Thermal load bill of quantities (Summary of Cooling Loads) Ruko PPN - Pramount Petals

Cooling load
12:00 14:00 16:00
Air Indoor load Indoor load Indoor load
Systematic Fresh air (Load per Fresh air (Load per Fresh air (Load per
Fioor Room name conditioning Total Total Total Remarks
name Sensible load m2) Sensible load m2) Sensible load m2)
system Total heat Total heat Total heat
heat heat heat
(W) (W) (W) (W) (PK) Btuh/m2 (W) (W) (W) (W) (PK) Btuh/m2 (W) (W) (W) (W) (PK) Btuh/m2
2nd Floor
1 2nd Lobby 7,953 8,907 2,119 11,026 8 626.7 6,617 7,902 2,119 10,021 8 570 7,220 8,535 2,119 10,654 8 606
Class Room 4,664 5,427 6,443 11,870 9 1,065 3,997 4,727 6,443 11,170 8 1,002 4,566 5,325 6,443 11,768 9 1,056
3rd Floor
2 3rd OFFICE 4,507 5,156 2,577 7,733 6 533 4,348 4,989 2,577 7,566 6 521 4,189 4,822 2,577 7,400 6 510
Manager Room 2,929 3,181 1,404 4,586 3 977 2,514 2,745 1,404 4,150 3 884 2,619 2,856 1,404 4,260 3 908
Meeting Room 4,016 4,535 438 4,973 4 848 3,677 4,179 438 4,617 3 787 3,783 4,290 438 4,728 4 806
Server room 1,410 1,728 452 2,180 2 991 1,211 1,498 452 1,951 1 887 1,290 1,590 452 2,042 2 928

Sub-total 1 25,479 28,934 13,434 42,368 31 22,364 26,041 13,434 39,475 30 23,667 27,417 13,434 40,851 31