Professional Documents
Culture Documents
M-Bus Plants
Planning Manual
CE1J5361E
April 1996
CE1J5361E
April 1996
Contents
2.3 Application....................................................4
2.3.1 Inhouse plants ..............................................4
2.3.2 Plants outside the house ..............................5
2.3.3 Mixed plants .................................................5
3. Engineering.................................................6
3.1.1 Planning procedure ......................................6
3.1.2 Line length charts .........................................7
4. Installation ................................................15
4.3 Procedure...................................................15
1.1 Objective
This documentation is intended to assist the planning engineer in the design of M-bus
plants. It provides information especially on electrical planning work required for M-bus
installations.
In addition, the manual aids the M-bus specialist in connection with installation work,
commissioning and fault tracing.
For general HVAC information, please refer to the relevant data sheets.
1.2 Standards
prEN 1434, part 3; heat meters, part 3: data exchange and interfaces, released in Febru-
ary 1995.
1.4 Literature
[1] Texas Instruments Technical Journal Vol. 8, No. 3, May - June 1991, Meter Bus: A
Bus Concept for Utility Meter Readouts
Authors: Heinrich Brenninger, Horst Diewald, Peter Fatelnig and Helmut Kiml
[2] The M-Bus, a Documentation, Version 4.3, 05. December 1994, M-Bus Usergroup
2.1.4 Repeater
The input of a repeater has the same characteristics as a slave. The output of a repea-
ter powers an M-bus segment.
At the output of the repeater, a new M-bus segment is created.
2.1.6 Extension
The overall extension of the bus system is restricted by:
• The number of M-bus devices (slaves)
• The total capacitance of the system (rate of transmission)
• The system’s resistance (voltage drop on the lines)
2.1.7 Segment
Figure 1 - Segments
U1 Repeater or signal converter
U2 Repeater
All M-bus devices that are connected to the same repeater or signal converter belong to
the same M-bus segment.
2.2.2 Topology
The M-bus supports all types of topology such as star, line, ring or tree. Depending on
the type of application, there are preferential topologies.
The ring topology is not recommended.
2.3 Application
The M-bus is used in two typical types of plant:
- M-bus plants inside the house (inhouse plants)
- M-bus plants outside the house
A combination of both is also possible.
WG3 WG4
1.OG M M M
WG1 WG2
EG M M M M
M-BUS
1.UG
MM
M
M
M
To cover long distances, repeaters are required. The location of the repeaters is de-
pendent upon future extensions and local conditions (power supply for the repeaters,
accessibility).
1.OG M M M 1.OG M M M
EG M M M M EG M M M M
M-bus device
Point of distribution
WG... Flat no. ...
UG/EG/OG Basement / ground floor / first floor
Determine
Precise plan
extension
(buildings/location)
of plant
Define
Enter zones
expansion
in the plan
zones
Determine
Enter cabling
layout for
in the plan
cabling
Ascertain
Enter distances
distances from
in the plan
the plan *
Determine cross-
sectional area and/or Enter repeaters
number and location in the plan
of repeaters
∗ Don’t measure the air distance. Often, the actual length of line is 3 to 5 times the air distance.
3.1.2.1 Charts
Curve 1: theoretical line length for M-bus devices that are spaced equally (e.g. one M-
bus device every 5 m). This is the upper design limit, which should never exceed 4 km.
Curve 2: theoretical line length for all M-bus devices at the end of the line.
Curve 3: same as curve 2, but in the event of a short-circuit.
Curve 1
Curve 2
Curve 3
4000
3500
3000
2500
Curve 1
2000 Curve 2
Curve 3
1500
1000
500
0
100
120
140
160
180
200
220
240
10
20
40
60
80
8000
7000
6000
5000
Curve 1
4000 Curve 2
3000 Curve 3
2000
1000
100
120
220
240
80
140
160
180
200
10
20
40
60
12000
10000
8000
Curve 1
6000 Curve 2
Curve 3
4000
2000
0
100
120
140
160
180
200
220
240
10
20
40
60
80
18000
16000
14000
12000
10000 Curve 1
Curve 2
8000 Curve 3
6000
4000
2000
0
100
120
140
160
180
200
220
240
10
20
40
60
80
3.1.2.2 Note
In the event of a short-circuit on an M-bus device, values below curve 3 permit pinpoint-
ing faulty M-bus devices in each M-bus segment, provided the overall capacitance does
not exceed a certain level.
Note: whenever possible, the plant should be designed based on the rate of transmis-
sion under extreme conditions (voltage drop of 1.5 V at the master when an M-bus
device is sending).
3.3.1 Example
To increase the line length, several new branches are created. The cable’s capacitance
and, thus, the total capacitance in the segment increases.
The cable used has the following technical data:
Diameter of line: 0.8 mm
Max. loop resistance: R’ = 73.2 Ω/km
Max. operating capacitance of line: C’ = 100 nF/km
Figure 11
Length of cable:
Ascertained from chart 2 (Figure 7): with no device short-circuit = 1280 m, with device
short-circuit = 720 m
Total capacitance:
CTotal = CR/C + CCable + n ∗ CM-bus device =
200 nF + 1280 km * 100 nF/km + 60 ∗ 0.5 nF = 358 nF
3.3.1.2 Variant 2
Two branches have been created, each comprising 30 M-bus devices. Both cable
length and total capacitance have increased. The rate of transmission in the two
branches has dropped:
Master
Figure 12
Length of cable:
Ascertained from chart 2 (Figure 7): with no device short-circuit = 1970 m, with device
short-circuit = 910 m
Total capacitance:
CTotal = CR/C + CCable + n ∗ CM-bus device =
200 nF + 2 ∗ 1970 km * 100 nF/km + 60 ∗ 0.5 nF = 624 nF
Master
Figure 13
Length of cable:
Ascertained from chart 2 (Figure 7): with no device short-circuit = 2400 m, with device
short-circuit = 1000 m
Total capacitance:
CTotal = CR/C + CCable + n ∗ CM-bus device =
200 nF + 3 ∗ 2.4 km ∗ 100 nF/km + 60 ∗ 0.5 nF = 950 nF
3.3.1.4 Variant 4
To reduce the total capacitance with variant 3, thus increasing the rate of transmission,
a repeater is used in branch 1. Since the number of M-bus devices in the various
branches has not changed, the length of cable has not changed either. The rate of
transmission in both segments and their branches has increased.
Repeater
5361Z15
Figure 14
4.2 Clearances
The distances between the M-bus cables and the power supply for other pieces of
equipment (non M-bus devices) should be as great as possible.
4.3 Procedure
The installation must be made as defined in the planning documentation. If problems
occur that do not allow work to be carried out as specified in the planning documenta-
tion, the changes made must be entered in the planning documentation and the project
leader must be notified. If there are major deviations from the documentation, the
project leader must immediately be notified (possibility of planning error).
Possible procedure in short:
1. Lay the cables (write down the actual length of cable)
2. Make the wiring (on the central unit)
3. Mark the bus line and give the bus line assignment (at the central unit)
4. Prepare the test (at the central unit)
5. Fit the main distributors and conduit boxes
6. Mark the main distributors and conduit boxes
7. Mark the bus line and give the bus line assignment (main distributors/conduit
boxes)
8. Check the bus line
9. Repeat steps 6 through 9 for each bus line
5.3 Procedure
All devices are connected to the M-bus and, if necessary, to the power source. On each
device, the M-bus address is set as specified by the supplier. From the central unit, the
bus segments are activated one by one.
In the event of a short-circuit of the bus (not short-circuit of an M-bus device), the bus
voltage fails. To detect a short-circuit of an M-bus device, it is necessary to measure the
current passing through the branch (IBR = nBR ∗ IM). If that current is 27.3 mA to 95 mA
greater than planned (depending on the position of the M-bus device), there is a short-
circuit of an M-bus device.
The M-bus device with the short-circuit can be pinpointed with the help of a communica-
tion call, provided the plant is not undersized.
Description of problem Solution
Power failure due to short-circuit on M- Disconnect branch and check (make
bus measurements at the conduit boxes)
Excessive power consumption by the Short-circuit of M-bus device if current
branch exceeds the normal current by 27.3 to
95 mA
M-bus device does not respond - Check M-bus device address
- Check M-bus connection
- Two or more M-bus devices with the
same M-bus device address (collision)
6.1.1 Assumptions
• Maximum quiescent current (Mark) passing through each meter
• Maximum measuring resistance in the central unit (signal converter/repeater)
• Two meters respond at the same time (collision)
6.1.2 Conditions
UMU,M = 36 V voltage at the master, quiescent level
UMU,S = 24 V voltage at the master, sending level
UM,M = 12 V voltage at the meter, quiescent level
UM,S = 11.3 V voltage at the meter, sending level
IM = 1.5 mA supply current, quiescent level
IS = 20 mA signal current (space level)
n = 1...250 number of meters in the bus system
RS = 440 Ω max. safety resistance in each meter
RC = ... Ω cable resistance
RM = 60 Ω max. measuring resistance in the master
RCON = 2Ω resistance of all connections
Central unit
(signal conver- Meter
ter / repeater)
l [m, km]
Figure 16
6.1.3.2 Example 1
64 meters; cross-sectional area of line A = 1.5 mm2; resulting in: 24 Ω/km, RCON = 2 Ω
• Meter receives data: RC = 25 Ω
• Meter sends data: RC = 89 Ω
(RC – RCON) ∗ A
l = = 3.6 km
2ρ
6.1.3.3 Example 2
259 meters; cross-sectional area of line A = 0.5 mm2; resulting in: 71 Ω/km, RCON = 2 Ω
• Meter receives data: RC = 32 Ω
• Meter sends data: RC = 29 Ω
(RC – RCON) ∗ A
l = = 380 m
2ρ
The formula used for “Meter sends data” is decisive for sizing the M-bus line.
A ∗ 56 ∗ (4020 – n)
l ≅ [m]
( n + 27 )
where:
A = cross-sectional are of line in mm2
n = number of M-bus devices
l = cable length in m
Meter Meter
Central unit
(signal conver- Meter
ter / repeater)
l/n
l [m, km]
Figure 17
6.1.4.2 Example 1
64 meters; cross-sectional area of line A = 1.5 mm2; resulting in: 24 Ω/km, RCON = 2 Ω
• Meter receives data: RC = 247 Ω
• Meter sends data: RC = 136 Ω
(RC – RCON) ∗ A
l = = 5500 m
2ρ
6.1.4.3 Example 2
250 meters; cross-sectional area of line A = 0.5 mm2 ; resulting in 71 Ω/km, RCON = 2 Ω
• Meter receives data: RC = 64 Ω
• Meter sends data: RC = 63 Ω
(RC – RCON) ∗ A
l = = 710 m
2ρ
The formula used for “Meter sends data” is decisive for sizing the M-bus line.
where:
A = cross-sectional are of line in mm2
n = number of M-bus devices
l = cable length in m
Formula:
∆VB ∗ CTotal
tr = [s]
Ims
where: