INSUL-SHEET R 8

sheet
to meet International Energy

Sheet Insulation
Conservation Code requirements
for Outdoor Ductwork

Flexible Closed Cell Insulation


Protected by the
Made in USA Refer to K-Flex USA L.L.C. Bio-Guard™ System
Designed for the HVAC/R Industry

can be used as duct covering. INSUL- no additional protection.


SHEET® is recommended for applica-
Additional vapor barrier protection
tions ranging from -297°F to 220°F
may be necessary for INSUL-SHEET®
(-182°C to 104°C) when used as pipe
when installed on low temperature
insulation where only the seams and
surfaces that are exposed to
butt joints are glued. On full adhesion
continuous high humidity.
applications, the upper limit is 200°F
(93°C).
FLAME AND SMOKE RATING
INSUL-SHEET® has a very tough INSUL-SHEET® insulation in thick-
skin which withstands tearing, rough nesses of 1 1/2" (38 mm) and below
handling, and severe environmental has a flame spread rating of 25 or
conditions, and yet is quite flexible for less and a smoke development rating
easy installation. INSUL-SHEET® has of 50 or less as tested by ASTM E 84
superior cold weather flexibility. Method of Testing entitled: “Surface
INSUL-SHEET® thickness has been Burning Characteristics of Building
calculated to control condensation Materials.”
DESCRIPTION on cold surfaces. Refer to the table INSUL-SHEET® insulation is accept-
INSUL-SHEET® insulation is an on the reverse side for specific rec- able for use in duct/plenum applica-
environmentally friendly, CFC-free, ommendations. tions meeting the requirements of
flexible elastomeric thermal insula- NFPA 90A/B.
tion. It is black in color and supplied INSTALLATION
as flat sheets (36" x 48") in standard When INSUL-SHEET® insulation is Numerical flammability ratings alone may not define
the performance of products under actual fire condi-
thicknesses of 1/8" thru 2". It is sup- applied to ductwork and equipment, tions. They are provided only for use in the selection of
plied skin two sides in 1/4” and above. use 100% coverage of an approved products to meet limits specified, when compared to a
INSUL-SHEET® is also available in contact adhesive. With a contact known standard.
rolls, with a standard roll width of 48". adhesive, both surfaces to be joined
INSUL-SHEET® is non-porous, non- should be coated and then joined SPECIFICATION COMPLIANCE
fibrous and resists mold growth. The after the adhesive is dry to the touch. ASTM C 534 Type 2 (Sheet), Grade 1
Bio-Guard™ antimicrobial system pro- Compression joints with adhesive ASTM D 1056-00-2C1
vides added protection against mold, applied should be used on all butt New York City MEA 186-86-M Vol. IV
fungal and bacterial growth. The active edges. INSUL-SHEET® is also avail- USDA Requirements
ingredient in Bio-Guard™ is registered able with pre-applied pressure sensi- STC = 17 per ASTM E 90
with the EPA. tive adhesive (PSA) with easy to use UL 94-5V Flammability Classification
K-Flex USA elastomeric insulation prod- release liner. Contact K-Flex USA for (Recognition No. E300774)
specific installation instructions. ASTM E 84 1 1/2" 25/50-tested according to
ucts are GREENGUARD certified as UL 723 and NFPA 255
low VOC materials, meeting the require- Complies with requirements of
ments of the “Children and Schools” OUTDOOR APPLICATIONS CAN/ULC S102-03
classification, the most stringent For optimum performance, outdoor NFPA No. 101 Class A Rating
requirements. Additionally, all K-Flex applications require 374 UV Protective
USA elastomeric insulation products are Meets requirements of NFPA 90A/B
Coating or other recommended pro- Sect. 2.3.3 for Supplementary
GREENGUARD listed for mold resis- tective coating, cladding or jacketing.
tance and meet the “mold resistant” Materials for Air Distribution Systems
For more detailed information refer to
criteria. the Application Guide. Meets requirements of UL 181
sections 11.0 and 16.0
(Mold Growth/Air Erosion)
APPLICATIONS RESISTANCE TO MOISTURE Meets requirements of ASTM C 411
INSUL-SHEET® insulation is used to VAPOR FLOW (Test Method for Hot Surface Performance of
retard heat gain and prevent condensa- The closed-cell structure and unique High Temperature Thermal Insulation)
tion or frost formation on cold equip- formulation of INSUL-SHEET® effec- MIL-P-15280, Form S (Sheet)
ment, tanks, vessels, ducts, or large tively retards the flow of moisture
R8 Sheet meets R-value requirements of the
O.D. pipes. It also effectively retards vapor, and is considered a low trans-
International Energy Conservation Code for
heat loss when used on hot equipment, mittance vapor retarder. For most Outdoor Ductwork.
ducts, or large pipes. INSUL-SHEET® applications, INSUL-SHEET® needs
INSUL-SHEET® S2S Sheet Insulation
PRODUCT DATA

Physical Properties INSUL-SHEET® Test


Insulation Methods

Thermal Conductivity (K) 90°F (32°C) Mean Temp .27 (.039) ASTM C 177/C 518
BTU -in/hr - Ft2 - °F (W/mK) 75°F (24°C) Mean Temp .25 (.036) ASTM C 177/C 518

Operating Temperature Range Upper 220°F (104°C)


Flexible to -40°F (-40°C) Lower -297°F (-182°C)
Water Vapor Permeability Dry Cup. Perm-In <0.06 ASTM E 96
Water Absorption % <0.20 by volume ASTM C 209
Flame Spread (up to 1-1/2” thickness) Not greater than 25 ASTM E 84
Smoke Developed (up to 1-1/2” thickness) Not greater than 50 ASTM E 84
Ozone Resistance Pass ASTM D 1171
Chemical/ Solvent Resistance Good
Mildew Resistance/Air Erosion Pass UL 181

Sound Absorption Co-efficients at Frequency


ASTM C-423/E-795 Type A Mounting/Sabins/Sq. Ft.
Thickness 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz NRC
1/4” (6mm) 0.00 0.03 0.05 0.10 0.25 0.45 0.10
1/2” (12mm) 0.03 0.04 0.08 0.15 0.40 0.25 0.20
1” (25mm) 0.10 0.15 0.45 0.30 0.40 0.33 0.35

Thickness Recommendations* - To Control Condensation


Sheet Size Ducts - Tanks - Vessels - Equipment - Metal - Surface Temperature
50°F 10°C 35°F 2°C 0˚F -18˚C -20˚ F -29˚C
Normal Conditions (Max 85°F, 29°C - 70% R.H.) 1/2" 13 mm 3/4" 19 mm 1" 25 mm 1-1/2" 38 mm**
Mild Conditions (Max 80˚F, 26˚C - 50% R.H.) 1/8" 3mm 1/4" 6 mm 1/2" 13 mm 3/4" 19 mm
Severe Conditions (Max 90˚F, 32˚C -80% RH) 3/4" 19 mm 1" 25 mm 1-3/4" 44 mm** 2" 50 mm**
**Multiple Layers

*INSUL-SHEET® in thickness noted within the specified temperature ranges will prevent condensation on indoor piping under design condi-
tions defined below.
Normal: Maximum severity of indoor conditions seldom exceed 85°F (29°C) and 70% R.H. in United States.
Mild: Typical conditions are most air-conditioned spaces and arid climates.
Severe: Generally found in areas where excessive moisture is introduced or in poorly ventilated areas where the temperature may be
depressed below the ambient. Under conditions of higher humidity, additional thickness of insulation may be required.
NOTE: Thickness recommendations calculated using 0.2575 K-factor (0.25 plus 3% test error allowance)

INSUL-SHEET® “R” Values (based on nominal thickness)

R Value R Value R Value R Value R Value R Value


3/8”* 1/2”* 3/4”* 1”* 1 1/2”* 2”*

1.5 2 3 4 6 8

*All sizes are nominal.

Note: “R” factors were calculated using a K factor of 0.2575 (0.25 plus 3% test error allowance at 75°F, 24°C mean temp.) and nominal wall thickness is each case.
Lower operating temperatures will result in improved R values. Contact Technical Services for specific recommendations.

R 8
sheet
to meet International Energy
Conservation Code requirements
for Outdoor Ductwork

K-Flex USA - 100 Nomaco Drive - Youngsville, NC 27596 - toll free 800-765-6475 - fax 800-765-6471 - www.kflexusa.com

©February 2008 K-Flex USA. INSUL-SHEET is a registered trademark of K-Flex USA. The GREENGUARD INDOOR AIR QUALITY CERTIFIED Mark
is a registered certification mark used under license through the GREENGUARD Environmental Institute.
ITPS-0003-0308