6 . TROUBLE SHOOTING
6-1. OUTDOOR UNIT
Display Method : Lighted continuously Note : LED4 may be lighted occasionally in the pattern
: 0.5sec ON/0.5sec OFF flashing not shown in the table.
( ) : Flashing times However this is not a problem.
SHOOTING
SHOOTING
TROUBLE
TROUBLE
Operation display Outdoor printed circuit board layouts
ON
LED 1
0.5sec 2sec
ON SW2 SW1
Switching Transformer
SW4 SW3
SW8 SW7
OFF
- (06 - 01) -
ABNORMAL MODE
SHOOTING
TROUBLE
TROUBLE
(4) : unit3
(5) : unit4
(6) : unit5
(7) : unit6
(8) : unit7
Error display
0.1sec
ON
0.1 sec
LED 1 ON/OFF
repeated
OFF
0.1sec 5sec
0.3sec 0.3sec
ON
LED 2-6
OFF
- (06 - 02) -
6-2. INDOOR UNIT
Error display
Error code Error contents
OPERATION TIMER 3rd (SWING)
indicator indicator indicator
E : 00
0.1sec 0.1sec
E : 02 Model information abnormal
ON/OFF ON/OFF
0.1sec 0.1sec 0.1sec
E : 04 Power supply frequency abnormal
ON/OFF ON/OFF ON/OFF
2 times 0.1sec
E : 09 Room temperature thermistor error
flashing ON/OFF
3 times 0.1sec 1 times
E : 0b Indoor unit heat exchanger thermistor (inlet) error
flashing ON/OFF flashing
3 times 0.1sec 2 times
E : 0A Indoor unit heat exchanger thermistor (middle) error
flashing ON/OFF flashing
4 times 0.1sec
E : 11 Drain abnormal
flashing ON/OFF
5 times 0.1sec 1 times Communication error 1
E : 18 (indoor unit Wired / Simple remote controller)
flashing ON/OFF flashing
5 times 0.1sec 2 times
E : 03 Microcomputer error
flashing ON/OFF flashing
5 times 0.1sec 4 times Communication error 2
E : 18 (indoor unit Wired / Simple remote controller)
flashing ON/OFF flashing
6 times 0.1sec
E : 13 Indoor unit fan error
flashing ON/OFF
0.1sec 3 times 3 times
SHOOTING
SHOOTING
E : 32 Outdoor unit error
TROUBLE
TROUBLE
ON/OFF flashing flashing
0.1sec 4 times 1 times
E : 06 EEPROM access error
ON/OFF flashing flashing
0.1sec 4 times 2 times EEPROM deletion error
E : 07
ON/OFF flashing flashing
0.1sec 5 times 1 times
E : 1F Transmission error
ON/OFF flashing flashing
0.1sec 6 times
E : 21 Parallel communication error
ON/OFF flashing
- (06 - 03) -
6-3. WIRED, SIMPLE REMOTE CONTROLLER
E : 00 No error
E : 11 Drain abnormal
SHOOTING
SHOOTING
TROUBLE
TROUBLE
E : 13 indoor unit fan error
Communication error 1 (Indoor unit wired/simple
E : 18
Communication error 2 remote controller)
E : 1F Transmission error
- (06 - 04) -
6-4. GROUP REMOTE CONTROLLER
GROUP REMOTE CONTROLLER
Error
Code Outdoor unit error Indoor unit error Group remote controller error
Convertor error
00 No error No error No error
01
02 Model information abnormal Model information abnormal
03 Microcomputer communication error Microcomputer communication error Microcomputer communication error
04 Power supply frequency abnormal Power supply frequency abnormal
05 Parallel communication error
06 EEPROM access error EEPROM access error EEPROM access error
07 EEPROM deletion error EEPROM deletion error
08
09 Compressor 1 error Room temperature thermistor error
0A Compressor 2 error Heat exchanger thermistor (middle) error
0b Compressor 3 error Heat exchanger thermistor (inlet) error
0C Heat exchanger thermistor (outlet) error
0d Discharge temperature thermistor 1 error Blower temperature thermistor error
0E Discharge temperature thermistor 2 error
0F Discharge temperature thermistor 3 error
10 Outdoor temperature thermistor error
11 Heat exchanger inlet thermistor 1 error Drain abnormal
12 Heat exchanger inlet thermistor 2 error Room temperature abnormal
13 Heat exchanger inlet thermistor 3 error Indoor unit fan error
14 Heat exchanger outlet thermistor 1 error
15 Heat exchanger outlet thermistor 2 error
16 Heat exchanger outlet thermistor 3 error
17 Suction temperature thermistor error
18 Standard wired remote control communication error
19 Discharge pressure sensor error
1A Liquid pressure sensor error Address setting error
1b Suction pressure sensor error
1C Oil sensor error Connection error
1d System error
1E
1F Transmission error Transmission error Transmission error
20
SHOOTING
SHOOTING
TROUBLE
TROUBLE
21 Discharge temperature 1 error
22 Discharge temperature 2 error
23 Discharge temperature 3 error
24 High-pressure error
25 Low-pressure error
26
27 Oil recovery error
28 Pump down error
- (06 - 05) -
NETWORK CONVERTOR
Normal
System malfunction
SHOOTING
TROUBLE
TROUBLE
Middle circuit board
D118 D119
D110
D111
D112
D113
D114
- (06 - 06) -
6-5. CASES SUCH AS THESE ARE NORMAL
Operation not trouble
From the standpoint of control, the following operations are incorporated for air conditioner operation
and protection. They do not indicate trouble.
Indicates that the power came on normally when power The red and green lamps flash
was applied (at power failure recovery). Indication is alternately in the operation stop
cleared by RUN command. state.
Red and green lamps flash
alternately.
When test run is performed, the unit operates
The red and green lamps flash
without regard to the temperature setting. Stopped by
simultaneously in the operation TEST
remote controller stop. or reset after 60 minutes.
state.
Indoor unit fan does not operate The fan is stopped to prevent blowing out of cold air
The fan stops and the red lamp
even through the RUN signal has when the machine is still not warm at the start of
lights steadily.
entered. heating operation. About 3 minutes are necessary.
SHOOTING
cooling/heating selection type or [HEAT] operation at a is not received. Operation before
TROUBLE
TROUBLE
accepted. Buzzer sounds.
cooling only unit is commanded, operation cannot be setting continues.
performed at that setting.
Makes a sound even after operation After cooling operation stops, the drain pump is
stops. operated. Remains for 3 minutes.
When operation and indication other than the above occurs, call the manager.