Professional Documents
Culture Documents
Type, material and sizes of earthing conductors and earth electrodes and number of
equipment earthing leads shall be as given in the enclosed table in Clause 9.
b) Earthing conductors around the station buildings shall be buried 800 mm below
finished grade level.
C. Earthing conductor around the building and switchyard/transformer yard fence shall
be buried in earth at a minimum distance of 1500 mm from the outer surface of wall
of building and switchyard fence/transformer yard fence.
E. Earthing conductors along their run on columns, beams, walls, etc. shall be supported
by saddles at intervals of 750 mm. Refer Fig 1.
F. Tap connections from the main earthing grid and/or earthing pads provided near the
equipment to the equipment/structure to be earthed shall be terminated on theearthing
terminals of the equipment/structure.
G. In outdoor areas, (switchyard, transformer yard etc.) leads from buried conductors
shall be brought out 1000 mm above ground level for making tap connection to
equipment/structures.
H. Earthing conductors crossing the road shall be provided with suitable protection as
directed by the site engineer.
J. Whenever earthing conductor is required to pass through external walls, floors, etc.,
galvanised iron sleeves shall be provided for the passage of the conductor. Both ends
of the sleeve shall be sealed to prevent the passage of water through the sleeves.
K. Connection between the earthing grid inside and outside the building shall be through
copper water stops as shown in Fig 2. Location of these Copper water stops will be
shown in relevant earthing layout drawings.
B. Steel columns, metallic stairs, hand-rails etc. of building portions housing electrical
equipment shall be connected to the nearby earthing grid by one lead. Electrical
continuity shall be ensured by bonding different sections of hand-rails and metallic stairs.
C. Metallic pipes, conduits carrying electrical cables shall be bonded to ensure electrical
continuity. They shall be earthed at minimum two points.
D. Cable tray sections shall be properly bonded through coupling plates to ensure
electrical continuity. Earthing conductor shall run along the top trays and to be bolted
to trays before installation of cables. All the tiers of cable pans shall be connected at
every 2.5 m interval. The cable tray shall be earthed at minimum two points and in
addition at 25 meters interval for longer length. Apart from the intermediate
connections, beginning and end points shall also be connected toearthing system.
E. Metallic conduits, pipes and cable trays shall not be used as earth continuity
conductor.
H. The earthing of street lighting poles, junction boxes on the poles, and flood light
supporting structures etc. shall be done by 8 SWG copper wire unless specified
otherwise. The distribution boards shall also be earthed with earth lead as per table
under Clause 9. The conductor shall be run buried in ground at a depth of 600 mm along the
supply cable and looped in and out to each lighting pole. The earth conductor shall be
connected to the nearby main earthing grid at first and last poles of each feeder circuit and
at some intermediate poles. Outdoor lighting boards are connected to the earth electrode.
I. Railway tracks within the plant area shall be bonded across by fish plates and
connected to earthing grid at one location as indicated in the relevant layout drawings.
J. Every alternate main post of the switchyard and transformer yard fence and gates
shall be connected to earthing grid by one lead. Gates shall be bonded by G.S. flexible
braid to the earthed post. Refer Fig 8.
K. Small electrical equipment like local push button stations, electrically operated
valves, power receptacles, small panels, small marshalling boxes, junction boxes,
exhaust fans shall be earthed by two earthing leads from the same earthing pad (with
two connections from the main embedded conductor to the pad).
M. The enclosures of generator, exciter, and turbine shall be earthed by two leads.
Generator circuit breaker enclosure shall not be earthed since isolated phase bus
duct (IPBD) shall be earthed at generator end only.
4. JOINTING:
A. Earthing connections with equipment earthing terminal shall be bolted type. Contact
surfaces shall be free from scales, paint, enamel, grease, rust or dirt. Two bolts shall
be provided for making each connection wherever possible.
B. For earthing connection, at equipment end as well as pad end, for conductor size equal
to and above 65.09 sq.mm connection will be through offset bar lugs using two bolts,
and for the conductor size less than 65.09 sq.mm connection shall be through
crimpable type lug with one bolt.
The lug shall be of copper alloys. The earthing lead shall be brazed to offset bar lugs
while earthing lead shall be crimpable type lugs. The lugs details are given in Fig 4.
Equipment earthing leads of 14 SWG copper and smaller size shall be directly bolted
to the earth pad which eliminates the provision of earthing lugs both at the equipment
and the pad end.
C. For the embedded earthing conductor copper to copper joints are done by cad weld
joint/brazing. The procedure and precautions to be followed is as follows:
iii. Borax or mixture of borax and boric acid shall be used as flux. The joint will be
washed with water after brazing to prevent corrosion due to residual flux.
ii. Once the joint is finished, the mould should be cleaned using a mold scrapper and
brush for the next joint.
iii. The conductors and as well as the mould used for jointing should be cleaned properly
and should be water or, moisture free for better results. Cleaning may be done either
mechanically or chemically without use of acids.
D. Steel to Copper connections shall be brazed type. Steel to steel connections shall be
welded type.
E. Resistance of the joint shall not be more than the resistance of the equivalent length
of the conductor.
5. CABLE EARTHING:
A. Metallic sheaths and armour of all multi-core power cables shall be earthed at both
equipment and switchgear ends. Metallic sheath and armour of single core power
cables shall be earthed at switchgear end only. The metallic sheaths and armour of
the cables shall be earthed through cable glands as shown in the drawing SH-25
6. INSTRUMENTATION EARTHING:
A. SAFETY EARTHING
All the metallic portion of instrument chasis, cabinets, panels and junction boxes
will be connected to the nearest earthing pad. The earthing pads are to the station
earthing system. The sizes of the copper earthing conductor will be as follows:
(a) Instrument chasis to Earthing bus - 14 SWG(4 sq.mm)
(b) Earthing bus to Earthing pad - 16 sq.mm
(c) Junction Box to Earthing pad -14 SWG(4 sq.mm)
B. SHIELD EARTHING
The shields of individual pair of signal cables will be connected to the zero signal
reference potential at only one point i.e. where the signal source is earthed. The other
end of the shield will be isolated from the zero signal reference point so that loops
are not formed.
The overall shields of control cables, instrument cables and compensating cables
are terminated on shield terminals in field junction boxes, CDF and panels/nodes.
The shield terminals inside the field junction boxes, CDF, and panels/nodes are
shorted respectively. The shield terminals are connected to safety earth bus bar of
CDF/panels/nodes in control centre by 2.5 sq. mm PVC insulated stranded copper
wire. The safety earth bus bar of CDF/panels/nodes is connected to nearest earthing
pad by 16 sq. mm bare copper conductor so as to ensure grounding at one end only.
C. SIGNAL EARTHING
The signal earth (zero reference signal point) for both digital and analog system will
be connected to signal ground bus bar inside the panel/node which is isolated from
safety ground. These signal ground bus bars inside nodes/panels are connected to
junction box by 10 sq.mm PVC insulated stranded copper wire. The bus bar inside
the junction box is connected to nearest earthing pad by 16 sq.mm PVC insulated
stranded copper wire.
D. GENERAL
The shield is connected to safety earthing at only one end and signal earthing is
connected to the safety earthing at only one point.
For signal grounding of TG and secondary cycle systems, the instrumentation
earthing will be brought out from the control centre with a two numbers of insulated
copper cables (50 sq. mm) and will be connected to the instrumentation earthing
through treated earth pit.
To control the earthing resistance of the Instrumentation earth grid to one Ohm, 216
meters length of earthing conductor will be provided in the earth.
A. Two earthing leads from the neutral of indoor transformers shall be connected to the
earthing pad which is in turn connected to main earthing grid. In the case of outdoor
transformers HT side of GT and SUT, the two earthing leads from the neutral shall
be connected to the two electrodes which are further connected to station earthing.
Neutral of LT side of SUT and UT are connected to the earth mat through a resistor.
Generator neutral through the grounding transformer is connected to theearthmat
provided partly below and above the raft of TB, by two leads. The earthmat will be
further connected to station earthing layout.
D. Flexible earthing leads shall be provided for earthing the equipment on moving
platforms.
8. LEGEND
EWP
Earthing pad flush with wall/column surface
M - Motor
F - Fan
CT - Cable Tray
S - Spare
P - Pump
V - Ventilation System
RE - 3 Phase – Receptacle
TN - Transformer neutral
PB - Push Button
PL - Panel
TK - Tank
B - Busduct
Earthing pad for connecting two earthing leads to same pad
from small equipment such as PB station etc.
TABLE
9.
EARTHING CONDUCTORS AND LEADS
Lighting DBs/control
65.09 mm2
2.7.8 boards space heater board/ " 2 Each
(19x2.11 mm)
VDBs
25 dia 3000 mm
3.0 EARTH ELECTRODES Copper N.A.
long rod
FIG 1
FIG 2
FIG 3 TRANSFORMER NEUTRAL/LIGHTNING ARRESTOR EARTHING
FIG 4
FIG 5
FIG 6
FIG 7
FIG 8: FENCE AND FENCE GATE EARTHING
FIG 9: EARTHING DETAILS AT FLOOR & WALL/BEAM EXPANSION JOINTS
FIG 10: CAD WELDING