6 . TROUBLE SHOOTING
6-1. OUTDOOR UNIT

NORMAL OPERATING MODE


Display Type LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
Not operating
Cooling operation (1)
Heating operation (2)
Compressor frequency 20 to 30Hz (1)
Compressor frequency 31 to 40Hz (2)
Compressor frequency 41 to 50Hz (3)
Compressor frequency 51 to 60Hz (4)
Compressor frequency 61 to 70Hz (5)
Compressor frequency 71 to 80Hz (6)
Compressor frequency 81 to 90Hz (7)
Compressor frequency 91Hz (8)
Pressure balance operation
Oil recovery operation (1)
Defrosting operation (2)
Test run (3)
Pump down completed (2) (2) (2) (2) (2)
SV1 open (2)
SV2 open (1)
Compressor rotation speed protection (5)

Display Method : Lighted continuously Note : LED4 may be lighted occasionally in the pattern
: 0.5sec ON/0.5sec OFF flashing not shown in the table.
( ) : Flashing times However this is not a problem.
SHOOTING

SHOOTING
TROUBLE

TROUBLE
Operation display Outdoor printed circuit board layouts

ON

LED 1

OFF LED 4 LED 1


LED 5 LED 2
0.5sec LED 6 LED 3

0.5sec 2sec
ON SW2 SW1
Switching Transformer
SW4 SW3

LED 2-6 SW6 SW5

SW8 SW7

OFF

- (06 - 01) -
ABNORMAL MODE

Display type LED 1 LED 2 LED 3 LED 4 LED 5 LED 6


Discharge temperature error (4)
High-pressure error (7)
Low-pressure error (8)
Pump down error (High-pressure error) (9)
Pump down error (Discharge temperature error) (10)
Pump down error (Others) (11)

Discharge temperature thermistor error (1)


Heat exchanger liquid temperature thermistor error (4)
Suction temperature thermistor error (10)
Outdoor temperature thermistor error (11)
Heat exchanger temperature thermistor (middle) error (6)

Pressure switch 1 (HP) error (1)


Pressure switch 2 (LP) error (2)
Compressor rotor location detection error (4)
Electric current trip error (5)
CT error (6)
Trip terminal L start-up error (9)
Power source frequency abnormal (2)
EEPROM error (3)
Microcomputers communication error (7)
Network communication error (8)
Indoor unit error (1) : unit0
(2) : unit1
(3) : unit2
SHOOTING

SHOOTING
TROUBLE

TROUBLE
(4) : unit3
(5) : unit4
(6) : unit5
(7) : unit6
(8) : unit7

: 0.1 sec ON / 0.1 sec OFF flashing


Display method { : 0.3 sec ON / 0.3 sec OFF flashing
( ) : Flashing times

Error display
0.1sec
ON
0.1 sec
LED 1 ON/OFF
repeated
OFF
0.1sec 5sec
0.3sec 0.3sec
ON

LED 2-6

OFF

- (06 - 02) -
6-2. INDOOR UNIT

Error display
Error code Error contents
OPERATION TIMER 3rd (SWING)
indicator indicator indicator

E : 00

0.1sec 0.1sec
E : 02 Model information abnormal
ON/OFF ON/OFF
0.1sec 0.1sec 0.1sec
E : 04 Power supply frequency abnormal
ON/OFF ON/OFF ON/OFF
2 times 0.1sec
E : 09 Room temperature thermistor error
flashing ON/OFF
3 times 0.1sec 1 times
E : 0b Indoor unit heat exchanger thermistor (inlet) error
flashing ON/OFF flashing
3 times 0.1sec 2 times
E : 0A Indoor unit heat exchanger thermistor (middle) error
flashing ON/OFF flashing
4 times 0.1sec
E : 11 Drain abnormal
flashing ON/OFF
5 times 0.1sec 1 times Communication error 1
E : 18 (indoor unit Wired / Simple remote controller)
flashing ON/OFF flashing
5 times 0.1sec 2 times
E : 03 Microcomputer error
flashing ON/OFF flashing
5 times 0.1sec 4 times Communication error 2
E : 18 (indoor unit Wired / Simple remote controller)
flashing ON/OFF flashing
6 times 0.1sec
E : 13 Indoor unit fan error
flashing ON/OFF
0.1sec 3 times 3 times
SHOOTING

SHOOTING
E : 32 Outdoor unit error
TROUBLE

TROUBLE
ON/OFF flashing flashing
0.1sec 4 times 1 times
E : 06 EEPROM access error
ON/OFF flashing flashing
0.1sec 4 times 2 times EEPROM deletion error
E : 07
ON/OFF flashing flashing
0.1sec 5 times 1 times
E : 1F Transmission error
ON/OFF flashing flashing
0.1sec 6 times
E : 21 Parallel communication error
ON/OFF flashing

- (06 - 03) -
6-3. WIRED, SIMPLE REMOTE CONTROLLER

Error cord Error contents

E : 00 No error

E : 02 Model information abnormal

E : 03 Micro computer error

E : 04 Power supply frequency abnormal

E : 06 EEPROM access error

E : 07 EEPROM deletion error

E : 09 Room temperature thermistor error

E : 0A Indoor unit heat exchanger thermistor (middle) error

E : 0b Indoor unit heat exchanger thermistor (inlet) error

E : 11 Drain abnormal
SHOOTING

SHOOTING
TROUBLE

TROUBLE
E : 13 indoor unit fan error
Communication error 1 (Indoor unit wired/simple
E : 18
Communication error 2 remote controller)

E : 1F Transmission error

E : 21 Parallel communication error

E : 32 Outdoor unit error

- (06 - 04) -
6-4. GROUP REMOTE CONTROLLER
GROUP REMOTE CONTROLLER
Error
Code Outdoor unit error Indoor unit error Group remote controller error
Convertor error
00 No error No error No error
01
02 Model information abnormal Model information abnormal
03 Microcomputer communication error Microcomputer communication error Microcomputer communication error
04 Power supply frequency abnormal Power supply frequency abnormal
05 Parallel communication error
06 EEPROM access error EEPROM access error EEPROM access error
07 EEPROM deletion error EEPROM deletion error
08
09 Compressor 1 error Room temperature thermistor error
0A Compressor 2 error Heat exchanger thermistor (middle) error
0b Compressor 3 error Heat exchanger thermistor (inlet) error
0C Heat exchanger thermistor (outlet) error
0d Discharge temperature thermistor 1 error Blower temperature thermistor error
0E Discharge temperature thermistor 2 error
0F Discharge temperature thermistor 3 error
10 Outdoor temperature thermistor error
11 Heat exchanger inlet thermistor 1 error Drain abnormal
12 Heat exchanger inlet thermistor 2 error Room temperature abnormal
13 Heat exchanger inlet thermistor 3 error Indoor unit fan error
14 Heat exchanger outlet thermistor 1 error
15 Heat exchanger outlet thermistor 2 error
16 Heat exchanger outlet thermistor 3 error
17 Suction temperature thermistor error
18 Standard wired remote control communication error
19 Discharge pressure sensor error
1A Liquid pressure sensor error Address setting error
1b Suction pressure sensor error
1C Oil sensor error Connection error
1d System error
1E
1F Transmission error Transmission error Transmission error
20
SHOOTING

SHOOTING
TROUBLE

TROUBLE
21 Discharge temperature 1 error
22 Discharge temperature 2 error
23 Discharge temperature 3 error
24 High-pressure error
25 Low-pressure error
26
27 Oil recovery error
28 Pump down error

- (06 - 05) -
NETWORK CONVERTOR

Error code Error contents

Normal

System malfunction

Main circuit board maintenance error

Middle circuit board connected incorrectly

Bottom circuit board connected incorrectly

Middle circuit board maintenance error

Bottom circuit board maintenance error

Circuit board and LED layouts

Bottom circuit board


SHOOTING

SHOOTING
TROUBLE

TROUBLE
Middle circuit board

Main circuit board

D118 D119
D110
D111
D112
D113
D114

- (06 - 06) -
6-5. CASES SUCH AS THESE ARE NORMAL
Operation not trouble

From the standpoint of control, the following operations are incorporated for air conditioner operation
and protection. They do not indicate trouble.

Operation Description Indoor unit Remote indication

Indicates that the power came on normally when power The red and green lamps flash
was applied (at power failure recovery). Indication is alternately in the operation stop
cleared by RUN command. state.
Red and green lamps flash
alternately.
When test run is performed, the unit operates
The red and green lamps flash
without regard to the temperature setting. Stopped by
simultaneously in the operation TEST
remote controller stop. or reset after 60 minutes.
state.

Operation is stopped and refrigerant is passed through


Red lamp flashes. the indoor unit to remove the outdoor unit frost The fan stops and the refrigerant
(defrosting operation) or to recover the refrigerant oil passes through. The red lamp DEFROST
(oil recovery operation). The indoor unit stops in about flashes slowly.
5-10 minutes.

Indoor unit fan does not operate The fan is stopped to prevent blowing out of cold air
The fan stops and the red lamp
even through the RUN signal has when the machine is still not warm at the start of
lights steadily.
entered. heating operation. About 3 minutes are necessary.

When the room temperature at heating operation reaches


the set temperature, the FAN is stopped and room
The fan continues to operate and
Fan turns on/off periodically. temperature rise is prevented. At this time, the fan is
the red lamp lights steadily.
operated periodically to detect the room temperature.
(4 minutes stop, 1minute operate)

When an [AUTO], [FAN] and an operation other than the


operation another indoor unit is already performing at Buzzer buzzes 5 times and setting
RUN signal is input, but is not
SHOOTING

SHOOTING
cooling/heating selection type or [HEAT] operation at a is not received. Operation before
TROUBLE

TROUBLE
accepted. Buzzer sounds.
cooling only unit is commanded, operation cannot be setting continues.
performed at that setting.

Makes a sound even after operation After cooling operation stops, the drain pump is
stops. operated. Remains for 3 minutes.

A sound changed by the refrigerant flow may be made


Flowing liquid by operation of another indoor unit connected to the
sound during same outdoor unit. A switching sound may be made at
operation the start and after the end of defrosting operation and
oil recovery operation.

Makes a sound This is due to expansion and contraction of resin parts


while operating. Squeaking sound
by the temperature change during heating operation
and oil recovery operation.

A sound is generated when the internal valve is


Switching sound switched at operation switching and at the start
of defrosting operation and oil recovery operation.

When operation and indication other than the above occurs, call the manager.

- (06 - 07) -