technical guide
U N D E R F LO O R H E AT I N G
AND COOLING
01 | 2013
The Tecto product line
Panels can be laid and connected by one man without the need Example of floor constructions with ND 11
for special tools pipe positioning panels
2 2 U P O N O R T E C TO T E C H N I C A L G U I D E
Tecto components
Two different pipe positioning panels Joining two panels with a double-sided strip Movement joint profile
Uponor Tecto panels are available in The double-sided strip allows The movement joint profile ensures
two different thicknesses which element off-cuts to be laid using correct pipe routing and the neces-
both withstand heavy loads: 500 butt joints, thus saving on time and sary movement clearance between
kg/m2 in a nominal thickness of materials: all you do is press them heating screeds. It is self-adhesive
38/35 mm and up to 7.5 t/m2 in a onto the maxi studs. Any off-cuts and can be quickly attached by
nominal thickness of 11 mm. can be butt-joined in this way. pulling off the protective laminate
on the bottom.
90°
45°
Uponor Tecto 90° compensation element Uponor Tecto 45° compensation element Uponor Tecto diagonal pipe fixing element
With the Uponor compensation Connecting lines that must cross With the Uponor Tecto diagonal
elements, door openings and under door saddles can be installed pipe fixing element, installation
other passages between rooms without protruding studs at angles at 45° angles is made easy even
can be bridged in a most simple of both 90° and 45°. The compen- where little room space is avail-
manner, as a single row of studs is sation elements ensure that pipes able. The diagonal pipe fixing foil
sufficient to provide a strong and can be quickly and properly laid at is simply mounted on the studs for
proper connection to the adjacent the correct distances even at door properly aligned pipe installation.
element. openings that require 45° angles.
The following system pipes can be installed in the pipe fixing panels:
Uponor PE-Xa pipe (14 x 2mm)
Uponor PE-Xa pipe (17 x 2mm)
Uponor MLCP RED composite pipe (14 x 1.6 mm)
Uponor MLCP RED composite pipe (16 x 2 mm)
U P O N O R T E C TO T E C H N I C A L G U I D E 3
Design data
The design tables below allow for the fast approximate calculation of the pipe spacing and maximum
heating circuit size. They do however not replace proper planning and calculation of the project.
The values in the design tables are based on the following key figures:
Rλ,ins = 0.75 m2K/W, θu = 20 °C, 130 mm concrete floor, spread = 3-30 K, max. heating circuit length = 150 m
max. pressure drop per heating circuit including 2 x 5 m connecting line Δp max = 250 mbar
For other flow temperatures, thermal resistance values, etc. please refer to the design diagrams.
1)
At θV,des > 55.5 °C the limit heat flow density and thus the max. floor surface temperature of 29 °C (33 °C for bathrooms) are exceeded.
4 4 U P O N O R T E C TO T E C H N I C A L G U I D E
Design diagram heating/cooling for Uponor Tecto 14 x 2 mm pipe fixing system with
cement screed load distribution layer including VD 450/450N/550N
(sü = 45 mm with lü = 1.2 W/mK)
180
Limit curve edge zone T 102)
45 mm
K
K
30
35
40
160
K
25
14 x 2 PE-Xa
140
120 K
20
Specific thermal output qH [W/m2]
7F 010 -F
Limit curve comfort zone T 10 1)
100
T 15
T 20
K
T 25
= 15
– θi
=θ
80 T 30 H 80
∆θ H
8K
40 40
6K
20 θC = 4 K 20
∆θC = θi –
0 0
0 5 T2
0 T 15 T 10
T3 T2 T q̇ N ∆θN
0.05
W/m2
Heating
cm K
10 98.6 15.9
Thermal resistance
15 96.3 18.1
Rl,B in [m2 K/W]
T
T
T qC ∆θC,N 0.05
Cooling cm
10
15
W/m2
34.8
39.8
K
8
8 0.10
20 27.5 8
25 24.5 8
0.15
1)
Limit curve valid for θi20 °C and θF, max 29 °C or θi 24 °C and θF, max 33 °C
2)
Limit curve valid for θi 20 °C and θF, max35 °C
Note: According to DIN EN 1264 are baths, showers and toilets not included.
The limit curves must not be exceeded.
The design supply water temperature must maximum be: θV, des = ∆θH, g + θi + 2.5 K .
∆θH, g is found by the limit curve for the occupied zone with the smallest pipe spacing.
At cooling the supply temperature to be controled by dew point temperature, humidity sensor to be included.
U P O N O R T E C TO T E C H N I C A L G U I D E 5
Uponor Tecto load area 17 for cement screed 17 x 2
load distribution layer:
nominal thickness 45 mm, heat conductivity 1.2 W/mK
The values in the design tables are based on the following key figures:
Rλ,ins = 0.75 m2K/W, θu = 20 °C, 130 mm concrete floor, spread = 3-30 K, max. heating circuit length = 150 m
max. pressure drop per heating circuit including 2 x 5 m connecting line Δp max = 250 mbar
For other flow temperatures, thermal resistance values, etc. please refer to the design diagrams.
1)
At θV,des > 54.9 °C the limit heat flow density and thus the max. floor surface temperature of 29 °C (33 °C for bathrooms) are exceeded.
6 6 U P O N O R T E C TO T E C H N I C A L G U I D E
Design diagram heating/cooling for Uponor Tecto 17 x 2 mm pipe fixing system with
cement screed load distribution layer including VD 450/450N/550N
(sü = 45 mm with lü = 1.2 W/mK)
180
Limit curve edge zone T 102)
45 mm
K
K
30
35
40
160
K
25
17 x 2 PE-Xa
140
120 K
20
Specific thermal output qH [W/m2]
7F 037 -F
Limit curve comfort zone T 10 1)
100
T 15
T 20
K
T 25 = 15
– θi
=θ
80 T 30 H 80
∆θ H
8K
40 40
6K
20 θC = 4 K 20
∆θC = θi –
0 0
T3
0
T2
5 T 20 T 15 T 10
T qH ∆θH,N
0.05
W/m2
Heating
cm K
10 98.6 15.6
Thermal resistance
15 96.1 17.6
Rl,B in [m2 K/W]
T qC ∆θC,N 0.05
Cooling cm
10
15
W/m2
35.4
31.6
K
8
8 0.10
20 28.3 8
25 25.3 8
0.15
1)
Limit curve valid for θi20 °C and θF, max 29 °C or θi 24 °C and θF, max 33 °C
2)
Limit curve valid for θi 20 °C and θF, max35 °C
Note: According to DIN EN 1264 are baths, showers and toilets not included.
The limit curves must not be exceeded.
The design supply water temperature must maximum be: θV, des = ∆θH, g + θi + 2.5 K
∆θH, g is found by the limit curve for the occupied zone with the smallest pipe spacing.
At cooling the supply temperature to be controled by dew point temperature, humidity sensor to be included.
U P O N O R T E C TO T E C H N I C A L G U I D E 7
Pressure drop diagrams
400
The pressure losses in the Uponor
PE-Xa pipes can be determined with 300
m
2m
0.6
x
17
0.5
m/
100
mm
0.4
m/
s
80 2
4x
.
s
m/
0.3
60 1
s
m/
50
0.2
s
40
m/
0.1
30
s
5m
0.
20
/s
1
m/
s
10
0.1 0.2 0.3 0.5 1 2 3 4 5 6 7 8 9 [mbar/m]
0.01 0.02 0.03 0.05 0.1 0.2 0.3 0.4 0.5
[kPa/m]
Pressure gradient R
1000
The pressure losses in the Uponor
800
multi-layer composite pipes can be
determined with the aid of the dia- mm
600
500 2
gram
16x
400
mm
.6
300 x1
14
Mass flow rate m in [kg/h]
200
0.7
0.6
m/
0.5
.
m/
100
0.4
m/
80
s
m/
0.3
60
s
m/
50
0.2
40
m/
30
s
20
10
0.1 0.2 0.3 0.5 1 2 3 4 5 10 20 [mbar/m]
0.01 0.02 0.03 0.05 0.1 0.2 0.3 0.4 0.5 1 2 [kPa/m]
Pressure gradient R
8 8 U P O N O R T E C TO T E C H N I C A L G U I D E
Installation
Maxi
2
Maxi
1
Mini
Mini
3
14 x 2
r ≥ 70 mm
17 x 2
r ≥ 85 mm
Tecto ND 11
Tecto ND 30 - 2
T
2
xT
r
Option: Uponor double-sided strip for connection Uponor PE-Xa pipe installation
U P O N O R T E C TO T E C H N I C A L G U I D E 9
Overview additional installations
A A A
45°
B B B
C C C
D D D
Installation from compensation element Installation from 45° compensation element Installation from compensation element
in door areas (overlapping taped) in door areas in edge zone
1 3
A
Up
on
or
,D
IN
18
56
0, B
2D
IN
41
02
(FC
KW
-fre
i) A
1000082
rt.-
N r. 1
00
00
81
B
-fr
KW
(FC
02
41
DIN
, B2
50
18
DIN 2
011
,
or
r. 1
00
00
81
Up
on
i) A
rt.-
Nr.
41
2
-fre
.-N
Art
-frei) KW
KW FC
C , B2
DIN
41
02
(FC
DIN
41
02(
18
50
, B2
DIN 50
on
or, 18 Up
Up IN on
r,D
or
,D
o IN
on 18
56
Up 0, B
2D
IN
41
02
(FC
KW
-fre
b i) A
rt.-
N
a
r. 4
10
11
12
D
18
00
10 10 U P O N O R T E C TO T E C H N I C A L G U I D E
Technical data
U P O N O R T E C TO T E C H N I C A L G U I D E 11
Uponor PE-Xa pipe 17x2 mm
Pipe dimensions 17 x 2 mm
Material PE-Xa
Colour White with black and red longitudinal stripes
Production According to DIN EN ISO 15875
Oxygen tightness According to DIN 4726
Density 0.938 g/cm3
Thermal conductivity 0.35 W/mK
Linear expansion coefficient At 20 °C 1.4 x 10-4 1/K, at 100 °C 2.05 x 10-4 1/K
Crystallite melting temperature 133 °C
Building material class B2
Min. bending radius 85 mm
Pipe roughness 0.007 mm
Water volume 0.13 l/m
Pipe identification [length] m < Uponor PE-Xa 17x2.0 C oxygen-tight
according to DIN 4726 EN ISO 15875 class 4/5 / 8 bar
[DIN approval mark] 3V208 PE-X Komo vloerverw.
ATG 2399 ONORM B5153 APPROVED [manufacturer
logo] [material/machine/production/date code]
Max. operating pressure (water 20 °C) 16.3 bar (safety factor ≥ 1.5)
Max. operating pressure (water 70 °C) 9.4 bar (safety factor ≥ 1.5)
For heating 70 °C/9.4 bar
DIN reg. no. 3V208 PE-X
Pipe fittings Pipe couplings and Uponor plus 17x2 type press-fittings
Optimum installation temperature ≥ 0 °C
Approved additive Uponor GNF anti-freeze agent substance
class 3 according to DIN 1988, part 4
UV protection Light-proof cardboard box
(unused piping must be stored in cardboard box!)