB = 10E-6μW/m2
3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound.

4D082470

• Ventilation • VAM-FA/FB 23
• Indoor Unit • VAM-FA/FB

9 Sound data
9-2 Sound Pressure Spectrum

VAM150FA VAM250FA
Octave band sound pressure level dB (0dB = 0.0002— bar)

Octave band sound pressure level dB (0dB = 0.0002— bar)


VAM150FA VAM250FA

Approximate Approximate
threshold threshold
hearing for hearing for
continuous noise continuous noise

Octave band center frequency (Hz) 4D036868 Octave band center frequency (Hz) 4D036870
NOTES NOTES
1. Over All (dB): Air ow rate 1. Over All (dB): Air ow rate
(B,G,N is already rectied) Scale (B,G,N is already rectied) Scale
U-H H I U-H H I
2. Operating conditions: A 27 26 20.5
2. Operating conditions: A 28 26 21
• Power source: • Power source:
C C
Model: VAM150FA Model: VAM250FA
• Ventilation mode: Total heat exchange • Ventilation mode: Total heat exchange
3. Measuring place: 3. Measuring place:
• Operation noise is measured in an anechoic chamber. • Operation noise is measured in an anechoic chamber.
• The operation noise level becomes greater than this value depending on the operation • The operation noise level becomes greater than this value depending on the operation
conditions, reected sound and peripheral noise. conditions, reected sound and peripheral noise.
• Operation noise differs with operation and ambient conditions. • Operation noise differs with operation and ambient conditions.
• U-H: ultra-high, H: high, L: low • U-H: ultra-high, H: high, L: low
4. Operation noise differs with operation and ambient conditions 4. Operation noise differs with operation and ambient conditions
5. Location of microphone. 5. Location of microphone.

1.5m 1.5m

measuring point measuring point

VAM350FB VAM500FB
2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU

2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU

9$0)% 9$0)%

$SSUR[LPDWH $SSUR[LPDWH
WKUHVKROG WKUHVKROG
KHDULQJIRU KHDULQJIRU
FRQWLQXRXVQRLVH FRQWLQXRXVQRLVH

2FWDYHEDQGFHQWHUIUHTXHQF\ +] 2FWDYHEDQGFHQWHUIUHTXHQF\ +]
4D082471 4D082472
$LUÀRZUDWH G% $LUÀRZUDWH G%
U-H H L U-H H L
32 31.5 23.5 33 31.5 24.5

NOTES NOTES
1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH 1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH
2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU 2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU
3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ 3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV 4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV
5. 8+XOWUDKLJK+KLJK/ORZ 5. 8+XOWUDKLJK+KLJK/ORZ
6. /RFDWLRQRIPLFURSKRQH 6. /RFDWLRQRIPLFURSKRQH

P P

PHDVXULQJSRLQW PHDVXULQJSRLQW

24 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

9 Sound data
9-2 Sound Pressure Spectrum

VAM650FB VAM800FB 3
2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU

2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU


9$0)% 9$0)%

$SSUR[LPDWH $SSUR[LPDWH
WKUHVKROG WKUHVKROG
KHDULQJIRU KHDULQJIRU
FRQWLQXRXVQRLVH FRQWLQXRXVQRLVH

2FWDYHEDQGFHQWHUIUHTXHQF\ +] 2FWDYHEDQGFHQWHUIUHTXHQF\ +]
4D082473 4D082474
$LUÀRZUDWH G% $LUÀRZUDWH G%
U-H H L U-H H L
34.5 33 27 35.5 34.5 31

NOTES NOTES
1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH 1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH
2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU 2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU
3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ 3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV 4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV
5. 8+XOWUDKLJK+KLJK/ORZ 5. 8+XOWUDKLJK+KLJK/ORZ
6. /RFDWLRQRIPLFURSKRQH 6. /RFDWLRQRIPLFURSKRQH

P P

PHDVXULQJSRLQW PHDVXULQJSRLQW

VAM1000FB VAM1500FB
2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU

2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU

9$0)% 9$0)%

$SSUR[LPDWH $SSUR[LPDWH
WKUHVKROG WKUHVKROG
KHDULQJIRU KHDULQJIRU
FRQWLQXRXVQRLVH FRQWLQXRXVQRLVH

2FWDYHEDQGFHQWHUIUHTXHQF\ +] 2FWDYHEDQGFHQWHUIUHTXHQF\ +]
4D082475 4D082476
$LUÀRZUDWH G% $LUÀRZUDWH G%
U-H H L U-H H L
36 35 31.5 39.5 38 34

NOTES NOTES
1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH 1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH
2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU 2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU
3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ 3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV 4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV
5. 8+XOWUDKLJK+KLJK/ORZ 5. 8+XOWUDKLJK+KLJK/ORZ
6. /RFDWLRQRIPLFURSKRQH 6. /RFDWLRQRIPLFURSKRQH

P P

PHDVXULQJSRLQW PHDVXULQJSRLQW

• Ventilation • VAM-FA/FB 25
• Indoor Unit • VAM-FA/FB

9 Sound data
9-2 Sound Pressure Spectrum

VAM2000FB 2FWDYHEDQGVRXQGSUHVVXUHOHYHOG% G% —EDU

9$0)%

$SSUR[LPDWH
WKUHVKROG
KHDULQJIRU
FRQWLQXRXVQRLVH

2FWDYHEDQGFHQWHUIUHTXHQF\ +]
4D082477
$LUÀRZUDWH G%
U-H H L
40 38 35

NOTES
1. 9HQWLODWLRQPRGHWRWDOKHDWH[FKDQJH
2. 2SHUDWLRQQRLVHLVPHDVXUHGLQDQDQHFKRLFFKDPEHU
3. 7KHRSHUDWLRQQRLVHOHYHOPD\EHFRPHKLJKHUWKDQWKLVYDOXHGHSHQGLQJRQWKHRSHUDWLRQ
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
4. 2SHUDWLRQQRLVHGLIIHUVZLWKRSHUDWLRQDQGDPELHQWFRQGLWLRQV
5. 8+XOWUDKLJK+KLJK/ORZ
6. /RFDWLRQRIPLFURSKRQH

P

PHDVXULQJSRLQW

26 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

10 Fan characteristics
10 - 1 Fan Characteristics

VAM150FA 3
50 Hz, 220-240V
60Hz, 220V Exchange efciency

VAM150FA
Tem
per
atu
10
re e
xch
ang
En ee
tha fci
lpy enc
exc y
han
ge
ef
cie
En ncy
tha (he
lpy atin
exc g)
han
ge
ef
External static pressure cie
ncy
(co
olin
Ultra-High g)

High
(Pa)

ø100
Pipe length

Air ow rate (m3/h)

4D036773

VAM250FA

50 Hz, 220-240V
60Hz, 220V Exchange efciency

VAM250FA

Tempe
ra ture e
xchan
ge ef
ciency
Entha
lpy ex
External static pressure chang
e efc
iency
Enthalp (heatin
y exch g)
ange e
fcienc
y (coo
ling)

Ultra-High
High
(Pa)

Low

Air ow rate (m3/h)

4D036774

• Ventilation • VAM-FA/FB 27
• Indoor Unit • VAM-FA/FB

10 Fan characteristics
10 - 1 Fan Characteristics

VAM350FB

UH speed H speed

10

External static pressure (Pa)

External static pressure (Pa)


External static pressure (Pa)

up
pe
r li
mi
tU
H-
sp
up ee
pe d Airow (m3/h) Airow (m3/h)
Fa r li
cto mi
ry tH
Fa se -sp
cto tU ee
ry H- d
low set sp
ee L speed
er H -sp d
lim ee
it U d
low H-s
er l pee
upp imi
tH d External static pressure (Pa)
er li -sp
Fac mit eed
tory L-s
set pee
lowe L-sp d
r lim e ed
it L-s
peed

Airow (m3/h)

UH Speed
H Speed
L Speed

NOTES
Airow (m3/h)

1. The fan speeds are valid for 230V 50Hz power supply 3D082177

VAM500FB

UH speed H speed
External static pressure (Pa)

External static pressure (Pa)


External static pressure (Pa)

up
pe
r li
mi
Fa tU
cto H-
ry sp
up se ee
pe tU d Airow (m3/h) Airow (m3/h)
r li H-
mi sp
low tH ee
er -sp d
up lim ee
pe Fact it U
H-
d L speed
r li or sp
mi y s
low t L et ee
er -sp H d
lim ee -sp
Fac it H d ee
-sp d
tory
External static pressure (Pa)

set e ed
low L-s
er li pee
mit d
L-s
pee
d

Airow (m3/h)

UH Speed
H Speed
L Speed

NOTES Airow (m3/h)

1. The fan speeds are valid for 230V 50Hz power supply 3D082178

28 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

10 Fan characteristics
10 - 1 Fan Characteristics

VAM650FB 3
UH speed H speed

External static pressure (Pa)


External static pressure (Pa)
10
External static pressure (Pa)

up
pe
r li
mi
tU
H-
sp
Fa ee
cto d
up ry
se Airow (m3/h) Airow (m3/h)
pe tU
r li H-
mi sp
low tH ee
e -sp d
Fa r limi ee
d L speed
c tU
upp tory H -sp
er l set
imi H ee
Fac lowe t L- -spe d
tory r li spe e
set mit H ed d
External static pressure (Pa)

L-s -
lowe pee speed
r lim d
it L-
spe
ed

Airow (m3/h)

UH Speed
H Speed
L Speed

NOTES Airow (m3/h)

1. The fan speeds are valid for 230V 50Hz power supply 3D082179

VAM800FB

UH speed H speed
External static pressure (Pa)
External static pressure (Pa)

up
pe
r li
External static pressure (Pa)

Fa mi
cto up tU
ry pe H-
se r li sp
tU mi ee
H- tH d
sp -sp
ee ee
up
pe
Fa
cto
d d Airow (m3/h) Airow (m3/h)
r lim ry
it L se
-sp tH
low ee -sp
er d low ee L speed
lim er d
it H lim
-sp it U
ee H-
d sp
Fa ee
External static pressure (Pa)

low cto d
er ry
lim se
it L tL
-sp -sp
ee ee
d
d

Airow (m3/h)
UH Speed
H Speed
L Speed

NOTES Airow (m3/h)

1. The fan speeds are valid for 230V 50Hz power supply 3D082180

• Ventilation • VAM-FA/FB 29
• Indoor Unit • VAM-FA/FB

10 Fan characteristics
10 - 1 Fan Characteristics

VAM1000FB

UH speed H speed

External static pressure (Pa)


External static pressure (Pa)
10

up
pe
rl
Fa im
cto it
External static pressure (Pa)

up UH
ry pe -s
se rl pe
tU im ed
up H- it H
pe sp -s
r li ee pe
mi d ed
tL
-sp Airow (m3/h) Airow (m3/h)
ee
d
lo
we L speed
Fa rl
cto im
ry it
se UH
lo tL -s
we -sp pe
low rl ee ed
im d
er it
lim H- External static pressure (Pa)
it L sp
-sp ee
ee d
d
Fac

Airow (m3/h)
tory
set

UH Speed
H-s

H Speed
pee

L Speed
d

Airow (m3/h)
NOTES

1. The fan speeds are valid for 230V 50Hz power supply 3D082181

VAM1500FB

UH speed H speed
External static pressure (Pa)

External static pressure (Pa)

up
pe
rl
External static pressure (Pa)

up

Fa im
pe

cto it
H-
rl
im

ry sp
se
it

ee
tH
UH

d
-sp
-s

up ee
p

Airow (m3/h) Airow (m3/h)


ee

pe d
d

r li
mi
tL
-sp
lo

ee
we

L speed
Fa

d
rl

cto

Fa lo
im

cto w
it

ry

er
U

ry lim
se
H-

se
it
sp

tU

tL H
External static pressure (Pa)

-s
ee

-s
H-

low pe
d

ed pe
sp

er ed
ee

lim
d

it L
-s
pe
ed

Airow (m3/h)
UH Speed
H Speed
L Speed

NOTES Airow (m3/h)

1. The fan speeds are valid for 230V 50Hz power supply 3D082182

30 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

10 Fan characteristics
10 - 1 Fan Characteristics

VAM2000FB 3
UH speed H speed

External static pressure (Pa)

External static pressure (Pa)


10
External static pressure (Pa)

up
pe
Fa

lim r
ct
or

it
y

UH
se
lo

Airow (m3/h) Airow (m3/h)


-s
tU
w

pe
er
up it U

ed
-s
lim

Fa
pe H

ct
ee
r l -s

or L speed
im pe

up lo y s
it ed

w et
H-

pe er H
sp

rl lim -s
im
ee

Fa it it pee
d

cto L -s H-s d
ry pe p
low se
t
ed ee
d External static pressure (Pa)
er L-
lim sp
it L ee
-s d
pe
ed

Airow (m3/h)
UH Speed
H Speed
L Speed

NOTES Airow (m3/h)

1. The fan speeds are valid for 230V 50Hz power supply 3D082183

• Ventilation • VAM-FA/FB 31
• Indoor Unit • VAM-FA/FB

11 Air filter characteristics


11 - 1 Air filter characteristics

VAM350-2000FB

High efficiency filter / dust filter for VAM350-2000FB


1 Information for filter selection
11 1 Choose required airflow
2 Choose the filters
3 Add up all the pressure drops of the duct system on the installation site and the filters
[For filter characteristics, refer to D-drawings]
4 Compare this with the unit performance characteristics to see resulting airflow & ESP
Download the VAM selection software on the Daikin extranet for easy selection

1 - 1 Choose required airflow


Choose the required airflow based upon the application/information

1 - 2 Choose the filters


Depending on the application prefilters and/or dust filters will be needed.
Filter requirements according to EN779: 2012

Table: Recommended dust filter classes per filter section (definition of filter classes according to EN 779)

Outdoor Air Quality Indoor Air Quality


IDA 1 (High) IDA 2 (Medium) IDA 3 (Moderate) IDA 4 (Low)
ODA 1 (pure air) N/A F8 F7 F5
ODA 2 (dust) N/A F6+F8 F5+F7 F5+F6
ODA 3 (very high concentrations of N/A N/A F5+F7 F5+F6
dust of gases)
*) GF = Gas filter (carbon filter) and/or chemical filter
Outdoor air Quality: Indoor air Quality:
ODA 1 - Pure air IDA 1 - Optium quality air (hospitals, laboratories, nursery)
ODA 2 - High concentration particles air IDA 2 - Good quality air (offices, residences, museum,...)
ODA 3 - High concetration gas pollution IDA 3 - Medium quality air (commercial buildings, cinema, theatre, room hotels,
ODA 4 - High concentration gas pollution and particles restaurants, bars, gym, computer room)
ODA 5 - Very high concentration gas pollution and particles
On the image below it is indicated where the standard prefilters and optional dust filters are installed. If 2 optional dust filters are used, the
second one replaces the standard filter.

OUTDOOR INDOOR

DUST FILTER

EA SA
(Exhaust air to outdoor) (Supply air - Feed air to room)

OA RA
(Outdoor air-fresh from outdoor) (Return air - Exhaust air from)

PREFILTER PREFILTER

NOTE

1 Prefilters are factory mounted, M6, F7 and F8 dust filters are options

32 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

11 Air filter characteristics


11 - 1 Air filter characteristics

VAM350-2000FB 3
1-3 Add up all the pressure drops of the duct system on the installation site and the filters
[For filter characteristics, refer to D-drawings]

unit airflow (m³/h) filter pressure drop 11


M6 F7 F8
VAM350F 350 39 52 88
VAM500F 500 65 87 148
VAM650F 650 61 83 140
VAM800F 800 89 121 206
VAM1000F 1000 80 109 185
VAM1500F 1500 79 106 181
VAM2000F 2000 80 109 185

NOTES

1 Table shows values at nominal level, refer to drawings for detailed information
2 Filters according to EN779:2012
3 For more information refer to VAM installation, operation manual or filter manual
To adjust static pressure after filter placement:

Setting mode Setting switch No. Description of setting


2 SA fan speed setting
19 (29)
3 EA fan speed setting

• Ventilation • VAM-FA/FB 33
• Indoor Unit • VAM-FA/FB

11 Air filter characteristics


11 - 1 Air filter characteristics

9$0)%
9$0)%
3UHVVXUHGURS 3D

11

$LUÀRZ PK

(.$)9)
(.$)9)
(.$)9)
'

9$0)%
9$0)%
3UHVVXUHGURS 3D

$LUÀRZ PK

(.$)9)
(.$)9)
(.$)9) '

34 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

11 Air filter characteristics


11 - 1 Air filter characteristics

9$0)%
3UHVVXUHGURS 3D 3

11

$LUÀRZ PK

(.$)9) [ ¿OWHUV


(.$)9) [ ¿OWHUV
(.$)9) [ ¿OWHUV '

9$0)%
3UHVVXUHGURS 3D

$LUÀRZ PK

(.$)9) [ ¿OWHUV


(.$)9) [ ¿OWHUV
(.$)9) [ ¿OWHUV '

• Ventilation • VAM-FA/FB 35
• Indoor Unit • VAM-FA/FB

11 Air filter characteristics


11 - 1 Air filter characteristics

9$0)%

3UHVVXUHGURS 3D

11

$LUÀRZ PK

(.$)9) [ ¿OWHUV


(.$)9) [ ¿OWHUV
(.$)9) [ ¿OWHUV '

36 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

12 Installation
12 - 1 Installation Method

VAM150FA 3
Maintenance space

Suspension bolt position Inspection hole 12

Air discharge grille

(Fresh air from outdoors)


VAM150FA
Heat insulator Round shape hood
(Field supply) (Field supply)

(Exhaust air to outdoors)

Suspension bolt position Air suction grille

Suspension bolt
(Field supply)

A gradient of more
than one in fty

(Fresh air from outdoors)


(Exhaust air to outdoors)
(Supply air to room) (Return air from room) Inspection hole Nominal diameter
(Field supply) (Field supply)

3D036781

VAM250FA

Maintenance space

Suspension bolt
position

Air discharge Inspection hole


grille

(Fresh air from outdoors)


VAM250FA
Heat insulator Round shape hood
(Field supply) (Field supply)

(Exhaust air to outdoors)


Suspension bolt
position Air suction grille
Suspension bolt
(Field supply)
A gradient of more
than one in fty

(Fresh air from outdoors)


(Exhaust air to outdoors)
(Supply air to room) (Return air from room) Inspection hole Nominal diameter
(Field supply) (Field supply)

3D036782

• Ventilation • VAM-FA/FB 37
• Indoor Unit • VAM-FA/FB

12 Installation
12 - 1 Installation Method

9$0)%

$LUGLVFKDUJHJULOOH

,QVSHFWLRQKROH
12
6XVSHQVLRQEROW 0DLQWHQDQFHVSDFH
SRVLWLRQ

2$
)UHVKDLUIURPRXWGRRUVRXWGRRUDLU
6$ 6XSSO\DLUWRURRP
+HDWLQVXODWRU 5RXQGVKDSHKRRG
9$0)% )LHOGVXSSO\ )LHOGVXSSO\

($
5$ 5HWXUQDLUIURPURRP ([KDXVWDLUWRRXWGRRUV

$LUVXFWLRQJULOOH
6XVSHQVLRQEROWSRVLWLRQ

6XVSHQVLRQEROW $JUDGLHQWRIPRUH
)LHOGVXSSO\ WKDQRQHLQIIW\

2$
)UHVKDLUIURPRXWGRRUVRXWGRRUDLU

6$ 5$ ,QVSHFWLRQKROH ¡1RPLQDOGLDPHWHU
)LHOGVXSSO\ )LHOGVXSSO\ ($
6XSSO\DLUWRURRP 5HWXUQDLUIURPURRP
([KDXVWDLUWRRXWGRRUV

'

9$0)%

$LUGLVFKDUJHJULOOH

6XVSHQVLRQEROW
SRVLWLRQ ,QVSHFWLRQKROH

0DLQWHQDQFHVSDFH

2$
6$ 6XSSO\DLUWRURRP )UHVKDLUIURPRXWGRRUVRXWGRRUDLU
+HDWLQVXODWRU 5RXQGVKDSHKRRG
9$0)% )LHOGVXSSO\ )LHOGVXSSO\

($
5$ ([KDXVWDLUWRRXWGRRUV
5HWXUQDLUIURPURRP

$LUVXFWLRQJULOOH
6XVSHQVLRQEROWSRVLWLRQ

6XVSHQVLRQEROW $JUDGLHQWRIPRUH
)LHOGVXSSO\
WKDQRQHLQIIW\

2$
)UHVKDLUIURPRXWGRRUVRXWGRRUDLU

6$ 5$ ,QVSHFWLRQKROH ¡1RPLQDOGLDPHWHU ($
6XSSO\DLUWRURRP 5HWXUQDLUIURPURRP )LHOGVXSSO\ )LHOGVXSSO\ ([KDXVWDLUWRRXWGRRUV

'

38 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

12 Installation
12 - 1 Installation Method

9$0)% 3

,QVSHFWLRQKROH
0DLQWHQDQFHVSDFH
12
$LUGLVFKDUJHJULOOH

2$
6$ 6XSSO\DLUWRURRP )UHVKDLUIURPRXWGRRUVRXWGRRUDLU
+HDWLQVXODWRU 5RXQGVKDSHKRRG
9$0)% )LHOGVXSSO\ )LHOGVXSSO\
6XVSHQVLRQEROW
SRVLWLRQ ($
5$ 5HWXUQDLUIURPURRP ([KDXVWDLUWRRXWGRRUV

$LUVXFWLRQJULOO

6XVSHQVLRQEROW 0HWDOVXVSHQVLRQEUDFNHW
SRVLWLRQ IRUDEVRUELQJYLEUDWLRQV 6XVSHQVLRQEROW $JUDGLHQWRIPRUH
IHOGVXSSO\ )LHOGVXSSO\ WKDQRQHLQIIW\

2$
)UHVKDLUIURPRXWGRRUVRXWGRRUDLU

,QVSHFWLRQKROH ¡1RPLQDOGLDPHWHU
)LHOGVXSSO\ )LHOGVXSSO\ ($
6$ 5$ ([KDXVWDLUWRRXWGRRUV
6XSSO\DLUWRURRP 5HWXUQDLUIURPURRP

'

VAM800FB

Maintenance space Inspection hole


Air discharge grille
Silencer
Flexible duct
OA
(Fresh air from
SA (Supply air to room) outdoors/outdoor air)
VAM800FB Round shape hood
(Field supply)
Suspension bolt RA EA
position Branch duct
(Return air from room) (Exhaust air to outdoors)

Heat insulator
Air suction grill (Field supply)
Air discharge grill

Suspension bolt
position
Suspension bolt
position

Metal suspension bracket for A gradient of more


absorbing vibrations (eld Suspension bolt
supply) (Field supply) than one in fty

OA
(Fresh air from outdoors/
outdoor air)

Inspection hole ø200 Nominal diameter


EA
(Field supply) (Field supply)
SA (Supply air to room) RA (Exhaust air to outdoors)
(Return air from room) 3D081270

• Ventilation • VAM-FA/FB 39
• Indoor Unit • VAM-FA/FB

12 Installation
12 - 1 Installation Method

VAM1000FB

Maintenance space Inspection hole


Air discharge grille
12 Flexible duct
Silencer
OA
(Fresh air from outdoors/
SA (Supply air to room) outdoor air)
Round shape hood
VAM1000FB (Field supply)
Suspension bolt
position Branch duct EA
RA (Exhaust air to outdoors)
(Return air from room)

Heat insulator
(Field supply)
Air discharge grill Air suction grill

Suspension bolt
Suspension bolt position
position

Metal suspension bracket for


absorbing vibrations (eld Suspension bolt A gradient of more
supply) (Field supply) than one in fty

OA
(Fresh air from outdoors/
outdoor air)

Inspection hole ø200 Nominal diameter EA


(Field supply) (Field supply) (Exhaust air to outdoors)
SA (Supply air to room) RA
(Return air from room) 3D081271

VAM1500FB Air discharge grille

Suspension bolt position

Maintenance space Inspection


hole
Silencer
Flexible duct
OA
(Fresh air from outdoors/
SA (Supply air to room) outdoor air)
VAM1500FB Round shape hood (Field supply)
Branch duct RA EA
(Return air from room)
(Exhaust air to outdoors)
Branch duct
(Field supply) Nominal diameter Heat insulator
(Field supply) (Field supply)
Suspension bolt Air suction grill
position
Suspension bolt
position
Air discharge grill Air suction grill

Air discharge grill

Nominal diameter Suspension bolt


Suspension bolt Suspension bolt (Field supply) position
position position
Air discharge grill
Metal suspension bracket for Suspension bolt
absorbing vibrations (eld supply) (Field supply)
A gradient of more
than one in fty

OA
(Fresh air from outdoors/
outdoor air)
EA
SA (Supply air to room) SA (Supply air to room) RA (Return air from room) RA (Return air from room) (Exhaust air to outdoors)
Inspection hole ø350 Nominal diameter
(Field supply) (Field supply) 3D081272

40 • Ventilation • VAM-FA/FB
• Indoor Unit • VAM-FA/FB

12 Installation
12 - 1 Installation Method

9$0)% $LUGLVFKDUJHJULOOH 3
6XVSHQVLRQEROWSRVLWLRQ
,QVSHFWLRQ
0DLQWHQDQFHVSDFH KROH
6LOHQFHU
)OH[LEOHGXFW
2$
)UHVKDLUIURPRXWGRRUV
12
6$ 6XSSO\DLUWRURRP RXWGRRUDLU
9$0)% 5RXQGVKDSHKRRG )LHOGVXSSO\
%UDQFKGXFW
5$ ($
%UDQFKGXFW 5HWXUQDLUIURPURRP ([KDXVWDLUWRRXWGRRUV
)LHOGVXSSO\
+HDWLQVXODWRU
1RPLQDOGLDPHWHU )LHOGVXSSO\
6XVSHQVLRQEROW )LHOGVXSSO\
6XVSHQVLRQEROW $LUVXFWLRQJULOO
SRVLWLRQ SRVLWLRQ
$LUGLVFKDUJHJULOO
$LUVXFWLRQJULOO
$LUGLVFKDUJHJULOO

6XVSHQVLRQEROW 6XVSHQVLRQEROW 1RPLQDOGLDPHWHU 6XVSHQVLRQEROW


SRVLWLRQ SRVLWLRQ )LHOGVXSSO\ SRVLWLRQ
$LUGLVFKDUJHJULOO 0HWDOVXVSHQVLRQEUDFNHWIRU 6XVSHQVLRQEROW
DEVRUELQJYLEUDWLRQV IHOGVXSSO\ )LHOGVXSSO\
$JUDGLHQWRIPRUH
WKDQRQHLQIIW\

2$
)UHVKDLUIURPRXWGRRUV
RXWGRRUDLU
($
6$ 6XSSO\DLUWRURRP 6$ 6XSSO\DLUWRURRP 5$ 5HWXUQDLUIURPURRP 5$ 5HWXUQDLUIURPURRP ([KDXVWDLUWRRXWGRRUV
,QVSHFWLRQKROH ¡1RPLQDOGLDPHWHU
)LHOGVXSSO\ )LHOGVXSSO\
'

• Ventilation • VAM-FA/FB 41
These products are not within the scope of
the Eurovent certification program
The present publication supersedes EEDEN14-205

The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
BARCODE Daikin products are distributed by:
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, re-
EEDEN15-205 • 01/15 • Copyright Daikin

liability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or re-
lated to the use and/or interpretation of this leaflet. All content is copy-
righted by Daikin Europe N.V.

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende