温度 湿度 FLOAT CHARG CONTR FLOAT LOAD BATT BATT 发现问题

设备 时间 CHARG OUT BUS CHARG CURR NUMB VOLT 负责人


Room T Room H Problem
Device Time (V) (V) (V) (A) (A) ON (V) PIC
(°C) (%) Found
110VDC I 9:22 24.8 42 116.2 116.2 116.3 0 20.6 52 2.22 - David

2022 / 03 /07 110VDC II 9:24 24.8 42 116.1 116.1 116.3 0 13.1 52 2.14 - David

220VDC I 9:26 24.8 42 232.2 232.2 232.4 0 1.4 104 2.23 - David

110VDC I 9:12 25.9 50 117 116.2 117.0 0 20.7 52 2.22 - Yakin

2022 / 03 /14 110VDC II 9:15 25.9 50 116 116.2 117.0 0 13.5 52 2.19 - Yakin

220VDC I 9:18 25.9 50 232.7 232.2 232.8 0 1.3 104 2.2 - Yakin

110VDC I 8:55 24.8 41 116.4 116.2 116.3 0 20.5 52 2.23 - Agung

2022 / 03 / 21 110VDC II 8:57 24.8 41 116.3 116.2 116.4 0 13.4 52 2.22 - Agung

220VDC I 9:01 24.8 41 232.3 232.1 232.2 0 1.3 104 2.22 - Agung

110VDC I 8:57 24.7 42 116.3 116.2 116.3 0 20.4 52 2.22 - David

2022 / 03 / 28 110VDC II 9:00 24.7 42 116.3 116.2 116.4 0 13 52 2.12 - David

220VDC I 9:03 24.7 42 232.2 232.3 232.3 0 1.3 104 2.22 - David
温度 湿度 FLOAT CHARG CONTR FLOAT LOAD BATT BATT 发现问题
设备 时间 CHARG OUT BUS CHARG CURR NUMB VOLT 负责人
日期 Date Room T Room H Problem
Device Time (V) (V) (V) (A) (A) ON (V) PIC
(°C) (%) Found
110VDC I 9:27 26.8 48 116.4 116.7 116.5 0 15.5 52 2.18 — Ali

2022 / 03 /07 110VDC II 9:30 26.8 48 116.4 116.4 116.5 0 14.7 52 2.23 — Ali

220VDC I 9:33 26.8 48 232.6 232.1 232.1 0 2.2 104 2.2 — Ali

110VDC I 9:28 26.3 52 116.6 116.7 117.1 0 15.5 52 2.19 — Yakin

2022 / 03 /14 110VDC II 9:30 26.3 52 116.3 116.4 117.2 0 14.4 52 2.23 — Yakin

220VDC I 9:32 26.3 52 229.1 232 233.7 0 2.1 104 2.21 — Yakin

110VDC I 9:08 27.9 41 118.9 116.7 117.1 0 15.5 52 2.19 — Yakin

2022 / 03 /21 110VDC II 9:04 27.9 41 116.3 116.3 117.2 0 14.4 52 2.23 — Yakin

220VDC I 8:58 27.9 41 230.3 232.2 234 0 2.2 104 2.22 — Yakin

110VDC I 8:58 26.3 41 116.4 116.8 116.4 0 15.4 52 2.18 — Ali

2022 / 03 /28 110VDC II 9:00 26.3 41 116.5 116.3 116.5 0 14.5 52 2.23 — Ali

220VDC I 9:02 26.3 41 232.4 232.0 232.0 0 2.1 104 2.20 — Ali
温度 湿度 旁路电源 逆变电源 输出功率 电池电量
设备 时间 输入电源 UPS 温度 频率 负责人
日期 Date Room T Room H B/P (V) & INV (V) & OUTPUT BATT (V) 发现问题 Problem Found
Device Time IN (V) T (°C) FREQ (Hz) PIC
(°C) (%) (A) (A) (V) & (A) & (A)
226 V
220 V 217 V 218 V 50 Hz 263 V
UPS I 9:29 24.8 42 225 V 29 UPS OK David
0A 59 A 59 A 50 Hz 0A
224V
2022 / 03 / 07
224 V
224 V 222 V 225 V 50 Hz 272 V
UPS II 9:31 24.8 42 224 V 28 UPS OK David
0A 57 A 57 A 50 Hz 0A
225 V

224 V
222 V 218 V 217 V 50 Hz 264 V
UPS I 9:32 25.8 42 223 V 31 UPS OK Yakin
0A 59 A 59 A 50 Hz 0A
221 V
2022 / 03 / 14
224 V
223 V 222 V 226 V 50 Hz 272 V
UPS II 9:35 25.8 42 224 V 30 UPS OK Yakin
0A 57 A 57 A 50.1 Hz 0A
224 V

223 V 225 222 V 0 218 V 217 V 50.0 Hz 264 V


UPS I 8:51 24.8 41 29 UPS OK Agung
V 221 V A 59 A 59 A 50.0 Hz 0A
2022/ 03 / 21

UPS II 8:53 24.8 41 225 V 225 224 V 0 222 V 57 227 V 57 28 50.0 Hz 272 V 0 UPS OK Agung
V 225 V A A A 50.0 Hz A

228 V 227 223 V 0 217 V 217 V 50.0 Hz 264 V


UPS I 9:04 24.7 42 29 UPS OK David
V 226 V A 59 A 59 A 50.0 Hz 0A
2022/ 03 / 28
224 V 224 225 V 0 222 V 57 227 V 57 50.0 Hz 273 V 0
UPS II 9:06 24.7 42 28 UPS OK David
V 225 V A A A 50.0 Hz A
温度 湿度 旁路电源 逆变电源 输出功率 电池电量
设备 时间 输入电源 UPS 温度 频率 负责人
日期 Date Room T Room H B/P (V) & INV (V) & OUTPUT BATT (V) 发现问题 Problem Found
Device Time IN (V) T (°C) FREQ (Hz) PIC
(°C) (%) (A) (A) (V) & (A) & (A)
226 V
223.9 V 222 V 223.8 V 50.07 Hz 271 V
UPS I 9:23 26.8 48 228 V 34 UPS OK ALI
0A 57 A 56.6 A 50.07 Hz 0A
227 V
2022 / 03 / 07
219 V
223.1 V 221 V 220.6 V 50.07 Hz 269 V
UPS II 9:26 26.8 48 221 V 34 UPS OK ALI
0A 34 A 34.9 A 50.07 Hz 0A
222 V

223 V
224 V 222 V 222 V 50.01 Hz 271 V
UPS I 9:49 26.3 52 226 V 32 UPS OK Yakin
0A 57 A 57 A 50.01 Hz 0A
226 V
2022 / 03 / 14
222 V
222 V 221 V 221 V 50.01 Hz 271 V
UPS II 9:46 26.3 52 224 V 32 UPS OK Yakin
0A 34 A 34 A 50.01 Hz 0A
225 V

222 V
223 V 222 V 222 V 50.00 Hz 273 V
UPS I 9:22 27.9 41 225 V 34 UPS OK Yakin
0A 57 A 57 A 50.01 Hz 0A
225 V
2022 / 03 / 21
220 V
UPS II 9:18 27.9 41 223 V 221 V 222 V 32 50.00 Hz 269 V UPS OK Yakin
222 V
0A 34 A 34 A 50.01 Hz 0A
223 V

226 V 229 221 V 223.8 V 49.98 Hz


UPS I 8:54 26.3 41 224 V 0 A 32 271 V 0 A UPS OK Ali
V 228 V 34 A 56.8 A 49.98 Hz
2022 / 03 /28
219 V 221 223.2 V 0 221 V 220.8 V 50.00 Hz 269 V
UPS II 8:57 26.3 41 30 UPS OK Ali
V 222 V A 34 A 34.3 A 50.01 Hz 0A