ANNEXURE-1

Heat Load Summary


Cooling Cooling
10AM 4PM Fresh air Total
A/C Area No. of Lighting Appliances ADP Capacity at Capacity at Total
Sl. No. Description Dehumidified Air Dehumidified Air Qty. OAACH SHF 4PM Dehumidified TAACH
(sq.ft) People (W/sq.ft) (kW) 4PM 10AM 4PM TR
Qty. (cfm) Qty. (cfm) (cfm) Air Qty. (cfm)
(TR) (TR)
1 GF-01-Auditorium 4996 520 1.0 2.00 15490 18292 4200 2.3 0.70 55.00 53.31 60.78 18292 10 60.8

2 GF-02-Stage 650 20 5.0 0.00 2070 2725 239 1.0 0.90 53.98 4.82 5.91 2725 11 5.9
3 GF-03-Green Room 274 10 3.0 0.00 1087 1014 66 1.2 0.88 53.58 2.18 2.14 1087 20 2.2
Summary 5921 550 2 18648 22031 4505 60 69 22104 69

Design Considerations :
Occupancy :- Floor to Bottom of Slab Height :- 6.7m
a. 520 Seating Capacities for Auditorium Seating area
b. 20 people in the Stage Area Glass Height Details :-
c. 10 people in the Green Room a. Windows :- 1.5m

Heat Emission from Equipments :- Type of Glass :- Ordinary Plain Glass


a. 2.0 kW of AV equipments a. Solar Factor :- 0.82 (82%)
2
b. "U" Value :- 5.7 Watts/m K
Heat Emission from Lights :-
a. 1.0 Watts/sq.ft for Auditorium area Design Condition :-
b. 3.0 Watts/sq.ft for Green room a. Outside (DBT & WBT) :- 103 °F (39.44°C) & 82°F (27.77°C) *
c. 5.0 Watts/sq.ft for Stage area b. Inside (DBT & RH) :- 73°F (22.77°C) & 55%

Fresh Air cfm :-


a. 7.5 cfm/person + 0.06 cfm/sq.ft for Auditorium Seating area (Considered as Multiuse assembly)
b. 10 cfm/person + 0.06 cfm/sq.ft for Stage.
c. 5 cfm/person + 0.06 cfm/sq.ft for Green room

* Note : Puducherry weather data is unavailable in ISHRAE HVAC Handbook. Hence, we have considered Chennai Weather data for calculation

Abbreviations :
A/C Air-conditioning
ADP Apparatus Dew point Temperature
cfm Cubic Feet per Minute
OAACH Outdoor Air Airchanges per Hour
SHF Sensible Heat Factor
TAACH Total Air Airchanges per Hour
TR Ton of Refrigeration

Rev. : R0
Date : 15-Feb-19 1 of 1