Design calculation sheet


Project no: Date: Sheet no.: 1 of 2 Computed by:
Project name : Castle Landmark Checked by:
Subject: Parking garage ventilation Approved by:

BASEMENT 1

Parameter Description Value Unit


N No. Of cars 4000 No.
N No. Of cars at peak 2500 No.
θ Travel And Operation Time 120 Sec
Sec.
Af Garage Floor Area 1345000 ft2
H Average Hight Of Garage 13.12 ft
CO max Max. Allowed CO Concentration 25 ppm
E Average CO Emission Rare 1.544 Ib/hr  ASHRAE 2007, Applications, Table (8)
2
Go Generation Rate Reference Ratio (Constant) 0.00546 Ib/hr.ft
2
G Emission Generation Rate at Peak 0.0028699 Ib/hr.ft  ASHRAE 2007, Applications, eq. (16)
f Generation Rate Normalization Ratio 52.56206 -  ASHRAE 2007, Applications, eq. (17)
2
C Constant 0.0001363 cfm/ft .s
Q Ventilation Ratio 0.8597051 cfm/ft2  ASHRAE 2007, Applications, eq. (18)

Required Ventilation Air Flow Rate CFM 1156303.3

Air Chang Per Hour (ACH) 3.931578

Air Chang Per Hour (ACH) @ Fire Case 6

29/01/2022 11:58 ‫م‬


2007 ASHRAE Handbook - HVAC Applications
Where:
C=2.370*10-4 CFM/FT2.S a  FOR COMAX =15ppm
C=1.363*10-4 CFM/FT2.S a  FOR COMAX =25ppm
C=0.948*10-4 CFM/FT2.S a  FOR COMAX =35ppm

Table 8 : Predicted CO Emissions in Parking Garages :


Hot Emission (Stabilized) Cold Emission
Ib/h Ib/h
Season 1991 1996 1991 1996
o
Summer,90 F 0.336 0.25 0.565 0.484
o
Winter,90 F 0.478 0.45 2.744 2.508

1.611 0.4505
1.4775 0.367
E at Winter 1.54425 E at Summer 0.40875

eq.(16)  G=NE/AF  Ib/hr.ft2


eq.(17)  F=100*G/GO  -
eq.(18)  Q=CFθ  CFM/FT2

Reference Value:  GO =5.46*10-3 Ib/hr.ft2 Constant