Professional Documents
Culture Documents
for the
hydro-Genius Professional
experimentation models
All rights reserved. These operating instructions and each separate part thereof are
protected by copyright. All exploitation, duplication or photocopying is prohibited except in cases
permitted by law.
Contents
P e2 Faraday's Laws 20
Materials required:
Instructions:
Voltmeter/Ammeter
+ -
V
+ -
A
DC Power supply
+ -
0 - 3,0 V Solar module
1. Place the solar module on a solid base and cover it completely with a piece of black cardboard.
2. Set up the apparatus as shown in Fig. s1a and connect the solar module to the DC power supply in "forward
direction", i.e. the positive terminal of the DC power supply to the positive terminal of the solar module and
the negative terminal of the DC power supply to the negative terminal of the solar module.
3. Adjust the DC power supply to different voltages (in 0.5 volt steps between 0 and 1.5 volts, and in 0.2 volt
steps between 1.5 and 2.5 volts) and measure the dark current and voltage.
The voltage across the DC power supply must not exceed 3.0 volts!
Voltage / V Current / mA
Evaluation:
1. Draw the IV diagram (dark IV characteristic curve of the solar
module).
2000
1500
Current / mA
1000
500
0
0 0.5 1 1.5 2 2.5
Voltage / V
You can verify this with a small experiment. Swap over the polarity at the
DC power supply according to Fig. s1a and gradually increase the
voltage. What happens to the current? (This measurement should only
be made within a range of 0 to 3 volts, otherwise the solar module will be
destroyed.)
+ - M
V
+ -
A
R
Solar module
Lamp
Evaluation:
1. Draw the IV diagram (light IV curve of the solar module).
1000
Short-circuit current
Current / mA
500
Open-circuit
voltage
0
0 0.5 1 1.5 2 2.5
Voltage / V
1. By drawing the rectangle with the largest possible area within the
IV characteristic curve (P = V x I).
2000
1500 MPP
Power / mW
1000
500
0
0 0.5 1 1.5 2 2.5
Voltage / V
Draw graphs plotting P against V and compare them with the diagram at
a lamp distance of 30 cm.
2000
Distance 20 cm
Distance 30 cm
1500
Distance 40 cm
Power / mW
1000
500
0
0 0.5 1 1.5 2 2.5
Voltage / V
P s2 of Distance and
Angle of Incidence of the
Light Source
Materials required:
Instructions:
Voltmeter/Ammeter
+ -
V
+ -
A
Solar module
Lamp
Evaluation:
1. Draw the I- and I-cos diagram.
2
2. Draw the I-d and I-1/d diagram.
3. What are the functional relations and what effects do they have on
practical applications?
The photocurrent is highest when the light strikes the solar module
perpendicularly.
1000
900
800
700
Curernt / mA
600
500
400
300
200
100
0
0 10 20 30 40 50 60 70 80 90
Angle / °
1000
900
800
700
Current / mA
600
500
400
300
200
100
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
cos
Note: deviations from the ideal cosine law are caused by fluctuations in
the cone of light
1000
900
800
700
Current / mA
600
500
400
300
200
100
0
40 60 80 100 120 140 160
Distance d / cm
1000
900
800
700
Current / mA
600
500
400
300
200
100
0
0 0.0001 0.0002 0.0003
1/d2 / cm-2
Th
e photocurrent of the solar module is inversely proportional tothe square of the distanceof the light source ( I ~ 1/d2).
For example, the sun's maximum angle of altitude (at 12 o'clock sun
time) in the south of Germany (latitude 48° north) varies between
When large-scale solar plants are installed, therefore, they are aligned to
the course of the sun's angle of altitude.
Pointing the solar modules towards the south (e.g. on the roof of a
building) proves to be favorable, since this makes it possible to tap the
radiation both in the morning and in the afternoon.
Materials required:
Instructions:
Fig. e1
Voltmeter/Ammeter
+ -
V
+ -
A
Electrolyser
O2 H2
0 ml ml 0
+ -
20 20
40 40
60 60
Solar module
Lamp
2. Vary the light intensity to adjust the current of the solar module, i.e. by turning the solar module at
different angles to the incident light (see Experiment s2). Set different current values, starting at
small currents of approx. 30 mA and going up to approx. 800 mA (depending on the type of lamp
used; with DC power supply up to about 3 amps). Also record the electrolysers voltage. Take at
least 8 pairs of measurements of electrolysis current and voltage and enter the values in the table
of measurements.
Voltage / V Current / mA
Evaluation:
1. Draw the IV characteristic curve of the electrolyser.
3000
2000
Current / mA
1000
0
1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
Voltage / V
A small voltage (e.g. 1.2 volts) does not set off an electrolysis current
that would lead to the release of hydrogen at the cathode and oxygen at
the anode.
Materials required:
Instructions:
Fig. e2a
Voltmeter/Ammeter
+ -
V
+ -
A
Electrolyser
O2 H2
0 ml ml 0
+
20
40
20
40
60
-
60
Solar module
Lamp
2. Make sure that both of the electrolyser's gas storage cylinders are filled with distilled water up to
the 0 ml mark. To take the measurement, seal the hydrogen storage cylinder with a tube clip (see
Fig. e2b). The hydrogen generated will then be collected in the storage cylinder.
Fig. e2b
Electrolyser
O2 H2
0 ml ml 0
+
20
40
60
20
40
60
-
Tube clip
3. Adjust the solar module to provide a constant current (e.g. 850 mA) and measure the volume of
hydrogen generated over different periods (60 to 210 s in 30 s steps) [Table of Measurement 1].
4. Prescribe a constant time (t = 180 s). Set different currents by lining up the solar module at
different angles (in 200 mA steps between 200 mA and 800 mA). Measure the volume of
hydrogen generated at these currents. [Table of Measurement 2]
The measurement value of 800 mA requires a correspondingly strong lamp. The solar
module may only be illuminated at this level of intensity for the duration of the
measurement.
I= mA = constant t= s = constant
Evaluation:
1. Plot two graphs based on the readings from tables [1] and [2]
(volume versus time and volume versus current).
20 Current = 850 mA
Volume V / ml
15
10
0
0 50 100 150 200 250
Measurement time t / s
20
t = 180
Volume V / ml
15
10
0
0 200 400 600 800 1000 1200
Current I / mA
V t
V I
If V t and V I , then:
V I t.
V Q
V n Vm
V 19 ml ,
the charge Q that flows can be calculated and set in relation to the
amount of material released:
Q I t
Q V
Qm n
n Vm
Q Vm
Qm Vm 24 l mol 1
(20 C , normal pressure)
V
1
153 C 24 l mol 1
Qm 193,300 C mol
0.019 l
Qm z F,
Qm ( H 2 ) 2 F 192,968 C mol 1 .
Materials required:
Instructions:
Fig. e3a
Voltmeter/Ammeter
+ -
V
+ -
A
Electrolyser
O2 H2
0 ml ml 0
+
20
40
20
40
60
-
60
Solar module
Lamp
2. Make sure that both of the electrolyser's gas storage cylinders are filled with distilled water up to
the 0 ml mark. To take the measurement, seal the hydrogen storage cylinder with a tube clip (see
Fig. e3b). The hydrogen generated will then be collected in the storage cylinder.
Fig. e3b
Electrolyser
O2 H2
0 ml ml 0
+
20
40
60
20
40
60
-
Tube clip
3. Adjust the illuminated solar module to provide a constant electrolysis current (e.g. 800 mA) and
measure the volume of hydrogen released over a given period of time. Take three measurements
over the same time period (e.g. t = 240 sec.) and use the average value of the stored hydrogen for
your calculations.
Table of measurements:
Time = s V1 = ml Vaverage = ml
Voltage = V V2 = ml
Current = mA V3 = ml
Evaluation:
1. Determine the Faraday efficiency of the electrolyser.
V H 2 exp erimental
F
V H 2 theoretical
Measurement results:
Time = 240 s V1 = 23 ml Vaverage = 23.5 ml
Voltage = 1.587 V V2 = 24 ml
The Faraday efficiency expresses how much of the current that has
flowed is converted into the desired reaction. If it was much smaller than
one (100 %), this would mean that secondary reactions were taking
place in the system (e.g. corrosion). This would shorten the service life of
the electrolyser and necessitate a higher energy input.
H 0 H 2 VH 2 exp erimental
E
U I t
The calorific value H is the amount of heat released during the combus-
tion of a specific volume (e.g. 1 m3) of gas. The gross calorific value HO
is quoted if the water left behind after combustion is in liquid form. The
gross calorific value of hydrogen HOH2 at a temperature of 20°C is
-3
11,920 kJ/m .
11,920 kJ m 3 23.5 ml
E 0.92
1.587V 0.8 A 240 s
Units: 1VAs 1 m3
1J 106 ml
Materials required:
Solar module 9 hook-up cables
Electrolyser 2 long tubes
Fuel cell 2 short tubes
Load module 2 tube clips
Demonstration Ammeter/Voltmeter Additional components:
Lamp 100-150 watts Distilled water
Instructions:
+ - M
1 V
+ O2 H2 -
2 + -
A
R
Electrolyser
O2 H2
0 ml ml 0
+
20
40
60
20
40
60
-
Solar module
Lamp
Fuel cell
1
+ O2 H2 -
2
5. Use the tube clips to close the two short tubes at the gas outlets of the fuel cell (see Fig. b1b).
6. Interrupt the connection between the solar module and the electrolyser when the 60 ml mark is
reached on the hydrogen side of the electrolyser.
7. Now measure the characteristic curve of the fuel cell by varying the measurement resistance
(rotary switch on the load module). Start at position "OPEN" (open-circuit voltage), then decrease
the resistance step by step by turning the rotary switch to the right. Record the current and
voltage at each switch position. Wait for 30 seconds each time before taking the measurements.
Enter the figures in the table of measurements. Also measure the figures when the lamp at the
load module is in operation.
8. After recording the characteristic curve, reset the rotary switch on the load module to "OPEN" and
remove the clips at the fuel cell.
+ - M
1 V
+ O2 H2 -
2 + -
A
R
Tube clips
Electrolyser
O2 H2
0 ml ml 0
+
20
40
20
40 -
60 60
Solar module
Lamp
Repeat the measurements with the fuel cells connected in series as illustrated in Fig. b1c.
3. Enter the voltage and current of the lamp into the VI characteristic
curve.
5. Draw the PI diagrams for the fuel cells connected in series and
parallel. Calculate the power consumption of the lamp and enter
the values into the PI diagrams.
Experiment variations:
6. In a further experiment, you can remove the tube from the oxygen
inlet nozzle of the fuel cell and in this way operate the fuel cell with
oxygen from the ambient air. Hydrogen will continued to be taken
from the electrolysers storage cylinder.
0.6
0.5
0.4
0.3
0.2
0.1
0
0 500 1000 1500 2000 2500
Current / mA
1.4
Voltage / V
1.2
Lamp
1
0.8
0.6
0.4
0.2
0
0 500 1000 1500 2000 2500
Current / mA
2 Connected in parallel
Power / W
1.5
0.5
0
0 500 1000 1500 2000 2500
Current / mA
1.2
0.5 Ohm
1
0.8
0.6
0.4
0.2
0
0 500 1000 1500 2000 2500
Current / mA
Materials required:
Solar module 9 hook-up cables
Electrolyser 2 long tubes
Fuel cell 2 short tubes
Load module 2 tube clips
Demonstration Ammeter/Voltmeter Additional components:
Lamp 100-150 watts Distilled water
Instructions:
+ - M
1 V
+ O2 H2 -
2 + -
A
R
Electrolyser
O2 H2
0 ml ml 0
+ -
20 20
40 40
60 60
Solar module
Lamp
Fuel cell
1
+ O2 H2 -
2
Experiment Variations:
Determine the energy efficiency as a function of the current flowing
through the fuel cell.
Set currents between 400 and 2000 mA by varying the resistance in the
load module. If necessary, adjust the measurement time to ensure that
you can carry out a measurement with a single filling of the storage
cylinders.
Table of measurements:
R= 0.3 time = s V1 = ml Vaverage= ml
voltage = V V2 = ml Vcorr = ml
current = A V3 = ml
Measured values:
R= 0.3 time = 180 s V1 = 45 ml Vaverage = 47 ml
current = 1.94 A V3 = 48 ml
V H 2 exp erimental
F
V H2 theoretical
V
I t n z F n
Vm
I t Vm
V H 2 theoretical z F
1
1.94 A 180 s 24 l mol
43.4 ml
V H 2 theoretical 2 96,484 C mol 1
Faraday efficiency:
V H 2 theoretical 43.4 ml
F 0.98
44 ml
V H 2 exp erimental
The Faraday efficiency of the fuel cell can be less than one for the
following reasons:
electrical energy
E
theoretica l energy contentof hydrogen
U I t
E
H0 H2 VH 2 exp erimenal
Units: 1VAs 1 m3
1J 106 ml
Materials required:
Solar module 9 hook-up cables
Electrolyser 2 long tubes
Fuel cell 2 short tubes
Load module 2 tube clips
Demonstration Ammeter/Voltmeter Additional components:
Lamp 100-150 watts Distilled water
Instructions:
+ - M
1 V
+ O2 H2 -
2 + -
A
R
Electrolyser
O2 H2
0 ml ml 0
+ -
20 20
40 40
60 60
Solar module
Lamp
2. Check that the gas tubes between the electrolyser and the fuel cell are correctly connected.
Adjust the rotary switch on the load module to "OPEN".
3. Make sure that both of the electrolyser's gas storage cylinders are filled with distilled water up to
the 0 ml mark. Use the illuminated solar module to set a constant current (between 700 and 900
mA). The solar module must be aligned toward the light source in such a way that gas production
can be clearly observed (see Experiment e1).
4. Purge the entire system for 5 minutes with the gases produced. Then set the rotary switch on the
load module to 2 for 3 minutes. The ammeter should now show a current of about 400 mA and
the voltmeter a voltage of about 0.75 volts. Now turn the rotary switch on the load module back to
"OPEN".
Fig. b3b (Storing the gases and measuring Faraday’s 1st law with a fuel cell):
+ - M
1 V
+ O2 H2 -
2 + -
A
R
Tube clips
Electrolyser
O2 H2
0 ml ml 0
+ -
20 20
40 40
60 60
Solar module
Lamp
6. Interrupt the connection between the solar module and the electrolyser when the 60 ml mark is
reached on the hydrogen side of the electrolyser.
7. Since the system always has a certain leakage rate because of its tubes and seals, an idle
measurement must be made first. Record the loss of hydrogen from the hydrogen storage cylinder
without load (position "OPEN") over a period of 3 minutes and determine the leakage rate in ml of
hydrogen per minute.
8. Reconnect the electrolyser to the solar module and refill the hydrogen storage cylinder up to the
60 ml mark. Then interrupt the power supply to the electrolyser again.
9. In order to determine the 1st part of Faraday's Law, set a resistance of 0.5 . Record the volume
of hydrogen consumed by the fuel cell over various periods (60 to 240 s in 60 s steps) [Table of
measurements 1]. Also measure the current of the fuel cell and record all values. Then adjust the
rotary switch back to the "OPEN" position.
10. Reconnect the solar module to the electrolyser and refill the hydrogen storage cylinder up to the
60 ml mark. Then interrupt the voltage supply to the electrolyser again.
11. In order to determine the 2nd part of Faraday's Law, successively set different levels of current by
selecting different resistances of 3, (2), 1, (0.5) and 0.3 using the rotary switch on the load
module. The measurement time should be 180 seconds.
12. After completing all the measurements, switch back to "OPEN" and remove the clips from the fuel
cell.
Evaluation:
1. Plot the recorded data from measurement tables [1] and [2]
(volume versus time and volume versus current).
40 I = 1250 mA
Volume V / ml
30
20
10
0
0 50 100 150 200 250
Measurement time t / s
40 t = 180 s
Volume V / ml
30
20
10
0
0 500 1000 1500 2000
Current I / mA
V t
V I
If V t and V I , then:
V I t.
V Q
V n Vm
Materials required:
Solar module 6 hook-up cables
Electrolyser 2 long tubes
Fuel cell 2 short tubes
Load module 2 tube clips
Lamp 100-150 watts Additional components:
Distilled water
Instructions:
M
1
+ O2 H2 -
2
R
Electrolyser
O2 H2
0 ml ml 0
+ -
20 20
40 40
60 60
Solar module
Lamp
2. Check that the gas tubes between the electrolyser and the fuel cell are correctly connected.
Adjust the rotary switch on the load module to "OPEN".
3. Make sure that both of the electrolyser's gas storage cylinders are filled with distilled water up to
the 0 ml mark. Use the illuminated solar module to set a constant current (between 700 and 900
mA). The solar module must be aligned toward the light source in such a way that gas production
can be clearly observed (see Experiment e1).
4. Purge the entire system for 5 minutes with the gases produced. Then set the rotary switch on the
load module to 2 . The ammeter should now show a current of about 400 mA and the voltmeter
a voltage of about 0.75 volts. Now turn the rotary switch on the load module back to "OPEN".
Fuel cell
1
+ O2 H2 -
2
5. Use the clips to close the two short tubes at the gas outlets of the fuel cell (see Fig. g1b).
6. Interrupt the connection between the solar module and the electrolyser when the 60 ml mark is
reached on the hydrogen side of the electrolyser. Also measure the volume of oxygen generated
during the same period.
7. Adjust the rotary switch on the load module to a resistance of 0.5 . A current flows, and the fuel
cell consumes the stored hydrogen.
8. Interrupt the electrical connection when the 0 ml mark on the hydrogen side is reached by setting
the rotary switch to "OPEN". The fuel cell has now consumed all the stored hydrogen (60 ml).
Measure the volume of consumed oxygen.
Volume of hydrogen ml ml
Volume of oxygen ml ml
Evaluation:
1. Measure the respective gas volumes.
3. Determine the ratio of the gases consumed by the fuel cell during
operation.
Interpretation/Notes:
The experiments carried out demonstrate the decomposition of water
into 2 parts of hydrogen and 1 part of oxygen:
2H2O 2H2 + O2
In the fuel cell, the reverse of electrolysis takes place, i.e. the gases
stored during electrolysis are converted back into water.
2H2 + O2 H2O
This proves that this reaction is reversible. The first reaction (electrolysis)
expends electrical energy, whereas the second reaction (fuel cell)
releases electrical energy. Altogether such a cycle involves energy
losses, i.e. the efficiency level is less than 1.