APPROVAL GUIDE
CHAPTER 1
AUTOMATIC SPRINKLER SYSTEMS
Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction
or combustible occupancies.
There are many FM Approved types of automatic sprinklers. Typical examples include: upright, pendent, flush,
recessed, concealed, sidewall, dry-pendent and dry-upright, Early Suppression Fast Response (ESFR), Quick
Response (QR), extended coverage, corrosion resistant, large drop, rack storage and decorative coated.
A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating.
Selection of the proper temperature rating for automatic sprinklers is important. The proper rating provides a factor
of safety designed to prevent premature operation. The rating should be selected from the following table:
*Frame arms of 135°F (57°C) sprinklers of some manufacturers are painted black.
Sprinklers of ‘‘very extra high’’ and ‘‘ultra high’’ ratings are primarily used for internal protection of chambers such
as ovens and dryers having working temperatures above 300°F (149°C). When the sprinklers are normally heated
to the working temperature of the oven or dryer, under accidental fire conditions they will operate fast enough for safe
protection. However, when the sprinklers are initially at the same temperature as a cold oven or dryer, operation may
be so severely retarded that the oven or dryer is virtually without internal sprinkler protection.
Specially coated or plated sprinklers are available for use where corrosion resistance is desired and decorative
coated sprinklers are available for areas where improved appearance is desired. For corrosion resistance, wax is
satisfactory except in extreme atmospheres. Wax has too low a melting point for high-degree heads, whereas a
bituminous coating affords some protection. A lead coating protects against certain mild corrosive atmospheres.
Wax-over-lead provides good sprinkler protection. Corrosion resistant sprinklers such as those manufactured from
stainless steel or other corrosion resistant materials currently afford the best available protection. Common
decorative finishes are bright brass, chrome, paint, or polyester coating. These finishes are for decorative purposes
only and are not FM Approved for corrosion resistance.
Only sprinklers supplied by the listed manufacturers are FM Approved. Any change in the device after it leaves the
manufacturer voids the Approval. Coated, plated and painted sprinklers rated above 165°F (74°C) have the standard
temperature color code either on the frame arms or on the compression screws, except in the case of bulb type
decorative coated sprinklers in which the bulb fluid color indicates the temperature rating per the following table:
When selecting a specific type of sprinkler, refer to the FM Global Property Loss Prevention Data Sheets to ensure
that the sprinkler selected is capable of providing adequate fire protection for the intended occupancy. In addition,
working plans of proposed layouts, showing all details with respect to location of sprinklers and piping, description
September 2007 — Approval Guide
1-2 Automatic Sprinkler Systems
of the occupancy and details of construction, should be sent to your insurance company for review before the
materials are fabricated. The plans will be accepted or changes will be recommended to assure that the work will be
done according to the best practice and to avoid the possibility of later requests for changes.
Unless otherwise noted, automatic sprinkler system components, which are subjected to system water pressure,
have a rated working pressure of 175 psi (1205 kPa).
Because this format limits the space in which the information can be provided, the following conventions are used:
The sprinkler nominal discharge coefficient (K-factor) is expressed in US customary units of gal/min/(psi)½.
Sprinkler response categories are abbreviated as follows:
SR Standard Response
QR Quick Response
FR Suppression Mode Fast Response
Heat responsive elements are identified as either Fusible or, in the case of bulb type elements, with the nominal
bulb diameter in millimeters (e.g., 2.5 mm, 3 mm, etc.)
Nominal thread sizes are expressed using American National Standard Taper Pipe Threads (NPT). Sprinklers
intended for sale outside the United States shall have threads which are in compliance with other national or
international standards as permitted at the sole discretion of FM Approvals.
Sprinkler nominal temperature ratings are expressed in degrees Fahrenheit (°F) followed by the equivalent in
degrees Celsius (°C).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-3
Window and cornice sprinklers are open sprinklers designed to protect windows and combustible cornices against outside exposing fires. Window and cornice sprinklers have no
automatic operating element and are available in various nominal orifice sizes. Their operation depends usually on the opening of a control valve by hand, although they are
sometimes automatically controlled with a thermostatically operated deluge valve.
Open Sprinklers, Control Mode (Specific Application) Window and Cornice (Class 2014)
Company Model Orifice Size NPT Type
Grinnell Issue A 1⁄4 in. 1⁄ 2 Window Sprinkler
Grinnell Issue A 5⁄16 in. 1⁄ 2 Window Sprinkler
Grinnell Issue A 3⁄8 in. 1⁄ 2 Window Sprinkler
Reliable R0413 1⁄4 in. 1⁄ 2 Window Sprinkler
Reliable R0414 5⁄16 in. 1⁄ 2 Window Sprinkler
Reliable R0415 3⁄8 in. 1⁄ 2 Window Sprinkler
Reliable R0418 1⁄2 in. 1⁄ 2 Window Sprinkler
Reliable R0416 5⁄8 in. 3⁄ 4 Window Sprinkler
Reliable R0411 3⁄4 in. 3⁄ 4 Window Sprinkler
Reliable R0428 1⁄2 in. 1⁄ 2 Cornice Sprinkler
Reliable R0426 5⁄8 in. 3⁄ 4 Cornice Sprinkler
Spraying Sys FM-1⁄2K60 17⁄64 in. 1⁄ 2 Window Sprinkler
Spraying Sys FM-1⁄2K80 5⁄16 in. 1⁄ 2 Window Sprinkler
Spraying Sys FM-3⁄4K120 3⁄8 in. 3⁄ 4 Window Sprinkler
Spraying Sys FM-3⁄4K210 1⁄2 in. 3⁄ 4 Window Sprinkler
Viking VK790 1⁄4 in. 1⁄ 2 Window Sprinkler
Viking VK791 5⁄16 in. 1⁄ 2 Window Sprinkler
Viking VK792 3⁄8 in. 1⁄ 2 Window Sprinkler
Viking VK793 7⁄16 in. 1⁄ 2 Window Sprinkler
Control mode standard spray sprinklers have deflectors specially designed to discharge water in all directions below the plane of the deflector. Thus, the spray pattern is roughly
that of a half sphere filled with water spray. Little or no water is discharged upward to wet the ceiling. Upright control mode sprinklers are not intended for use in the pendent position;
FM Approved pendent control mode sprinklers are required. Control mode automatic sprinklers with a nominal discharge coefficient of 2.8 gal/min/(psi)½ have cross sectional
dimensions of the water passageway less than 3⁄8 in. and may require the use of individual or system strainers per the appropriate FM Global Property Loss Prevention Data Sheets.
FM Approvals
September 2007 — Approval Guide
1-4 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Kidde AS2702 2.8 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Wax, Lead, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Wax Over Lead
1⁄ 2 Brass, Chrome, Black Plated,
Reliable R1021 2.8 Upright SR Fusible Bright Brass, Lead 135°, 165°, 212°F (57°, 74°, 100°C)
Reliable R1021 2.8 Upright SR Fusible 1⁄ 2 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Reliable R1721 2.8 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Black Plated, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Bright Brass
Tyco TY1151 2.8 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester
Tyco Mfg Ltd TY1151 2.8 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester
1⁄ 2 Brass, Chrome, Bright Brass,
Victaulic V2701 2.8 Upright SR 5 mm Polyester, Lead 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Victaulic V2701 2.8 Upright SR 5 mm 1⁄ 2 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Viking VK001 2.8 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Viking VK005 2.8 Upright SR Fusible 1⁄ 2 Brass 165°, 220°F (74°, 104°C)
Viking SA VK001 2.8 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY1131 2.8 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Victaulic V2702 2.8 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester, Lead
Viking VK325 2.8 Upright QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS2701 2.8 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Wax, Lead, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Wax Over Lead
1⁄ 2 Brass, Chrome, Black Plated,
Reliable R1011 2.8 Pendent SR Fusible Bright Brass, Lead 135°, 165°, 212°F (57°, 74°, 100°C)
Reliable R1011 2.8 Pendent SR Fusible 1⁄ 2 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Tyco TY1251 2.8 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
Tyco Mfg Ltd TY1251 2.8 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-5
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK003 2.8 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Viking VK007 2.8 Pendent SR Fusible 1⁄ 2 Brass 165°, 220°F (74°, 104°C)
Viking SA VK003 2.8 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Tyco TY1231 2.8 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93° 141°C)
Polyester
Viking VK329 2.8 Pendent QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R2211 2.8 Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable R2212 2.8 Adj. Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable R5411 2.8 Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable R5412 2.8 Adj. Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Viking VK003 2.8 Recessed Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 212°F (57°, 68°, 79°, 93°, 100°C)
Brass, Chrome with E-1 Recessed Escutcheon
1⁄2 135°, 155°, 175°, 200°, 212°F (57°, 68°, 79°, 93°, 100°C)
Viking VK003 2.8 Recessed Pendent SR 5 mm Brass, Chrome with E-2 Threaded Recessed Escutcheon
Viking VK461 2.8 Concealed Pendent SR 3 mm 1⁄2 Brass 155°, 175°, 200°F (68°, 79°, 93°C)
FM Approvals
September 2007 — Approval Guide
1-6 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN5661 5.6 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286° (57°, 68°, 79°, 93°, 141° )
Angus S 5.6 Upright SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Polyester 182°C)
CPF SKR 15 5.6 Upright SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
GW S 5.6 Upright SR 5 mm Brass, Chrome, Polyester 182°C)
Globe GL5661 5.6 Upright SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Polyester 182°C)
Globe GL5661 5.6 Upright SR 5 mm 1⁄ 2 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
Kidde AS5602 5.6 Upright SR 5 mm 1⁄ 2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Lead 182°C)
Kidde AS5602 5.6 Upright SR 5 mm 1⁄ 2 Wax, Wax Over Lead 155°, 175°, 200°F (68°, 79°, 93°C)
Nanjing NX003 5.6 Upright SR 5 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°F (57° , 68°, 79°, 93°C)
Reliable R1025 5.6 Upright SR Fusible 1⁄ 2 Wax, Lead, Wax Over Lead 165°, 212°F (74°, 100°C)
1⁄ 2 Brass, Chrome, Black Plated, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Reliable R1725 5.6 Upright SR 5 mm Bright Brass 182°C)
Rolland N 5.6 Upright SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome 182°C)
Senju SS6512 5.6 Upright SR Fusible 1⁄ 2 Brass 162°, 205°, 282°F (72°, 96°, 139°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Tyco TY3104 5.6 Upright SR 5 mm Polyester 141°, 182°, 260°C)
Tyco TY3104 5.6 Upright SR 5 mm 1⁄ 2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco TY3111 5.6 Upright SR Fusible 1⁄ 2 Brass, Chrome 165°, 212°, 280°F (74°, 100°, 138°C)
Tyco TY3111 5.6 Upright SR Fusible 1⁄ 2 Wax, Lead 165°, 212°F (74°, 100°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Tyco TY3151 5.6 Upright SR 5 mm Polyester 141°, 182°, 260°C)
Tyco TY3151 5.6 Upright SR 5 mm 1⁄ 2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Tyco Mfg Ltd TY3104 5.6 Upright SR 5 mm Polyester 182°C)
Tyco Mfg Ltd TY3151 5.6 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
Victaulic V2703 5.6 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester, Lead 182°C)
Victaulic V2703 5.6 Upright SR 5 mm 1⁄ 2 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-7
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
1⁄ 2 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°,
Viking VK100 5.6 Upright SR 5 mm Brass, Chrome, Wax, Polyester 93°, 100°, 141°, 182°, 260°C)
Viking VK108 5.6 Upright SR Fusible 1⁄ 2 Brass, Polyester 165°, 220°, 286°F (74°, 104°, 141°C)
1⁄ 2 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°,
Viking VK145 5.6 Upright SR 5 mm Brass, Chrome, Wax, Polyester 93°, 100°, 141°, 182°, 260°C)
1⁄ 2 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°,
Viking SA VK100 5.6 Upright SR 5 mm Brass, Chrome, Wax 93°, 100°, 141°, 182°, 260°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN5615 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Angus S 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°F (57°,68°,79°C)
CPF SKR 15 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
GW S 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
Globe GL5615 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS5652 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Plated 135°, 155°F (57°, 68°C)
Nanjing NX004 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Paradise PI211 5.6 Upright QR 3 mm 1⁄ 2 Chrome 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R3625 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Rolland N 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY3121 5.6 Upright QR Fusible 1⁄ 2 Brass, Chrome 165°, 212°F, (74°, 100°C)
Tyco Mfg Ltd TY3105 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Tyco Mfg Ltd TY3131 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
1⁄ 2 Brass, Chrome, Bright Brass,
Victaulic V2704 5.6 Upright QR 3 mm Polyester, Lead 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V2704 5.6 Upright QR 3 mm 1⁄ 2 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
Viking VK300 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK301 5.6 Upright QR Fusible 1⁄ 2 Brass, Chrome, Polyester 165°, 205°F, (74°, 96°C)
Viking VK345 5.6 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
FM Approvals
September 2007 — Approval Guide
1-8 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN5651 5.6 Pendent SR 5 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286° (57°, 68°, 79°, 93°, 141°)
Angus S 5.6 Pendent SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Polyester 182°C)
CPF SKR 15 5.6 Pendent SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
GW S 5.6 Pendent SR 5 mm Brass, Chrome, Polyester 182°C)
Globe GL5651 5.6 Pendent SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Polyester 182°C)
Globe GL5651 5.6 Pendent SR 5 mm 1⁄ 2 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
Kidde AS5601 5.6 Pendent SR 5 mm 1⁄ 2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Lead 182°C)
Kidde AS5601 5.6 Pendent SR 5 mm 1⁄ 2 Wax, Wax Over Lead 155°, 175°, 200°F (68°, 79°, 93°C)
Paradise PI220 5.6 Pendent SR 5 mm 1⁄ 2 Chrome 155°, 200°F (68°, 93°C)
Reliable R1015 5.6 Pendent SR Fusible 1⁄ 2 Brass, Chrome, Black Plated, 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Bright Brass
Reliable R1015 5.6 Pendent SR Fusible 1⁄ 2 Lead 165°, 212°, 286°F (74°, 100°, 141°C)
Reliable R1015 5.6 Pendent SR Fusible 1⁄ 2 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Reliable R1715 5.6 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Black Plated, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Bright Brass 182°C)
Reliable RA1314 5.6 Pendent SR 5 mm 1⁄ 2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Black Plated, Polyester
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Rolland N 5.6 Pendent SR 5 mm Brass, Chrome 182°C)
Senju SS6511 5.6 Pendent SR Fusible 1⁄ 2 Brass 162°, 205°, 282°F (72°, 96°, 139°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Tyco TY3204 5.6 Pendent SR 5 mm Polyester 141°, 182°, 260°C)
Tyco TY3204 5.6 Pendent SR 5 mm 1⁄ 2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco TY3211 5.6 Pendent SR Fusible 1⁄ 2 Brass, Chrome 165°, 212°, 280°F (74°, 100°, 138°C)
Tyco TY3211 5.6 Pendent SR Fusible 1⁄ 2 Wax, Lead 165°, 212°F (74°, 100°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Tyco TY3251 5.6 Pendent SR 5 mm Polyester 141°, 182°, 260°C)
Tyco TY3251 5.6 Pendent SR 5 mm 1⁄ 2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Tyco Mfg Ltd TY3204 5.6 Pendent SR 5 mm Polyester 182°C)
Tyco Mfg Ltd TY3251 5.6 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
Victaulic V2707 5.6 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester, Lead 182°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-9
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2707 5.6 Pendent SR 5 mm 1⁄ 2 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Viking VK102 5.6 Pendent SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°,
Brass, Chrome, Polyester, Wax 93°, 100°, 141°, 182°, 260°C)
Viking VK110 5.6 Pendent SR Fusible 1⁄ 2 Brass, Polyester 165°, 220°, 286°F (74°, 104°, 141°C)
Viking SA VK102 5.6 Pendent SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 212°, 286°, 360°, 500°F (57°, 68°, 79°,
Brass, Chrome, Polyester, Wax 93°, 100°, 141°, 182°, 260°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN5601 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Angus S 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
CPF SKR 15 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
GW S 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
Globe GL5601 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS5651 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass 135°, 155°F (57°, 68°C)
Paradise PI221 5.6 Pendent QR 3 mm 1⁄ 2 Chrome 135°, 155°, 200°F (57°, 68°, 93°C)
Paradise PI222 5.6 Pendent QR 3 mm 1⁄ 2 Chrome 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R3615 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Reliable RA1414 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Black Plated, Polyester
Rolland N 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY3201 5.6 Pendent QR 3 mm 1⁄ 2 Chrome 155°F (68°C)
Tyco TY3205 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Tyco TY3221 5.6 Pendent QR Fusible 1⁄ 2 Brass 165°, 212°F (74°, 100°C)
Tyco TY3231 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
1⁄ 2 Brass, Chrome, Bright Brass,
Tyco Mfg Ltd TY3205 5.6 Pendent QR 3 mm Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco Mfg Ltd TY3231 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Victaulic V2708 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester, Lead
Victaulic V2708 5.6 Pendent QR 3 mm 1⁄ 2 Wax, Wax Over Lead 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK302 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK303 5.6 Pendent QR Fusible 1⁄ 2 Brass, Chrome, Polyester 165°, 205°F (74°, 96°C)
FM Approvals
September 2007 — Approval Guide
1-10 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking SA VK302 5.6 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F, (57°, 68°, 79°, 93°, 141°C)
Sidewall automatic sprinklers are equipped with a special deflector which discharges most of the water in a forward direction. They are special purpose sprinklers originally
developed for locations such as executive offices, hotel lobbies and dining rooms, where the installation of standard sprinklers with the usual ceiling spacing and pipe location may
be objectionable because of appearance. Installed near the junction of the ceiling and wall, they are satisfactory for light hazards and where ceiling protection is not an important
factor. They are also installed for special applications where their directional properties are desirable. Approval is limited to control mode sprinklers with a nominal discharge
coefficient of 5.6. gal/min/(psi)½ only, in nominal temperature ratings of 300°F (149°C) or lower. Vertical sidewall sprinklers are FM Approved for use in both the upright and pendent
positions, except where noted otherwise.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
GW S 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Globe GL5670 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Globe GL5675 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS5632 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Wax, Lead, Wax Over Lead
Reliable R1235 5.6 Horizontal Sidewall SR Fusible 1⁄2 Brass, Chrome, Black 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Plated, Bright Brass, Lead
Reliable R1235 5.6 Horizontal Sidewall SR Fusible 1⁄2 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Reliable R1285 5.6 Vertical Sidewall SR Fusible 1⁄2 Lead 165°, 212°, 286°F (74°, 100°, 141°C)
Reliable R1285 5.6 Vertical Sidewall SR Fusible 1⁄2 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Reliable R1285 5.6 Vertical Sidewall SR Fusible 1⁄2 Brass, Chrome, Black 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Plated, Bright Brass, Lead
Reliable R1735 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome, Black 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Plated, Bright Brass
Reliable R1735 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Lead, Wax, Wax Over Lead 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Reliable R1785 5.6 Vertical Sidewall SR 5 mm 1⁄2 Lead, Wax, Wax Over Lead 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Reliable R1785 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome, Black 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Plated, Bright Brass
Tyco TY3304 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C)
Tyco TY3304 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco TY3311 5.6 Horizontal Sidewall SR Fusible 1⁄2 Brass, Chrome 165°, 212°, 280°F (74°, 100°, 138°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-11
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY3351 5.6 Horizontal Sidewall SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°F, 360°F (57°, 68°, 79°, 93°,
Brass, Chrome, Polyester 141°, 182°C )
Tyco TY3351 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco TY3451 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Polyester 141°, 182°C)
Tyco TY3451 5.6 Vertical Sidewall SR 5 mm 1⁄2 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco Mfg Ltd TY3304 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C)
Tyco Mfg Ltd TY3451 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Polyester
Victaulic V2709 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester, Lead
Victaulic V2709 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Viking VK104 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK106 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK112 5.6 Horizontal Sidewall SR Fusible 1⁄2 Brass 165°, 220°, 286°F (74°, 104°, 141°C)
Viking VK114 5.6 Vertical Sidewall SR Fusible 1⁄2 Brass, Chrome 165°, 220°, 286°F (74°, 104°, 141°C)
Viking SA VK104 5.6 Horizontal Sidewall SR 5 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK106 5.6 Vertical Sidewall SR 5 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Vertical Sidewall QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
GW S 5.6 Vertical Sidewall QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
Globe GL5626 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Globe GL5632 5.6 Vertical Sidewall QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS5633 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°F (57°, 68°C)
Reliable R3635 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Reliable R3685 5.6 Vertical Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY3305 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C)
Polyester
Tyco TY3321 5.6 Horizontal Sidewall QR Fusible 1⁄2 Brass, Chrome 165°, 212°F (74°, 100°C)
Tyco TY3331 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY3431 5.6 Vertical Sidewall QR 3 mm Polyester
FM Approvals
September 2007 — Approval Guide
1-12 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°C)
Tyco Mfg Ltd TY3305 5.6 Horizontal Sidewall QR 3 mm Polyester
1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco Mfg Ltd TY3331 5.6 Horizontal Sidewall QR 3 mm Polyester
1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco Mfg Ltd TY3431 5.6 Vertical Sidewall QR 3 mm Polyester
1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V2710 5.6 Horizontal Sidewall QR 3 mm Polyester, Lead
Viking VK304 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK305 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK306 5.6 Vertical Sidewall QR 3 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK304 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK306 5.6 Vertical Sidewall QR 3 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
The sprinklers listed below are primarily manufactured from a stainless steel alloy. These sprinklers afford improved corrosion protection, but should be selected for compatibility
with the intended environment.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
1⁄2 AISI 316 (UNS S31254) Stainless
Angus S 5.6 Upright SR 5 mm Steel Alloy 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)
1⁄2 316L (UNS-NO8367) Stainless 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°,
Viking VK130 5.6 Upright SR 5 mm Steel Alloy 182°, 260°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
1⁄2 AISI 316 (UNS S31254) Stainless
Angus S 5.6 Upright QR 3 mm Steel Alloy 135°, 155°, 175°F (57°, 68°, 79°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-13
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Pendent SR 5 mm 1⁄2 AISI 316 (UNS S31254) Stainless 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)
Steel Alloy
1⁄2 AISI 316 (UNS S31254) Stainless
GW S 5.6 Pendent SR 5 mm Steel Alloy 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°, 182°C)
1⁄2 316L (UNS-NO8367) Stainless 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°, 141°,
Viking VK132 5.6 Pendent SR 5 mm Steel Alloy 182°, 260°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Pendent QR 3 mm 1⁄2 AISI 316 (UNS S31254) Stainless 135°, 155°, 175°F (57°, 68°, 79°C)
Steel Alloy
1⁄2 AISI 316 (UNS S31254) Stainless
GW S 5.6 Pendent QR 3 mm Steel Alloy 135°, 155°, 175°F (57°, 68°, 79°C)
Pendent flush, recessed and concealed sprinklers are intended for use with a concealed piping system. Flush types are constructed with an operating element which extends a
short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist of a sprinkler
installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated and can be
manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired, in such
occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties.
Sidewall flush, recessed and concealed sprinklers are similar to pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the
junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward direction. FM Approved flush, recessed and concealed
sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss Prevention Data Sheets.
Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Polyester 155°F (68°C)
GW S 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Polyester 155°F (68°C)
Globe GL5651 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Globe GL5654 5.6 Concealed Pendent SR 5 mm 1⁄2 Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Kidde AS5601 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Reliable R1015 5.6 Recessed Pendent SR Fusible 1⁄2 Brass 135°, 165°, 212°F (57°, 74°, 100°C)
Reliable R1118 5.6 Adj. Recessed Pendent SR Fusible 1⁄2 Brass 135°, 165°, 212°F (57°, 74°, 100°C)
FM Approvals
September 2007 — Approval Guide
1-14 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R1715 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Black Plated, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Bright Brass
Reliable R2215 5.6 Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable R2218 5.6 Adj. Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable R5415 5.6 Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable R5418 5.6 Adj. Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Reliable RA1314 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Black Plated, Polyester
Senju SS2531 5.6 Flush Pendent SR Fusible 1⁄2 Chrome, Painted 162°F , 205°F (72°, 96°C)
Tyco TY3204 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) *
Tyco TY3211 5.6 Recessed Pendent SR Fusible 1⁄2 Brass, Chrome 165°, 212°F (74°, 100°C)
Tyco TY3251 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) *
Tyco TY3504 5.6 Adj. Concealed Pendent SR 5 mm 1⁄2 Brass 155°, 200°F (68°, 93°C)
Tyco TY3505 5.6 Adj. Concealed Pendent SR 3 mm 1⁄2 Brass 155°, 200°F (68°, 93°C)
Tyco TY3551 5.6 Adj. Concealed Pendent SR 5 mm 1⁄2 Brass 155°, 200°F (68°, 93°C)
Tyco Mfg Ltd TY3204 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) *
Tyco Mfg Ltd TY3251 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C) *
Victaulic V2707 5.6 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester
Victaulic V3802 5.6 Concealed Pendent SR 3 mm 1⁄2 Brass 155°, 175°, 200°F (68°, 79°, 93°C)
Viking VK102 5.6 Recessed Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Brass, Chrome, Polyester with Viking E-1 or E-2 Recessed Escutcheon
1⁄2 155°, 175°, 200°F (68°, 79°, 93°C)
Viking VK102 5.6 Concealed Pendent SR 5 mm Brass with Viking E-1 or E-2 Recessed Escutcheon
1⁄2 155°, 175°, 200°F (68°, 79°, 93°C)
Viking VK302 5.6 Concealed Pendent SR 3 mm Brass with Viking E-1 or E-2 Recessed Escutcheon
Viking VK400 5.6 Flush Pendent SR Fusible 1⁄2 Brass, Chrome, Polyester 165°, 220°F (74°, 104°C)
Viking VK404 5.6 Concealed Pendent SR Fusible 1⁄2 Brass 165°F (74°C)
Viking SA VK102 5.6 Recessed Pendent SR 5 mm 1⁄2 135, 155, 175, 200, (57, 68, 79, 93) with Viking E-1, or E-2
Brass, Chrome, Polyester Recessed Escutcheon
*This sprinkler is FM Approved with a die cast frame only.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 155°F (68°C)
GW S 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 155°F (68°C)
Globe GL5601 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Reliable R3615 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Reliable RA1414 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Bright Brass, Chrome, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Black Plated, Polyester
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-15
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY3205 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Tyco TY3231 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Tyco Mfg Ltd TY3205 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Tyco TY3231 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Victaulic V2708 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester
1⁄2 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Viking VK302 5.6 Recessed Pendent QR 3 mm Brass, Chrome, Polyester with Viking E-1 or E-2 Recessed Escutcheon
Viking VK402 5.6 Flush Pendent QR Fusible 1⁄2 Brass, Chrome, Polyester 165°F (74°C)
Viking SA VK302 5.6 Recessed Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
K5.6 Sidewall Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY3305 5.6 Recessed Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200 °F (57°, 68°, 79°, 93°C)
Polyester
1⁄2 Brass, Chrome, Bright Brass,
Tyco TY3331 5.6 Recessed Horizontal Sidewall QR 3 mm Polyester 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
1⁄2 Brass, Chrome, Bright Brass,
Tyco Mfg Ltd TY3305 5.6 Recessed Horizontal Sidewall QR 3 mm Polyester 135°, 155°, 175°, 200 °F (57°, 68°, 79°, 93°C)
1⁄2 Brass, Chrome, Bright Brass,
Tyco Mfg Ltd TY3331 5.6 Recessed Horizontal Sidewall QR 3 mm Polyester 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
1⁄2 Brass, Chrome, Bright Brass,
Victaulic V2710 5.6 Recessed Horizontal Sidewall QR 3 mm Polyester, Lead 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
K5.6 Dry
Control mode dry automatic sprinklers are similar to other control mode sprinklers except that the sprinkler body is permanently secured to an extension nipple which includes
a valve at the inlet end to prevent water from entering the nipple until the sprinkler operates. The sprinkler is threaded into a pipe fitting above the ceiling or enclosure at the valve
end, thus replacing a drop nipple. The purpose of these devices is (1) to eliminate possible freezing due to the collection of condensation in the drop nipple (2) to eliminate the need
to remove standard pendent sprinklers installed in a dry-pipe system in order to drain the system after flooding, and (3) to provide protection for unheated areas such as store windows
or food freezers using a wet system in which the sprinkler pipes are located in a heated area. Unless otherwise noted, FM Approved dry sprinklers are limited to a maximum nominal
length of 48 in. (1.2 m).
FM Approvals
September 2007 — Approval Guide
1-16 Automatic Sprinkler Systems
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5639* 5.6 Dry Upright QR 3 mm 1 Brass, Chrome, Polyester 155°, 200°, 286°F (68°, 93°, 141°C)
Tyco TY3135 5.6 Dry Upright QR 3 mm 1 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3602 5.6 Dry Upright QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5679* 5.6 Dry Pendent SR 5 mm 1 Brass, Chrome, Polyester 155°, 200°, 286°F (68°, 93°, 141°C)
Reliable R5314 5.6 Dry Pendent SR 5 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
135°, 155°, 175°, 200°, 286°, 360°F (56°, 68°, 79°, 93°,
Tyco TY3255 5.6 Dry Pendent SR 5 mm 1 Brass, Chrome 141°, 182°C)
Victaulic V3605 5.6 Dry Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Viking VK150 5.6 Dry Pendent SR 5 mm 1 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK154 5.6 Dry Adj. Pendent SR 5 mm 1 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5635* 5.6 Dry Pendent QR 3 mm 1 Brass, Chrome, Polyester 155°, 200°, 286°F (68°, 93°, 141°C)
Reliable R5714 5.6 Dry Pendent QR 3 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Tyco TY3235 5.6 Dry Pendent QR 3 mm 1 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-17
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3606 5.6 Dry Pendent QR 3 mm 1 Brass, NICOTEF Coated 155°, 286°F (68°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5685* 5.6 Dry Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Polyester 155°, 200°, 286°F (68°, 93°, 141°C)
Reliable R5334 5.6 Dry Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Tyco TY3355 5.6 Dry Horizontal Sidewall SR 5 mm 1 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (56°, 68°, 79°, 93°, 141°C)
Victaulic V3609 5.6 Dry Horizontal Sidewall SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Viking VK152 5.6 Dry Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK156 5.6 Dry Adj. Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5641* 5.6 Dry Horizontal Sidewall QR 3 mm 1 Brass, Chrome, Polyester 155°, 200°, 286°F (68°, 93°, 141°C)
Reliable R5734 5.6 Dry Horizontal Sidewall QR 3 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Tyco TY3335 5.6 Dry Horizontal Sidewall QR 3 mm 1 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3610 5.6 Dry Horizontal Sidewall QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Dry pendent flush, recessed and concealed sprinklers are dry sprinklers intended for use with a concealed piping system. Flush types are constructed with an operating element
which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist
of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated
and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired,
in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties.
Dry sidewall flush, recessed and concealed sprinklers are similar to dry pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall
near the junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward direction. FM Approved flush, recessed and
concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss Prevention
Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.
FM Approvals
September 2007 — Approval Guide
1-18 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5679* 5.6 Dry Recessed Pendent SR 5 mm 1 Brass, Chrome, Polyester 155°, 200°F (68°, 93°C)
Globe GL5685* 5.6 Dry Recessed Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Polyester 155°, 200°F (68°, 93°C)
Reliable R5314 5.6 Dry Concealed Pendent SR 5 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R5314 5.6 Dry Recessed Pendent SR 5 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R5334 5.6 Dry Recessed Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R5714 5.6 Dry Concealed Pendent SR 3 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R5714 5.6 Dry Recessed Pendent SR 3 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C)
Reliable R5734 5.6 Dry Recessed Horizontal Sidewall SR 3 mm 1 Brass, Chrome, Polyester 135°, 155°, 200°F (57°, 68°, 93°C)
135°, 155°, 175°, 200°F (56°, 68°, 79°,
Tyco TY3255 5.6 Dry Recessed Pendent SR 5 mm 1 Brass, Chrome 93°C)
Victaulic V3605 5.6 Dry Recessed Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°, 68°, 93°C)
Victaulic V3609 5.6 Dry Recessed Horizontal Sidewall SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°, 68°, 93°C)
135°, 155°, 175°, 200°F (57°, 68°, 79°,
Viking VK158 5.6 Dry Recessed Pendent SR 5 mm 1 Brass, Chrome 93°C)
135°, 155°, 175°, 200°F (57°, 68°, 79°,
Viking VK162 5.6 Dry Recessed Horizontal Sidewall SR 5 mm 1 Brass, Chrome, Bright Brass 93°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
K5.6 Dry Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5635* 5.6 Dry Recessed Pendent QR 3 mm 1 Brass, Chrome, Polyester 155°, 200°F (68°, 93°C)
Globe GL5641* 5.6 Dry Recessed Horizontal Sidewall QR 3 mm 1 Brass, Chrome, Polyester 155°, 200°F (68°, 93°C)
135°, 155°, 175°, 200°F (57°, 68°, 79°,
Tyco TY3235 5.6 Dry Recessed Pendent QR 3 mm 1 Brass, Chrome 93°C)
Victaulic V3606 5.6 Dry Recessed Pendent QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°, 68°, 93°C)
Victaulic V3610 5.6 Dry Recessed Horizontal Sidewall QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°, 68°, 93°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).
Rack storage sprinklers (also called intermediate level sprinklers) provide in-rack protection for rack storage arrays. These sprinklers are similar to the basic sprinkler types from
which they are derived except that they are equipped with a disc mounted above the thermal-sensitive element which protects it from delayed operation as a result of water discharge
from nearby sprinklers at higher elevations. Rack storage sprinklers are available with nominal discharge coefficients of 5.6 gal/min/(psi)½ and 8.0 gal/min/(psi)½ and in both upright
and pendent configurations. When using quick response rack storage sprinklers, standard response sprinklers will continue to be required at the ceiling level in accordance with the
FM Global Property Loss Prevention Data Sheets. Reference should be made to the FM Global Property Loss Prevention Data Sheets with regard to selection of type and
temperature rating for a given installation.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-19
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5663 5.6 Rack Storage Upright SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°, 182°C)
1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Kidde AS5604 5.6 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
Reliable R1425 5.6 Rack Storage Upright SR Fusible 1⁄2 Brass 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Tyco TY3113 5.6 Rack Storage Upright SR Fusible 1⁄2 Brass 165°, 212°, 280°F (74°, 100°, 138°C)
Tyco TY3153 5.6 Rack Storage Upright SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°,182°C)
1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Victaulic V2721 5.6 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
Viking VK550 5.6 Rack Storage Upright SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°, 182°C)
Viking VK552 5.6 Rack Storage Upright SR Fusible 1⁄2 Brass 165°, 220°, 286°F (74°, 104°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL5617 5.6 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Reliable R7095 5.6 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY3123 5.6 Rack Storage Upright QR Fusible 1⁄2 Brass 165°, 212°F (74°, 100°C)
Tyco TY3133 5.6 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V2722 5.6 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK556 5.6 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK556 5.6 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 5.6 Rack Storage Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass, Chrome, Polyester 141°, 182°C)
1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
GW S 5.6 Rack Storage Pendent SR 5 mm Brass, Chrome, Polyester 141°, 182°C)
Globe GL5672 5.6 Rack Storage Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°, 182°C)
FM Approvals
September 2007 — Approval Guide
1-20 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Kidde AS5601 5.6 Rack Storage Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°, 182°C)
Reliable R1015 5.6 Rack Storage Pendent SR Fusible 1⁄2 Brass 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Reliable R7025 5.6 Rack Storage Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°, 182°C )
Tyco TY3204 5.6 Rack Storage Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°,
Polyester 93°, 141°, 182°, 260°C)
Tyco TY3251 5.6 Rack Storage Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°,175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°,
Polyester 93°, 141°, 182°, 260°C)
1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Victaulic V2723 5.6 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
Viking VK102 5.6 Rack Storage Pendent SR 5 mm 1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Brass 141°, 182°C)
Viking VK110 5.6 Rack Storage Pendent SR Fusible 1⁄2 Brass 165°, 220°, 286°F (74°, 104°, 141°C)
Tyco TY3205 5.6 Rack Storage Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Tyco TY3221 5.6 Rack Storage Pendent QR Fusible 1⁄2 Brass 165°, 212°F, (74°, 100°C)
Tyco TY3231 5.6 Rack Storage Pendent QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Victaulic V2724 5.6 Rack Storage Pendent QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK302 5.6 Rack Storage Pendent QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK302 5.6 Rack Storage Pendent QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft
(4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers,
regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge
coefficient of 5.6 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 20 ft (4.9 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient
of 8.0 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 24 ft (4.9 m by 7.3 m). The FM Global Property Loss Prevention Data Sheets should be closely followed
when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-21
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK600 5.6 Pendent SR 3 mm 1⁄2 Brass, Chrome, Polyester 175°F (79°C)
Viking SA VK600 5.6 Pendent SR 3 mm 1⁄2 Brass, Chrome, Polyester 175°F (79°C)
Extended Coverage Light Hazard (ECLH) K5.6 Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY3232 5.6 Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 155°F (68°C)
Viking VK600 5.6 Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Viking SA VK600 5.6 Pendent QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY3332 5.6 Horizontal Sidewall SR 3 mm 1⁄2 Brass, Chrome, Polyester 175°F (79°C)
Tyco Mfg Ltd TY3332 5.6 Horizontal Sidewall SR 3 mm 1⁄2 Brass, Chrome, Polyester 175°F (79°C)
Extended Coverage Light Hazard (ECLH) K5.6 Sidewall, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R4865 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°F (57°, 68°, 79°C)
Black Plated, Polyester
1⁄2 Brass, Chrome, Bright Brass, 155°F (68°C)
Tyco TY3302 5.6 Horizontal Sidewall QR 3 mm Polyester
Tyco TY3322 5.6 Horizontal Sidewall QR Fusible 1⁄2 Brass, Chrome 165°F (74°C)
Tyco TY3332 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Tyco Mfg Ltd TY3332 5.6 Horizontal Sidewall QR 3 mm 1⁄2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
K5.6 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent or Sidewall)
Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush
pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to
provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling.
Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. Sidewall flush, recessed and
concealed sprinklers are similar to pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall.
They are equipped with a special deflector which discharges most of the water in a forward direction. All of these sprinkler types are intended for use in light hazard occupancies
where attractive apearance under a ceiling is desired.
FM Approvals
September 2007 — Approval Guide
1-22 Automatic Sprinkler Systems
The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick
response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.
Extended Coverage Light Hazard (ECLH) Flush, Recessed and Concealed (Class 2022)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY3332 5.6 Recessed Horizontal Sidewall SR 3 mm 1⁄ 2 Brass, Chrome, Polyester 175°F (79°C)
Tyco Mfg Ltd TY3332 5.6 Recessed Horizontal Sidewall SR 3 mm 1⁄ 2 Brass, Chrome, Polyester 175°F (79°C)
Viking VK600 5.6 Recessed Pendent SR 3 mm 1⁄ 2 Brass, Chrome, Polyester 175°F (79°C)
Extended Coverage Light Hazard (ECLH) Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Brass, Chrome, Bright
Reliable R4865 5.6 Recessed Horizontal Sidewall QR 3 mm 1⁄ 2 Brass, Black Plated, 135°F (57°C)
Polyester
Tyco TY3232 5.6 Recessed Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright 155°F (68°C)
Brass, Polyester
1⁄ 2 Brass, Chrome, Bright
Tyco TY3302 5.6 Recessed Horizontal Sidewall QR 3 mm Brass, Polyester 155°F (68°C)
Tyco TY3332 5.6 Recessed Horizontal Sidewall QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Tyco Mfg Ltd TY3332 5.6 Recessed Horizontal Sidewall QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Viking VK600 5.6 Recessed Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C)
and where the environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C)
These sprinklers are not recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R1025 5.6 Upright SR Fusible 1⁄2 Wax 286°F (141°C)
Reliable R1725 5.6 Upright SR 5 mm 1⁄2 Wax 286°F (141°C)
Tyco TY3104 5.6 Upright SR 5 mm 1⁄2 Wax 286°F (141°C)
Tyco TY3151 5.6 Upright SR 5 mm 1⁄2 Wax 286°F (141°C)
Victaulic V2703 5.6 Upright SR 5 mm 1⁄2 Wax, Wax Over Lead 286°F (141°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-23
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R1015 5.6 Pendent SR Fusible 1⁄2 Wax 286°F (141°C)
Reliable R1715 5.6 Pendent SR 5 mm 1⁄2 Wax 286°F (141°C)
Tyco TY3204 5.6 Pendent SR 5 mm 1⁄2 Wax 286°F (141°C)
Tyco TY3251 5.6 Pendent SR 5 mm 1⁄2 Wax 286°F (141°C)
Victaulic V2707 5.6 Pendent SR 5 mm 1⁄2 Wax, Wax Over Lead 286°F (141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Grinnell G1036 5.6 Upright SR 11 mm 1⁄2 Brass 400°, 500°, 650°F (204°, 260°, 343°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Grinnell G1040 5.6 Pendent SR 11 mm 1⁄2 Brass 400°, 500°, 650°F (204°, 260°, 343°C)
FM Approvals
September 2007 — Approval Guide
1-24 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN8164 8.0 Upright SR 5 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Angus S 8.0 Upright SR 5 mm and 3⁄4 Brass, Chrome, Polyester 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
GW S 8.0 Upright SR 5 mm and 3⁄4 Brass, Chrome, Polyester, 182°C)
3⁄ 4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Globe GL8164 8.0 Upright SR 5 mm Brass, Chrome, Polyester 182°C)
Globe GL8164 8.0 Upright SR 5 mm 3⁄ 4 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
Kidde AS8002 8.0 Upright SR 5 mm 1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Lead 182°C)
Kidde AS8002 8.0 Upright SR 5 mm 1⁄ 2 Wax, Wax Over Lead 155°, 175°, 200°F (68°, 79°, 93°C)
Kidde AS8004 8.0 Upright SR 5 mm 3⁄ 4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Lead 182°C)
Kidde AS8004 8.0 Upright SR 5 mm 3⁄ 4 Wax, Wax Over Lead 155°, 175°, 200°F (68°, 79°, 93°C)
Reliable R1026 8.0 Upright SR Fusible 1⁄ 2 Brass, Chrome, Black Plated, 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Bright Brass
Reliable R1027 8.0 Upright SR Fusible 3⁄ 4 Brass, Chrome, Black Plated, 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Bright Brass
Reliable R1027 8.0 Upright SR Fusible 3⁄ 4 Lead 165°, 212°, 286°F (74°, 100°, 141°C)
Reliable R1027 8.0 Upright SR Fusible 3⁄ 4 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Reliable R1722 8.0 Upright SR 5 mm 3⁄ 4 Brass, Chrome, Black Plated, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Rolland N 8.0 Upright SR 5 mm and 3⁄4 Brass, Chrome 182°C)
Tyco TY4111 8.0 Upright SR Fusible 3⁄ 4 Brass, Chrome 165°, 212°, 280°, 360°F (74°, 100°, 138°, 182°C)
Tyco TY4111 8.0 Upright SR Fusible 3⁄ 4 Wax, Lead 165°, 212°F (74°, 100°C)
3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Tyco TY4151 8.0 Upright SR 5 mm Polyester 141°, 182°, 260°C)
Tyco TY4151 8.0 Upright SR 5 mm 3⁄ 4 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco TY4811 8.0 Upright SR Fusible 1⁄ 2 Brass, Chrome 165°, 212°, 280°F (74°, 100°, 138°C)
Tyco TY4811 8.0 Upright SR Fusible 1⁄ 2 Wax, Lead 165°, 212°F (74°, 100°C)
1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Tyco TY4851 8.0 Upright SR 5 mm Polyester 141°, 182°, 260°C)
Tyco Mfg Ltd TY4151 8.0 Upright SR 5 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
Tyco Mfg Ltd TY4851 8.0 Upright SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
Victaulic V3401 8.0 Upright SR 5 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-25
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3401 8.0 Upright SR 5 mm 3⁄ 4 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Viking VK200 8.0 Upright SR 5 mm and 3⁄4 Brass, Chrome, Polyester 141°, 182°, 260°C)
Viking VK200 8.0 Upright SR 5 mm 1⁄ 2 and 3⁄4 Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Viking VK204 8.0 Upright SR Fusible 3⁄ 4 Brass, Polyester 165°, 220°, 286°F (74°, 104°, 141°C)
Viking SA VK200 8.0 Upright SR 5 mm 1⁄ 2 3⁄4 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
and Brass, Chrome 141°, 182°, 260°C)
Viking SA VK200 8.0 Upright SR 5 mm 1⁄ 2 and 3⁄4 Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN8118 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Angus S 8.0 Upright QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
GW S 8.0 Upright QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
Globe GL8115 8.0 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Globe GL8118 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS8052 8.0 Upright QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass 135°, 155°F (57°, 68°C)
Kidde AS8054 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass 135°, 155°F (57°, 68°C)
Reliable R3622 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Rolland N 8.0 Upright QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY4121 8.0 Upright QR Fusible 3⁄ 4 Brass, Chrome 165°, 212°F (74°, 100°C)
Tyco TY4131 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
Tyco Mfg Ltd TY4131 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
3⁄ 4 Brass, Chrome, Bright Brass,
Victaulic V3402 8.0 Upright QR 3 mm Polyester, Lead 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK350 8.0 Upright QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3603* 8.0 Dry Upright SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).
FM Approvals
September 2007 — Approval Guide
1-26 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3604* 8.0 Dry Upright QR 3 mm 1 Brass, NICOTEF Coated 155°, 286°F (68°, 141°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3607* 8.0 Dry Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3608* 8.0 Dry Pendent QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN8156 8.0 Pendent SR 5 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Angus S 8.0 Pendent SR 5 mm and 3⁄4 Brass, Chrome, Polyester 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
GW S 8.0 Pendent SR 5 mm and 3⁄4 Brass, Chrome, Polyester 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Globe GL8151 8.0 Pendent SR 5 mm Brass, Chrome, Polyester 182°C)
Globe GL8156 8.0 Pendent SR 5 mm 3⁄ 4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Polyester 182°C)
Globe GL8156 8.0 Pendent SR 5 mm 3⁄ 4 Wax, Lead, Wax Over Lead 155°, 200°F (68°, 93°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Kidde AS8001 8.0 Pendent SR 5 mm Brass, Chrome, Lead 182°C)
Kidde AS8001 8.0 Pendent SR 5 mm 1⁄ 2 Wax, Wax Over Lead 155°, 175°, 200°F (57°, 68°, 79°C)
Kidde AS8003 8.0 Pendent SR 5 mm 3⁄ 4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Lead 182°C)
Kidde AS8003 8.0 Pendent SR 5 mm 3⁄ 4 Wax, Wax Over Lead 155°, 175°, 200°F (57°, 68°, 79°C)
Reliable R1016 8.0 Pendent SR Fusible 1⁄ 2 Brass, Chrome, Black Plated, 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Bright Brass
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-27
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R1017 8.0 Pendent SR Fusible 3⁄ 4 Brass, Chrome, Black Plated, 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
Bright Brass
Reliable R1017 8.0 Pendent SR Fusible 3⁄ 4 Lead 165°, 212°, 286°F (74°, 100°, 141°C)
Reliable R1017 8.0 Pendent SR Fusible 3⁄ 4 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Reliable R1712 8.0 Pendent SR 5 mm 3⁄ 4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Brass, Chrome, Black Plated 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Rolland N 8.0 Pendent SR 5 mm and 3⁄4 Brass, Chrome 182°C)
Tyco TY4211 8.0 Pendent SR Fusible 3⁄ 4 Brass, Chrome 165°, 212°, 280°F (74°, 100°, 138°C)
Tyco TY4211 8.0 Pendent SR Fusible 3⁄ 4 Wax, Lead 165°, 212°F (74°, 100°C)
Tyco TY4251 8.0 Pendent SR 5 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Polyester 141°, 182°, 260°C)
Tyco TY4251 8.0 Pendent SR 5 mm 3⁄ 4 Wax 135°, 155°, 200°F (57°, 68°, 93°C)
Tyco TY4911 8.0 Pendent SR Fusible 1⁄ 2 Brass, Chrome 165°, 212°, 280°, 360°F (74°, 100°, 138°, 182°C)
Tyco TY4911 8.0 Pendent SR Fusible 1⁄ 2 Wax, Lead 165°, 212°F (74°, 100°C)
Tyco TY4951 8.0 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Polyester 141°, 182°, 260°C)
3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Tyco Mfg Ltd TY4251 8.0 Pendent SR 5 mm Polyester 182°C)
Tyco Mfg Ltd TY4951 8.0 Pendent SR 5 mm 1⁄ 2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester 182°C)
Victaulic V3405 8.0 Pendent SR 5 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Polyester, Lead 182°C)
Victaulic V3405 8.0 Pendent SR 5 mm 3⁄ 4 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
Viking VK202 8.0 Pendent SR 5 mm and 3⁄4 Brass, Chrome 141°, 182°, 260°C)
Viking VK202 8.0 Pendent SR 5 mm 1⁄ 2 and 3⁄4 Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Viking VK206 8.0 Pendent SR Fusible 3⁄ 4 Brass 165°, 220°, 286°F (74°, 104°, 141°C)
Viking SA VK202 8.0 Pendent SR 5 mm 1⁄ 2 3⁄4 135°, 155°, 175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°, 93°,
and Brass, Chrome 141°, 182°, 260°C)
Viking SA VK202 8.0 Pendent SR 5 mm 1⁄ 2 and 3⁄4 Wax 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Anber Globe GN8106 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Angus S 8 Pendent QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
FM Approvals
September 2007 — Approval Guide
1-28 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
GW S 8.0 Pendent QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
Globe GL8101 8.0 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Globe GL8106 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS8051 8.0 Pendent QR 3 mm 1⁄ 2 Brass, Chrome, Bright Brass 135°, 155°F (57°, 68°C)
Kidde AS8053 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass 135°, 155°F (57°, 68°C)
Reliable R3612 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Rolland N 8.0 Pendent QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY4221 8.0 Pendent QR Fusible 3⁄ 4 Brass, Chrome 165°, 212°F (74°, 100°C)
Tyco TY4231 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester
3⁄ 4 Brass, Chrome, Bright Brass,
Tyco Mfg Ltd TY4231 8.0 Pendent QR 3 mm Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3406 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Polyester, Lead
Viking VK352 8.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
The sprinklers listed below are primarily manufactured from a stainless steel alloy. These sprinklers afford improved corrosion protection, but should be selected for compatibility
with the intended environment. Corrosion resistant automatic sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ are similar to corrosion resistant sprinklers with a
nominal discharge coefficient of 5.6 gal/min/(psi)½ except that they discharge 40% more water at the same discharge pressure. The greater capacity is useful in some situations
where very high density is required. Special size piping systems are needed.
Angus S 8.0 Upright SR 5 mm 1⁄ 2 3⁄4 AISI 316 (UNS S31254) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
and Stainless Steel Alloy 182°C)
1⁄ 2 AISI 316 (UNS S31254) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
GW S 8.0 Upright SR 5 mm and 3⁄4 Stainless Steel Alloy 182°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 8.0 Upright QR 3 mm 1⁄ 2 and 3⁄4 AISI 316 (UNS S31254) 135°, 155°, 175°F (57°, 68°, 79°C)
Stainless Steel Alloy
GW S 8.0 Upright QR 3 mm 1⁄ 2 and 3⁄4 AISI 316 (UNS S31254) 135°, 155°, 175°F (57°, 68°, 79°C)
Stainless Steel Alloy
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-29
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
1⁄ 2 AISI 316 (UNS S31254) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
Angus S 8.0 Pendent SR 5 mm and 3⁄4 Stainless Steel Alloy 182°C)
1⁄ 2 and 3⁄4 AISI 316 (UNS S31254) 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
GW S 8.0 Pendent SR 5 mm Stainless Steel Alloy 182°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 8.0 Pendent QR 3 mm 1⁄ 2 and 3⁄4 AISI 316 (UNS S31254) 135°, 155°, 175°F (57°, 68°, 79°C)
Stainless Steel Alloy
1⁄ 2 AISI 316 (UNS S31254)
GW S 8.0 Pendent QR 3 mm and 3⁄4 135°, 155°, 175°F (57°, 68°, 79°C)
Stainless Steel Alloy
Pendent flush, recessed and concealed sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi)½ are similar to those with a nominal discharge coefficient of 5.6
gal/min/(psi)½ except that they discharge 40% more water at the same discharge pressure. These sprinklers are intended for use with a concealed piping system. Flush types are
constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water
distribution. Recessed types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate
a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use where attractive
appearance under a ceiling is desired, in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar properties.
FM Approved flush, recessed and concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the
FM Global Property Loss Prevention Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems
qualifying as Wet Systems only.
Tyco TY4251 8.0 Recessed Pendent SR 5 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Tyco TY4951 8.0 Recessed Pendent SR 5 mm 1⁄2 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester
3⁄4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Victaulic V3405 8.0 Recessed Pendent SR 5 mm Polyester
Viking VK202 8.0 Recessed Pendent SR 5 mm 1⁄ 2 and 3⁄4 Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
FM Approvals
September 2007 — Approval Guide
1-30 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK202 8.0 Concealed Pendent SR 5 mm 3⁄4 Brass 155°, 175°, 200°F (68°, 79°, 93°C)
Viking VK352 8.0 Concealed Pendent SR 3 mm 3⁄4 Brass 155°, 175°, 200°F (68°, 79°, 93°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3607* 8.0 Dry Recessed Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°, 68°, 93°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).
Tyco TY4231 8.0 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
in. Polyester
Tyco Mfg Ltd TY4231 8.0 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
in. Polyester
Viking VK352 8.0 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Viking SA VK352 8.0 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
K8.0 Dry Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3608* 8.0 Dry Recessed Pendent QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°, 68°, 93°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-31
1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Globe GL8163 8.0 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Globe GL8166 8.0 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Kidde AS8006 8.0 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
Reliable R1427 8.0 Rack Storage Upright SR Fusible 3⁄4 Brass 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Reliable R7022 8.0 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
Tyco TY4113 8.0 Rack Storage Upright SR Fusible 3⁄4 Brass 165°, 212°, 280°F (74°, 100°, 138°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Tyco TY4153 8.0 Rack Storage Upright QR 5 mm Brass 141°, 182°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Victaulic V3417 8.0 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Viking VK560 8.0 Rack Storage Upright SR 5 mm Brass 141°, 182°C)
Viking VK562 8.0 Rack Storage Upright SR Fusible 3⁄4 Brass 165°, 220°, 286°F (74°, 104°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Globe GL8117 8.0 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Globe GL8120 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Kidde AS8052 8.0 Rack Storage Upright QR 3 mm 1⁄2 Brass 135°, 155°F (57°, 68°C)
Kidde AS8056 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°F (57°, 68°C)
Reliable R7092 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY4123 8.0 Rack Storage Upright QR Fusible 3⁄4 Brass 165°, 212°F (74°, 100°C)
Tyco TY4133 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3418 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK566 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK566 8.0 Rack Storage Upright QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
FM Approvals
September 2007 — Approval Guide
1-32 Automatic Sprinkler Systems
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Angus S 8.0 Rack Storage Pendent SR 5 mm and 3⁄4 Brass, Chrome, Polyester 141°, 182°C)
1⁄ 2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
GW S 8.0 Rack Storage Pendent SR 5 mm and 3⁄4 Brass, Chrome, Polyester 141°, 182°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Globe GL8158 8.0 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
1⁄2 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Globe GL8172 8.0 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
Grinnell G3152 8.0 Rack Storage Pendent SR Fusible 3⁄4 Brass 165°, 212°, 280°F (74°, 100°, 138°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Kidde AS8003 8.0 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
Reliable R1017 8.0 Rack Storage Pendent SR Fusible 3⁄4 Brass 135°, 165°, 212°, 286°F (57°, 74°, 100°, 141°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Reliable R1712 8.0 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
3⁄4 135°, 155°,175°, 200°, 286°, 360°, 500°F (57°, 68°, 79°,
Tyco TY4251 8.0 Rack Storage Pendent SR 5 mm Brass, Chrome, Polyester 93°, 141°, 182°, 260°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Victaulic V3419 8.0 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
3⁄4 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°,
Viking VK202 8.0 Rack Storage Pendent SR 5 mm Brass 141°, 182°C)
Viking VK206 8.0 Rack Storage Pendent SR Fusible 3⁄4 Brass 165°, 220°, 286°F (74°, 104°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Angus S 8.0 Rack Storage Pendent QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
GW S 8.0 Rack Storage Pendent QR 3 mm 1⁄ 2 and 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
Globe GL8112 8.0 Rack Storage Pendent QR 3 mm 1⁄2 Brass 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Globe GL8108 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Kidde AS8053 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass 135°, 155°F (57°, 68°C)
Reliable R3612 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Tyco TY4221 8.0 Rack Storage Pendent QR Fusible 3⁄4 Brass 165°, 212°F (74°, 100°C)
Tyco TY4231 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3420 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK352 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Viking SA VK352 8.0 Rack Storage Pendent QR 3 mm 3⁄4 Brass 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-33
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R1016 8.0 Pendent SR Fusible 1⁄ 2 Wax 286°F (141°C)
Reliable R1017 8.0 Pendent SR Fusible 3⁄ 4 Wax 286°F (141°C)
Tyco TY4211 8.0 Pendent SR Fusible 3⁄ 4 Wax 280°F (138°C)
Tyco TY4251 8.0 Pendent SR 5 mm 3⁄ 4 Wax 286°F (141°C)
Tyco TY4951 8.0 Pendent SR 5 mm 1⁄ 2 Wax 286°F (141°C)
Victaulic V3405 8 Pendent SR 5 mm 3⁄ 4 Wax, Wax Over Lead 286°F (141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Grinnell G1136 8.0 Upright SR 11 mm 3⁄ 4 Brass 400°, 500°F (204°, 260°C)
Grinnell G1140 8.0 Pendent SR 11 mm 3⁄ 4 Brass 400°, 500°F (204°, 260°C)
FM Approvals
September 2007 — Approval Guide
1-34 Automatic Sprinkler Systems
coefficient of 5.6 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 20 ft (4.9 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient
of 8.0 gal/min/(psi)½ have a maximum spacing (width by length) of 16 ft by 24 ft (4.9 m by 7.3 m). The FM Global Property Loss Prevention Data Sheets should be closely followed
when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK602 8.0 Pendent SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
Viking SA VK602 8.0 Pendent SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
K8.0 Extended Coverage Light Hazard (ECLH), Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R4842 8.0 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Coated
3⁄4 Brass, Chrome, Bright Brass, 135°, 155°F (57°, 68°C)
Tyco TY4232 8.0 Pendent QR 3 mm Polyester
Viking VK602 8.0 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Viking SA VK602 8.0 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY4332 8.0 Horizontal Sidewall SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
Tyco Mfg Ltd TY4332 8.0 Horizontal Sidewall SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
Victaulic V3415 8.0 Horizontal Sidewall SR 5 mm 3⁄4 Brass, Chrome, Polyester 135°F (57°C)
K8.0 Extended Coverage Light Hazard (ECLH), Sidewall, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R4862 8.0 Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Bright Brass, 135°, 155, °175°F (57°, 68°, 79°C)
Black Plated, Polyester
Tyco TY4322 8.0 Horizontal Sidewall QR Fusible 3⁄4 Brass, Chrome 165°F (74°C)
Tyco TY4332 8.0 Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-35
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco Mfg Ltd TY4332 8.0 Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Victaulic V3416 8.0 Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Viking VK606 8.0 Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Viking VK630 8.0 Horizontal Sidewall QR 3mm 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175° F (57°, 68°, 79°C)
K8.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent or Sidewall)
Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush
pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to
provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling.
Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. Sidewall flush, recessed and
concealed sprinklers are similar to pendent flush recessed and concealed sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall.
They are equipped with a special deflector which discharges most of the water in a forward direction. All of these sprinkler types are intended for use in light hazard occupancies
where attractive appearance under a ceiling is desired.
The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick
response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.
K8.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Class 2022)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY4332 8.0 Recessed Horizontal Sidewall SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
Tyco Mfg Ltd TY4332 8.0 Recessed Horizontal Sidewall SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
Victaulic V3416 8.0 Recessed Horizontal Sidewall SR 3 mm 3⁄4 Brass, Chrome, Polyester 155°F (68°C)
Viking VK602 8.0 Recessed Pendent SR 3 mm 3⁄4 Brass, Chrome, Polyester 175°F (79°C)
K8.0 Extended Coverage Light Hazard (ECLH), Flush Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R4842 8.0 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome, Bright Brass, 135°, 155°F (57°, 68°C)
Black Plated, Polyester
Reliable R4862 8.0 Recessed Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Bright Brass, 135°, 155°F (57°, 68°C)
Black Plated, Polyester
3⁄4 Brass, Chrome, Bright Brass, 135°F (57°C)
Tyco TY4232 8.0 Recessed Pendent QR 3 mm Polyester
Tyco TY4332 8.0 Recessed Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Tyco Mfg Ltd TY4332 8.0 Recessed Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
FM Approvals
September 2007 — Approval Guide
1-36 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3416 8.0 Recessed Horizontal Sidewall QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°F (57°C)
Viking VK602 8.0 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
Viking VK606 8.0 Recessed Horizontal Sidewall QR 3 mm 3⁄4 135°, 155°F (57°, 68°C)
Brass, Chrome, Polyester with Viking E-1 or E-2 recessed escutcheon
Viking VK630 8.0 Recessed Horizontal Sidewall QR 3mm 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175° F (57°, 68°, 79°C)
Control mode specific application (CMSA) automatic sprinklers with a nominal discharge coefficient of 11.2 gal/min/[psi]1⁄2 are generally utilized for storage type occupancies. Install
these sprinklers in accordance with FM Global Property Loss Prevention Data Sheet 2-7, Installation Rules for Sprinkler Systems Using Control Mode Specific Application (CMSA)
Ceiling Sprinklers for Storage Applications, and base their design on the occupancy-specific FM Global Property Loss Prevention Data Sheet.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK540 11.2 Upright SR 5 mm 3⁄4 Brass 155°, 200°, 286°F (68°, 93°, 141°C)
Control mode automatic sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of
8.0 gal/min/(psi)½ except that they discharge approximately 40% more water at the same discharge pressure. They are not control mode (specific application) sprinklers (i.e., they
are not to be utilized in ‘‘large drop’’ sprinkler applications.) These are standard spray sprinklers intended for use in automatic sprinkler fire protection systems designed using the
‘‘Density/Area’’ method. Control mode sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply
pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps.
See the appropriate occupancy/hazard specific data sheet to determine the sprinkler’s acceptable minimum and maximum operating parameters such as sprinkler spacing,
operating pressure, etc.
The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R2921 11.2 Upright SR Fusible 1⁄2 and 3⁄ 4 Brass, Chrome 165°, 212°, 286°F (74°, 100°, 141°C)
Tyco TY5151 11.2 Upright SR 5 mm 3⁄4 Brass, Chrome, Lead 155°, 200°, 286°F (68°, 93°, 141°C)
Tyco TY5151 11.2 Upright SR 5 mm 3⁄4 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Tyco TY5851 11.2 Upright SR 5 mm 1⁄2 Brass, Chrome, Lead 155°, 200°, 286°F (68°, 93°, 141°C)
Tyco TY5851 11.2 Upright SR 5 mm 1⁄2 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-37
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY5811 11.2 Upright SR Fusible 1⁄2 Brass, Chrome, Lead 165°, 212°, 286°F (74°, 100°, 141°C)
Tyco TY5811 11.2 Upright SR Fusible 1⁄2 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Tyco TY5111 11.2 Upright SR Fusible 3⁄4 Brass, Chrome, Lead 165°, 212°, 286°F (74°, 100°, 141°C)
Tyco TY5111 11.2 Upright SR Fusible 3⁄4 Wax, Wax Over Lead 165°, 212°F (74°, 100°C)
Victaulic V3403 11.2 Upright SR 5 mm 3⁄4 Brass, Chrome, Polyester, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Lead
Victaulic V3403 11.2 Upright SR 5 mm 3⁄4 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Viking VK530 11.2 Upright SR 5 mm 3⁄4 Brass, Chrome 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY5131 11.2 Upright QR 3 mm 3⁄4 Brass, Chrome 155°, 200°, 286°F (68°, 93°, 141°C)
Victaulic V3404 11.2 Upright QR 3 mm 3⁄4 Brass, Chrome, Polyester, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Lead
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY5211 11.2 Pendent SR Fusible 3⁄4 Brass, Chrome 165°, 212°, 286°F (74°, 100°, 141°C)
Tyco TY5251 11.2 Pendent SR 5 mm 3⁄4 Brass, Chrome, Lead 155°, 200°, 286°F (68°, 93°, 141°C)
Tyco TY5251 11.2 Pendent SR 5 mm 3⁄4 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Victaulic V3407 11.2 Pendent SR 5 mm 3⁄4 Brass, Lead 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3407 11.2 Pendent SR 5 mm 3⁄4 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY5231 11.2 Pendent QR 3 mm 3⁄4 Brass, Chrome 155°, 200°, 286°F (68°, 93°, 141°C)
Victaulic V3408 11.2 Pendent QR 3 mm 3⁄4 Brass, Lead 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Victaulic V3408 11.2 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Lead
FM Approvals
September 2007 — Approval Guide
1-38 Automatic Sprinkler Systems
Control mode, Extended Coverage Ordinary Hazard (ECOH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of
15 ft × 15 ft (4.6 m × 4.6 m) for upright and pendent standard coverage sprinklers. ECOH sprinklers with a nominal discharge coefficient of 11.2 gal/min/(psi) have a maximum spacing
of 16 ft × 16 ft (4.9 m × 4.9 m) and a minimum spacing of 10 ft × 10 ft (3.0 m × 3.0 m). ECOH sprinklers are equipped with a quick response heat responsive element. However,
they are FM Approved as standard response sprinklers due the delay caused by the extended maximum spacing between adjacent sprinklers. The FM Global Property Loss
Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers. Sprinklers not installed to these
guidelines will not provide adequate property protection in the event of a fire.
Viking VK532 11.2 Upright SR 3 mm 3⁄4 Brass, Chrome, Polyester 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft
(4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers,
regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). The FM Global Property Loss Prevention Data Sheets should
be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature
rating of 175°F (79°C).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-39
K11.2 Extended Coverage Light Hazard (ECLH) Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY5237 11.2 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester, 135°, 155°F (57°, 68°C)
Lead
3⁄4 Brass, Chrome, Bright Brass,
Victaulic V3412 11.2 Pendent QR 3 mm Polyester 135°, 155°F. (57°, 68°C)
Viking VK608 11.2 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent)
Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush
pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to
provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling.
Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are
intended for use in light hazard occupancies where attractive appearance under a ceiling is desired.
The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick
response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.
K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed Types (Class 2022)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3411 11.2 Recessed Pendent SR 5 mm 3⁄ 4 Brass, Chrome, Bright Brass, Polyester 135°, 155°F (57°, 68°C)
K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed Types, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY5237 11.2 Recessed Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester, Lead 135°, 155°F (57°, 68°C)
Victaulic V3412 11.2 Recessed Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°F (57°C)
Viking VK608 11.2 Recessed Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
FM Approvals
September 2007 — Approval Guide
1-40 Automatic Sprinkler Systems
There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C)
and where the environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C)
These sprinklers are not recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).
Control mode automatic sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of
11.2 gal/min/(psi)½ except that they discharge approximately 25% more water at the same discharge pressure. These are standard spray sprinklers intended for use in automatic
sprinkler fire protection systems designed using the ‘‘Density/Area’’ method. Control mode automatic sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ offer the
advantage of higher design densities at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. The
FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-41
Control mode, Extended Coverage Ordinary Hazard (ECOH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of
15 ft × 15 ft (4.6 m × 4.6 m) for upright and pendent standard coverage sprinklers. ECOH sprinklers with a nominal discharge coefficient of 14.0 gal/min/(psi)½ have a maximum
spacing of 20 ft × 20 ft (6.1 × m × 6.1 m) and a minimum spacing of 10 ft × 10 ft (3.0 m × 3.0 m). ECOH sprinklers are equipped with a quick response heat responsive element.
However, they are FM Approved as standard response sprinklers due the delay caused by the extended maximum spacing between adjacent sprinklers. The FM Global Property
Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers. Sprinklers not installed to these
guidelines will not provide adequate property protection in the event of a fire.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY6137 14.0 Upright SR 3 mm 3⁄ 4 Brass, Chrome, Polyester, Lead 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco Mfg Ltd TY6237 14.0 Pendent SR 3 mm 3⁄ 4 Brass, Chrome, Polyester, Lead 135° , 155° , 175° , 200° , 286°F (57°, 68°, 79°, 93°, 141°C)
Viking VK572 14.0 Pendent SR 3 mm 3⁄ 4 Brass 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)
Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft
(4.6 m by 4.6 m) for upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers,
regardless of nominal discharge coefficient, have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). The FM Global Property Loss Prevention Data Sheets should
be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature
rating of 175°F (79°C).
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3413 14.0 Pendent SR 5 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°, 175°F (57°, 68°, 79°C)
K14.0 Extended Coverage Light Hazard (ECLH), Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco Mfg Ltd TY6237 14.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester, Lead 135°, 155°F, (57°, 68°C)
Victaulic V3414 14.0 Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
FM Approvals
September 2007 — Approval Guide
1-42 Automatic Sprinkler Systems
K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent)
Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush
pendent types are constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to
provide a proper water distribution. Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling.
Concealed pendent types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are
intended for use in light hazard occupancies where attractive appearance under a ceiling is desired.
K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Class 2015)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3413 14.0 Recessed Pendent SR 5 mm 3⁄ 4 Brass, Chrome, Polyester 135°, 155°F (57°, 68°C)
K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco Mfg Ltd TY6237 14.0 Recessed Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester, Lead 135°, 155°F, (57°, 68°C)
Victaulic V3414 14.0 Recessed Pendent QR 3 mm 3⁄ 4 Brass, Chrome, Polyester 135°F (57°C)
Control mode, extended coverage metal building sidewall sprinklers are designed to protect metal buildings by discharging water perpendicular to the beams. These sprinklers
are equipped with a quick response heat responsive element. However, they are FM Approved as standard response sprinklers due the delay caused by the extended maximum
spacing between adjacent sprinklers. They are intended to protect certain light and ordinary hazard occupancies where a ‘‘Density/Area’’ design is permitted in the FM Global Loss
Prevention Data Sheets. Care must be exercised to utilize these sprinklers only in applications for which they have been shown to be effective, as various restrictions apply. The
FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Reliable R6932 14.0 Horizontal Sidewall SR Fusible 3⁄4 Brass 165°, 212°F (74°, 100°C)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-43
Control mode automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ are similar to control mode sprinklers with a nominal discharge coefficient of
11.2 gal/min/(psi)½ except that they discharge approximately 50% more water at the same discharge pressure. These are standard spray sprinklers intended for use in automatic
sprinkler fire protection systems designed using the ‘‘Density/Area’’ method. These sprinklers are expected to 1) prewet combustibles surrounding the actual fire area to limit fire size,
2) cool the roof area directly over the fire to prevent structural failure, and 3) cool the roof area remote from the actual fire area so that too many sprinklers do not open and overtax
the water supply. Control mode automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply
pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps. Care must be exercised to utilize these sprinklers only in
applications for which they have been shown to be effective, as various restrictions apply. The FM Global Property Loss Prevention Data Sheets should be strictly adhered to when
designing and installing automatic fire protection systems utilizing these sprinklers.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK580 16.8 Upright SR 5 mm 3⁄4 Brass 155°, 175°, 200°, 286°F (68°, 79°, 93°, 141°C)
Control mode (specific application) automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ are designed to 1) prewet combustibles surrounding the actual
fire area to limit fire size, 2) cool the roof area directly over the fire to prevent structural failure, and 3) cool the roof area remote from the actual fire area so that too many sprinklers
do not open and overtax the water supply. These sprinklers differ from control mode (density/area) sprinklers in that a fire protection system utilizing control mode (specific application)
sprinklers is designed based on a given number of sprinklers operating at a specified minimum water supply pressure. Control mode (specific application) automatic sprinklers with
a nominal discharge coefficient of 16.8 gal/min/(psi)½ offer the advantage of higher design densities at lower water supply pressures, which may allow adequate sprinkler protection
to be achieved without the need for additional fire pumps. Care must be exercised to only utilize these sprinklers in applications for which they have been shown to be effective. The
FM Global Property Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY7103 16.8 Upright SR 5 mm 3⁄4 Brass 286°F (141°C)
FM Approvals
September 2007 — Approval Guide
1-44 Automatic Sprinkler Systems
Control mode, Extended Coverage sprinklers are designed to be installed at spacing and coverage areas up to 14 ft × 14 ft (4.3 m × 4.3 m) and a minimum spacing of 10 ft × 10 ft
(3.0 m × 3.0 m). These sprinklers are for use in occupancies where a ‘‘Density/Area’’ design is permitted in the FM Global Loss Prevention Data Sheets. The FM Global Property
Loss Prevention Data Sheets should be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers. Sprinklers not installed to these
guidelines may not provide adequate property protection in the event of a fire.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY9128 25.2 Upright SR Fusible 1 Brass 165°, 214°F (74°, 101°C)
Automatic control mode sprinklers for cooling towers are special purpose heads developed for the protection of fill areas of crossflow water cooling towers.
Automatic Sprinklers, Control Mode (Specific Application), Cooling Tower (Class 2019)
Company Model Orifice Size Type Notes
Grinnell Issue C, Type I Cooling Tower Nozzle For use in towers with diffusion decks.
Grinnell Issue C, Type II Cooling Tower Nozzle For use in towers without diffusion decks.
Kidde 38E Nominal 7⁄16, 1⁄2 in. orifice dia. Cooling Tower Nozzle
Residential sprinklers are fast response sprinklers that have been specifically investigated for their ability to enhance the survivability of occupants in the room of fire origin. They
are intended to prevent flashover in the room of origin, thus improving the chance for occupants to escape or be evacuated. These sprinklers are FM Approved for use in the
protection of dwelling units only. FM Approved sprinklers have been tested for effective performance as life safety devices at the minimum single sprinkler flow rates and maximum
coverage areas listed in the Residential Sprinkler Minimum Flow Requirements Table below. These flow rates and coverage areas correspond to a discharge density equal to or
greater than the minimum allowable discharge density of 0.05 gal/min/ft2 (2.04 mm/min), in accordance with NFPA 13R and 13D. FM Approved residential sprinklers have been
determined to perform effectively as property protection devices when installed in accordance with the coverage area and density limitations specified in FM Global Property Loss
Prevention Data Sheet 3-26. Residential sprinklers shall be installed in strict accordance with the FM Global Property Loss Prevention Data Sheets.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-45
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY4234 6.9 Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 155°, 175°F (68°, 79°C)
Tyco TY4234 6.9 Recessed Pendent QR 3 mm 3⁄4 Brass, Chrome, Polyester 155°, 175°F (68°, 79°C)
Tyco TY4334 5.8 HSW QR 3 mm 1⁄2 Brass, Chrome, White 155°, 175°F (68°, 79°C)
Painted
1⁄2 Brass, Chrome, White
Tyco TY4334 5.8 Recessed HSW QR 3 mm Painted 155°, 175°F (68°, 79°C)
1⁄2 Brass, Chrome, White
Viking VK420 3.8 Flush Pendent QR Fusible Painted 165°F (74°C)
FM Approvals
September 2007 — Approval Guide
1-46 Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Viking VK520 14.0 Upright FR Fusible 3⁄4 Brass 165°, 205°F (74°, 96°C)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Kidde AS1451 14.0 Pendent FR 2.5 mm 3⁄4 Brass 155°, 200°F (68°, 93°C)
Reliable R5012 14.0 Pendent FR 2.5 mm 3⁄4 Brass 155°, 200°F (68°, 93°C)
Reliable RA0512 14.0 Pendent FR Fusible 3⁄4 Brass 165°, 212°F (74°, 100°C)
Tyco TY6226 14.0 Pendent FR Fusible 3⁄4 Brass 165°, 214°F (74°, 101°C)
Viking VK500 14.0 Pendent FR Fusible 3⁄4 Brass 165°, 205°F (74°, 96°C)
Suppression mode (formerly called Early Suppression-Fast Response or ‘‘ESFR’’) automatic sprinklers with a nominal discharge coefficient of 16.8 gal/min/(psi)½ are similar to
suppression mode sprinklers with nominal discharge coefficients of 14.0 gal/min/(psi)½ in that they are designed to be used against severe fire challenges in occupancies where fire
suppression is possible. They are not intended for use in occupancies where fires cannot be suppressed with water (e.g., low flash point flammable liquids, oxidizing chemicals, etc.).
This sprinkler offers the advantage of adequate hydraulic design at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need
for additional fire pumps. Consult the FM Global Property Loss Prevention Data Sheets concerning suppression mode sprinklers prior to designing and installing automatic fire
protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention Data Sheets shall be strictly adhered to when designing and installing automatic fire
protection systems utilizing these sprinklers.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-47
Suppression mode (formerly called Early Suppression-Fast Response or ‘‘ESFR’’) automatic sprinklers with a nominal discharge coefficient of 22.4 gal/min/(psi)½ are similar to
suppression mode sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in that they are designed to be used against severe fire challenges. They are not,
however, direct replacements for suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in all applications. They are intended for
use in certain occupancies where fire suppression is possible and are not suitable for use in occupancies where fires cannot be suppressed by water. This sprinkler offers the
advantage of adequate hydraulic design at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps.
The range of applications for which this sprinkler can be used is smaller than that of suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and
16.8 gal/min/(psi)½.
Care must be exercised to only utilize these sprinklers in applications for which they have been shown to be effective. Consult the FM Global Property Loss Prevention Data Sheets
concerning suppression mode sprinklers prior to designing and installing automatic fire protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention
Data Sheets shall be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.
Suppression mode (formerly called Early Suppression-Fast Response or ‘‘ESFR’’) automatic sprinklers with a nominal discharge coefficient of 25.2 gal/min/(psi)½ are similar to
suppression mode sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in that they are designed to be used against severe fire challenges. They are not,
however, direct replacements for suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and 16.8 gal/min/(psi)½ in all applications. They are intended for
use in certain occupancies where fire suppression is possible and are not suitable for use in occupancies where fires cannot be suppressed by water. This sprinkler offers the
advantage of adequate hydraulic design at lower water supply pressures, which may allow adequate sprinkler protection to be achieved without the need for additional fire pumps.
The range of applications for which this sprinkler can be used is smaller than that of suppression mode pendent sprinklers with nominal discharge coefficients of 14.0 and
16.8 gal/min/(psi)½.
Care must be exercised to only utilize these sprinklers in applications for which they have been shown to be effective. Consult the FM Global Property Loss Prevention Data Sheets
concerning suppression mode sprinklers prior to designing and installing automatic fire protection systems utilizing this type of sprinkler. The FM Global Property Loss Prevention
Data Sheets shall be strictly adhered to when designing and installing automatic fire protection systems utilizing these sprinklers.
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Tyco TY9226 25.2 Pendent FR Fusible 1 Brass 165°, 214°F (74°, 101°C)
Viking VK510 25.2 Pendent FR Fusible 1 Brass 165°, 205°F (74°, 96°C)
FM Approvals
September 2007 — Approval Guide
1-48 Automatic Sprinkler Systems
Sprinkler Guards/Shields
Sprinkler guards are designed to protect automatic sprinklers from mechanical damage in the event of a minor impact. They can be used on upright or pendent automatic sprinklers.
Specific guards listed below for use with Early Suppression Fast Response (ESFR) automatic sprinklers are only intended for use under conveyors, mezzanines or other similar
obstructions and are specifically not for use at ceiling level. Sprinkler shields are mounted directly to the sprinkler casting or may accompany the sprinkler guard to protect the thermal
sensitive element from retarded operation due to water discharge from nearby sprinklers at higher elevations.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-49
FM Approvals
September 2007 — Approval Guide
1-50 Automatic Sprinkler Systems
SIGHT DRAINS
Sight drains may be used in sprinkler systems where the drain discharge outlet is not readily visible. When they
are used, the discharge should conform to FM Global Property Loss Prevention Data Sheets and any local health
or water department regulations. They are not to be used upstream of a valve or fitting which can trap pressure
between the sight drain and the drain line. Unless otherwise noted in the listing, these sight drains have 175 psi
(1205 kPa) rated working pressure.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
1, 11⁄4, 11⁄2, 2 in. NPS 250 psi (1725 kPa) rated working pressure.
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Grinnell or TFP Fig. SF1. 1, 2 in. NPS.
Telescoping sprinkler assemblies are used to extend automatic or open sprinklers below the tips of the anechoic
material in anechoic chambers. The assemblies are to be installed according to manufacturer’s directives and in
compliance with FM Global Property Loss Prevention Data Sheet 1-53.
SI-1.0 3⁄ 4 1 8.6
(0.3) (2.6)
SI-1.5 3⁄ 4 1.5 9.4
(0.46) (2.8)
SI-2.0 3⁄ 4 2 10.2
(0.61) (3.1)
SI-2.5 3⁄ 4 2.5 11.0
(0.76) (3.3)
SI-3.0 3⁄ 4 3 11.8
(0.91) (3.6)
SI-3.5 3⁄ 4 3.5 12.0
(1.1) (3.7)
SI-4.0 3⁄ 4 4 12.2
(1.2) (3.7)
SI-4.5 3⁄ 4 4.5 12.4
(1.4) (3.8)
SI-5.0 3⁄ 4 5 12.6
(1.5) (3.8)
SI-5.5 3⁄ 4 5.5 12.8
(1.7) (3.8)
SI-6.0 3⁄ 4 6 12.9
(1.8) (3.9)
Approval is limited to the vertical down position and with two cables attached to the springs. Approval is limited to the horizontal position
and with one cable attached to the spring. The maximum rated working pressure is 175 psi (1205 kPa). These models were tested with a
automatic sprinkler with a Nominal Discharge Coefficient of 8.0 gal/min/(psi)½. The minimum water pressure required to move the piston to
the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are FM Approved for use in the models listed above:
SI-1.0 3⁄ 4 1 9.2
(0.3) (2.8)
SI-1.5 3⁄ 4 1.5 10.1
(0.46) (3.1)
SI-2.0 3⁄ 4 2 11.1
(0.61) (3.4)
SI-2.5 3⁄ 4 2.5 12.1
(0.76) (3.7)
SI-3.0 3⁄ 4 3 13.1
(0.91) (3.9)
SI-3.5 3⁄ 4 3.5 13.2
(1.1) (4.0)
SI-4.0 3⁄ 4 4 13.4
(1.2) (4.1)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-51
Approval is limited to the vertical down position and with two cables attached to the springs. Approval is limited to the horizontal position
and with one cable attached to the spring. The maximum rated working pressure is 175 psi (1205 kPa). These models were tested with an
automatic sprinkler with a Nominal Discharge Coefficient of 11.2 gal/min/(psi)½. The minimum water pressure required to move the piston to
the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are FM Approved for use in the models listed above:
SI-B-1.0 3⁄ 4 1 3.7
(0.3) (1.1)
SI-B-1.5 3⁄ 4 1.5 3.7
(0.5) (1.1)
SI-B-2.0 3⁄ 4 2 3.7
(0.6) (1.1)
SI-B-2.5 3⁄ 4 2.5 3.7
(0.8) (1.1)
SI-B-3.0 3⁄ 4 3 3.7
(0.9) (1.1)
SI-B-3.5 3⁄ 4 3.5 4.15
(1.1) (1.3)
SI-B-4.0 3⁄ 4 4 4.6
(1.2) (1.4)
SI-B-4.5 3⁄ 4 4.5 5.05
(1.4) (1.5)
SI-B-5.0 3⁄ 4 5 5.5
(1.5) (1.7)
SI-B-5.5 3⁄ 4 5.5 5.95
(1.7) (1.8)
SI-B-6.0 3⁄ 4 6 6.4
(1.8) (1.9)
Approval is limited to the vertical down position only and with two cables attached to the springs. The maximum rated working pressure is
175 psi (1205 kPa). These models were tested with an automatic sprinkler with a Nominal Discharge Coefficient of 8.0 gal/min/(psi)½. The
minimum water pressure required to move the piston to the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are
FM Approved for use in the models listed above:
SI-B-1.0 3⁄ 4 1 3.3
(0.3) (1.0)
SI-B-1.5 3⁄ 4 1.5 3.6
(0.5) (1.1)
SI-B-2.0 3⁄ 4 2 3.8
(0.6) (1.2)
SI-B-2.5 3⁄ 4 2.5 4.1
(0.8) (1.3)
SI-B-3.0 3⁄ 4 3 4.3
(0.9) (1.4)
SI-B-3.5 3⁄ 4 3.5 4.9
(1.1) (1.5)
SI-B-4.0 3⁄ 4 4 5.4
(1.2) (1.6)
SI-B-4.5 3⁄ 4 4.5 6.0
(1.4) (1.8)
SI-B-5.0 3⁄ 4 5 6.5
(1.5) (2.0)
SI-B-5.5 3⁄ 4 5.5 7.1
(1.7) (2.2)
SI-B-6.0 3⁄ 4 6 7.6
(1.8) (2.3)
FM Approvals
September 2007 — Approval Guide
1-52 Automatic Sprinkler Systems
Approval is limited to the vertical down position only and with two cables attached to the springs. The maximum rated working pressure is
175 psi (1205 kPa). These models were tested with an automatic sprinkler with a Nominal Discharge Coefficient of 11.2 gal/min/(psi)½. The
minimum water pressure required to move the piston to the fully extended position is 25 psi (170 kPa). The following automatic sprinklers are
FM Approved for use in the models listed above:
Flexible sprinkler hose with threaded end fittings are for use in cleanroom ceilings. The flexible hoses are to be
installed according to the manufacturer’s directives. Unless indicated, the hoses have a rated working pressure of
175 psi (1205 kPa).
AA Precision Metal Ltd, No. 23 Ta Pu, Wu Chuan Village, Ta Yuan Hsiang, Tao-Yuan Hsien, Taiwan ROC
Model NPT Hose Assembly Equivalent Length of 1 in.
in. length ft Schedule 40 Pipe, ft
(m) (m)
AA001-13 1⁄ 2 2 5.5
(0.61) (1.7)
AA001-13 1⁄ 2 4 7.8
(1.22) (2.4)
AA001-13 1⁄ 2 6 11.1
(1.83) (3.4)
AA001-13 1⁄ 2 7 12.6
(2.13) (3.7)
1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited
for use in cleanroom ceilings manufactured by AA Precision Metal Ltd.
Clean-Flex Model Welded. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanrooms.
Approval is limited for use in cleanroom ceilings manufactured by CLEANPAK International Inc. When properly installed, the collar on the
outlet pipe butts up against hold-down bracket on upper surface of ceiling and the sprinkler head frame extends below the ceiling.
WF-WCO-N-50-C304L 1⁄ 2 4 15.4
(1.2) (4.7)
WF-WCO-N-50-C316L 1⁄ 2 4 15.4
(1.2) (4.7)
WF-WCO-A-50-C304L 1⁄ 2 4 15.4
(1.2) (4.7)
WF-WCO-A-50-C316L 1⁄ 2 4 15.4
(1.2) (4.7)
WF-WCO-N-72-C304L 1⁄ 2 6 21.4
(1.8) (6.5)
WF-WCO-N-72-C316L 1⁄ 2 6 21.4
(1.8) (6.5)
WF-WCO-A-72-C304L 1⁄ 2 6 21.4
(1.8) (6.5)
WF-WCO-A-72-C316L 1⁄ 2 6 21.4
(1.8) (6.5)
Cleanpak Model WF WCO: 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanrooms. The
WCO Series is constructed of extruded seamless vacuum-formed white tube of open-pitch convoluted PTFE, protected by stainless steel
braid. Available with and without armor covering. Approval is limited for use in cleanroom ceilings manufactured by CLEANPAK International
Inc.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-53
Flexible sprinkler hose with threaded end fittings are for use in commercial suspended ceilings. The flexible hoses are to be installed
according to the manufacturer’s directives. Unless indicated, the hoses have a rated working pressure of 175 psi (1205 kPa).
Dektronic Enterprise Co Ltd, 8F, No. 155, Sec. 1, Jung Shan Road, Yung He City, Taipei, Hsien Taiwan ROC 83113
1⁄ 2 4.2 11.5
DK-FLH1001-UIS
(1.3) (3.5)
1⁄ 2 6.1 53.9
DK-FLH1002-UIS
(1.8) (16.4)
1⁄ 2 7.1 63.5
DK-FLH1003-UIS
(2.1) (19.3)
1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited
for use in cleanroom ceilings manufactured by United Information Systems Co., Ltd. (‘‘T’’ Grid Model TG001 and Cross Joint Model CJ001).
1⁄ 2 4.2 11.5
DK-FLH1001-CTC
(1.3) (3.5)
1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited
for use in cleanroom ceilings manufactured by Cherng-Gang Technology Construct Co., Ltd.
1⁄ 2 4.2 11.5
DK-FLH1001-F
(1.3) (3.5)
1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is limited
for use in cleanroom ceilings manufactured by Fuji Electric Co., Ltd.
1⁄ 2 2.5 1.6
EFSPC-01A
(750) (0.5)
1⁄ 2 3.9 9.5
EFSPC-02A
(1200) (2.9)
1⁄ 2 5.6 13.6
EFSPC-03A
(1700) (4.1)
1⁄ 2 7.2 19.2
EFSPC-04A
(2200) (5.9)
1⁄ 2 8.5 25.4
EFSPC-05A
(2600) (7.7)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanrooms. Approval is limited for use in
cleanrooms manufactured by Shin Sung Engineering Co., Ltd.
1⁄ 2 3 15.1
CRCS0036
(0.9) (4.6)
Model CRCS0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.
1⁄ 2 6 27.5
CRCS0072
(1.8) (8.4)
Model CRCS0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.
FM Approvals
September 2007 — Approval Guide
1-54 Automatic Sprinkler Systems
1⁄ 2 3 15.1
CRC 0036
(0.9) (4.6)
Model CRC 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Clestra Cleanrooms Inc., now owned and manufactured by Gordon Inc.
1⁄ 2 6 27.5
CRC 0072
(1.8) (8.4)
Model CRC 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Clestra Cleanrooms Inc., now owned and manufactured by Gordon Inc.
1⁄ 2 3 15.1
CRCAPL-0036
(0.9) (4.6)
Model CRAPL-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling grid manufactured by Kikukawa.
1⁄ 2 6 27.5
CRCAPL-0072
(1.8) (8.5)
Model CRAPL-0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling grid manufactured by Kikukawa.
1⁄ 2 3 15.1
CRCS0036
(0.9) (4.6)
Model CRCS0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.
1⁄ 2 6 27.5
CRCS0072
(1.8) (8.4)
Model CRCS0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model CG6200 manufactured by Channel Systems Inc.
1⁄ 2 3 15.1
CRD 0036
(0.9) (4.6)
Model CRD 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.
1⁄ 2 6 28.4
CRD 0072
(1.8) (8.4)
Model CRD 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-55
1⁄ 2 3 15.1
CRD 1036
(0.9) (4.6)
Model CRD 1036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.
1⁄ 2 3 15.1
CRSBB 0036
(0.9) (4.6)
Model CRFH-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling grid Model No. UG-1, UG-1 Gel, UG-Lite and UG-Lite-Gel manufactured by F. H. Chase Inc..
1⁄ 2 6 27.5
CRSBB 0072
(1.8) (8.4)
Model CRFH 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling grid Model No. UG-1, UG-1 Gel, UG-Lite and UG-Lite-Gel manufactured by F. H. Chase Inc..
1⁄ 2 6 27.5
CRD 1072
(1.8) (8.4)
Model CRD 1072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Daw Technologies, Inc.
1⁄ 2 3 15.1
CRGDS0036
(0.9) (4.6)
Model CRGDS0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model DS/20 manufactured by Gordon Inc.
1⁄ 2 6 27.5
CRGDS0072
(1.8) (8.4)
Model CRGDS0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model DS/20 manufactured by Gordon Inc.
1⁄ 2 3 15.1
CRF20036
(0.9) (4.6)
Model CRF20036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model F2000D manufactured by Facilities Incorporated.
1⁄ 2 6 27.5
CRF20072
(1.8) (8.4)
Model CRF20072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model F2000D manufactured by Facilities Incorporated.
FM Approvals
September 2007 — Approval Guide
1-56 Automatic Sprinkler Systems
1⁄ 2 3 15.1
CRF40036
(0.9) (4.6)
Model CRF40036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model F4000D manufactured by Facilities Incorporated.
1⁄ 2 6 27.5
CRF40072
(1.8) (8.4)
Model CRF40072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling Model F4000D manufactured by Facilities Incorporated.
1⁄ 2 3 15.1
CRG 0036
(0.9) (4.6)
Model CRG 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Gordon Inc.
1⁄ 2 6 27.5
CRG 0072
(1.8) (8.4)
Model CRG 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Gordon Inc.
1⁄ 2 3 15.1
CRGV0036
(0.9) (4.6)
Model CRGV0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Galvani SRL.
1⁄ 2 6 27.5
CRGV0072
(1.8) (8.4)
Model CRGV0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Galvani SRL.
1⁄ 2 3 15.1
CRH 0036
(0.9) (4.6)
Model CRH 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 6 28.4
CRH 0072
(1.8) (8.4)
Model CRH 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-57
1⁄ 2 3 15.1
CRS 0036
(0.9) (4.6)
Model CRS 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.
1⁄ 2 3.3 15.3
CRS 0040
(1.0) (4.7)
Model CRS 0040. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.
1⁄ 2 5 24
CRS 0060
(1.52) (7.3)
Model CRS 0060. 1 in. nominal dia. flexible sprinkler metal hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.
1⁄ 2 6 27.5
CRS 0072
(1.8) (8.4)
Model CRS 0072. 1 in. nominal dia. flexible sprinkler metal hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering.
1⁄ 2 3 15.1
CRSBB 0036
(0.9) (4.6)
Model CRSBB-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling grid Model No. 2035 manufactured by SBB Inc.
1⁄ 2 6 27.5
CRSBB 0072
(1.8) (8.4)
Model CRSBB 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceiling grid Model No. 2035 manufactured by SBB Inc.
1⁄ 2 3 15.1
CRW 0036
(0.9) (4.6)
Model CRW 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by M+W Zander (formerly Meissner & Wurst).
1⁄ 2 6 28.4
CRW 0072
(1.8) (8.4)
Model CRW 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by M+W Zander (formerly Meissner & Wurst).
FM Approvals
September 2007 — Approval Guide
1-58 Automatic Sprinkler Systems
1⁄ 2 3 15.1
CRYCF 0036
(0.9) (4.6)
Model CRYCF 0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng.
1⁄ 2 6 27.5
CRYCF 0072
(1.8) (8.4)
Model CRYCF 0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng.
1⁄ 2 3 10.4
CRH0036-PTFE
(0.9) (3.4)
Model CRH0036-PTFE. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
This hose assembly utilizes a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is
limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 6 15.1
CRH0072-PTFE
(1.8) (4.6)
Model CRH0072-PTFE. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
This hose assembly utilizes a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene) convoluted hose. Approval is
limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 3 10.4
CRH0036-PTFE-A
(0.9) (3.4)
Model CRH0036-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene)
convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 6 15.1
CRH0072-PTFE-A
(1.8) (4.6)
Model CRH0072-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene)
convoluted hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 3 10.4
CRW0036-PTFE-A
(0.9) (3.4)
Model CRW0036-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene)
convoluted hose. Approval is limited for use in cleanroom ceiling grid manufactured by M&W.
1⁄ 2 6 15.1
CRW0072-PTFE-A
(1.8) (4.6)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-59
Model CRW0072-PTFE-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
This hose assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. PTFE (polytetrafluoroethylene)
convoluted hose. Approval is limited for use in cleanroom ceiling grid manufactured by M&W.
1⁄ 2 3 15.1
CRGLRP-0036
(0.9) (4.6)
Model CRGLRP-0036. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom
ceilings. Approval is limited for use in cleanroom ceiling grid P/N LRPSCSTROUGH manufactured by Gordon.
1⁄ 2 6 27.5
CRGLRP-0072
(1.8) (8.5)
Model CRGLRP-0072. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom
ceilings. Approval is limited for use in cleanroom ceiling grid P/N LRPSCSTROUGH manufactured by Gordon.
1⁄ 2 6 23.5
GRA0141
(1.8) (7.2)
Model GRA0141 DROP NIPPLE ASSEMBLY. 1 in. nominal dia flexible metal sprinkler hose for providing a connection to automatic
sprinklers in cleanroom ceilings. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 2.5 1.6
KFB-SPC-01A
(750) (0.5)
1⁄ 2 3.9 9.5
KFB-SPC-02A
(1200) (2.9)
1⁄ 2 5.6 13.6
KFB-SPC-03A
(1700) (4.1)
1⁄ 2 7.2 19.2
KFB-SPC-04A
(2200) (5.9)
1⁄ 2 8.5 25.4
KFB-SPC-05A
(2600) (7.7)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanrooms. Approval is limited for use in
cleanrooms manufactured by Shin Sung Engineering Co., Ltd.
Panew Company Limited, 8F-5, No. 2 Jianba Road, Chung Ho, Taipei Hsien, Taiwan ROC
1⁄ 2 2 5.5
P-9700
(0.6) (1.7)
1⁄ 2 4 7.8
P-9700
(1.2) (2.4)
1⁄ 2 6 11.1
P-9700
(1.8) (3.4)
1⁄ 2 7 12.6
P-9700
(2.1) (3.7)
Model P-9700 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by AA Precision Metal Ltd.
FM Approvals
September 2007 — Approval Guide
1-60 Automatic Sprinkler Systems
1⁄ 2 2 5.5
P-9710
(0.6) (1.7)
1⁄ 2 4 7.8
P-9710
(1.2) (2.4)
1⁄ 2 6 11.1
P-9710
(1.8) (3.4)
1⁄ 2 7 12.6
P-9710
(2.1) (3.7)
Model P-9710 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Topline Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9720
(0.6) (1.7)
1⁄ 2 4 7.8
P-9720
(1.2) (2.4)
1⁄ 2 6 11.1
P-9720
(1.8) (3.4)
1⁄ 2 7 12.6
P-9720
(2.1) (3.7)
Model P-9720 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Fuji Electric Co., Ltd.
1⁄ 2 2 5.5
P-9730
(0.6) (1.7)
1⁄ 2 4 7.8
P-9730
(1.2) (2.4)
1⁄ 2 6 11.1
P-9730
(1.8) (3.4)
1⁄ 2 7 12.6
P-9730
(2.1) (3.7)
Model P-9730 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9740
(0.6) (1.7)
1⁄ 2 4 7.8
P-9740
(1.2) (2.4)
1⁄ 2 6 11.1
P-9740
(1.8) (3.4)
1⁄ 2 7 12.6
P-9740
(2.1) (3.7)
Model P-9740 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by United Information Systems Co., Ltd.
1⁄ 2 2 5.5
P-9750
(0.6) (1.7)
1⁄ 2 4 7.8
P-9750
(1.2) (2.4)
1⁄ 2 6 11.1
P-9750
(1.8) (3.4)
1⁄ 2 7 12.6
P-9750
(2.1) (3.7)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-61
Model P-9750 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Topwell Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9760
(0.6) (1.7)
1⁄ 2 4 7.8
P-9760
(1.2) (2.4)
1⁄ 2 6 11.1
P-9760
(1.8) (3.4)
1⁄ 2 7 12.6
P-9760
(2.1) (3.7)
Model P-9760 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by M+W Zander Facility Engineering GmbH.
1⁄ 2 2 5.5
P-9770
(0.6) (1.7)
1⁄ 2 4 7.8
P-9770
(1.2) (2.4)
1⁄ 2 6 11.1
P-9770
(1.8) (3.4)
1⁄ 2 7 12.6
P-9770
(2.1) (3.7)
Model P-9770 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Tenryo Technology and Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9790
(0.6) (1.7)
1⁄ 2 4 7.8
P-9790
(1.2) (2.4)
1⁄ 2 6 11.1
P-9790
(1.8) (3.4)
1⁄ 2 7 12.6
P-9790
(2.1) (3.7)
Model P-9790 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Tien Hann Engineering Co., Ltd.
Paradise Industry Co Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City Kyunggi-Do, Korea (420-120)
1⁄ 2 4.5 14.4
SFT-1000
(1.4) (4.4)
1⁄ 2 6.1 16.7
SFT-1000
(1.8) (5.1)
1⁄ 2 7.2 23.3
SFT-1500
(2.2) (7.1)
1⁄ 2 4.5 14.4
SFT-1500-1
(1.4) (4.4)
1⁄ 2 6.1 16.7
SFT-1500-1
(1.8) (5.1)
1⁄ 2 3.3 13.1
SFT-D
(1.0) (4.2)
1⁄ 2 8.5 28.2
SFT-D
(2.6) (8.6)
1⁄ 2 3.3 13.7
SFT-E
(1.0) (4.2)
1⁄ 2 8.5 36.8
SFT-E
(2.6) (11.2)
FM Approvals
September 2007 — Approval Guide
1-62 Automatic Sprinkler Systems
1⁄ 2 3.3 13.7
SFT-F
(1.0) (4.2)
1⁄ 2 8.5 36.8
SFT-F
(2.6) (11.2)
1⁄ 2 3.3 13.7
SFT-L
(1.0) (4.2)
1⁄ 2 8.5 31.1
SFT-L
(2.6) (9.5)
1⁄ 2 3.3 13.7
SFT-M
(1.0) (4.2)
1⁄ 2 8.5 36.8
SFT-M
(2.6) (11.2)
Model SFT-1500.
1 in. nominal dia. flexible metal sprinkler hose with fittings for providing a connection to automatic sprinklers in cleanroom ceilings. Approval
is limited for use in cleanroom ceilings manufactured by Shin Sung Engineering Co., Ltd. and Songhwa Engineering.
Seung Jin Industry Co Ltd, 612, 5 Bar Shi-Wha Industrial Complex, 685-11 Sunggog-Dong, Ansan-Si
Kyunggi-Do, 429-450 Korea
1⁄ 2 2.6 8.3
CRXXYY – ZZZZ
(0.8) (2.6)
1⁄ 2 8.5 31.8
CRXXYY – ZZZZ
(2.6) (9.7)
3⁄ 4 3.3 7.6
CRXXYY – ZZZZ
(1.0) (2.3)
3⁄ 4 8.2 31.4
CRXXYY – ZZZZ
(2.5) (9.6)
CR: Cleanroom
XX: 12 for 1⁄2 in. reducer and 34 for 3⁄4 in. reducer.
YY: Length of Hose assembly. (08 is a 0.8 m (2.6 ft) long hose assembly and 26 is a 2.6 m (8.5 ft) long hose assembly. 08 through 26 for 1⁄2 in. reducer, and 10 through
25 for 3⁄4 in. reducer.
ZZZZ: Year and month manufactured.
Approval of this 1 in. nominal dia. flexible metal hose is limited for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in a cleanroom ceiling Model S-139 manufactured by Shin Sung Engineering Co., Ltd.
1⁄ 2 3.3 9.9
SJ-CR-01
(1.0) (3.0)
3⁄ 4 3.3 9.4
SJ-CR-01
(1.0) (2.9)
Model SJ-CR-01. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval
of 3.3 ft (1.0 m). Approval is limited for use in cleanroom ceiling Model S-139 manufactured by Shinsung Engineering Co., Ltd.
1⁄ 2 6 19.3
SJ-CR-02
(1.8) (5.9)
3⁄ 4 6 19.0
SJ-CR-02
(1.8) (5.8)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-63
Model SJ-CR-02. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval
of 6 ft (1.8 m). Approval is limited for use in cleanroom ceiling Model S-139 manufactured by Shinsung Engineering Co., Ltd.
1⁄ 2 8.3 26
SJ-CR-03
(2.5 ) (7.9)
3⁄ 4 8.3 31.6
SJ-CR-03
(2.5) (9.6)
Model SJ-CR-03. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval
of 8.3 ft (2.5 m). Approval is limited for use in cleanroom ceiling Model S-139 manufactured by Shinsung Engineering Co., Ltd.
1⁄ 2 2.6 10.9
SJ-CR-08
(0.8) (3.3)
1⁄ 2 8.2 35.3
SJ-CR-25
(2.5) (10.8)
Model SJ-CR-08 through SJ-CR-25. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom
ceilings. Approval is limited for use in a cleanroom ceiling Model S-139 manufactured by Shin Sung Engineering Co., Ltd.
Approval of these models is in the range as stated above. 08 to 25 is the range of length, 0.8 m to 2.5 m (2.6 ft to 8.2 ft).
Shanghai Genius Technical Corp Ltd, No. 7166 Zhong Chun Road, Qibao Town, Minhang District, Shanghai,
P.R. China 201101
1⁄ 2 2 5.5
P-9700
(0.6) (1.7)
1⁄ 2 4 7.8
P-9700
(1.2) (2.4)
1⁄ 2 6 11.1
P-9700
(1.8) (3.4)
1⁄ 2 7 12.6
P-9700
(2.1) (3.7)
Model P-9700. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by AA Precision Metal Ltd.
1⁄ 2 2 5.5
P-9710
(0.6) (1.7)
1⁄ 2 4 7.8
P-9710
(1.2) (2.4)
1⁄ 2 6 11.1
P-9710
(1.8) (3.4)
1⁄ 2 7 12.6
P-9710
(2.1) (3.7)
Model P-9710. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Topline Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9720
(0.6) (1.7)
1⁄ 2 4 7.8
P-9720
(1.2) (2.4)
1⁄ 2 6 11.1
P-9720
(1.8) (3.4)
1⁄ 2 7 12.6
P-9720
(2.1) (3.7)
Model P-9720. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Fuji Electric Co., Ltd.
FM Approvals
September 2007 — Approval Guide
1-64 Automatic Sprinkler Systems
1⁄ 2 2 5.5
P-9730
(0.6) (1.7)
1⁄ 2 4 7.8
P-9730
(1.2) (2.4)
1⁄ 2 6 11.1
P-9730
(1.8) (3.4)
1⁄ 2 7 12.6
P-9730
(2.1) (3.7)
Model P-9730. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Yung Cheng Feng Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9740
(0.6) (1.7)
1⁄ 2 4 7.8
P-9740
(1.2) (2.4)
1⁄ 2 6 11.1
P-9740
(1.8) (3.4)
1⁄ 2 7 12.6
P-9740
(2.1) (3.7)
Model P-9740. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by United Information Systems Co., Ltd.
1⁄ 2 2 5.5
P-9750
(0.6) (1.7)
1⁄ 2 4 7.8
P-9750
(1.2) (2.4)
1⁄ 2 6 11.1
P-9750
(1.8) (3.4)
1⁄ 2 7 12.6
P-9750
(2.1) (3.7)
Model P-9750. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Topwell Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9760
(0.6) (1.7)
1⁄ 2 4 7.8
P-9760
(1.2) (2.4)
1⁄ 2 6 11.1
P-9760
(1.8) (3.4)
1⁄ 2 7 12.6
P-9760
(2.1) (3.7)
Model P-9760. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by M+W Zander Facility Engineering GmbH.
1⁄ 2 2 5.5
P-9770
(0.6) (1.7)
1⁄ 2 4 7.8
P-9770
(1.2) (2.4)
1⁄ 2 6 11.1
P-9770
(1.8) (3.4)
1⁄ 2 7 12.6
P-9770
(2.1) (3.7)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-65
Model P-9770. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Tenryo Technology and Engineering Co., Ltd.
1⁄ 2 2 5.5
P-9790
(0.6) (1.7)
1⁄ 2 4 7.8
P-9790
(1.2) (2.4)
1⁄ 2 6 11.1
P-9790
(1.8) (3.4)
1⁄ 2 7 12.6
P-9790
(2.1) (3.7)
Model P-9790. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Approval is limited for use in cleanroom ceilings manufactured by Tien Hann Engineering Co., Ltd.
Super Flex Enterprises Co Ltd, No. 16, Lane 561, Sec 2, Kouji Rd, Taoyuan City, Taoyuan, Taiwan ROC
1⁄ 2 1.9 12.5
SP-L
(0.60) (3.8)
1⁄ 2 2.1 12.7
SP-L
(0.64) (3.9)
1⁄ 2 2.6 13.1
SP-L
(0.80) (4.0)
1⁄ 2 3.1 15.8
SP-L
(0.96) (4.8)
1⁄ 2 3.3 16.4
SP-L
(1.0) (5.0)
1⁄ 2 3.5 17.4
SP-L
(1.0) (5.3)
1⁄ 2 3.8 19.0
SP-L
(1.2) (5.8)
1⁄ 2 3.9 19.7
SP-L
(1.2) (6.0)
1⁄ 2 4.4 21.9
SP-L
(1.3) (6.7)
1⁄ 2 5.2 28.8
SP-L
(1.6) (8.8)
1⁄ 2 6.9 17.8
SP-L
(2.1) (5.4)
1⁄ 2 7.8 18.2
SP-L
(2.4) (5.5)
1⁄ 2 8.4 18.5
SP-L
(2.6) (5.6)
Model SP-L. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is
limited for use in the following cleanroom ceilings:
1⁄ 2 1.9 12.5
SP-L-1
(0.60) (3.8)
FM Approvals
September 2007 — Approval Guide
1-66 Automatic Sprinkler Systems
1⁄ 2 2.1 12.7
SP-L-1
(0.64) (3.9)
1⁄ 2 2.6 13.1
SP-L-1
(0.80) (4.0)
1⁄ 2 3.1 15.8
SP-L-1
(0.96) (4.8)
1⁄ 2 3.3 16.4
SP-L-1
(1.0) (5.0)
1⁄ 2 3.5 17.4
SP-L-1
(1.0) (5.3)
1⁄ 2 3.8 19.0
SP-L-1
(1.2) (5.8)
1⁄ 2 3.9 19.7
SP-L-1
(1.2) (6.0)
1⁄ 2 4.4 21.9
SP-L-1
(1.3) (6.7)
1⁄ 2 5.2 28.8
SP-L-1
(1.6) (8.8)
1⁄ 2 6.9 17.8
SP-L-1
(2.1) (5.4)
1⁄ 2 7.8 18.2
SP-L-1
(2.4) (5.5)
1⁄ 2 8.4 18.5
SP-L-1
(2.6) (5.6)
Model SP-L-1. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. Approval is
limited for use in the following cleanroom ceilings:
1⁄ 2 5 22.4
SF56016TFWC000
(1.5) (6.8)
Model SF56016TFWC000. 1 in. nominal dia. flexible sprinkler hose for connection to automatic sprinklers in cleanrooms. This hose
assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. (polytetrafluoroethylene) PTFE convoluted
hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
1⁄ 2 6 29.9
SF56016TFWC001
(1.8) (9.1)
Model SF56016TFWC001. 1 in. nominal dia. flexible sprinkler hose for connection to automatic sprinklers in cleanrooms. This hose
assembly has an armor protective covering over a stainless steel braid over a nominal 1 in. I.D. (polytetrafluoroethylene) PTFE convoluted
hose. Approval is limited for use in cleanroom ceilings manufactured by HUNTAIR.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-67
1⁄ 2 3.3 14.2
T1S025
(1.0) (4.2)
Model T1S025. 1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in cleanroom ceilings. This hose
assembly has a stainless steel braid over a nominal 1 in. I.D. (polytetrafluoroethylene) PTFE hose. Approval is limited for use in cleanroom
ceilings manufactured by M+W Zander Type 55/70-T/E Profile.
1⁄ 2 3.3 7.7
HYDRA
(1.0) (2.3)
1⁄ 2 7.7 16.0
HYDRA
(2.0) (4.8)
HYDRA Hose. 1 in. (25 mm) nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom
ceilings. Approval is in the range of 3.3 ft to 7.7 ft (1000 mm to 2000 mm). Approval is limited for use in cleanroom ceilings manufactured by
the following companies:
M & W Zander Facility Eng. GmbH M & W Profile Type Grid 55/60-FL/E
M & W Zander Facility Eng. GmbH M & W Profile Type Grid 55/70-T/E
Daldrop & Dr. Ing Huber GmbH + Co. 40N
Yong Won E.N.C. Ltd, 116-1 Sedgu-Ri, Kwangjeuk-Myun, Yangju-Gun Keungki-Do, Korea
1⁄ 2 3.5 9.3
YB25-I
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB25-I
(2.57) (5.6)
Model YB25-I. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB25-I is a one piece style. The reducer and nipple are welded to the flexible hose.
1⁄ 2 3.5 9.3
YB25-II
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB25-II
(2.57) (5.6)
Model YB25-II. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB25-II is a three piece style. The reducer and nipple are connected to the flexible hose using as a nut.
1⁄ 2 3.5 9.3
YB25-III
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB25-III
(2.57) (5.6)
Model YB25-III. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB25-III is a two piece style. The reducer is welded to the flexible hose and nipple is connected to the flexible
hose using a nut.
FM Approvals
September 2007 — Approval Guide
1-68 Automatic Sprinkler Systems
1⁄ 2 3.5 9.3
YB28-IA
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB28-IA
(2.57) (5.6)
Model YB28-lA. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB28-IA is a one piece style. The reducer and nipple are welded to the flexible hose.
1⁄ 2 3.5 9.3
YB28-I
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB28-I
(2.57) (5.6)
Model YB28-l. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB28-I is a one piece style. The reducer and nipple are welded to the flexible hose.
1⁄ 2 3.5 9.3
YB28-II
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB28-II
(2.57) (5.6)
Model YB28-II. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB28-II is a three piece style. The reducer and nipple are connected to the flexible hose using as a nut.
1⁄ 2 3.5 9.3
YB28-III
(1.07) (2.8)
1⁄ 2 8.4 18.4
YB28-III
(2.57) (5.6)
Model YB28-III. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in cleanroom ceilings.
Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). Approval is limited for use in cleanroom ceilings manufactured by Shin Sung
Engineering Co. Ltd. The Model YB28-III is a two piece style. The reducer is welded to the flexible hose and nipple is connected to the flexible
hose using a nut.
Flexible sprinkler hose with threaded end fittings are for use in ducts. The flexible hoses are to be installed
according to the manufacturer’s directives. All of the models listed below are 1 in. nominal dia. flexible metal sprinkler
hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in ducts only. Unless
indicated, the hoses have a rated working pressure of 175 psi (1205 kPa).
Dektronic Enterprise Co Ltd, 8F, No. 155, Sec. 1, Jung Shan Road, Yung He City, Taipei, Hsien Taiwan ROC 83113
1⁄ 2 1.9 5.9
IL001
(0.6) (1.8)
1⁄ 2 3.9 11.5
IL001
(1.2) (3.5)
1⁄ 2 6.6 20.1
IL001
(2.0) (6.1)
The 1 in. nominal diameter flexible sprinkler hose Model IL001 is Approved for providing a connection to automatic sprinkler protection to
the interior of Fiberglass Reinforced Plastic (FRP) ducts and is not FM Approved for use in other applications. Approval is limited to using
GS27 resin as the bonding agent between the bottom mounting block and the FRP duct.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-69
1⁄ 2 1.9 5.9
IL001
(0.6) (1.8)
1⁄ 2 3.9 11.5
IL001
(1.2) (3.5)
1⁄ 2 6.6 20.1
IL001
(2.0) (6.1)
The 1 in. nominal diameter flexible sprinkler hose Model IL001 is Approved for providing a connection to automatic sprinkler protection to
the interior of steel ducts and is not FM Approved for use in other applications. Approval is limited to using GS27 resin as the bonding agent
between the bottom mounting block and the steel duct.
1⁄ 2 1.9 5.9
IL001
(0.6) (1.8)
1⁄ 2 3.9 11.5
IL001
(1.2) (3.5)
1⁄ 2 6.6 20.1
IL001
(2.0) (6.1)
The 1 in. nominal diameter flexible sprinkler hose Model IL001 is Approved for providing a connection to automatic sprinkler protection to
the interior of polypropylene plastic ducts and is not FM Approved for use in other applications. Approval is limited to using GS27 resin as
the bonding agent between the bottom mounting block and the polypropylene plastic duct.
1⁄ 2 2.5 8.7
EFDC-01A
(750) (2.6)
1⁄ 2 3.9 16.7
EFDC-02A
(1200) (5.1)
1⁄ 2 5.6 22.5
EFDC-03A
(1700) (6.9)
1⁄ 2 7.2 28.3
EFDC-04A
(2200) (8.6)
1⁄ 2 8.5 34.5
EFDC-05A
(2600) (10.5)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in circular
flange metal ducts.
1⁄ 2 2.5 8.7
EFDS-01A
(750) (2.6)
1⁄ 2 3.9 16.7
EFDS-02A
(1200) (5.1)
1⁄ 2 5.6 22.5
EFDS-03A
(1700) (6.9)
1⁄ 2 7.2 28.3
EFDS-04A
(2200) (8.6)
1⁄ 2 8.5 34.5
EFDS-05A
(2600) (10.5)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in square flange
metal ducts.
1⁄ 2 2 11
1024
(0.6) (3.6)
1⁄ 2 3 19
1036
(.9) (5.8)
FM Approvals
September 2007 — Approval Guide
1-70 Automatic Sprinkler Systems
1⁄ 2 4 21
1048
(1.2) (6.4)
Approval of the Model 1000 series is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP)
ducts and is not FM Approved for use in ducts of other materials or for other applications.
Approval is limited to using Derakane 510 resin as the bonding agent between the bottom mounting block and the FRP duct.
1⁄ 2 2 11
1124
(0.6) (3.6)
1⁄ 2 3 19
1136
(0.6) (5.8)
1⁄ 2 4 21
1148
(1.2) (6.4)
Approval of the Model 1100 series is limited to use in providing sprinkler protection to the interior of metal ducts and is not FM Approved
for use in ducts of other materials or for other applications.
1⁄ 2 2.5 11
1224
(0.7) (3.6)
1⁄ 2 3.5 19
1236
(1.1) (5.8)
1⁄ 2 4.5 21
1248
(1.4) (6.4)
Approval of the Model 1200 series is limited to use in providing sprinkler protection to the interior of polypropylene plastic ducts and is not
FM Approved for use in ducts of other materials or for other applications.
1⁄ 2 2.5 11
1324
(0.7) (3.6)
1⁄ 2 3.5 19
1336
(1.1) (5.8)
1⁄ 2 4.5 21
1348
(1.4) (6.4)
Approval of the Model 1300 series is limited to use in providing sprinkler protection to the interior of polyvinyl chloride (PVC) plastic ducts
and is not FM Approved for use in ducts of other materials or for other applications.
1⁄ 2 2.5 8.7
KFB-SPDC-01A
(750) (2.6)
1⁄ 2 3.9 16.7
KFB-SPDC-02A
(1200) (5.1)
1⁄ 2 5.6 22.5
KFB-SPDC-03A
(1700) (6.9)
1⁄ 2 7.2 28.3
KFB-SPDC-04A
(2200) (8.6)
1⁄ 2 8.5 34.5
KFB-SPDC-05A
(2600) (10.5)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in circular
flange metal ducts.
1⁄ 2 2.5 8.7
KFB-SPDS-01A
(750) (2.6)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-71
1⁄ 2 3.9 16.7
KFB-SPDS-02A
(1200) (5.1)
1⁄ 2 5.6 22.5
KFB-SPDS-03A
(1700) (6.9)
1⁄ 2 7.2 28.3
KFB-SPDS-04A
(2200) (8.6)
1⁄ 2 8.5 34.5
KFB-SPDS-05A
(2600) (10.5)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in ducts. Approval is limited for use in square flange
metal ducts.
Panew Company Limited, 8F-5, No. 2 Jianba Road, Chung Ho, Taipei Hsien, Taiwan ROC
1⁄ 2 2 5.5
P-9900
(0.6) (1.7)
1⁄ 2 4 7.8
P-9900
(1.2) (2.4)
1⁄ 2 6 11.1
P-9900
(1.8) (3.4)
1⁄ 2 7 12.6
P-9900
(2.1) (3.7)
Model P-9900 Approval is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts,
Polypropylene plastic ducts and metal ducts and is not FM Approved for use in ducts of other materials or for other applications.
Paradise Industry Co Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City Kyunggi-Do, Korea (420-120)
1⁄ 2 3.3 13.7
SFT-N
(1.0 ) (4.2 )
1⁄ 2 8.5 18.5
SFT-N
(2.6 ) (5.6 )
1⁄ 2 3.3 13.7
SFT-O
(1.0 ) (4.2 )
1⁄ 2 8.5 18.5
SFT-O
(2.6 ) (5.6 )
1 in. nominal dia. flexible sprinkler hose with fittings for providing a connection to automatic sprinklers in ducts. Approval is in the range of
3.3 ft (1000 mm) to 8.5 ft (2600 mm).
Seung Jin Industry Co Ltd, 612, 5 Bar Shi-Wha Industrial Complex, 685-11 Sunggog-Dong, Ansan-Si
Kyunggi-Do, 429-450 Korea
1⁄ 2 2.6 8.3
DUXX-YYYY
(0.8) (2.6)
1⁄ 2 8.5 31.8
DUXX-YYYY
(2.6) (9.7)
3⁄ 4 2.6 7.6
DUXX-YYYY
(0.8) (2.3)
3⁄ 4 8.5 31.4
DUXX-YYYY
(2.6) (9.6)
DU: Duct
XX: Product length. 08 through 26 (08 is a 0.8 m (2.6 ft) long hose assembly and 26 is a 2.6 m (8.5 ft) long hose assembly.
YYYY: Year and month manufactured.
Approval of these 1 in. nominal dia. flexible metal sprinkler hose model is limited to use in providing sprinkler protection to the interior of
Fiberglass Reinforced Plastic (FRP) ducts and is not Approved for use in ducts of other materials or for other applications.
FM Approvals
September 2007 — Approval Guide
1-72 Automatic Sprinkler Systems
Shanghai Genius Technical Corp Ltd, No. 7166 Zhong Chun Road, Qibao Town, Minhang District, Shanghai,
P.R. China 201101
1⁄ 2 2 5.5
P-9900
(0.6) (1.7)
1⁄ 2 4 7.8
P-9900
(1.2) (2.4)
1⁄ 2 6 11.1
P-9900
(1.8) (3.4)
1⁄ 2 7 12.6
P-9900
(2.1) (3.7)
Model P-9900. Approval is limited to use in providing sprinkler protection to the interior of Fiberglass Reinforced Plastic (FRP) ducts,
Polypropylene plastic ducts and metal ducts and is not FM Approved for use in ducts of other materials or for other applications.
Yong Won E.N.C. Ltd, 116-1 Sedgu-Ri, Kwangjeuk-Myun, Yangju-Gun Keungki-Do, Korea
1⁄ 2 3.5 5.5
YB28-D-B
(1.07) (1.6)
1⁄ 2 8.4 15.2
YB28-D-B
(2.57) (4.6)
3⁄ 4 3.5 5.7
YB28-D-B
(1.07) (1.7)
3⁄ 4 8.4 17.0
YB28-D-B
(2.57) (5.2)
1⁄ 2 3.5 5.5
YB28-D-F
(1.07) (1.6)
1⁄ 2 8.4 15.2
YB28-D-F
(2.57) (4.6)
3⁄ 4 3.5 5.7
YB28-D-F
(1.07) (1.7)
3⁄ 4 8.4 17.0
YB28-D-F
(2.57) (5.2)
Model YB28-D-BP 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in ducts. Available in
a range from (3.5 to 8.4 feet) 1075 mm to 2575 mm.
Approval is limited to interior sprinkler protection of Polypropylene Plastic ducts of 10 to 60 in. (25.4 to 152.4 cm) diameter and is not
Approved for use in ducts of other materials or for other applications. The Model YB28-D-BP is a one piece hose with nuts on each end. A
threaded nipple is connected to the nut at the inlet of the hose.
Approval is limited to interior sprinkler protection of Fiberglass Reinforced Plastic (FRP) ducts of 10 to 60 in. (25.4 to 152.4 cm) diameter
and is not Approved for use in ducts of other materials or for other applications.
Approval is limited to using FRP bond made by Korea Chemical Company as the bonding agent between the bottom mounting block and
the FRP duct.
Flexible sprinkler hose with threaded end fittings are for use in commercial suspended ceilings. The flexible hoses
are to be installed according to the manufacturer’s directives. Unless indicated, the hoses have a rated working
pressure of 175 psi (1205 kPa).
1⁄ 2 2 18.9
AFBW24H
(0.6) (5.7)
1⁄ 2 2.6 26.5
AFBW31H
(0.78) (8.1)
1⁄ 2 3 31.9
AFBW36H
(0.91) (9.7)
1⁄ 2 4 44.3
AFBW48H
(1.2) (13.5)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-73
1⁄ 2 5 55.5
AFBW60H
(1.5) (16.9)
1⁄ 2 6 61.5
AFBW72H
(1.8) (18.7)
1⁄ 2 7 59.9
AFBW84H
(2.1) (18.3)
1⁄ 2 2 18.9
AFB24H
(0.6) (5.7)
1⁄ 2 2.6 26.5
AFB31H
(0.78) (8.1)
1⁄ 2 3 31.9
AFB36H
(0.91) (9.7)
1⁄ 2 4 44.3
AFB48H
(1.2) (13.5)
1⁄ 2 5 55.5
AFB60H
(1.5) (16.9)
1⁄ 2 6 61.5
AFB72H
(1.8) (18.7)
1⁄ 2 7 59.9
AFB84H
(2.1) (18.3)
3⁄ 4 2 18.2
AFBW24T
(0.6) (5.5)
3⁄ 4 2.6 26.0
AFBW31T
(0.78) (7.9)
3⁄ 4 3 31.6
AFBW36T
(0.91) (9.6)
3⁄ 4 4 40.3
AFBW48T
(1.2) (12.3)
3⁄ 4 5 54.1
AFBW60T
(1.5) (16.5)
3⁄ 4 6 60.1
AFBW72T
(1.8) (18.3)
3⁄ 4 7 59.5
AFBW84T
(2.1) (18.1)
3⁄ 4 2 18.2
AFB24T
(0.6) (5.5)
3⁄ 4 2.6 26.0
AFB31T
(0.78) (7.9)
3⁄ 4 3 31.6
AFB36T
(0.91) (9.6)
3⁄ 4 4 40.3
AFB48T
(1.2) (12.3)
3⁄ 4 5 54.1
AFB60T
(1.5) (16.5)
3⁄ 4 6 60.1
AFB72T
(1.8) (18.3)
3⁄ 4 7 59.5
AFB84T
(2.1) (18.1)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is
limited for use in commercial suspended ceilings with a bracket system manufactured by AF-USA LLC.
Marking Description
AF Manufacturer’s initials
B Braid
W Welded: These model hoses have a weld on the outlet end, securing the outlet reducer to the
hose. A slip nut connects the flexible hose to the inlet nipple.
FM Approvals
September 2007 — Approval Guide
1-74 Automatic Sprinkler Systems
Marking Description
24 24 in.
31 31 in.
36 36 in.
48 48 in.
60 60 in.
72 72 in.
84 84 in.
Dong-A Flexible Metal Tubes Co Ltd, 5th Floor, Yuchang B/D, #108-6, Yangjae Dong, Seocho-Gu, Seoul,
Korea (137-130)
1⁄ 2 2.5 14.6
DA-SPB-01A-NPT
(0.78) (4.5)
1⁄ 2 4 28.0
DA-SPB-02A-NPT
(1.2) (8.5)
1⁄ 2 5 50.2
DA-SPB-03A-NPT
(1.5) (15.3)
1⁄ 2 6.2 53.5
DA-SPB-04A-NPT
(1.8) (16.3)
1⁄ 2 8.3 67.1
DA-SPB-05A-NPT
(2.5) (20.4)
1⁄ 2 2.5 14.6
DA-SPNB-01A-NPT
(0.78) (4.5)
1⁄ 2 4 28.0
DA-SPNB-02A-NPT
(1.2) (8.5)
1⁄ 2 5 50.2
DA-SPNB-03A-NPT
(1.5) (15.3)
1⁄ 2 6.2 53.5
DA-SPNB-04A-NPT
(1.8) (16.3)
1⁄ 2 8.3 67.1
DA-SPNB-05A-NPT
(2.5) (20.4)
1⁄ 2 2.5 14.6
DA-SPWB-01A-NPT
(0.78) (4.5)
1⁄ 2 4 28.0
DA-SPWB-02A-NPT
(1.2) (8.5)
1⁄ 2 5 50.2
DA-SPWB-03A-NPT
(1.5) (15.3)
1⁄ 2 6.2 53.5
DA-SPWB-04A-NPT
(1.8) (16.3)
1⁄ 2 8.3 67.1
DA-SPWB-05A-NPT
(2.5) (20.4)
3⁄ 4 2.5 20.7
DA-SPB-01B-NPT
(0.78) (6.3)
3⁄ 4 4 32.1
DA-SPB-02B-NPT
(1.2) (9.8)
3⁄ 4 5 48.4
DA-SPB-03B-NPT
(1.5) (14.7)
3⁄ 4 6.2 56.6
DA-SPB-04B-NPT
(1.8) (17.2)
3⁄ 4 8.3 77.1
DA-SPB-05B-NPT
(2.5) (23.5)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-75
3⁄ 4 2.5 20.7
DA-SPNB-01B-NPT
(0.78) (6.3)
3⁄ 4 4 32.1
DA-SPNB-02B-NPT
(1.2) (9.8)
3⁄ 4 5 48.4
DA-SPNB-03B-NPT
(1.5) (14.7)
3⁄ 4 6.2 56.6
DA-SPNB-04B-NPT
(1.8) (17.2)
3⁄ 4 8.3 77.1
DA-SPNB-05B-NPT
(2.5) (23.5)
3⁄ 4 2.5 20.7
DA-SPWB-01B-NPT
(0.78) (6.3)
3⁄ 4 4 32.1
DA-SPWB-02B-NPT
(1.2) (9.8)
3⁄ 4 5 48.4
DA-SPWB-03B-NPT
(1.5) (14.7)
3⁄ 4 6.2 56.6
DA-SPWB-04B-NPT
(1.8) (17.2)
3⁄ 4 8.3 77.1
DA-SPWB-05B-NPT
(2.5) (23.5)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is
limited for use in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system
manufactured by Dong-A Flexible Metal Tubes Co., Ltd.
Marking Description
DA Manufacturer’s initials
SPB The hose is threaded to a nipple on the inlet end and threaded to a reducer at the outlet.
SPNB The hose is threaded to a nipple on the inlet end and the reducer is brazed to the flexible
hose at the outlet
SPWB The hose is brazed to a nipple on the inlet end and brazed to a reducer at the outlet
1⁄ 2 2.5 8.7
EFB231
(750) (2.6)
1⁄ 2 3.9 16.7
EFB248
(1200) (5.1)
1⁄ 2 5.6 22.5
EFB260
(1700) (6.9)
1⁄ 2 7.2 28.3
EFB285
(2200) (8.6)
1⁄ 2 8.5 34.5
EFB2102
(2600) (10.5)
3⁄ 4 2.5 7.2
EFB331
(750) (2.2)
FM Approvals
September 2007 — Approval Guide
1-76 Automatic Sprinkler Systems
3⁄ 4 3.9 12.7
EFB348
(1200) (3.9)
3⁄ 4 5.6 18.8
EFB360
(1700) (5.7)
3⁄ 4 7.2 22.9
EFB385
(2200) (6.9)
3⁄ 4 8.5 33.4
EFB3102
(2600) (10.2)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is
limited for use in commercial suspended ceilings with a bracket system manufactured by Easyflex Inc.
1⁄ 2 2 3.5
2024
(0.6) (1.1)
1⁄ 2 3 4.8
2036
(0.9) (1.5)
1⁄ 2 4 6.8
2048
(1.2) (2.1)
1⁄ 2 5 8.5
2060
(1.5) (2.6)
1⁄ 2 6 8.9
2072
(1.8) (2.7)
This is a standard flexible hose with a pressure rating of 175 psi (1205 kPa). Approval on these models of flexible metal sprinkler hose is
limited for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings, with a ceiling bracket system manufactured
by FlexHead Industries Inc. The FlexHead brackets are identified as follows:
Part Numbers:
• SP-24-BKT (1)
• SP-24-BKT (2)
• MP-24-BKT
• MP-24-BKT-2
• SP-06TZ-BKT
• AD-16-BKT-2
• AD-24-BKT-2
• UH-2
The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3⁄8 in. nominal size threaded rod is for attachment to support these hose
models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.
1⁄ 2 2 11
2024H
(0.6) (3.6)
1⁄ 2 3 19
2036H
(0.9) (5.8)
1⁄ 2 4 21
2048H
(1.2) (6.4)
1⁄ 2 5 24
2060H
(1.5) (7.3)
1⁄ 2 6 27.5
2072H
(1.8) (8.4)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-77
The ‘‘H’’ indicates a high pressure of 300 psi (2070 kPa). Approval of this flexible metal sprinkler hose is limited for use in commercial
suspended ceilings, (T-Bar Grid) and Sheetrock suspended ceilings with a ceiling bracket system manufactured by FlexHead Industries Inc.
The FlexHead brackets are identified as follows:
Part Numbers:
• SP-24-BKT (1)
• SP-24-BKT (2)
• MP-24-BKT
• MP-24-BKT-2
• SP-06TZ-BKT
• AD-16-BKT-2
• AD-24-BKT-2
• UH-2
The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3⁄8 in. nominal size threaded rod is for attachment to support these hose
models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.
1⁄ 2 2 2.9
2024M
(0.6) (0.9)
1⁄ 2 3 4.4
2036M
(0.9) (1.3)
1⁄ 2 4 6.7
2048M
(1.2) (2.0)
1⁄ 2 5 10.4
2060M
(1.5) (3.4)
1⁄ 2 6 11.4
2072M
(1.8) (3.5)
The ‘‘M’’ indicates a mechanical flare type connection with a pressure rating of 300 psi (2070 kPa). Approval of this flexible metal sprinkler
hose is limited for use in commercial suspended ceilings, with a ceiling bracket system manufactured by FlexHead Industries Inc. The
FlexHead brackets are identified as follows:
Part Numbers:
• SP-24-BKT (1)
• SP-24-BKT (2)
• MP-24-BKT
• MP-24-BKT-2
• SP-06TZ-BKT
• AD-16-BKT-2
• AD-24-BKT-2
• UH-2
The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3⁄8 in. nominal size threaded rod is for attachment to support these hose
models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.
1⁄ 2 2 5.5
2024E
(0.6) (1.7)
1⁄ 2 3 6.8
2036E
(0.9) (2.1)
1⁄ 2 4 8.8
2048E
(1.2) (2.7)
1⁄ 2 5 10.5
2060E
(1.5) (3.2)
1⁄ 2 6 10.9
2072E
(1.8) (3.3)
The ‘‘E’’ indicates an elbow welded on the end of the hose. Approval of these models of flexible metal sprinkler hose incorporate a stainless
steel elbow welded on the outlet end of the hose and are limited for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock
suspended ceilings, with a ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows:
FM Approvals
September 2007 — Approval Guide
1-78 Automatic Sprinkler Systems
Part Numbers:
• SP-24-BKT (1)
• SP-24-BKT (2)
• MP-24-BKT
• MP-24-BKT-2
• SP-06TZ-BKT
• AD-16-BKT-2
• AD-24-BKT-2
• UH-2
The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3⁄8 in. nominal size threaded rod is for attachment to support these hose
models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.
1⁄ 2 2 5.5
2024E-LP
(0.6) (1.7)
1⁄ 2 3 6.8
2036E-LP
(0.9) (2.1)
1⁄ 2 4 8.8
2048E-LP
(1.2) (2.7)
1⁄ 2 5 10.5
2060E-LP
(1.5) (3.2)
1⁄ 2 6 10.9
2072E-LP
(1.8) (3.3)
3⁄ 4 2 7.8
2024E-LP 75
(0.6) (2.4)
3⁄ 4 3 8.1
2036E-LP 75
(0.9) (2.5)
3⁄ 4 4 17.9
2048E-LP 75
(1.2) (5.4)
3⁄ 4 5 19.9
2060E-LP 75
(1.5) (6.1)
3⁄ 4 6 24.3
2072E-LP 75
(1.8) (7.4)
The ‘‘E-LP’’ indicates a ‘‘low profile’’ elbow unit welded on the end of the hose. Approval of these models of flexible metal sprinkler hose
incorporates a stainless steel elbow welded on the outlet end of the hose and with unistrut channel and pipe clamp is limited to securing these
models to the building structure. These models are for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings
with very limited room between floors.
1⁄ 2 3 10.4
2036-E-PTFE
(0.9) (3.4)
Model 2036-E-PTFE. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in commercial suspended
ceilings (T-Bar Grid) and Sheetrock suspended ceilings. This assembly utilizes a stainless steel braid over a nominal 1 in. I.D. PTFE
(polytetrafluoroethylene) convoluted hose. The ‘‘E’’ indicates an elbow attached on the end of the hose. This hose model is for use with the
Model UH-2 (Universal Hub) FlexHead clamp with a maximum 2 ft (610 mm) 3⁄8 in. nominal size threaded rod.
3⁄ 4 2 7.8
2024 75
(0.6) (2.4)
3⁄ 4 3 8.1
2036 75
(0.9) (2.5)
3⁄ 4 4 17.9
2048 75
(1.2) (5.4)
3⁄ 4 5 19.9
2060 75
(1.5) (6.1)
3⁄ 4 6 24.3
2072 75
(1.8) (7.4)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-79
This is a standard hose with a pressure rating of 175 psi (1205 kPa). The ‘‘75’’ indicates a 3⁄4 inch NPT outlet. Approval on these models
of flexible metal sprinkler hose is limited for use in commercial suspended ceilings (T-Bar Grid) and Sheetrock suspended ceilings, with a
ceiling bracket system manufactured by FlexHead Industries Inc. The FlexHead brackets are identified as follows:
Part Numbers:
• SP-24-BKT (1)
• SP-24-BKT (2)
• MP-24-BKT
• MP-24-BKT-2
• SP-06TZ-BKT
• AD-16-BKT-2
• AD-24-BKT-2
• UH-2
The FlexHead Clamp Model UH-2 with a maximum 2 ft (610 mm) 3⁄8 in. nominal size threaded rod is for attachment to support these hose
models. The Model UH-2 FlexHead clamp is manufactured by FlexHead Industries Inc.
1⁄ 2 2.0 6.8
KFB224
(610) (2.1)
KFB231 1⁄ 2 2.6 8.7
(790) (2.6)
1⁄ 2 3.0 11.5
KFB236
(915) (3.5)
KFB248 1⁄ 2 4.0 16.7
(1220) (5.1)
1⁄ 2 5.0 20.6
KFB260
(1525) (6.3)
KFB267 1⁄ 2 5.6 22.5
(1700) (6.9)
1⁄ 2 6.0 24.0
KFB272
(1830) (7.3)
KFB287 1⁄ 2 7.2 28.3
(2200) (8.6)
KFB2102 1⁄ 2 8.5 34.5
(2600) (10.5)
3⁄ 4 2.0 4.7
KFB324
(610) (1.4)
KFB331 3⁄ 4 2.6 7.2
(790) (2.2)
3⁄ 4 3.0 10.6
KFB336
(915) (3.2)
KFB348 3⁄ 4 4.0 12.7
(1220) (3.9)
3⁄ 4 5.0 17.0
KFB360
(1525) (5.2)
KFB367 3⁄ 4 5.6 18.8
(1700) (5.7)
3⁄ 4 6.0 19.8
KFB372
(1830) (6.0)
3⁄ 4 7.2 22.9
KFB387
(2200) (6.9)
3⁄ 4 8.5 33.4
KFB3102
(2600) (10.2)
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is
limited for use in commercial suspended ceilings with the following bracket systems manufactured by Kofulso Co., Ltd.
FM Approvals
September 2007 — Approval Guide
1-80 Automatic Sprinkler Systems
1⁄ 2 2.0 18.0
KFBL224
(610) (5.5)
1⁄ 2 2.6 20.6
KFBL231
(790) (6.3)
1⁄ 2 3.0 22.3
KFBL236
(915) (6.8)
1⁄ 2 4.0 26.7
KFBL248
(1220) (8.1)
1⁄ 2 5.0 20.6
KFBL260
(1525) (6.3)
1⁄ 2 5.6 32.9
KFBL267
(1700) (10.0)
1⁄ 2 6.0 26.3
KFBL272
(1830) (8.0)
1⁄ 2 7.2 33.6
KFBL287
(2200) (10.2)
1⁄ 2 8.5 41.0
KFBL2102
(2600) (12.5)
2.0 16.2
KFBL324 3/4
(610) (4.9)
2.6 19.4
KFBL331 3/4
(790) (5.9)
3.0 21.6
KFBL336 3/4
(915) (6.6)
4.0 27.1
KFBL348 3/4
(1220) (8.3)
5.0 22.5
KFBL360 3/4
(1525) (6.8)
5.6 33.8
KFBL367 3/4
(1700) (10.3)
6.0 26.1
KFBL372 3/4
(1830) (7.9)
7.2 33.3
KFBL387 3/4
(2200) (10.1)
8.5 41.7
KFBL3102 3/4
(2600) (12.7)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-81
Model Description
B: Braided hose
L: Elbow
B: Braided hose
1⁄ 2 2.5 8.7
KFB-SP-01A
(750) (2.6)
1⁄ 2 3.9 16.7
KFB-SP-02A
(1200) (5.1)
1⁄ 2 5.6 22.5
KFB-SP-03A
(1700) (6.9)
1⁄ 2 7.2 28.3
KFB-SP-04A
(2200) (8.6)
1⁄ 2 8.5 34.5
KFB-SP-05A
(2600) (10.5)
3⁄ 4 2.5 7.2
KFB-SP-01AB
(750) (2.2)
3⁄ 4 3.9 12.7
KFB-SP-02AB
(1200) (3.9)
3⁄ 4 5.6 18.8
KFB-SP-03AB
(1700) (5.7)
3⁄ 4 7.2 22.9
KFB-SP-04AB
(2200) (6.9)
3⁄ 4 8.5 33.4
KFB-SP-05AB
(2600) (10.2)
Model Description
KFB-SP-01A KF: Kofulso (Manufacturer’s initials)
or
KFB-SP-01AB
B: Braided hose
SP:
Flexible Hose Lengths:
01 in. = 2.5 ft (750 mm)
02 in. = 3.9 ft (1200 mm)
03 in. = 5.6 ft (1700 mm)
04 in. = 7.2 ft (2200 mm)
05 in. = 8.5 ft (2600 mm)
A: 1⁄2 in. NPT
AB: 3⁄4 in. NPT
Panew Company Limited, 8F-5, No. 2 Jianba Road, Chung Ho, Taipei Hsien, Taiwan ROC
1⁄ 2 2 10.4
P-9100
(0.61) (3.2)
1⁄ 2 4 14.5
P-9100
(1.22) (4.4)
1⁄ 2 6 18.6
P-9100
(1.83) (5.7)
FM Approvals
September 2007 — Approval Guide
1-82 Automatic Sprinkler Systems
1⁄ 2 7 20.4
P-9100
(2.13) (6.2)
Model P-9100. 1 in. nominal dia. Two piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter is threaded to the flexible hose. Approval is limited for use in commercial suspended
ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.
1⁄ 2 2 6.5
P-9120
(0.6) (1.9)
1⁄ 2 4 15.9
P-9120
(1.2) (4.8)
1⁄ 2 6 23.1
P-9120
(1.8) (7.1)
1⁄ 2 7 26.2
P-9120
(2.1) (8.0)
Model P-9120. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial
suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.
1⁄ 2 2 6.5
P-9200
(0.6) (1.9)
1⁄ 2 4 15.9
P-9200
(1.2) (4.8)
1⁄ 2 6 23.1
P-9200
(1.8) (7.1)
1⁄ 2 7 26.2
P-9200
(2.1) (8.0)
Model P-9200. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial
suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.
1⁄ 2 2 6.5
P-9210
(0.6) (1.9)
1⁄ 2 4 15.9
P-9210
(1.2) (4.8)
1⁄ 2 6 23.1
P-9210
(1.8) (7.1)
1⁄ 2 7 26.2
P-9210
(2.1) (8.0)
Model P-9210. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use
in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.
1⁄ 2 2 6.5
P-9211
(0.6) (1.9)
1⁄ 2 4 15.9
P-9211
(1.2) (4.8)
1⁄ 2 6 23.1
P-9211
(1.8) (7.1)
1⁄ 2 7 26.2
P-9211
(2.1) (8.0)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-83
Model P-9211. 1 in. nominal dia. One piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use
in commercial suspended ceilings with a ceiling sprinkler system manufactured by Panew Company Limited.
Paradise Industry Co Ltd, 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon-City Kyunggi-Do, Korea (420-120)
Model SFT-A. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings.
Approval is in the range of 3.3 ft (1000 mm) to 8.4 ft (2550 mm), and is limited for use in commercial suspended ceilings.
Model SFT-C. 1 in. nominal dia. flexible sprinkler hose for providing a connection to automatic sprinklers in commercial suspended ceilings.
Approval is in the range of 3.3 ft (1000 mm) to 8.1 ft (2470 mm), and is limited for use in commercial suspended ceilings.
1⁄ 2 3.3 6.1
SFT-A
(1.0) (1.8)
1⁄ 2 8.4 14.9
SFT-A
(2.55) (4.5)
1⁄ 2 3.3 5.9
SFT-C
(1.0) (1.8)
1⁄ 2 8.1 14.6
SFT-C
(2.47) (4.5)
Approval is limited for use in commercial suspended ceilings, with a ceiling bracket system manufactured by Paradise Industry Co., Ltd.
Rapidrop Limited, Rutland Business Park, Newark Road, Peterborough PE1 5WA, United Kingdom
FM Approvals
September 2007 — Approval Guide
1-84 Automatic Sprinkler Systems
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is
limited for use in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system
manufactured by Rapidrop Limited.
Marking Description
Rapidrop® Company Name & Trademark
SPB The hose is threaded to a nipple on the inlet end and threaded to a reducer at the outlet.
SPNB The hose is threaded to a nipple on the inlet end and the reducer is brazed to the flexible hose at the outlet
SPWB The hose is brazed to a nipple on the inlet end and brazed to a reducer at the outlet
01 Flexible Hose Lengths:
02 01 = 780 mm
03 02 = 1,220 mm
04 03 = 1,540 mm
05 04 = 1,880 mm
05 = 2,500 mm
A 1⁄ 2 in. NPT
B 3⁄ 4 in. NPT
Seung Jin Industry Co Ltd, 612, 5 Bar Shi-Wha Industrial Complex, 685-11 Sunggog-Dong, Ansan-Si
Kyunggi-Do, 429-450 Korea
1⁄ 2 2.6 8.3
CCBUXX-YYYY
(0.8) (2.6)
1⁄ 2 8.5 31.8
CCBUXX-YYYY
(2.6) (9.7)
3⁄ 4 2.6 7.6
CCBUXX-YYYY
(0.8) (2.3)
3⁄ 4 8.5 31.4
CCBUXX-YYYY
(2.6) (9.6)
1⁄ 2 2.6 8.3
CCXX-YYYY
(0.8) (2.6)
1⁄ 2 8.5 31.8
CCXX-YYYY
(2.6) (9.7)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-85
3⁄ 4 2.6 7.6
CCXX-YYYY
(0.8) (2.3)
3⁄ 4 8.5 31.4
CCXX-YYYY
(2.6) (9.6)
Approval of these 1 in. nominal dia. flexible metal sprinkler hose models is limited to use in providing sprinkler protection to commercial
suspended ceilings. Approval is limited for use in commercial suspended ceilings with a ceiling sprinkler system manufactured by Seung Jin
Industry Co., Ltd.
Shanghai Genius Technical Corp Ltd, No. 7166 Zhong Chun Road, Qibao Town, Minhang District, Shanghai,
P.R. China 201101
1⁄ 2 2 10.4
P-9100
(0.61) (3.2)
1⁄ 2 4 14.5
P-9100
(1.22) (4.4)
1⁄ 2 6 18.6
P-9100
(1.83) (5.7)
1⁄ 2 7 20.4
P-9100
(2.13) (6.2)
Model P-9100. 1 in. nominal dia. two piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter is threaded to the flexible hose. Approval is limited for use in commercial suspended
ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.
1⁄ 2 2 6.5
P-9120
(0.6) (1.9)
1⁄ 2 4 15.9
P-9120
(1.2) (4.8)
1⁄ 2 6 23.1
P-9120
(1.8) (7.1)
1⁄ 2 7 26.2
P-9120
(2.1) (8.0)
Model P-9120. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial
suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.
1⁄ 2 2 6.5
P-9200
(0.6) (1.9)
1⁄ 2 4 15.9
P-9200
(1.2) (4.8)
1⁄ 2 6 23.1
P-9200
(1.8) (7.1)
1⁄ 2 7 26.2
P-9200
(2.1) (8.0)
Model P-9200. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and nipple is welded to the flexible hose. Approval is limited for use in commercial
suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.
1⁄ 2 2 6.5
P-9210
(0.6) (1.9)
FM Approvals
September 2007 — Approval Guide
1-86 Automatic Sprinkler Systems
1⁄ 2 4 15.9
P-9210
(1.2) (4.8)
1⁄ 2 6 23.1
P-9210
(1.8) (7.1)
1⁄ 2 7 26.2
P-9210
(2.1) (8.0)
Model P-9210. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use
in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.
1⁄ 2 2 6.5
P-9211
(0.6) (1.9)
1⁄ 2 4 15.9
P-9211
(1.2) (4.8)
1⁄ 2 6 23.1
P-9211
(1.8) (7.1)
1⁄ 2 7 26.2
P-9211
(2.1) (8.0)
Model P-9211. 1 in. nominal dia. one piece style flexible metal sprinkler hose for providing a connection to automatic sprinklers in
commercial suspended ceilings. The sprinkler adapter and coupling/threaded fitting is welded to the flexible hose. Approval is limited for use
in commercial suspended ceilings with a ceiling sprinkler system manufactured by Shanghai Genius Technical Corp., Ltd.
Super Flex Enterprises Co Ltd, No. 16, Lane 561, Sec. 2, Kouji Rd., Taoyuan City, Taoyuan, Taiwan, R.O.C.
1⁄ 2 1.9 4.4
SP-A
(0.6) (1.4)
1⁄ 2 2.9 5.9
SP-A
(0.9) (1.9)
1⁄ 2 3.9 8.2
SP-A
(1.2) (2.6)
1⁄ 2 4.9 10.1
SP-A
(1.5) (3.2)
1⁄ 2 5.9 12.1
SP-A
(1.8) (3.7)
The model SP-A has a pressure rating of 230 psi (1585 kPa). 1 in. nominal diameter flexible metal sprinkler hose for providing a connection
to automatic sprinklers in commercial suspended ceilings. Approval is limited for use in commercial suspended ceilings with a bracket system
manufactured by Super Flex Enterprises Co., Ltd.
Virotec Rohrtechnik GmbH & Co KG, Meininger Weg 8, D-36132 Eiterfeld Germany
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-87
FM Approvals
September 2007 — Approval Guide
1-88 Automatic Sprinkler Systems
1 in. nominal dia. flexible metal hose for providing a connection to automatic sprinklers in commercial suspended ceilings. Approval is
limited for use in commercial suspended ceilings with a bracket system manufactured by Virotec Rohrtechnik GmbH & Co. KG.
Yong Won E.N.C. Ltd, 116-1 Seogu-Ri, Kwangjeuk-Myun, Yangju-Gun Keungki-Do, Korea
1⁄ 2 2.2 18.6
YB25
(0.7) (5.7)
1⁄ 2 8.2 91.5
YB25
(2.5) (27.8)
1⁄ 2 2.2 5.5
YB28
(0.7) (1.6)
1⁄ 2 8.4 15.2
YB28
(2.6) (4.6)
3⁄ 4 2.2 5.7
YB28
(0.7) (1.6)
3⁄ 4 8.4 17.0
YB28
(2.6) (5.2)
Model YB25 and YB28. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial
ceilings. Available in a range from 2.2 to 8.4 ft (700 mm to 2600 mm). Approval is limited for use in commercial suspended ceilings with a
ceiling bracket system manufactured by Yong Won E.N.C., Ltd. These models are available as a two piece style and three piece style.
The two piece style, the reducer is welded to the flexible hose and the nipple is connected to the flexible hose using a nut. The three piece
style, the reducer and nipple is threaded to the flexible hose.
1⁄ 2 3.5 5.5
YB28 A Type
(1.07) (1.6)
1⁄ 2 8.4 15.2
YB28 A Type
(2.57) (4.6)
3⁄ 4 3.5 5.7
YB28 A Type
(1.07) (1.7)
3⁄ 4 8.4 17.0
YB28 A Type
(2.57) (5.2)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-89
Model: YB28 A Type. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial
ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). This model is a one piece style as the reducer and nipple are welded
to the flexible hose. Approval is limited for use in a wood tile ceiling. The tile size is 11.5 × 11.5 × 1 in. (292 × 292 × 25 mm) with a ceiling
bracket system manufactured by Yong Won E.N.C., Ltd.
1⁄ 2 3.5 5.5
YB28 B Type
(1.07) (1.6)
1⁄ 2 8.4 15.2
YB28 B Type
(2.57) (4.6)
3⁄ 4 3.5 5.7
YB28 B Type
(1.07) (1.7)
3⁄ 4 8.4 17.0
YB28 B Type
(2.57) (5.2)
Model: YB28 B Type. 1 in. nominal dia. flexible metal sprinkler hose for providing a connection to automatic sprinklers in commercial
ceilings. Available in a range from 3.5 to 8.4 ft (1075 mm to 2575 mm). This model is a one piece style as the reducer and nipple are welded
to the flexible hose. Approval is limited for use in a S.G.P Ceiling (metal panel). The tile size is 11.75 × 11.75 × 15⁄8 in.
(300 × 300 × 41.3 mm), with a ceiling bracket system manufactured by Yong Won E.N.C., Ltd.
Adjustable fittings are designed for use on wet-pipe pendent-sprinkler drop-pipes. They allow the sprinkler
contractor, after the suspended ceiling has been installed, to adjust the drop to the desired length without cutting the
pipe.
Merit Manufacturing, Division of Anvil International Inc, 110 Corporate Dr, Suite 10, Portsmouth NH 03801
FM Approvals
September 2007 — Approval Guide
1-90 Automatic Sprinkler Systems
Virotec Rohrtechnik GmbH & Co KG, Meininger Weg 8, D-36132B 36132 Eiterfield, Germany
*These fittings are available with either a 3⁄8, 1⁄2 or 3⁄4 in. female NPT outlet sprinkler connection.
†These fittings are available with either a 3⁄8 or 1⁄2 in. female NPT outlet sprinkler connection.
*These fittings have a 300 psi (2070 kPa) rated working pressure.
These fittings are available with an optional escutcheon plate which can be positioned anywhere on the lower three inches of the fitting,
to fit up to a clearance hole in the suspended ceiling. The escutcheon plate is not designed for use with a specific sprinkler, and is not to be
fitted to any sprinkler body.
Model 80
1⁄2 in. NPT Outlet 4 through 36 inch lengths, in
2 inch increments
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-91
Model 81
3⁄4 in. NPT Outlet 4 through 36 inch lengths, in
2 inch increments
Model 82
1⁄ 2
or 3⁄4 in. NPT 4 through 36 inch lengths, in
both ends 2 inch increments
These fittings have a 300 psi (2070 kPa) rated working pressure.
The number of sprinklers carried for replacement should be governed by size of system, time needed to get
sprinklers from supplier and number of sprinklers likely to be opened by extraordinary conditions, such as flash fire.
Ordinarily, under average conditions, the number of emergency sprinklers should be:
6 for systems not over 300 sprinklers;
12 for systems of 300-1000 sprinklers;
24 for systems above 1000 sprinklers.
There should be spare heads of the various temperature ratings used and a wrench for each make of sprinkler.
Globe Pipe Hanger Products Inc, 14601 Industrial Pkwy, Cleveland OH 44135
Cabinet for six automatic sprinklers and sprinkler wrench.
A trim water pressure relief valve is a small valve designed to relieve pressure build-up in a sprinkler system or
in valve trim. It is open to a drain line. Unless otherwise specified, rated working pressure is 175 psi (1205 kPa) and
factory set pressure is 175 psi (1205 kPa).
1⁄ 2 175
Model M7000 –
(1205)
3⁄ 4 175
Model M7200 –
(1205)
An adjustable set pressure trim water pressure relief valve is a small valve designed to relieve pressure build-up
in a sprinkler system or in valve trim. It is open to a drain line. Unless otherwise specified, rated working pressure
is 175 psi (1205 kPa). The range of pressure setting is shown below.
Cla-Val Canada Corp, 4687 Christie Dr, Beamsville, Ontario L0R 1B4, Canada
Remarks:
FM Approvals
September 2007 — Approval Guide
1-92 Automatic Sprinkler Systems
Remarks:
300
Model 20 ¾, 1, 1-1⁄2, 2, 2-1⁄2 a, b, c
(2070)
Remarks:
Kunkle Valve, Div of Tyco Valves and Control, 1221 Katherine Street NW, Cullman AL 35055
3⁄ 4 300
Model 918BDD a, b, c
(2070)
300
Model 918BDE 1 a, b, c
(2070)
Remarks:
a. Valve supplied with Male NPT inlet connection and Female NPT outlet connection.
b. Adjustable relief pressure settings from 60 to 125, 126 to 175, or 176 to 250 psi (415 to 860, 870 to 1205, or 1215 to 1725 kPa).
c. Not suitable for discharging the full rated pump capacity.
Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446
Remarks:
Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the
system for each floor must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain
piping arrangement is required. The alarm testers listed below combine test and drain valves, a waterflow sight glass,
and a calibrated flow orifice in a single assembly to simplify the piping required for such arrangements.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-93
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Model A61. 1 and 11⁄4 NPT female threaded connections. 5.6 nominal K-factor. 175 psi (1205 kPa) rated working pressure.
National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE
Model A61. 1 and 11⁄4 in. NPT female threaded connections. 1⁄2 in. nominal orifice. 175 psi (1205 kPa) rated working pressure.
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Model A61. 1 and 11⁄4 NPT female threaded connections. 1⁄2 in. nominal orifice. 175 psi (1205 kPa) rated working pressure.
These devices are intended to replace a field fabricated assembly of components, which normally include a shutoff
valve, an orifice made from an open sprinkler head, a sight glass, a water collection wastecone, a vane-type
waterflow indicator and interconnecting pipe and fittings. They are usually mounted aboveground and indoors where
the water supply enters a building.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model CR commercial risers are intended for commercial applications in 11⁄2 through 8 in. nominal sizes. 300 psi (2070 kPa) rating.
Nominal Pipe Description
Size, in.
Model FCV floor control valves are intended for commercial applications in 11⁄2 through 8 in. nominal sizes. 300 psi (2070 kPa).
Nominal Pipe Description
Size, in.
FM Approvals
September 2007 — Approval Guide
1-94 Automatic Sprinkler Systems
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Model 513 is intended for commercial applications in 11⁄2 through 6 in. nominal sizes.
Nominal Pipe Description
Size, in.
Model 513R is intended for residential applications in 11⁄2 through 2 in. sizes.
Line testers are installed on sprinkler system branch lines between the last sprinkler and its fitting. Opening a side
outlet allows water to flow through the tester. This simplifies and reduces the cost of testing and flushing system
branch lines.
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Line Tester. Model A59. 1 in. female pipe thread.
Waterflow alarm valves (alarm check valves) are installed in either vertical or horizontal positions in wetpipe
sprinkler systems to sound a fire alarm gong when a flow of water from the system equals or exceeds that of a single
sprinkler. They are designed for use with hydraulic or electric gongs or both.
There are two designs, the differential type and the pilot valve type. The differential type has a rubber-faced
clapper with an annular groove in the seat; the pilot valve type has a metal-faced clapper with a pilot valve attached
to the clapper arm.
A retard chamber, which minimizes false alarms due to surges and fluctuations in water supply pressure, may be
supplied with the alarm valve. If a retard chamber is supplied, only the listed chamber for a specific manufacturer and
valve model shall be used. Alarm valves are FM Approved with specific trim, and no substitutes or omissions in part
or in full are allowed.
Alarms are tested by flowing water through the system test pipe. Pilot valves may be field-adjusted to assure alarm
reliability. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain
175
H-1 Flange Inlet × Flange Outlet 3, 4, 6 a, b, c
(1205)
175
H-2 Grooved Inlet × Grooved Outlet 3, 4 b, c
(1205)
175
H-3 Flange Inlet × Groove Outlet 3, 4, 6 a, b, c
(1205)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-95
Remarks:
Model E. 21⁄2 in. and 65 mm. Model E-1 retard chamber. All valves available with flanged connections. Standard size valves painted black
or gray. Metric size valves painted blue.
Model E. 21⁄2 in. and 65 mm. Model E-1 retard chamber and E3 trim package. All valves available with flanged connections. Standard size
valves painted black or gray. Metric size valves painted red (when supplied with ISO threads in valve trim). NOTE: The placement of a test
and drain valve (E3 trim option) in lieu of the 2’’ (50 mm) drain valve does not replace the need for an inspector’s test connection
at the most remote location of the sprinkler system. The test and drain valve shall not be used in lieu of the inspector’s test
connection for the testing of the entire wet piping system. The test and drain valve shall only be used to exercise the clapper and
check the mechanical alarm (water motor gong).
Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT United Kingdom
Max Rated
End Connections Nominal Valve
Product Description Working Pressure, Remarks
Inlet x Outlet Size, NPS
psi (kPa)
4 in. 290
Model C-1 Flange x Flange a, b
(100 mm) (2000)
4 in. 290
Model C-1 Flange x Grooved a, b
(100 mm) (2000)
4 in. 290
Model C-1 Grooved x Grooved a, b
(100 mm) (2000)
6, 8 in. 175
Model C-1 Flange x Flange a, b
(150, 200 mm) (1205)
6 in. 175
Model C-1 Flange x Grooved a, b
(150 mm) (1205)
4 in. 290
Model C1-H Flange x Flange a, c
(100 mm) (2000)
Remarks:
Max Rated
Product End Connections Nominal Valve
Working Pressure, Remarks
Description Inlet × Outlet Size, NPS
psi (kPa)
3, 4, 6, 8 in. 175
Model E Flange × Flange a
(80, 100, 150, 200 mm) (1205)
4 in. 290
Model C-1 Flange × Flange b, c
(100 mm) (2000)
4 in. 290
Model C-1 Flange × Grooved b, c
(100 mm) (2000)
4 in. 290
Model C-1 Grooved × Grooved b, c
(100 mm) (2000)
6, 8 in. 175
Model C-1 Flange × Flange b, c
(150, 200 mm) (1205)
6 in. 175
Model C-1 Flange × Grooved b, c
(150 mm) (1205)
3, 4 in. 290
Model C1-H Flange × Flange b, d
(80, 100 mm) (2000)
Remarks:
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Models B, G-2. 4, 6, 8 in. NPS.
Model J-1. 4, 6 in.
Model J-2. 4, 6 in. Cut grooved inlet and outlet.
Model H-1. 4, 6 in. Flanged inlet and outlet connections.
Model H-1. 8 in. Flanged inlet and outlet connections. Vertical installation only.
Model H-2. 4 in. Cut-grooved inlet and outlet connections.
FM Approvals
September 2007 — Approval Guide
1-96 Automatic Sprinkler Systems
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
a. Resilient seat.
b. With Model NAV retard chamber.
Paradise Industry Co Ltd, Plant 65-2 Chooneui-Dong, Woonmi-Ku, Bucheon City, Kyunggi-Do, Korea (420-120)
Model FAVB Water Flow Alarm Valves in sizes 100 and 150 mm NPS. Flanged inlet and outlet connections, ANSI or Korean Standard with
others available. Suitable for vertical installation. Supplied with retard chamber.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model E. 21⁄2, 3, 4, 6, 8 in.; 65, 100, 150, 200 mm. Model E-1 retard chamber. All valves available with flanged connections. 3, 4, 6, 8 in.
sizes also available with grooved outlets. Standard size valves painted black or gray. Metric size valves painted blue.
Model E. 21⁄2, 3, 4, 6, 8 in., and 65, 100, 150, 200 mm. Model E-1 retard chamber and E3 trim package. All valves available with flanged
connections. 3, 4, 6, 8 in. sizes also available with grooved outlets. Standard size valves painted black or gray. Metric size valves painted red
(when supplied with ISO threads in valve trim). NOTE: The placement of a test and drain valve (E3 Trim option) in lieu of the 2’’ (50mm)
drain valve does not replace the need for an inspector’s test connection at the most remote location of the sprinkler system. The
test and drain valve shall not be used in lieu of the inspector’s test connection for the testing of the entire wet piping system. The
test and drain valve shall only be used to exercise the clapper and check the mechanical alarm (water motor gong).
Model E3. 4, 6, and 8 in., and 100, 165, 200 mm Model E-1 retard chamber, and E3 trim package. Valves are available with cut grooved
inlet and outlet end connections, with a 300 psi (2070 kPa) maximum pressure rating. Standard size valves are painted black or red (when
supplied with ISO threads in valve trim). Valves are considered FM Approved for horizontal and vertical installations. NOTE: The placement
of a test and drain valve (E3 Trim option) in lieu of the 2’’ (50 mm) drain valve does not replace the need for an inspector’s test
connection at the most remote location of the sprinkler system. The test and drain valve shall not be used in lieu of the inspector’s
test connection for the testing of the entire wet piping system. The test and drain valve shall only be used to exercise the clapper
and check the mechanical alarm (water motor gong).
Shanghai Jindun Fire-Fighting Security Service Co Ltd, 65# Henqiao Road Fanrong Industrial Area Zhoupu,
Pudong, Shanghai, 201318, Peoples’ Republic of China
Remarks:
Tecnicas e Ingenieria de Proteccion SA (TIPSA), Apartado de Correos 293, 08720 Vilafranca del Penedes,
Barcelona Spain
80 12.5
P3 Flange × Flange DN 80 a, b, c
(3) (181)
100 12.5
P4 Flange × Flange DN 100 a, b, c
(4) (181)
Remarks:
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-97
Total Walther GmbH, Feuerschutz und Sicherheit, Waltherstrasse 51, 51069 Köln, Germany
Model NV 100/3. 100 mm.
Model NV 150/3. 150 mm.
Model NV 200/3. 200 mm.
The above are limited to installation at locations having constant water supply pressures.
Model NV 200. 8 in. NPS.
175
AV-1 Flange x Flange 4, 6, 8 in. a, b, c
(1205)
4, 6 in. 175
AV-1 Flange x Flange d, e
165 mm (1205)
21⁄2,
4, 6, 8 in. 175
AV-1 Flange x Groove a, b, c
76.1 mm, 165 mm (1205)
4, 6 in. 175
AV-1 Flange x Groove d, e
165 mm (1205)
21⁄2,
4, 6 in. 175
AV-1 Groove x Groove a, c
76.1 mm, 165 mm (1205)
4, 6 in. 175
AV-1 Groove x Groove d
165 mm (1205)
300
AV-1 Flange x Flange 4, 6, 8 in. a, b, c
(2070)
4, 6, 8 in. 300
AV-1 Flange x Flange a, d, e
165 mm (2070)
21⁄2,
4, 6, 8 in. 300
AV-1 Flange x Groove a, b, c
76.1 mm, 165 mm (2070)
4, 6, 8 in. 300
AV-1 Flange x Groove a, d, e
165 mm (2070)
2 1⁄ 2,
4, 6, 8 in. 300
AV-1 Groove x Groove a, c
76.1 mm, 165 mm (2070)
4, 6, 8 in. 300
AV-1 Groove x Groove a, d
165 mm (2070)
Remarks:
Tyco Fire Products Manufacturing Ltd, Stockport Trading Estate Yew St, Stockport Cheshire SK4 2JW,
United Kingdom
a. Resilient seat.
b. Limited to installation at locations having constant water supply pressures.
Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada
a. Resilient seat.
b. With Model E retard chamber.
c. Limited to installations with vertical risers only.
FM Approvals
September 2007 — Approval Guide
1-98 Automatic Sprinkler Systems
a. Resilient seat.
b. Available with Series 752 retard chamber.
c. Suitable for vertical or horizontal installation.
a. Resilient seat.
b. With Model C-1 retard chamber.
Waterflow detectors installed in sprinkler systems provide an electrical alarm when a flow of water from the system
equals or exceeds that of a single sprinkler. They can be used with either open or closed signaling circuits.
They may consist of a flexible vane which projects into the waterway or a pressure-sensing device. For the flexible
vane type, water movement deflects the vane, and the motion is transmitted to an alarm-actuating switch after a
predetermined time delay. The time delay is accomplished by the use of an instantly recycling retard.
Unless otherwise noted in the listing, the flexible vane type is to be used with pipe having an inside diameter which
corresponds to Schedule 40 pipe for sizes up to and including 6 in. (152 mm) or Schedule 30 pipe for sizes 8 and
10 in. (203 and 254 mm).
Waterflow detectors should not be specified for those systems where the time duration of a pressure fluctuation
is greater than the retard time. Instantly recycling retards will not transmit an electrical alarm until the time duration
of the pressure fluctuation or waterflow past the vane of the flow detector has exceeded the predetermined time
setting of 30-60 seconds. Unless otherwise noted in the listing, these detectors have 175 psi (1205 kPa) rated
working pressure.
ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486
Model B6145. Model 6156 (explosionproof). 21⁄2 through 8 in. NPS. 1 A at 110 V ac, 1 A at 12 V dc, 110 V dc. Used with any FM Approved
recycling retard and/or transmitter.
No. D6123. 21⁄2 through 8 in. NPS. Pneumatic retard and transmitter.
No. E6127. 21⁄2 through 8 in. NPS. Pneumatic retard not instantly recycling. Used with FM Approved Type C2130-001 transmitter.
Waterflow Detector. Model 6155. Obtains input signal from a pressure transducer connected by a high pressure hose into the sprinkler
system. Power requirements are 11-15 V dc; output contacts are DPDT alarm contacts for connections to transmitter and local annunciation.
Contacts rated for 1 A at 115 V ac, 2 A at 24 V dc.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-99
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Model WFG. 2 through 8 in. NPS. Pneumatic retard and two snap switches. 250 psi (1725 kPa) rated working pressure. Contacts rated for
7 A at 125 V ac, 0.25 A at 24 V dc. A Model T tamper switch kit (P/N 546-6000) is available as optional equipment for field installation on the
Model WFG device.
Potter Electric Signal & Manufacturing Ltd, 55 Glencameron Rd, Thornhill, Ontario L3T 1P2, Canada
Model VSR-D. 2 through 10 in. NPS. Furnished with two snap switches and pneumatic retard.
Model VSR-T. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm);
8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). 250 psi (1725 kPa) rated working pressure.
A tamper switch kit (P/N 5420220) is available as optional equipment for field installation on the Models VSR-D, VSR-T devices.
Model VSR-E. 2 through 6 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3105 kPa) rated working pressure.
Model VSR-F. 2 through 8 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3105 kPa) rated working pressure.
Models VS-F, VSR-F. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in.
(3 mm); 8 in. NPS (203 mm), for use with pipe having a wall thickness of 0.188 in. (5 mm), or Schedule 40 pipe.
Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146
Model VSR. 2 through 8 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3100 kPa) rated working pressure.
Model VSR-TSK. 2 through 6 in. NPS. Furnished with two snap switches and pneumatic retard, and a tamper switch to indicate that the
cover was removed. 450 psi (3100 kPa) rated working pressure.
Model VSR-F. 2 through 8 in. NPS. Furnished with two snap switches and pneumatic retard. 450 psi (3105 kPa) rated working pressure.
Models VS-F, VSR-F. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in.
(3 mm); 8 in. NPS (203 mm), for use with pipe having a wall thickness of 0.188 in. (5 mm), or Schedule 40 pipe.
Model VSR-FE-2. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in.
(3 mm); 8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). All sizes also for use in Schedule 40 pipe. 450 psi (3105 kPa)
rated working pressure. Furnished with electronic retard.
Model VSR-FEX. 2 through 8 in. NPS. For simultaneous usage as explosionproof for Class I, Division 1, Groups C and D; dust-ignitionproof
for Class II/III, Division 1, Groups E, F and G hazardous (classified) locations indoors and outdoors (NEMA Type 4); 2 through 5 in. NPS, for
use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm); 8 in. NPS, for use with pipe having a wall
thickness of 0.188 in. (5 mm). All sizes also for use in Schedule 40 pipe. 450 psi (3105 kPa) rated working pressure. Furnished with pneumatic
retard.
System Sensor, Div of Honeywell, 3825 Ohio Ave, Saint Charles IL 60174
Accuflow Model AFDXX, 2 through 8 in. NPS as indicated in table below. 2 through 5 in. NPS have a 450 psi (3105 kPa) rated working
pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two switches and a solid state retard. Contacts rated for 0.6 A,
at 125 V ac, 2.0 A, 30 V dc.
Nominal Pipe
Model No.* Size, mm
AFD20*† 2
AFD25#† 21⁄2
AFD30-2#† 3
AFD35#† 31⁄2
AFD40#† 4
AFD50#† 5
AFD60#‡ 6
AFD80§ 8
All models suitable for use in schedule 40 steel sprinkler pipe.
*Also for use with Schedule 5 steel sprinkler pipe.
#Also for use with Lightwall steel sprinkler pipe.
†Also for use with Schedule 10 steel sprinkler pipe.
‡Also for use with pipe having a wall thickness of 0.134 in. (3 mm).
§ Also for use with pipe having a wall thickness of 0.188 in. (5 mm).
AFDXXA:
Models AFD20A, 25A, 30-2A, 35A, 40A, 50A, 60A, and 80A for Canadian distribution have a factory installed tamper switch rated for 5 A
at 125/250 V ac, 3 A at 30 V dc.
AFDXXE:
Accuflow Model AFDXXE, 2 through 8 in. NPS as indicated in table below. 2 through 4 in. NPS have a 450 psi (3105 kPa) rated working
pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two switches and a solid state retard. Contacts rated for 0.6 A,
at 125 V ac, 2.0 A, 30 Vdc.
Nominal Pipe
Model No.* Size, mm
AFD20E 2
(60)
AFD25E 21⁄2
(76)
AFD30-2E 3
(89)
AFD40E 4
(114)
AFD60E 6
(165)
AFD80E 8
(219)
*All models suitable for use with BS 1387 medium and heavy pipe, DIN 2448 and 2458 pipe.
Model 546-9000. Cover tamper switch available for Models AFD20 (E), 25 (E), 30 (E), 35, 40 (E), 50, 60 (E) and 80 (E) rated for 5 A at
125/250 V ac, 3 A at 30 V dc.
FM Approvals
September 2007 — Approval Guide
1-100 Automatic Sprinkler Systems
Model WFD-XX 2 through 8 in. NPS as indicated in Table below. 2 through 4 in. NPS have a 450 psi (3105 kPa) rated working pressure.
6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two snap switches and pneumatic retard.
2 through 6 in. NPS sizes rated for Schedules 10 and 40.
8 in. NPS size rated for 0.188 in wall, Schedules 10 and 30 pipe.
Nominal Pipe
Model No.* Size, mm
WFD20E 60
WFD25E 76
WFD30E 89
WFD30E-2E 89
WFD40E 114
WFD60E 165
WFD80E 219
*Suitable for use in BS 1387 medium and heavy pipe, DIN 2448 and 2458 pipe. 2 through 4 in. NPS have a 450 psi (3105 kPa) rated working pressure. 6 and 8 in.
NPS have a 400 psi (2760 kPa) rated working pressure. Two snap switches and pneumatic retard.
Nominal Pipe
Model No. Size, in.
WFD20 2
WFD25 21⁄2
WFD30 3
WFD30-2 3
WFD35 31⁄2
WFD40 4
WFD50 5
WFD60 6
WFD80 8
Model WFD-10. 2 through 5 in. NPS, for use with Schedule 10 pipe; 6 in. NPS, for use with pipe having a wall thickness of 0.134 in. (3 mm);
8 in. NPS, for use with pipe having a wall thickness of 0.188 in. (5 mm). 450 psi (3105 kPa) rated working pressure. 2 through 5 in. NPS have
a 450 psi (3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Model WFD-10 has two
snap switches and pneumatic retard. Contacts rated for 7 A at 125 V ac, 0.25 A at 24 V dc.
Nominal Pipe
Model No.* Size, in.
WFD20† 2
WFD25† 21⁄2
WFD30† 3
WFD30-2† 3
WFD35† 31⁄2
WFD40† 4
WFD50† 5
WFD60‡ 6
WFD80§ 8
Model WFDXX-EXP 2 through 8 in. NPS as indicated in table below. These models are suitable for use in hazardous locations: Class I,
Groups B, C, D Division 1, Class II, Groups E, F, G, Division 1, and Class III, Division 1 NEMA 4 enclosure. 2 through 5 in. NPS have a 450 psi
(3105 kPa) rated working pressure. 6 and 8 in. NPS have a 400 psi (2760 kPa) rated working pressure. Two snap switches and pneumatic
retard. Contacts rated for 10 A, at 125/250 V ac, 2.5 A, 24 V dc.
Nominal Pipe
Model No.* Size, in.
WFD20-EXP† 2
WFD25-EXP† 21⁄2
WFD30-EXP† 3
WFD30-2EXP 3
WFD35-EXP† 31⁄2
WFD40-EXP† 4
WFD50-EXP† 5
WFD60-EXP‡ 6
WFD80-EXP§ 8
*All models suitable for use in Schedule 40 pipe. Two snap switches and pneumatic retard. Two snap switches and pneumatic retard.
†Also for use with Schedule 10 pipe.
‡Also for use with pipe having a wall thickness of 0.134 in. (3 mm).
§Also for use with pipe having a wall thickness of 0.188 in. (5 mm).
Models WFD20A, 25A, 30A, 40A, 50A, 60A, 80A for Canadian distribution have factory installed cover tamper switch rated for 5 A at
125/250 V ac, 2.5 A at 24 V dc.
Model 546-7000. Cover tamper switch available for Models WFD20, 25, 30, 35, 40, 50, 60, 80 rated for 5 A at 125/250 V ac, 2.5 A at 24 V dc.
The Viking Corp, 210 N Industrial Park Rd, Hastings MI 49058
Model VSR-D. 2 through 10 in. NPS. Furnished with two snap switches and pneumatic retard.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-101
Unless otherwise specified, these testers have 175 psi (1205 kPa) rated working pressure.
National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE
‘‘Zonecheck’’ Vane Type Waterflow Indicator Test Devices. Available in sizes 2 through 6 in. NPS. Can be original installation, or a retrofit,
to run piping around indicator. All sizes available in Schedule 10 and 40 piping configurations. Either 120 V ac or 230 V ac power required.
Project Fire Products Ltd, Pasturefields Lane, Industrial Estate, Hixon, Staffordshire ST18 0PH, United Kingdom
‘‘Zonecheck’’ Vane Type Waterflow Indicator Test Devices. Available in sizes 1 through 6 in. NPS. Can be original installation, or a retrofit,
to run piping around indicator. All sizes available in Schedule 10, 40, BS 1387 Medium and Heavy piping configurations. Either 120 V ac or
230 V ac power required.
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
‘‘Zonecheck’’ Vane Type Waterflow Indicator Test Devices. Available in sizes 2 through 6 in. NPS. Can be original installation, or a retrofit,
to run piping around indicator. All sizes available in Schedule 10 and 40 piping configurations. Either 120 V ac or 230 V ac power required.
In buildings where it is impractical to keep temperatures above freezing, automatic sprinkler systems can be
equipped with an FM Approved dry pipe valve. The sprinkler piping contains air under pressure, instead of water.
When a sprinkler operates, air escapes, the dry pipe valve trips, and water is admitted automatically to the system
Dry pipe systems should be installed in accordance with FM Global Loss Prevention Data Sheet 2-8N, Installation
of Sprinkler Systems. Additionally, if their use is intended for refrigerated storage, FM Global Loss Prevention Data
Sheet 8-29 should be referred to. System calculations regarding required system air capacity should be performed
if only one air pressure maintenance device is contemplated for several sprinkler systems.
Dry pipe valves are designed so that a moderate amount of air pressure will hold back a much greater water
pressure. In the differential type, the air pressure holds the water clapper closed either by means of a difference in
areas on which the water and air pressures act, or by a combination of this principal with a lever action. In the
mechanical type, a clapper on the water seat is held closed by a system of levers which are controlled by a relatively
small air clapper.
A suitable alarm is connected to the dry pipe valve so that a warning is given when the valve operates. This may
be a mechanical alarm that operates by a hydraulic motor, or a hydraulic pressure switch that closes an electric
circuit to operate a bell, horn, or remote signaling system. Unless otherwise noted in the listing, these dry pipe valves
have 175 psi (1205 kPa) rated working pressure.
Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain
Model A. 21⁄2 in. NPS. 90° angle. Threaded or cut groove inlet and outlet connections.
Model D. 4, 6 in. NPS; 100, 150 mm NPS. Standard size valves painted black or gray. Metric size valves painted blue. Flanged inlet.
Flanged or grooved outlet.
Model LDX Dry Pipe Valve System, 4 and 6 in. NPS.
Model LDX dry pipe valves have a flanged inlet and grooved outlet.
Model LDX check valves have grooved inlet and outlet connections.
Model DDX-LP Dry Pipe Valve System consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. NPS (100 mm and 150 mm) NPS. A
mechanical latch prevents the valve from resetting after the initial trip. The Model DDX-LP Dry Pipe Valves have an external reset feature
whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. The Model DDX Deluge
Valves have grooved inlet and grooved outlet end connections. The DDX-LP system is designed for systems with water supply pressures from
20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system air pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa).
A loss of system air pressure, such as when a sprinkler activates, opens the pneumatic actuator which opens the DDX valve, sending water
to the sprinklers and sounding alarms. The system utilizes a Model LP (low pressure) pilot line actuator, a Model LP low pressure pneumatic
actuator, a Model B Manual Pull Station, and a System Sensor EPS10-1 pressure alarm switch. A Model B1 accelerator is an available option
for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply system or water from
a valve trip, a drain valve is provided to drain the valve body and riser. The rated working pressure of the Model DDX-LP Dry Pipe Valve
System is 250 psi (1724 kPa).
Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT, United Kingdom
Model D. 100, 150 mm NPS.
Metric size valves painted blue.
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Model 39. 4, 6 in. NPS. Flange/flange connection.
‘‘Automatic’’ Model 39A. 6 in. NPS. Flange/flange connection.
‘‘Automatic’’ Model GTO. 4, 6 in. NPS. Flange/groove connection.
FM Approvals
September 2007 — Approval Guide
1-102 Automatic Sprinkler Systems
Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD, United Kingdom
MAG Model M799DG-04E. 3, 4, 6, 8 in. NPS. 300 psi rated working pressure. Available with wafer or flanged inlet and outlet connections.
Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840, Bad Oldesloe, Germany
Flanged × Flanged
3, 4, 6 175
Model TMX Flanged × Grooved –
(80, 100, 150) (1205)
Grooved × Grooved
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model A. 21⁄2 in. NPS. 90° angle. Threaded or cut groove inlet and outlet connections.
Model D. 4, 6 in. NPS; 100, 150 mm NPS. Standard size valves painted black or gray. Metric size valves painted blue. Flanged inlet.
Flanged or grooved outlet.
Model LDX low pressure Dry Pipe Valve System, 4 and 6 in. NPS, 100 and 150 mm NPS.
Model LDX dry pipe valves have a flanged inlet and grooved outlet.
Model LDX low pressure check valves have grooved inlet and outlet connections.
The Model LDX Dry Pipe Valves are available with the optional Model B-1 Accelerator.
Model DDX-LP Dry Pipe Valve System consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. NPS (100 mm and 150 mm) NPS. A
mechanical latch prevents the valve from resetting after the initial trip. The Model DDX-LP Dry Pipe Valves have an external reset feature
whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. The Model DDX Deluge
Valves have grooved inlet and grooved outlet end connections. The DDX-LP system is designed for systems with water supply pressures from
20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system air pressures, nominally, of 12 psi (83 kPa) to 24 psi (165 kPa).
A loss of system air pressure, such as when a sprinkler activates, opens the pneumatic actuator which opens the DDX valve, sending water
to the sprinklers and sounding alarms. The system utilizes the Reliable Model LP (low pressure) pilot line actuator, the Reliable Model LP low
pressure pneumatic actuator, the Reliable Model B Manual Pull Station, and a System Sensor EPS10-1 pressure alarm switch. The Reliable
Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to
condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. The rated working
pressure of the Model LP Dry Pipe Valve System is 250 psi (1724 kPa).
SES Enser Engineering, Via Carolina Romani 8/10, 20091 Bresso (MI), Italy
FARES Model F799DG-04E. 3, 4, 6, 8 in. NPS. 300 psi rated working pressure. Available with wafer or flanged inlet and outlet connections.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Model A. 2*, 3, 4, 6 in. NPS. Available with flange/flange and flange/groove end connections.
Model A-1. 4, 6 in. NPS. Flange/Groove end connections.
Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada
Astra Model A. 3, 4, 6 in. NPS. Flange/flange connection.
Astra Model B. 4, 6 in. NPS. Flange/groove connection.
Astra Model E. 4 in. NPS. Groove/groove connection.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-103
Series 768 Firelock NXT Dry Valve in sizes 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS, grooved inlet and grooved outlet, installed vertically. The
system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:
• Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 729 alarm line Drip Check Valve
• Series 748 anti-flood Ball Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/off
• Series 768 Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
All Dry Pipe Valves are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system
components and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and
detection connections, and the electrical power supply.
These combine the operating characteristics of an accelerator and antiflooding device in a single mechanical unit.
When installed on a dry pipe valve, they cause the valve to trip more quickly and also to exclude foreign particles
from entering the accelerator mechanism.
Because both the accelerator and antiflooding feature are combined in a single unit, no separate antiflooding
device is required. Unless otherwise noted in the listing, these accelerators have 175 psi (1205 kPa) rated working
pressure.
Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT, United Kingdom
Model B1. For use with Angus Model D dry pipe valve.
FM Approvals
September 2007 — Approval Guide
1-104 Automatic Sprinkler Systems
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Models B, B1. For use with Reliable Model D or Star Model A dry pipe valve.
The Model B-1 Accelerator is an optional component for use with the Reliable Model LDX Dry Pipe Valve System.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Model S430. For use with Grinnell or Gem Models F302, F3021, 4, 6 in. or Star Model A, 2, 3, 4, 6 in. NPS dry pipe valves, 4, 6 in. Duomatic
dry systems (Refrigerated Area Sprinkler Systems).
An accelerator or exhauster, attached to a dry pipe valve, causes the valve to trip quickly upon sprinkler operation.
These devices operate when loss of system air pressure exceeds a predetermined rate. Unless otherwise noted in
the listing, these accelerators and exhausters have 175 psi (1205 kPa) rated working pressure.
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Model 1 Accelerator. For use with ‘‘Automatic’’ Model 39 dry pipe valve.
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Accelerator. Model C.
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
Model SE2 Accelerator. For use with Model TMX dry pipe valves.
Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146
Model QRS Electronic Accelerator System. Consists of a Potter Model QRS Quick Release Pressure Switch, Potter Model PFC-100RC Fire
Alarm Releasing Panel, Skinner Model 73218BN4UNLVNOC111C2 solenoid valve and associated trim for use on the following dry pipe
valves:
Manufacturer Model No. Size, in.
Model QRS Electronic Accelerator System. Consists of a Potter Model QRS Quick Release Pressure Switch, Potter Model PFC-4410-RC
Fire Alarm Releasing Panel, Skinner Model 73218BN4UNLVNOC111C2 solenoid valve and associated trim for use on the following dry pipe
valves (Note 2) and a preaction valve (Note 3):
Note 3: The Model PFC-4410-RC Panel, standard program #13, is configured such that one control panel is utilized for one preaction valve with one Model QRS
Accelerator.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-105
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Star Exhauster. Model BB.
When a dry pipe valve operates, water flows to the accelerator. Foreign particles may be carried with the water
to the accelerator. An antiflooding device is installed in the line between the valve and accelerator to prevent foreign
material from entering the accelerator where it is likely to cause malfunction. Unless otherwise noted in the listing,
these devices have 175 psi (1205 kPa) rated working pressure.
These pressure maintenance devices automatically maintain a predetermined air or nitrogen pressure in dry pipe
sprinkler systems. Some devices may be used with a noncontinuous air supply which is capable of initially filling the
system. Other systems require a continuous air or nitrogen supply. Unless noted otherwise in the listing, these air
maintenance devices have a pressure rating of 175 psi (1205 kPa).
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Models A, A-1.
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Models H-1, H-2, H-3.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Models A-2, B-1, B-2.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Models A, B.
These devices are designed for use with fire protection equipment which requires supervisory air pressure of
approximately 1.5 psi (10 kPa).
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Air Compressor Panel. Reliable Model B.
Automatic Air Pressure Maintenance Device. Reliable Model C.
FM Approvals
September 2007 — Approval Guide
1-106 Automatic Sprinkler Systems
These devices are intended for use in a dry pipe or a refrigerated area spinkler system application. Each unit, in
conjunction with an FM Approved air maintenance device, provides air with reduced humidity to lower the possibility
of ice formation in a single dry pipe system.
Deluge sprinkler systems have open sprinklers or open spray nozzles and are used where it is desirable to
discharge water through all of the system’s sprinklers or nozzles simultaneously. Prior to discharge there is no water
in the sprinkler piping. The water supply is held back by a control valve which is operated manually or automatically
by the actuation of a fire detection system. The fire detection system is required to be one of the following types: wet
pilot sprinkler line, dry pilot sprinkler line, hydraulic rate-of-rise, pneumatic rate-of-rise or electric. FM Approved
combinations of control valves and fire detection system(s) are listed under AUTOMATIC WATER CONTROL
VALVES.
Automatic sprinklers are used on wet or dry pilot sprinkler lines. The dry pilot sprinkler line may also require a dry
pilot actuator depending upon the type of automatic water control valve. When required, only the compatible dry pilot
actuator listed for a specific valve under AUTOMATIC WATER CONTROL VALVES shall be used in FM Approved
systems.
Electrically operated deluge sprinkler systems are FM Approved on a component basis. Only the major,
compatible components listed for a specific valve under AUTOMATIC WATER CONTROL VALVES shall be used in
an FM Approved system. FM Global installation acceptance may stipulate that only heat-actuated fire detection
devices be used. Acceptance criteria by other jurisdictional authorities may vary.
Deluge sprinkler systems identified in the listing by an asterisk (*) have either hydraulic or pneumatic rate-of-rise
fire detection and are FM Approved as complete systems. Only the listed components for a specific manufacturer
shall be used in an FM Approved system.
Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain
Deluge Sprinkler System consist of Model A, 21⁄2 in. NPS and Models B and BX in sizes 4 and 6 in. and 100 and 150 mm NPS deluge
valves. Model BX deluge valves have an external reset feature. Systems are Approved for hydraulic, pneumatic or electric releasing means.
Model DDX Deluge Sprinkler System consists of Model DDX Deluge Valves in sizes 4 inch and 6 inch NPS (100 mm and 150 mm) NPS.
A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas
a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Systems are Approved for
hydraulic (wet pilot line), pneumatic (dry pilot line), or electric (solenoid valve) releasing means. Model DDX valves have grooved inlet and
grooved outlet end connections. In the event that water builds up inside the deluge valve due to condensate from the air supply system or
water from a valve trip, a drain valve is provided to drain the valve body and riser.
The Wet Pilot Trim set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water supply
pressure gage, and the push rod chamber supply connections. A wet pilot line, which extends up to the open deluge sprinkler grid, contains
a closed sprinklers or other fixed temperature releases. When the closed sprinkler is activated and opened by a fire, the pilot line pressure
is released which opens the DDX valve, sending water to the sprinklers and sounding alarms. TheWet Pilot Trim set is used when the Model
F1-FTR fixed temperature release is used in the wet pilot line, and/or when the Model A or B emergency stations/manual pull boxes can be
used for releasing. The rated working pressure of the Wet Pilot Deluge System is 250 psi (1724 kPa).
The Dry Pilot Trim set is used when a fixed temperature release is used in the dry pilot line. A dry pilot line, which extends up to the open
deluge sprinkler grid, contains closed sprinklers or other fixed temperature releases. When a closed sprinkler is activated and opened by a
fire, the pilot line pressure is released which opens the pneumatic actuator, which opens the DDX valve, sending water to the sprinklers and
sounding alarms. The Model LP (low pressure) pilot line actuator is used in the dry pilot line and is designed for systems with water supply
pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding dry pilot line pneumatic pressures, nominally, of 12 psi (83 kPa)
to 24 psi (165 kPa). The system uses the Model A or B emergency stations/manual pull boxes which can be used for manual releasing. The
rated working pressure of the Dry Pilot Deluge System is 250 psi (1724 kPa).
The Electric Actuation Trim set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water
supply pressure gage, and the push rod chamber supply connections. The Model A or B emergency stations/manual pull boxes can be used
for manual releasing. This system’s Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions.
Only when there is an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat detector is
activated, does the solenoid valve open which opens the DDX valve, sending water to the sprinklers. Only FM Approved fixed temperature
heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier
Model PS 12120, to provide 90 hours of backup emergency power. The system utilizes the normally closed solenoid valve, P/N 6871020020.
The rated working pressure of the Electric Actuation Deluge System is 250 psi (1724 kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-107
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Suprotex Deluge System*. Consists of Model C automatic water control valve, sizes 21⁄2, 6 in.; 1⁄8 in. circuit tubing with the
following Heat Actuated Devices (HADs): 87-100A, 87-150, 87-180, 87-190, 87-530A, 87-540A, 87-560, 87-570; No. 90-100 compensating
vent; Nos. 81-100A, 83-100A releases; Nos. 81-600A, 83-600 secondary releases (only acceptable when rate-of-rise circuits are a secondary
means of system activation); Model 70-200 break glass station; manual pull handle; Model 64-100G manual pull station; No. 148-200C air
pump panel; No. 2403C2H low pressure regulator; No. 79-340A air dryer; No. 39-713 drum drip or No. 79-943C reservoir; No. 1621 high
pressure regulator; No. 148-250 restriction orifice; No. 79-840B air line mercury check; No. 121 mercury check; No. S76-650 weight switch;
Model 94-160 low pressure actuator; emergency release (quick opening valve); Model 123-100 hydropneumatic control.
‘‘Automatic’’ Deluge Sprinkler System. Consists of Model D, F water control valves, 21⁄2, 4, 6 in. or Model E water control valve, 6 in., which
must be equipped with Viking Model C-1 pressure-operated relief valve.
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Consists of Model F Water Control Valve. 21⁄2, 4, 6 in.
Consists of Model D1.5, 11⁄2 in. NPS, and Model D2, 2 in. NPS, Water Control Valves.
Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD, United Kingdom
MAG Model M799DG-04A (wet pilot), MAG Model M799DG-04B (dry pilot), MAG Model M799DG-04C (electric). Consists of 3, 4, 6, 8 in.
NPS MAG Model M799DG-04 automatic water control valve. MAG Models M799DG-04A and M799DG-04B have a rated working pressure
of 300 psi (2070 kPa).
Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel
INBAL Model 799-DG-01-HMP (wet pilot) and INBAL Model 799-DG-01-PMP (dry pilot). Consists of 3, 4, 6, 8 in. NPS INBAL Model
799-DG-01 water control valve. 6 in. NPS rated working pressure of 300 psi (2070 kPa).
INBAL Model 799-DG04-A (wet pilot), INBAL Model 799-DG04-B (dry pilot), INBAL Model 799-DG04-C (electric). Consists of 3, 4, 6, 8 in.
NPS INBAL Model 799-DG04 automatic water control valve. INBAL Models 799-DG04-A and 799-DG04-B have a rated working pressure of
300 psi (2070 kPa).
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
Deluge Sprinkler Systems. Consists of Model FSX deluge valves with either Electric, Dry Pilot Line, or Wet Pilot Line releasing means. The
valves are available in Flange by Flange end connections, DIN sizes of 50, 80, 100, and 150 mm NPS. The electric solenoid is an impulse
type solenoid valve, Minimax P/N 84 0131. The dry pilot line actuator is a diaphragm valve, Minimax P/N 20 9353-E. With electrical releasing,
the Minimax control panel FMZ 4100 GAB 32, with 90 hours of 24 Vdc battery backup is used. The Models FSX deluge valves have a rated
working pressure of 232 psi (16 bar).
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Deluge Sprinkler System consists of Model A, 21⁄2 in. NPS and Models B and BX in sizes 4 and 6 in. and 100 and 150 mm NPS deluge
valves. Model BX deluge valves have an external reset feature. Systems are FM Approved for hydraulic, pneumatic or electric releasing
means.
Model DDX Deluge Sprinkler System. Consists of Model DDX Deluge Valves in sizes 4 inch and 6 inch NPS (100 mm and 150 mm) NPS.
A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas
a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Systems are Approved for
hydraulic (wet pilot line), pneumatic (dry pilot line), or electric (solenoid valve) releasing means. Model DDX valves have grooved inlet and
grooved outlet end connections. In the event that water builds up inside the deluge valve due to condensate from the air supply system or
water from a valve trip, a drain valve is provided to drain the valve body and riser.
The Wet Pilot Trim. Set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water supply
pressure gage, and the push rod chamber supply connections. A wet pilot line, which extends up to the open deluge sprinkler grid, contains
a closed sprinklers or other fixed temperature releases. When the closed sprinkler is activated and opened by a fire, the pilot line pressure
FM Approvals
September 2007 — Approval Guide
1-108 Automatic Sprinkler Systems
is released which opens the DDX valve, sending water to the sprinklers and sounding alarms. The Wet Pilot Trim set is used when the Reliable
Model F1-FTR fixed temperature release is used in the wet pilot line, and/or when the Reliable Model A or B emergency stations/manual pull
boxes can be used for releasing. The rated working pressure of the Wet Pilot Deluge System is 250 psi (1724 kPa).
The Dry Pilot Trim. Set is used when a fixed temperature release is used in the dry pilot line. A dry pilot line, which extends up to the open
deluge sprinkler grid, contains closed sprinklers or other fixed temperature releases. When a closed sprinkler is activated and opened by a
fire, the pilot line pressure is released which opens the pneumatic actuator, which opens the DDX valve, sending water to the sprinklers and
sounding alarms. The Reliable Model LP (low pressure) pilot line actuator is used in the dry pilot line and is designed for systems with water
supply pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding dry pilot line pneumatic pressures, nominally, of 12 psi
(83 kPa) to 24 psi (165 kPa). The system uses the Reliable Model A or B emergency stations/manual pull boxes which can be used for
manual releasing. The rated working pressure of the Dry Pilot Deluge System is 250 psi (1724 kPa).
The Electric Actuation Trim. Set is connected to the push rod chamber outlet and provides the 2 inch main drain, the alarm test, the water
supply pressure gage, and the push rod chamber supply connections. The Reliable Model A or B emergency stations/manual pull boxes can
be used for manual releasing. This system’s Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm
functions. Only when there is an electrical signal to the releasing control panel from a fire detector, such as when a fixed temperature heat
detector is activated, does the solenoid valve open which opens the DDX valve, sending water to the sprinklers. Only FM Approved fixed
temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery,
Notifier Model PS 12120, to provide 90 hours of backup emergency power. The system utilizes the normally closed solenoid valve, Reliable
P/N 6871020020. The rated working pressure of the Electric Actuation Deluge System is 250 psi (1724 kPa).
SES Enser Engineering, Via Carolina Romani 8/10, 20091 Bresso (MI), Italy
FARES Model F799DG-04A (wet pilot), FARES Model F799DG-04B (dry pilot), FARES Model F799DG-04C (electric). Consists of 3, 4, 6,
8 in. NPS FARES Model 799-DG04 automatic water control valve. FARES Models F799DG-04A and F799DG-04B have a rated working
pressure of 300 psi (2070 kPa).
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Star Deluge Sprinkler System. Consists of Model D water control valve, 3, 6 in. NPS. With 24 V dc operating coils.
Star Hidromatic Deluge Sprinkler System. Consists of Model G, 3, 4, 6 in. NPS water control valve.
Star Hidromatic Deluge Sprinkler System. Consists of Model G-1, 3, 4, 6 in. NPS water control valve. Model G-1 water control valves have
an external reset feature. Systems are FM Approved for hydraulic, pnuematic or electric release trim. Rated working pressure is 250 psi
(2070 kPa).
Star Deluge Sprinkler System. Consists of Model F430 thermal control valve, 1, 11⁄2 in. NPS; Model B flooding valve, 2 in. NPS.
Star Deluge Sprinkler System. Consists of Model B flooding valve, 2 in. NPS.
Total Walther GmbH, Feuerschutz und Sicherheit, Waltherstrasse 51, 51069 Köln, Germany
Deluge Sprinkler System. Consists of Model EKFV water control valve. DN 200 mm. A spool piece containing a 2 in. (51 mm) drain valve
is attached to the inlet flange of each valve.
The Deluge Sprinkler Systems, with the DV-5 water control valve, is available factory assembled vertically inside the Model DV-5 Red-E
Cabinet in sizes 11⁄2, 2, 3, 4, and 6 in. NPS. The Red-E cabinet and assembled system components comprise an integrated fire protection
system which is assembled and tested at the factory. The cabinet contains: the system shutoff valve, Model DV-5 deluge valve, 24 Vdc battery
backup, and an electrical control/release panel which is pre wired to the switches for the alarm, supervisory, and trouble functions. Installation
requires the connection to the water inlet and outlet, main drain, electrical power supply, and the alarm and detection circuits. When dry pilot
release is utilized, a built-in air compressor and air maintenance device provides controlled pilot line air pressure.
Series 769 Firelock NXT Deluge Valves with Dry Pilot Line Pneumatic Release. Sizes 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS. Grooved inlet and
grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:
• Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve; Series 729 alarm line Drip Check Valve
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-109
Series 769 Firelock NXT Deluge Valves with Wet Pilot Line Hydraulic Release. Sizes 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS. Grooved inlet and
grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 729 alarm line Drip Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/off
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
Series 769 Firelock NXT Deluge Valve with Electric Release. Sizes 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet,
installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:
The 11⁄2, 2, 21⁄2, 3, 4, and 6 in. NPS Deluge Sprinkler Systems are available factory assembled in the Victaulic Series 745 Fire-Pac
enclosure, a cabinet containing all system components and accessories, and requires only the connection to the water supply inlet, water
outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. The Series 745 Fire-Pacs may be
connected to Notifier AFP-200 Programmable Analog Fire control with software no. AFP2R2.42 or System Sensor PDRP-1001 fire control
with operating system firmware revision level A. The AFP-200 control contains FMM-1 Module with a signaling line circuit which can be
configured to meet Styles 4, 6 or 7 wiring performance as described in NFPA72. The addressable panels utilize model XP-10M module which
may be configured at the factory to monitor the Fire-Pac cabinet and valve station. Optional LED Interface Module 4XTM and Relay Module
RTM-8 provide outputs for auxiliary applications.
Deluge Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking Total Pac2
enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations: 1) the system
FM Approvals
September 2007 — Approval Guide
1-110 Automatic Sprinkler Systems
fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve system fully
enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote control
panel.
All Deluge Sprinkler Systems are available with the TrimPac package in both conventional and Easy Trim configurations.
Preaction systems are equipped with automatic sprinklers and are used where it is important to prevent the
accidental discharge of water. These systems may also be used where an alarm is desired in advance of sprinkler
operation or where it is desired to minimize the water delivery delay inherent in a standard dry-pipe system. For this
reason, the following factors must be carefully assessed: detector spacing and sensitivity, sprinkler piping
arrangement and ceiling construction.
Supervisory air pressure is maintained in the sprinkler piping of a preaction sprinkler system. A trouble alarm
sounds if the supervisory air pressure is not maintained; however, such a condition will not cause the automatic water
control valve to operate. Generally, a single check valve is installed downstream of the automatic water control valve
to contain the supervisory air pressure. Except for the addition of a single check valve and the use of automatic
sprinklers, components of preaction sprinkler systems are identical or similar to those of deluge sprinkler systems.
The water supply is held back by a water control valve which is operated manually or automatically by the
actuation of a fire detection system. The fire detection system is required to be one of the following types: hydraulic
rate-of-rise, pneumatic rate-of-rise or electric. FM Approved combinations of control valves and fire detection
system(s) are listed under AUTOMATIC WATER CONTROL VALVES.
Electrically operated preaction sprinkler systems are FM Approved on a component basis. Only the major,
compatible components listed for a specific valve under AUTOMATIC WATER CONTROL VALVES shall be used in
designing an FM Approved system. FM Global installation acceptance may stipulate that only heat-actuated fire
detection devices be used. Acceptance criteria by other jurisdictional authorities may vary.
Preaction sprinkler systems identified in the listing by an asterisk (*) have either hydraulic or pneumatic rate-of-rise
fire detection and are FM Approved as complete systems. Only the listed components for a specific manufacturer
shall be used in an FM Approved system.
Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain
Preaction Sprinkler System consists of Model A 21⁄2 in. NPS and Models B and BX 4 or 6 in. NPS water control valves and Approved rubber
faced check valve. Model BX water control valves have an external reset feature. Systems are Approved for hydraulic, pneumatic or electric
releasing means.
Preaction Sprinkler Systems utilizing electric releasing means are available factory assembled in the PrePak enclosure and the Model BX
PrePak Preaction System, utilizing a size 4 or 6 in. Model BX deluge valve. The PrePak enclosure and assembled valve systems comprise
an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water supply inlet,
water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.
Preaction Sprinkler System, a Supertrol Single Interlock Preaction, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm
and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset
feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX
valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 2 psi (13.8 kPa), sprinkler system
supervisory air pressure to activate alarms, with electric activation for a valve trip. A loss of system air pressure, such as when a sprinkler
activates, will not open the Model DDX valve but causes the low pressure alarm to sound. Only when there is also an electrical signal to the
releasing control panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve open which
opens the DDX valve, sending water to the sprinklers. The Model A or B emergency stations/manual pull boxes can be used for manual
releasing. This system’s Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. The
release solenoid valve is P/N 6871020020. Only FM Approved fixed temperature heat devices shall be used in the release system and in the
sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency
power. The rated working pressure of the Supertrol Single Interlock Preaction System is 250 psi (1724 kPa).
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Suprotex Preaction Sprinkler System*. Consists of Model C, 21⁄2, 6 in. water control valve; FM Approved rubber-faced check
valve; 1⁄8 in. circuit tubing with the following Heat Actuated Devices (HADs): 87-500B, 87-550, 87-580, 87-590, 87-530A, 87-540A, 87-560,
87-570; No. 90-100 compensating vent; Nos. 81-100A, 83-100A releases; Nos. 81-600A, 83-600 secondary releases (only acceptable when
rate-of-rise circuits are a secondary means of system activation); Model 70-200 break glass station; manual pull handle; Model 64-100G
manual pull station; No. 148-100C air pump panel; No. 2403C2H low pressure regulator; No. 79-904B or 79-904C low pressure alarm switch;
No. 79-340A air dryer; No. 39-713 drum drip or No. 79-943C reservoir; No. 1621 high pressure regulator; No. 148-250 restriction orifice; No.
79-840B air line mercury check; No. 121 mercury check; No. S76-650 weight switch; Model 94-160 low pressure actuator; emergency release
(quick opening valve); Model 123-100 hydropneumatic control.
‘‘Automatic’’ Preaction Sprinkler System. Consists of Model D, F water control valves, 21⁄2, 4, 6 in. with FM Approved rubber-faced check
valve or Model E water control valve, 6 in. equipped with Viking Model C-1 pressure-operated relief valve and FM Approved rubber-faced
check valve.
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Consists of Model F Water Control Valve. 21⁄2, 4, 6 in. with FM Approved water-faced check valve.
Consists of Model D1.5, 11⁄2 in. NPS, and Model D2, 2 in. NPS, Water Control Valves.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-111
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Preaction Sprinkler System consists of Model A, 21⁄2 in. NPS and Models B and BX 4 or 6 in. NPS water control valves and FM Approved
rubber-faced check valve. Model BX, in sizes 4 and 6 in., as well as 100 and 150 mm NPS, water control valves have an external reset feature.
Systems are FM Approved for hydraulic, pneumatic or electric releasing means.
Preaction Sprinkler Systems utilizing electric releasing means are available factory assembled in the Reliable PrePak enclosure, both the
Model A PrePak Preaction System, size 21⁄2 in., and the Model BX PrePak Preaction System, utilizing a size 4 or 6 in. Model BX deluge valve.
The PrePak enclosure and assembled valve systems comprise an integrated fire protection system which is assembled and tested at the
factory, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections,
and the electrical power supply.
Preaction Sprinkler Systems.
A Supertrol Single Interlock Preaction, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in. (100 mm and 150 mm) NPS. A
mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an external reset feature whereas a
knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper. Model DDX valves have grooved
inlet and grooved outlet end connections. The system utilizes low pressure, nominally 2 psi (13.8 kPa), sprinkler system supervisory air
pressure to activate alarms, with electric activation for a valve trip. A loss of system air pressure, such as when a sprinkler activates, will not
open the Model DDX valve but causes the low pressure alarm to sound. Only when there is also an electrical signal to the releasing control
panel from a fire detector, such as when a fixed temperature heat detector is activated, does the solenoid valve open which opens the DDX
valve, sending water to the sprinklers. The Reliable Model A or B emergency stations/manual pull boxes can be used for manual releasing.
This system’s Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. The release solenoid
valve is the Reliable P/N 6871020020. Only FM Approved fixed temperature heat devices shall be used in the release system and in the
sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency
power. The rated working pressure of the Supertrol Single Interlock Preaction System is 250 psi (1724 kPa).
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Star Preaction Sprinkler System. Consists of Model G Hidromatic, 4 in. NPS water control valve and FM Approved rubber-faced check
valve.
Star Preaction Sprinkler System. Consists of Model B, 2 in. flooding valve and FM Approved rubber-faced check valve.
The Preaction Systems, with the DV-5 water control valve, are available factory assembled vertically inside the Model DV-5 Red-E Cabinet
in sizes 11⁄2, 2, 3, 4, and 6 in. NPS. The Red-E cabinet and assembled system components comprise an integrated fire protection system
which is assembled and tested at the factory. The cabinet contains: the system shutoff valve, Model DV-5 deluge valve, 24 Vdc battery
backup, and an electrical control/release panel for the solenoid valve release. The control panel is prewired to the switches for the alarm,
supervisory, and trouble functions. Installation requires the connection to the water inlet inlet and outlet, main drain, electrical power supply,
and the alarm and detection circuits. A built-in air compressor and air maintenance device provides controlled system air pressure.
Series 769 Firelock NXT Single-Interlocked Valve with Electric Release. Sizes 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS. The system rated working
pressure is 300 psi (2070 kPa). Grooved inlet and grooved outlet, installed vertically. Major trim components consist of the following:
FM Approvals
September 2007 — Approval Guide
1-112 Automatic Sprinkler Systems
All preaction sprinkler systems discussed above offer the Series 75-B supplemental alarm valve as an option recommended for systems
where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained.
Some Preaction Sprinkler Systems are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all
system components and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the
alarm and detection connections, and the electrical power supply. The Series 745 Fire-Pacs may be connected to Notifier AFP-200 Pro-
grammable Analog Fire control with software no. AFP2R2.42 or System Sensor PDRP-1001 fire control with operating system firmware
revision level A. The AFP-200 control contains FMM-1 Module with a signaling line circuit which can be configured to meet Styles 4, 6 or 7
wiring performance as described in NFPA72. The addressable panels utilize model XP-10M module which may be configured at the factory
to monitor the Fire-Pac cabinet and valve station. Optional LED Interface Module 4XTM and Relay Module RTM-8 provide outputs for auxiliary
applications.
with 0.063 in. (1.6 mm) dia. orifice; Model B-1 Release control Panel, equipped with an appropriately sized battery to provide 90 hours of
emergency power, equipped capable of cross zoned operation with FM Approved compatible pressure switch and heat actuated device;
FM Approved solenoid valves include the normally open Viking Model 11595, the normally closed Viking Model 11591, the normally open
explosion proof Viking Model 11596, the normally closed explosion proof Viking Model 11592; or N.C. Solenoid Valve, Viking P/N 11591 and
N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure. Pneumatic actuators Model H-1 or R-1; Model C-1 or
C-2 emergency releases; dual SPDT Model 09473 air supervisory switch; Model 09470 or Model 09471 pressure switch; dehydrator P/N
01285A; Model D-2 air pressure maintenance device; available with Easy Trim option, utilizing a Model A-1 or A-2 pressure shut-off valve
(PSOV); trim available in galvanized, brass or stainless steel piping; FM Approved rubber-faced system check valve. Available with TrimPac
trim package in Easy Trim configuration. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and
in the sprinkler piping. Model F-1 and F-2 valves are capable of vertical installation. Same valve end connections as noted above. Rated
working pressure 250 psi (1725 kPa); piping above the riser check valve contains supervisory air pressure at 30-50 psi (205-345 kPa) to
monitor system integrity. If the system piping is damaged, the low air pressure alarm is activated and the normally open solenoid valve is
activated closed but the main water control valve does not trip and no water flows into the sprinkler system until the heat detection device
is actuated. This causes the normally closed solenoid valve to open which activates the control valve and water flow is supplied to the sprinkler
system. Also when heat detector is activated by fire, the main control valve operates supplying water to the sprinkler system. In loss of power
condition, the system operates from system supervisory air and the pneumatic actuator.
Preaction Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking Total Pac2
enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations: 1) the system
fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve system fully
enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote control
panel.
A refrigerated area sprinkler system affords fire protection in refrigerated rooms or buildings and includes special
safeguards against accidental filling with water and subsequent freezing of the system. A fire detection system must
actuate and one or more automatic sprinklers in the piping must operate before water will enter the sprinkler system.
An alarm sounds if the detection system only is actuated while pneumatic pressure is maintained in the sprinkler
piping. An alarm also sounds if the pneumatic pressure in the sprinkler piping is not properly maintained. In either
case, water does not enter the system piping. These systems should be installed in accordance with FM Global Loss
Prevention Data Sheet 8-29, ‘‘Refrigerated Storage’’. System calculations regarding required system air capacity
should be performed if only one air maintenance device is contemplaed for several sprinkler systems.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-113
Refrigerated area sprinkler systems which are operated pneumatically/hydraulically are FM Approved as complete
systems. Only the listed components for a given system may be used in combination.
Fire detection systems which are operated electrically are FM Approved on a component basis. Only compatible
components may be used in combination.
Anber Globe SA, Av de Las Flores 13, Parque Ind El Molino, 28970 Humanes de Madrid, Madrid Spain
Type A Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric
release system and pneumatic system pressure. Consists of a Model B or BX deluge valve (4, 6 in. NPS), compatible solenoid valve, Model
A dry pilot actuator, Model B1 or A2, air pressure maintenance device, Model A hydraulic manual pull box, or Model B manual emergency
station, United Electric switch Models J54-8300 and J54-8295 or system sensor EPS10 and EPS40 series pressure alarm switches, Approved
rubber faced check valve and an Approved compatible automatic release control panel with appropriately sized battery to provide 90 hours
emergency power. Only Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping.
Type D Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric
release system and pneumatic system pressure. Consists of a Model B or BX deluge valve (4, 6 in. NPS) or Model A deluge valve (21⁄2 in.
NPS), compatible solenoid valve, Model B1, or A2, air pressure maintenance device, Model A hydraulic manual pull box, or Model B manual
emergency station, United Electric switch Models J54-8300 and J54-8295 or system sensor EPS10 and EPS40 series pressure alarm
switches, Approved rubber faced check valve and an Approved compatible automatic release control panel capable of cross-zone operation
with appropriately sized battery to provide 90 hours emergency power. Only Approved fixed temperature heat sensitive devices shall be used
in the release system and in the sprinkler piping.
Type D Supertrol Refrigerated Area Sprinkler Systems are available factory assembled in the PrePak enclosure and the Model BX PrePak
Refrigerated Area Sprinkler System, utilizing a size 4 or 6 in. Model BX deluge valve. The PrePak enclosure and assembled valve systems
comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water
supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.
Supertrol Type D Double Interlock Preaction System, pneumatic-electric/electric, consists of Model DDX Deluge Valves in sizes 4 in. and
6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have
an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the
clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 10 psi
(69 kPa), sprinkler system supervisory air pressure and a cross-zoned releasing control panel such that two electrical signals must energize
two control panel initiating circuits before water flows through the valve. A loss of system air pressure, such as when a sprinkler activates,
activates the EPS10-2 pressure switch and provides one signal to the control panel. An electrical signal from a fire detector, such as when
a fixed temperature heat detector is activated, provides the other signal to the control panel. The two signals open the solenoid valve, P/N
6871020020, and results in flow out the sprinklers. The Model A or B emergency stations/manual pull boxes can be used for manual releasing.
The Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to
condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system’s
Notifier RP 1001 Fire Alarm/Releasing Control Panel, adjusted for cross-zoned operation, is utilized for the electric release and alarm
functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel
has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure
of the Supertrol Type D Double Interlock Preaction System is 250 psi (1724 kPa).
Supertrol Type F Double Interlock Preaction System, pneumatic/electric, consists of Model DDX Deluge Valves in sizes 4 in. and 6 in.
(100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an
external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper.
Model DDX valves have grooved inlet and grooved outlet end connections. The Type F system is designed for systems with water supply
pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system pneumatic pressures, nominally, of 12 psi
(83 kPa) to 24 psi (165 kPa). A loss of system air pressure, such as when a sprinkler activates, opens the Model LP (low pressure) pilot line
actuator causing the low pressure alarm to sound, but the DDX valve remains closed. The system utilizes the System Sensor EPS10-2
pressure alarm switch. Only when there is also an electrical signal to the releasing control panel from a fire detector, such as when a fixed
temperature heat detector is activated, does the solenoid valve, P/N 6871020020, open which opens the DDX valve, sending water to the
sprinklers. The Model A or B emergency stations/manual pull boxes can be used for manual releasing. The Model B1 accelerator is an
available option for use with this system. In the event that water builds up inside the deluge valve due to condensate from the air supply
system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system’s Notifier RP 1001 Fire Alarm/
Releasing Control Panel is utilized for the electric release and alarm functions. Only FM Approved fixed temperature heat devices shall be
used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery, Notifier Model PS 12120, to
provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Type F Double Interlock Preaction System is
250 psi (1724 kPa).
FM Approvals
September 2007 — Approval Guide
1-114 Automatic Sprinkler Systems
Magisco Valves Ltd, 53 Limes Rd, Tettenhall, Wolverhampton WV6 8RD, United Kingdom
Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure.
Consists of 3, 4, 6, 8 in. NPS MAG Model M799DG-04K automatic water control valve, Model 284-08 3-way pilot, Model 377 pneumatic
actuator, Model 379 air reset unit, Model 375 flow release pilot, Skinner Model 73218BN4UNLVN0C111C2 or ASCO Model 8210G207,
24 V dc solenoid valve, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of
emergency power. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler
piping.
Mil Ltd, 17 Moshe Beker St, Box 15200, Rishon Lezion 75051, Israel
Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure.
Consists of 3, 4, 6, 8 in. NPS INBAL Model 799-DG04-K automatic water control valve, Model 284-08 3-way pilot, Model 377 pneumatic
actuator, Model 379 air reset unit, Model 375 flow release pilot, Skinner Model 73218BN4UNLVN0C111C2 or ASCO Model 8210G207, 24 V
dc solenoid valve, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency
power. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Type A Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric
release system and pneumatic system pressure. Consists of a Reliable Model B or BX, in sizes 4 and 6 in., as well as 100 and 150 mm NPS,
water control valve, compatible solenoid valve, Reliable Model A dry pilot actuator, Reliable Model B1, or A2, air pressure maintenance device,
Reliable Model A hydraulic manual pull box, or Model B manual emergency station, United Electric switch Models J54-8300 and J54-8295
or system sensor EPS10 and EPS40 series pressure alarm switches, FM Approved rubber faced check valve and an FM Approved com-
patible automatic release control panel with appropriately sized battery to provide 90 hours emergency power. Only FM Approved fixed
temperature heat sensitive devices shall be used in the release system and in the sprinkler piping.
Type D Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric
release system and pneumatic system pressure. Consists of a Reliable Model B or BX, in sizes 4 and 6 in., as well as 100 and 150 mm NPS,
or Reliable Model A deluge valve (21⁄2 in. NPS), compatible solenoid valve, Reliable Model B1, or A2, air pressure maintenance device,
Reliable Model A hydraulic manual pull box, or Model B manual emergency station, United Electric switch Models J54-8300 and J54-8295
or system sensor EPS10 and EPS40 series pressure alarm switches, FM Approved rubber faced check valve and an FM Approved com-
patible automatic release control panel capable of cross-zone operation with appropriately sized battery to provide 90 hours emergency
power. Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler piping.
Type D Supertrol Refrigerated Area Sprinkler Systems are available factory assembled in the Reliable PrePak enclosure, both the
Model A PrePak Refrigerated Area Sprinkler System, size 21⁄2 in., and the Model BX PrePak Refrigerated Area Sprinkler System, utilizing
a Model BX deluge valve, in sizes 4 and 6 in., as well as 100 and 150 mm NPS. The PrePak enclosure and assembled valve systems
comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the water
supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.
Type F Supertrol Refrigerated Area System. Double interlocked supervised refrigerated area sprinkler system, controlled by an electric
solenoid valve release in series with a pneumatic pressure release pneumatic actuator. Consists of a Reliable Model B or BX Deluge valve,
a Model G Right-Check riser valve, both in sizes of 4 or 6 in. NPS, as well as in sizes 100 and 150 mm NPS. Model B or BX Deluge valves
have ANSI flanged inlets and grooved outlets. Model G Right-Check riser valves have grooved inlets and outlets. Also utilized are: a Reliable
Model LDX pneumatic actuator, Reliable Models B-2 or A-2 air pressure maintenance devices, a Reliable Model B manual emergency pull
station, a System Sensor EPS 10-1 pressure switch, or a United Electric J54-A-8300, forlow air pressure supervision, and a System Sensor
EPS 10-2, or a United Electric J54-A-8295, for water flow indication. The Reliable Model B1 accelerator is an available option for use with
this system. This system’s Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. Only
FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has a
appropriately sized battery, Notifier Model PS 12120, to provide 90 hours emergency power. Compatible 24Vdc energized NC solenoid valves
are listed in the ‘‘Automatic Water Control Valve’’ section of this Guide. System rated working pressure is 175 psi.
The Type F Supertrol Refrigerated Area Sprinkler Systems are available factory assembled in the the PrePak enclosure. The PrePak
enclosure integrates the complete fire protection system in a cabinet which is assembled and tested at the factory, and requires only the
connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.
Supertrol Type D Double Interlock Preaction System. Pneumatic-electric/electric, consists of Model DDX Deluge Valves in sizes 4 in. and
6 in. (100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have
an external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-115
clapper. Model DDX valves have grooved inlet and grooved outlet end connections. The system utilizes low pressure, nominally 10 psi
(69 kPa), sprinkler system supervisory air pressure and a cross-zoned releasing control panel such that two electrical signals must energize
two control panel initiating circuits before water flows through the valve. A loss of system air pressure, such as when a sprinkler activates,
activates the EPS10-2 pressure switch and provides one signal to the control panel. An electrical signal from a fire detector, such as when
a fixed temperature heat detector is activated, provides the other signal to the control panel. The two signals open the solenoid valve, Reliable
P/N 6871020020, and results in flow out the sprinklers. The Reliable Model A or B emergency stations/manual pull boxes can be used for
manual releasing. The Reliable Model B1 accelerator is an available option for use with this system. In the event that water builds up inside
the deluge valve due to condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body
and riser. This system’s Notifier RP 1001 Fire Alarm/Releasing Control Panel, adjusted for cross-zoned operation, is utilized for the electric
release and alarm functions. Only FM Approved fixed temperature heat devices shall be used in the release system and in the sprinkler piping.
The control panel has an appropriately sized battery, Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated
working pressure of the Supertrol Type D Double Interlock Preaction System is 250 psi (1724 kPa).
Supertrol Type F Double Interlock Preaction System, pneumatic/electric. Consists of Model DDX Deluge Valves in sizes 4 in. and 6 in.
(100 mm and 150 mm) NPS. A mechanical latch prevents the valve from resetting after the initial trip. Model DDX Deluge Valves have an
external reset feature whereas a knob attached to the outside of the valve body is pushed in and then rotated manually to reseat the clapper.
Model DDX valves have grooved inlet and grooved outlet end connections. The Type F system is designed for systems with water supply
pressures from 20 psi (138 kPa) to 250 psi (1724 kPa), and corresponding sprinkler system pneumatic pressures, nominally, of 12 psi
(83 kPa) to 24 psi (165 kPa). A loss of system air pressure, such as when a sprinkler activates, opens the Reliable Model LP (low pressure)
pilot line actuator causing the low pressure alarm to sound, but the DDX valve remains closed. The system utilizes the System Sensor
EPS10-2 pressure alarm switch. Only when there is also an electrical signal to the releasing control panel from a fire detector, such as when
a fixed temperature heat detector is activated, does the solenoid valve, Reliable P/N 6871020020, open which opens the DDX valve, sending
water to the sprinklers. The Reliable Model A or B emergency stations/manual pull boxes can be used for manual releasing. The Reliable
Model B1 accelerator is an available option for use with this system. In the event that water builds up inside the deluge valve due to
condensate from the air supply system or water from a valve trip, a drain valve is provided to drain the valve body and riser. This system’s
Notifier RP 1001 Fire Alarm/Releasing Control Panel is utilized for the electric release and alarm functions. Only FM Approved fixed
temperature heat devices shall be used in the release system and in the sprinkler piping. The control panel has an appropriately sized battery,
Notifier Model PS 12120, to provide 90 hours of backup emergency power. The rated working pressure of the Supertrol Type F Double
Interlock Preaction System is 250 psi (1724 kPa).
SES Enser Engineering, Via Carolina Romani 8/10, 20091 Bresso (MI), Italy
Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure.
Consists of 3, 4, 6, 8 in. NPS FARES Model F799-DG04K automatic water control valve, Model 284-08 3-way pilot, Model 377 pneumatic
actuator, Model 379 air reset unit, Model 375 flow release pilot, Skinner Model 73218BN4UNLVN0C111C2 or ASCO Model 8210G207, 24 V
dc solenoid valve, compatible FM Approved automatic release control panel with appropriately sized battery to provide 90 hours of emergency
power. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure.
Consists of automatic water control valve Model A, 3, 4, 6 in. NPS with 3⁄32 in. diaphragm chamber orifice, Skinner LV2LBX25 or
73218BN4UNLVNOC111C2 solenoid valves, Star Model AA-R or Tyco Model DP-1 dry pilot actuator, compatible FM Approved automatic
release control panel with appropriately sized battery to provide 90 hours of emergency power; United Electric Control Co Models J54-8300
and J54-8295 pressure alarm switches; Star Model A manual control station. Only FM Approved fixed temperature, heat sensitive devices
shall be used in the release system and in the sprinkler piping.
Sprinkler System. Double interlocked, uses a deluge valve controlled by an electric release system and pneumatic system pressure.
Consists of automatic water control valve Model A-1, 3, 4, 6 in. NPS with 3⁄32 in. diaphragm chamber orifice, Skinner
73212BN4TNLVNOC322C2 solenoid valves, Tyco Model DP-1 dry pilot actuator, compatible FM Approved automatic release control panel
with appropriately sized battery to provide 90 hours of emergency power; United Electric Control Co Models J54-8300 and J54-8295 pressure
alarm switches; Tyco Model MC-1 manual control station. Only FM Approved fixed temperature, heat sensitive devices shall be used in the
release system and in the sprinkler piping.
FM Approvals
September 2007 — Approval Guide
1-116 Automatic Sprinkler Systems
solenoid valve will be rated at 175 psi (1205 kPa). Systems using a Skinner Model No. 73212BN4TNLVN0C322C2 solenoid valve will be rated
at 250 psi (1725 kPa). Only FM Approved fixed temperature heat sensitive devices shall be used in the release system and in the sprinkler
piping.
Refrigerated Area Sprinkler Systems, with the DV-5 water control valve, are available factory assembled vertically inside the Model DV-5
Red-E Cabinet in sizes 11⁄2, 2, 3, 4, and 6 in. NPS. The Red-E cabinet and assembled system components comprise an integrated fire
protection system which is assembled and tested at the factory. The cabinet contains: the system shutoff valve, Model DV-5 deluge valve,
24 Vdc battery backup, and an electrical control/release panel for the solenoid valve release. The control panel is prewired to the switches
for the alarm, supervisory, and trouble functions. Installation requires the connection to the water inlet inlet and outlet, main drain, electrical
power supply, and the alarm and detection circuits. A built-in air compressor and air maintenance device provides controlled system air
pressure.
Series 769 Firelock NXT Double-Interlocked Valve with Electric-Pneumatic/Electric Release for Cross-Zoned Control Panel. Sizes 11⁄2, 2,
21⁄2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa).
Major trim components consist of the following:
Series 769 Firelock NXT Double-Interlocked Valve with Electric/Pneumatic Release. Sizes 21⁄2, 3, 4, 6 and 8 in. NPS. Grooved inlet and
grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:
• Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve
• Series 753-E normally closed solenoid valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 729 alarm line Drip Check Valve
• Series 748 anti-flood Ball Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/off
• Series 768 Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
Series 769 Firelock NXT Double-Interlocked Valve with Electric/Pneumatic Release Sizes 11⁄2, 2, 21⁄2, 3, 4, 6, and 8 in. NPS. Grooved inlet
and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa).
• Series 767 Electric/Pneumatic Actuator; an Auto Vent pressure operated system air pressure relief valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-117
Series 769 Firelock NXT Double-Interlocked Valve with Pneumatic/Pneumatic Release. Sizes 11⁄2, 2, 21⁄2, 3, 4, 6, and 8 in. NPS. Grooved
inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of: the
following:
• Series 798 Pneumatic/Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 729 alarm line Drip Check Valve
• Series 748 anti-flood Ball Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/off
• Two Series 768 Air Manifold Assemblies with integral restrictor/screen/anti-flood ball check valve
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly
All refrigerated area sprinkler systems discussed above offer the Series 757-P Air Maintenance Trim Assembly as an option. It is used to
control the system air pressure on all refrigerated area sprinkler systems, by controlling small air compressors which do not have pressure
control switches.
All refrigerated area sprinkler systems discussed above offer the Series 75-W Water Column Drain Kit as an option, which automatically
drains water from the sprinkler systems and subsequently reseals to maintain air pressure in the system piping.
All refrigerated area sprinkler systems discussed above offer the Series 75-B supplemental alarm valve as an option recommended for
systems where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained.
All the 11⁄2, 2, 21⁄2, 3, 4, and 6 in. NPS Refrigerated Area Sprinkler Systems discussed above are available factory assembled in the Victaulic
Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the connection to the water
supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply. The Series 745
Fire-Pacs may be connected to Notifier AFP-200 Programmable Analog Fire control with software no. AFP2R2.42 or System Sensor
PDRP-1001 fire control with operating system firmware revision level A. The AFP-200 control contains FMM-1 Module with a signaling line
circuit which can be configured to meet Styles 4, 6 or 7 wiring performance as described in NFPA72. The addressable panels utilize model
XP-10M module which may be configured at the factory to monitor the Fire-Pac cabinet and valve station. Optional LED Interface Module
4XTM and Relay Module RTM-8 provide outputs for auxiliary applications.
FM Approvals
September 2007 — Approval Guide
1-118 Automatic Sprinkler Systems
Model H-1 or R-1 pneumatic actuator; Model C pressure-operated relief valve (PORV); dehydrator P/N 01285A; Model D-2 air pressure
maintenance device; compatible FM Approved solenoid valve and automatic release panel equipped with appropriately sized battery to
provide required 90 hours of emergency power; available with Speed Control Assembly trim option; FM Approved rubber-faced check valve.
Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping.
Model E-3 and E-4, 11⁄2 in. NPS and Model E-1 and E-2, 2 in. NPS available with screwed connections only.
Model E-1 or E-2, 3, 4, 6 in. NPS available with flanged inlet and outlet or flanged inlet and cut-grooved outlet connections.
Model F-1 and F-2, in-line globe water control valves, 8 in. NPS, are available with grooved by grooved end connections or flanged by
flanged end connections.
Model F-1 or F-2 in-line globe water control valves, 3, 4, and 6 in. NPS, are available with grooved by grooved, flanged by flanged end,
or flanged inlet by grooved outlet connections.
Model F-1 or F-2 in-line globe water control valves, 11⁄2, 2 and 21⁄2 in. NPS, are available with grooved by grooved, or screwed end
connections. Rated working pressure is 250 psi (1725 kPa).
Previous system ratings are dependent on the solenoid valve used. See table of related components shown under Automatic Water Control
Valves.
Sprinkler System. Double interlocked, Electric Pneu-Lectric, supervised dry system using a deluge valve controlled by electric release
system and pneumatic system pressure. Consists of water control valve Model E-1 or E-2 in size 2, 3, 4 or 6 in. NPS or Model E-3 or E-4
in size 11⁄2 in. NPS or Model F-1 or F-2 in-line globe water control valves 11⁄2, 2, 21⁄2, 3, 4, 6 or 8 in. NPS; priming line including strainer,
0.063 in. (1.6 mm) dia. orifice and spring loaded check valve; Model C-1 or C-2 emergency release; for 10 psi (69 kPa) supervisory air system
use Model 09471 dual SPDT pressure switches; for 30 psi (207 kPa) supervisory air system use Model 09473 dual SPDT pressure switches;
Model C-1 pressure-operated relief valve (PORV) including conventional deluge trim; dehydrator P/N 01285A; Model D-2 air pressure
maintenance; compatible FM Approved solenoid valve and automatic release control panel, equipped capable of cross zoned operation with
FM Approved compatible pressure switch and heat actuated device and appropriately sized battery to provide required 90 hours of emergency
power; available with Speed Control Assembly trim option; available with Easy Trim option utilizing Model A-1 or A-2 pressure shut-off valve
(PSOV); FM Approved rubber-faced check valve. Only FM Approved fixed temperature, heat sensitive devices shall be used in the release
system and sprinkler piping.
Model E-3 and E-4, 11⁄2 in. NPS and Model E-1 and E-2, 2 in. NPS available with screwed connections only. Model E-1 or E-2, 3, 4, 6 in.
NPS available with flanged end connections or flanged inlet and cut-groove outlet connections. Model F-1 and F-2, 3, 4, 6, 8 in. NPS available
with grooved end connections or flanged end connections or flanged inlet and grooved outlet end connections.
Model F-1 or F-2 in-line globe water control valves, 11⁄2, 2 and 21⁄2, in. NPS, are available with grooved by grooved, or screwed end
connections. Rated working pressure is 250psi (1725 kPa).
The rated working pressure of the Electric/Pnue-Electric refrigerated area sprinkler system is dependent on the solenoid valve used. See
table of related components shown under Automatic Water Control Valves.
Refrigerated Area Sprinkler Systems are available factory assembled in the Viking Total Pac enclosure with in sizes 11⁄2 through 6 in. NPS,
with electric/pneumatic, pneumatic/pneumatic, and electric-pneumatic/electric releases. The Total Pac enclosure and assembled valve
systems comprise an integrated fire protection system which is assembled and tested at the factory, and requires only the connection to the
water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical power supply.
Sprinkler System. Sure Fire Fail/Safe double interlocked, supervised dry system using a deluge valve controlled by a electric release
system and pneumatic system pressure. Consists of angle type water control valves Model E-1 or E-2, in sizes 2, 3, 4, and 6 in. NPS, or Model
E-3 or E-4 in size 11⁄2 in. NPS; or in-line Model F-1 or F-2 in-line globe type water control valves in sizes 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS;
strainer; restricted orifice with 0.063 in. (1.6 mm) dia. orifice; Model B-1 release control panel, with an appropriately sized battery to provide
90 hours of emergency power, equipped capable of cross zoned operation with FM Approved compatible pressure switch and heat actuated
device; FM Approved solenoid valves include the normally open Viking Model 11595, the normally closed Viking Model 11591, the normally
open explosion proof Viking Model 11596, the normally closed explosion proof Viking Model 11592; or N.C. Solenoid Valve, Viking P/N 11591
and N.O. Solenoid Valve, Viking P/N 13215 for 250 psi (1725 kPa) rated working pressure. Pneumatic actuators Model H-1 or R-1; Model
C-1 or C-2 emergency releases; dual SPDT Model 09473 and single SPDT Model 09472 air supervisory switch; Model 09470, 09471 pressure
switch; dehydrator P/N 01285A; Model D-2 air pressure maintenance device; available with Easy Trim option, utilizing a Model A-1 or A-2
pressure shut-off valve (PSOV); trim available in galvanized, brass or stainless steel piping; FM Approved rubber-faced System check valve.
Only FM Approved fixed temperature, heat sensitive devices shall be used in the release system and in the sprinkler piping. Model F-1 and
F-2 valves are capable of vertical installation. Same valve end connections as noted above. Rated working pressure 250 psi (1725 kPa).
Piping above the riser check valve contains supervisory air pressure at 30-50 psi (205-345 kPa) to monitor system integrity. If the system
piping is damaged, the low air pressure alarm is activated and the normally open solenoid valve is activated closed, but the main water control
valve does not trip, and no water flows into the sprinkler system until the heat detection device is actuated. This causes the normally closed
solenoid valve to open which activates the control valve and water flow is supplied to the sprinkler system. Also the low air supervisory switch
and the heat detection device must activate before the system control valve will open and supply water to the sprinkler system. In loss of
power condition, the system operates from system supervised air and the pneumatic actuator.
Refrigerated Area Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking
Total Pac2 enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations:
1) the system fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve
system fully enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote
control panel. All Refrigerated Area Sprinkler Systems are available with TrimPac trim package.
Multicycle sprinkler systems are FM Approved automatic sprinklers and hydraulic controls capable of repeated
on-off cycles appropriate to the possible redevelopment of fire in the protected area.
The cycling occurs as the result of fire detector operation which, acting as an electrical interlock, causes the main
water control valve to open and close. Fire detector actuation precedes sprinkler operation so water is discharged
as from a conventional water system. Should the fire rekindle after its initial control, water again flows from the
opened sprinklers. Manual control valve operation, in the event of detector impairment, is a required system
capability. Sprinkler replacement after a fire does not cause impairment of protection.
Plans for converting existing wet or dry sprinkler systems to multicycle should be reviewed by your insurance
company before actual installation.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-119
A very important feature of the multicycle sprinkler system is its effect toward the reduction of the closed-valve,
catastrophic fire. With the multicycle system, the manual sprinkler control valve would not have to be closed except
in the very infrequent case of major maintenance involving a certain small section of the overall system. Unless
otherwise noted in the listing, this system has 175 psi (1205 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
1-120 Automatic Sprinkler Systems
(minimum 30 psi, for 20 psi water supply pressure, up to 50 psi, for 250 psi water supply pressure) to monitor system integrity. If the system
piping is damaged or a sprinkler activates, the low air pressure alarm is activated, but the main water control valve does not trip and no water
flows to the sprinkler system. When the heat detection system has been activated, the main water control valve opens and water will flow out
any open sprinklers.
The Firecycle III Model E-1 Control Panel automatically starts and stops water flow to the sprinkler system in response to the on-off cycling
of the heat responsive detectors. The heat detectors open when the detectors are exposed to the heat of the fire and close when the detector
cools below its set point. Sprinkler discharge continues for a timed ‘‘soak’’interval (5 min normally) after all normally closed contact detectors
have closed. This interval should be extended to15 minutes where persistent localized fire is anticipated. The on-off cycling of the heat
responsive contacts controls the system solenoid valves which in turn control the opening and closing of the main water control valve.
The temperature rating of the detectors should be lower than the rating of its adjacent sprinklers. Power failure and fire alarms are signaled
automatically. System is powered by line voltage (110/220/240 VAC) and operates (cycles) normally with the 24 VDC emergency battery
back-up system (90 hr standby capability).
Detectors are spaced according to ceiling construction and possible obstruction conditions, but should not exceed 40 ft (12 m) for P/N 11727
or 25 ft (8 m) for P/N 11728, 11729 and 11730; their location should be in accordance with NFPA 72E. The manufacturer’s instructions and
appropriate sprinkler installation rules should be followed in Firecycle III-OH installation, testing and maintenance. The FireCycle III
System-OH is rated for 250 psi (1725 kpa) operating pressure.
Firecycle III-OH Cycling Wet Pipe System. Consists of: Model H-3 main water control valve, size 11⁄2 NPS, or Model H-1 main water control
valve, sizes 2, 3, 4 or 6 in. NPS, or Models J-1 or J-2, 11⁄2, 2, 21⁄2, 3, 4, 6 and 8 in. NPS main water control valve and accessories; Water
Flow Switch and system Drain Valve down stream of control valve. Firecycle III Control Panel E-1, Viking P/N 10751 and 10752; Firecycle
III-OH heat detectors are self-restoring, normally closed, heat-actuated switches. There are two types: Viking Model C surface mount and
Viking Model C flush mount. The surface mount is attached directly to a ceiling or to a ceiling mounted standard octagonal electrical box, and
the detector wire in conduit is exposed below the ceiling. The flush mount detector is attached to a standard octagonal electrical box recessed
in the ceiling, and the detector wire is concealed above the ceiling. The detector wire is Viking P/N 09954, NEC FPL rated wire, 16 gage, 2
conductor, 2 hour rated (in conduit or equal), or Viking P/N 11988, NEC FPL rated wire, 18 gage, 2 conductor, 2 hour rated (in conduit or
equal), or Viking P/N 04236A, aluminum clad wire installed behind proper rated construction.; Model C normally closed heat-actuated flush
mounted fire detectors for Ordinary Hazard applications: 140°F (60°C), P/N 11723; 160°F (71°C), P/N 11724; 190°F (88°C), P/N 11725; 225°F
(107°C), P/N 11726; Model C normally closed heat-actuated surface mounted fire detectors for Ordinary Hazard applications: 140°F (60°C),
P/N 11727; 160°F (71°C), P/N 11728; 190°F (88°C), P/N 11729; 225°F (107°C), P/N 11730; Model C-1 emergency release; 90- hour,18 A-H
battery back-up power supply capable of being recharged in 48 hours, P/N A-09867. For 250 psi rated working pressure, N.C. solenoid valve,
Viking P/N 11591 and N.O. solenoid valve, Viking P/N 11596; or N.C. Solenoid Valve, Viking P/N 11591 and N.O. Solenoid Valve, Viking P/N
13215 for 250 psi (1725 kPa) rated working pressure.
The Firecycle III-OH Cycling Wet System in the normal set condition has the main water control valve in the open position, the sprinkler
piping is filled with water, and water will flow from any activated sprinklers. The Firecycle III Model E-1 Control Panel automatically starts and
stops water flow to the sprinkler system in response to the on-off cycling of the heat responsive detectors. The heat detectors open when the
detectors are exposed to the heat of the fire and close when the detector cools below its set point. Sprinkler discharge continues for a timed
‘‘soak’’interval (5 min normally) after all normally closed contact detectors have closed. This interval should be extended to 15 minutes where
persistent localized fire is anticipated. The on-off cycling of the heat responsive contacts controls the system solenoid valves which in turn
control the opening and closing of the main water control valve. The temperature rating of the detectors should be lower than the rating of
its adjacent sprinklers. Power failure and fire alarms are signaled automatically. System is powered by line voltage 110/220/240 V ac) and
operates (cycles) normally with the 24 VDC emergency battery back-up system (90 hr standby capability).
Detectors are spaced according to ceiling construction and possible obstruction conditions, but should not exceed 40 ft (12 m) for P/N 11727
or 25 ft (8 m) for P/N 11728, 11729 and 11730; their location should be in accordance with NFPA 72E. The manufacturer’s instructions and
appropriate sprinkler installation rules should be followed in Firecycle III-OH installation, testing and maintenance. The FireCycle III
System-OH is rated for 250 psi (1725 kpa) operating pressure.
Multicycle On-Off Sprinkler Systems, which utilize the angle type main water control valves, are available factory assembled in the Viking
Total Pac2 enclosure, a second generation enclosure which replaces the Total Pac. The Total Pac2 is available in several configurations:
1) the system fully enclosed on legs with an access door and a built in electrical control panel (when electric activation required); 2) the valve
system fully enclosed on legs with an access door and a remote control panel; 3) the valve system assembled to a skid and used with a remote
control panel. Available with TrimPac trim package.
The function of these releases is to open water valves automatically via FM Approved fire detection devices.
Release control panels FM Approved for deluge and preaction sprinkler systems are compatible with the specified
solenoid-operated valves, have standby power supplies capable of providing the required 90-hour system operation
should primary power fail, and fire detection circuitry capable of operation during open circuit fault condition.
ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486
Unimode II. Programmable fire alarm panel using firmware revision level 6. The min configuration consists of either a CAB-A2, -B2, -C2,
-D2, -A3, -B3, -C3 or -D3 enclosure, CPU-5000 central processing unit, MPS-24, -24A or -24B power supply, and an initiating module IZM-4
or -8. CPU-5000 provides two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit, and a local energy municipal
tie for auxiliary protective signaling. Indicating appliance circuits supply 18-30 V dc; therefore, the FM Approved devices used must be capable
of operating throughout the entire voltage range. Unimode II requires TCM-2 or -4 time control modules with operating system firmware
revision level 2. Modules are programmable for either cross zone or dual zone operation. For deluge and preaction sprinkler system release,
compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star
Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER
CONTROL VALVES. Standby battery packs (24 V dc, 12 and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE
SIGNALING listing for other FM Approved modules.
Unimode 4-16. Programmable fire alarm panel using firmware revision level 3. The min configuration consists of a CAB-500 enclosure,
CPU-500 central processing unit, MPS-24BPCA power supply, 4000TA transformer, and an initiating module IZ-4 or -8. CPU-500 provides
two indicating circuits; one alarm and one trouble relay output, reverse polarity circuit, and a local energy municipal tie for auxiliary protective
signaling. Requires TC-2 or -4 time control modules with operating system firmware revision level 2. Modules are programmable for either
cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models
R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM Approved
combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24 V dc, 12
and 25 AH) provide 90 hour standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules.
ADT Unimode-300 or Unimode-400 Fire Alarm Control Panel. Programmable control. Basic system consists of a combination of ADT-
CPU-300 or ADT-CPU-400 module and MPS-400 power supply. 120/240 V ac primary system provides four notification appliance circuit/
releasing circuit outputs from the MPS-400 rated at 24 V dc 2.5 A. Release circuit requires REL 2.2K end-of-line device for supervision. Total
MPS-400 power output is 6 A in alarm. Standby battery (24 V dc up to 55 AH) provides 90 hour standby operation. (See control panel
description under LOCAL PROTECTIVE SIGNALING.)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-121
Unimode-640 Fire Alarm Control Panel. Basic system consists of the ADT-CPU-640 module with internal power supply. 120 V ac primary
system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary
outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge
and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner
Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES.
Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH)
provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING.
Buckeye Fire Equipment Co, 110 Kings Road, King Mountain NC 28086
Shield-SZ DipSwitch Programmable Fire Alarm Control Panel using Version 1.00 firmware; P/N SZ-120-2R (110 V ac) and SZ-240-2R (240
V ac). The system may include SZ120-0c (110 V ac) or SZ250-0c (208 or 240 V ac) enclosures with transformer, SZ200-17 (17 AH) battery
assembly, SZ101 controller, SZ400 Class A Input Module, and SZ440 Relay module. In the sprinkler mode, the SZ101 Controller Card
provides two initiating device circuits (capable of cross-zone, sequential alarm or single detector release) for fire detection, one waterlow
circuit; one supervisory circuit, all of which are Class B Style A. Initiating device circuits must be converted to Class A Style D with Class A
input module SZ400 for sprinkler release. In addition, the controller provides three notification circuits (all Class B, Style Y); one alarm relay
(non-programmable); one trouble relay (non-programmable), and one solenoid releasing circuit for activation of compatible 24 V solenoid
valves. For FM Approved combinations of solenoid and deluge water valves refer to AUTOMATIC WATER CONTROL VALVES.
CHEMETRON Fire Systems, 4801 Southwick Dr, 3rd Floor, Matteson IL 60443
Micro 1001 with operating system Firmware Revision Level A. Including a zone relay module. Panel provides four input circuits: one
detector; one manual release/detector; one waterflow; one supervisory and four output circuits; one alarm/waterflow bell; one waterflow/
FM Approvals
September 2007 — Approval Guide
1-122 Automatic Sprinkler Systems
supervisory bell; one release; one supervisory bell/release. In addition, one regulated and one unregulated 24 V auxiliary power output; one
alarm and one trouble relay output are provided. Combined load for all external devices not to exceed 2.25 A. Field programmable using dip
switches for either cross zone or dual zone. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO
Models T8210A107, R8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid for Star Sprinkler Model D deluge valve. For FM
Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. In the event of primary power
failure, battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby power.
Fire Alarm Control. Micro-200I Analog Fire Panel. Programmable control (see listing under LOCAL PROTECTIVE SIGNALING). Contains
a signaling line circuit with cross-zone capability and four indicating appliance/release circuits. For deluge and preaction sprinkler system
release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25 and solenoid for
Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER
CONTROL VALVES. Standby battery packs (24 V dc, 7 to 12 AH) provide 90 hours standby operation.
MICRO-640I Fire Alarm Control Panel. Basic system consists of the MICRO-640-CPU module with internal power supply. 120 V ac primary
system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary
outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. Release circuit
can be provided via FCM-1 module and/or XP5-C and XP5-M Transponders. For deluge and preaction sprinkler system release, compatible
solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For Approved combinations of
solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Transmitter Module (TM-4) provides a local energy
municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH) provides 90 hour standby operation. See control panel
description under LOCAL PROTECTIVE SIGNALING.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-123
55-047 Supervised Control Module (SCM) to provide peer-to-peer digital communication protocol between the conventional notification
appliance circuits and the CyberCat signaling line circuit. In addition, the SCM operates solenoids rated up to 2 Amps @ 24 V dc. Controller
is also compatible with P/N 55-052 and P/N 55-053 Releasing Control Modules (RCM). The RCM supervises solenoid of a sprinkler water
control valve and is connected to the controller SLC loop. For Approved combinations of solenoid and water control valves, refer to the
Automatic Water Control Valve listings that follow. 24 V dc batteries rated 18-75 AH are available to provide 90 hours of emergency operation.
[See further description under LOCAL PROTECTIVE SIGNALING].
Cheetah Xi Fire Alarm Control System (P/N 10-068). Programmable addressable system consisting of P/N 10-2542 Cheetah Xi Controller
with V1.30, within P/N 10-2541(R/G) enclosure, and power supply with transformers P/N 02-10881 (120 Vac) or P/N 02-10882 (240 Vac).
Controller connects with p/ns 55-042 or 55-047 Supervised Control Module (SCM) to provide peer-to-peer digital communication protocol
between the conventional notification appliance circuits and the CyberCat signaling line circuit. In addition, the SCM operates solenoids rated
up to 2 Amps @ 24 V dc. In addition, Release Control Module p/ns 55-042 or 55-047 operates solenoids rated up to 2 Amps @24 V dc. For
Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc batteries
rated 18-75 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE SIGNALING].
Cheetah Xi 50 and Cyber Cat 50 Fire Alarm Control units are programmable addressable systems consisting of [P/N 10-2622,
P/N 10-2620], respectively Controller with V3.00, within P/N 10-2623(R/G) and 10-2621 (R/B) enclosure, and power supply with transformers
P/N 02-10881. Controller connects with p/ns 55-042 or 55-047 Supervised Control Module (SCM) to provide peer-to-peer digital communi-
cation protocol between the conventional notification appliance circuits and the signaling line circuit. In addition, the SCM operates solenoids
rated up to 2 Amps @24V dc. In addition, Release Control Module [p/ns 55-042 or 55-047] operates solenoids rated up to 2 Amps @24 V dc.
For Approved combinations of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. 24 V dc
batteries rated 18-75 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTECTIVE
SIGNALING].
Rhino programmable control includes (DCM) detection and control module P/N 10-2141 (110 V ac) or -2144 (220 V ac) which are capable
of cross-zone detection. Compatible with ASCO Models 8210A107, R8210A107, T8210A107 and Skinner Model LV2LBX25 and
73218BN4UNLVNOC111C2 solenoid valves. For FM Approved combinations of solenoid water control valves, refer to AUTOMATIC WATER
CONTROL VALVES. 24 V dc batteries rated 17-33 AH are available to provide 90 hours of emergency operation. (See also LOCAL
PROTECTIVE SIGNALING.)
Shark Fire Alarm Control. Analog Addressable Control P/N 10-056-1 with firmware level 2.00. The Detector Board (P/N 10-2323) provides
one signaling line circuit (SLC) which meets NFPA Style 4, 6, or 7 wiring performance. Two notification appliance circuits (Class A or B) Style
Y, or Z are provided. Each NAC is rated for 1.5 Amps output and can control one solenoid each. Solenoid Series Impedance device
P/N 10-2360 must be used when connecting a solenoid to the NAC circuit. Optional Addressable NAC Module P/N 55-038 (which requires
a separate 24 V dc power to operate) provides a 2 A, 30 V dc output for a solenoid valve. The output circuit is supervised using a 47K ohm
end of line resistor. 24 V dc batteries rated 7-65 AH are available to provide 24 hours of emergency operation. For FM Approved combinations
of solenoid and water control valves, refer to the Automatic Water Control Valve listings that follow. [For specific details on this system see
LOCAL PROTECTIVE SIGNALING].
FM Approvals
September 2007 — Approval Guide
1-124 Automatic Sprinkler Systems
for either cross zone or dual zone operation. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO
Models R8210A107, T8210A107, 8210A107, Skinner Model LV2LBX25, and solenoid for Star Sprinkler Model D deluge valve. For FM
Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby battery packs (24
V dc, 12 and 15 AH) provide 90 hours of standby operation. See LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-125
Automatic Release. XLS-1000 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits
are via XLS-REL releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system
release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107,
821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and
71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL
VALVES. Standby batteries are available in 65 AH capacity to provide the required 90 hours of standby operation.
XLS140(E) Fire Alarm Control Panel. Basic system consists of the XLS140-CPU module with internal power supply. 120 V ac primary
system provides four notification appliance circuit/releasing circuit outputs rated at 24 V dc 2.5 A plus two 24 V dc 1.25 A (total) auxiliary
outputs. Total power output is 6 A in alarm, 3A in standby. Release circuit requires REL 2.2K end-of-line device for supervision. For deluge
and preaction sprinkler system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner
Model LV2LBX25. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES.
Transmitter Module (TM-4) provides a local energy municipal tie for auxiliary protective signaling. Standby battery (24 V dc up to 60 AH)
provides 90 hour standby operation. See control panel description under LOCAL PROTECTIVE SIGNALING.
FM Approvals
September 2007 — Approval Guide
1-126 Automatic Sprinkler Systems
PEGAsys and PEGAsys LV programmable analog control panels equipped with CCM (single loop P/N 76-100008-701) Rev. CCMP82.3SL.
PEGAsys ML is equipped with CCM (multi-loop P/N 76-200008-800) software Rev. CCMP82.3ML. All the controls are equipped with power
supply module (P/N 76-100009-010) Rev. AA (configured for releasing service). Optional agent release module (P/N 76-100001-001) Rev. AD
may be installed in the PEGAsys and PEGAsys ML. For Approved combinations of solenoid and water control valves, refer to the Automatic
Water Control Valve listings that follow. 24 V dc batteries rated 17-99 AH are available to provide 90 hours of emergency operation. (See
description under LOCAL PROTECTIVE SIGNALING.)
FENWALNET 6000 programmable analog addressable fire alarm control system with operating software Rev. 1.2.1. The control has one
(Class A) Style 6, 7 or (Class B), Style 4 Signaling Line Circuit (SLC) that communicates with up to 255 analog addressable devices. The
control also has two (Class A), Style Z or (Class B), Style Y Notification Appliance Circuits (NACs) rated 1.5 A @ 24 V dc. In addition, there
are two releasing circuits rated 2.4A (max) @ 24 V dc for explosive initiators or solenoid-operated control heads and valves. Two more
configurable output circuits are located on the mother board. The output circuits are used for connection to solenoid-operated control heads
and valves, rated 2.4 A (max) @ 24 V dc. 24 V dc batteries rated 7 - 70 AH are available to provide 90 hours of emergency operation. [See
further description under LOCAL PROTECTIVE SIGNALING.]
ARIES programmable analog addressable fire alarm control system with operating software Rev. 1.2.1. The control has one (Class A) Style
6, 7 or (Class B), Style 4 Signaling Line Circuit (SLC) that communicates with up to 255 analog addressable devices. The control also has
two (Class A), Style Z or (Class B), Style Y Notification Appliance Circuits (NACs) rated 1.5 A @ 24 V dc. In addition, there are two releasing
circuits rated 2.4A (max) @ 24 V dc for solenoid-operated control heads and valves. Two more configurable output circuits are located on the
mother board. The output circuits are used for connection to solenoid-operated control heads and valves, rated 2.4 A (max) @ 24 V dc.
24 V dc batteries rated 7-70 AH are available to provide 90 hours of emergency operation. [See further description under LOCAL PROTEC-
TIVE SIGNALING].
Model AEGIS conventional fire alarm-suppression control panel consists of Rev. 1.0.0 operating software. The control panel has one
manual release circuit rated 24 V dc, 10 mA. One abort circuit rated 24 V dc, 10 mA. There are two (Class B) Style Y, supervised, releasing
circuits rated 2.4A (max) @ 24 V dc. The panel is provided with the releasing circuits for agent release or sprinkler release which will actuate
a 24 V dc control head. For Approved combination of solenoid and water control valves, refer to Automatic Water Control Valve listings that
follow. The panel is provided with standby battery capacity up to 68 AH to supply the required 90 hours of standby. (See control panel
description under LOCAL SERVICE.)
Model 732 conventional fire alarm-suppression control panel consists of Rev. 1.0.0 operating software. The control panel has one manual
release circuit rated 24 V dc, 10 mA. One abort circuit rated 24 V dc, 10 mA. There are two (Class B) Style Y, supervised, releasing circuits
rated 2.4A (max) @ 24 V dc. The panel is provided with the releasing circuits for agent release or sprinkler release which will actuate a 24
V dc control head. For Approved combination of solenoid and water control valves, refer to Automatic Water Control Valve listings that follow.
The panel is provided with standby battery capacity up to 68 AH to supply the required 90 hours of standby. (See control panel description
under LOCAL SERVICE.)
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
Fire Alarm Control Panel FMZ 4100 GAB 32. Control uses software level 41EGB32X, P/N 902657. Control consists of the Line Card Rack
(P/N 802599), which houses redundant CPU cards ZKR (P/N 895465), LED control card LEDAK (P/N 806271), Line cards LK and LKA
(P/N 802551 and P/N 805424), Extinguishing Control card LO (P/N 837190), FTX Spark Test card (P/N 802540), SK Loop (MxLoop) card
(P/N 902026), PC/printer interface card PC/DRUIF (P/N 832349), relay interface card IF2 (P/N 802538). The following cards connect directly
to external modules and detectors: 8 relay card RK8 and RK8TQ (P/N 802587 and P/N 800843), line termination cards LAK8 and LAK8A
(P/N 802563and P/N 806477), solenoid valve/monitored output cards MVA4F (P/N 853507), SAK2 loop (MxLoop) connection card
(P/N 800255), spark test connection cards FTX-AK8 (P/N 806209). Logic power supply 5 V DC/2 A (P/N 837104), Logic power supply
15 V DC/2 A (P/N 837116), 24V/6amp power supply USVI-SE-210 (P/N 835193 )). Front panel FPTUL with 8x40 character LCD display
(P/N 801215), LED panels F + S FPFUS (P/N 837189) and FPS for MxLoop devices indication only (P/N 851973), ground fault module MEM
(P/N 800096). Control can provide up to 32/96/128 × 9V Class B detection input zones (maximum 32 detectors per one zone), the panel
designations being FMZ 4100 GAB 32, FMZ 4100 GAB 96, and FMZ 4100 GAB 128 respectively. The latter use line termination cards LAK8
or LAK8A, 32/96/128 Zener groups for manual pull stations (open circuit) connections, 32/96/128 solenoid/notification appliances/monitored
outputs via MVA4F cards. Compatible with the following initiating devices: DMX 3000, and 3003 manual stations, IMX 1001E ionization type
smoke detector, rated IP 23, OMX 1001C, OMX 1111C photoelectric type smoke detectors, rated IP 23, WMX 1000 D60, WMX 1000 D90,
WMX 1000 F60, rated IP 65 and WMX 1000 F90 (rated IP 65) heat detectors, FMX 3100, FMX3511, and UMX 3000 flame detectors, all rated
IP 65 and FUX 3001(L1) spark detector, rated IP65. Series F60 and D60 heat detectors are combination of fixed temperature and rate-of-rise
140°F (60°C), while Series F90 and D90 heat detectors have triggering temperature ranging from 201°F (94°C) to 230°F (110°C). Spacing
guide for D60 and D90 series heat detectors is 25 × 25 feet (7.6 × 7.6 m); while for F60 and F90 series it is 15 × 15 feet (4.6 × 4.6 m).
Compatible with the following analog addressable devices via the MxLoop card: IMX50 ionization smoke detector, OMX50 photoelectric
smoke detector, WMX50 D60 rate-of-rise heat detector: spacing guide for D60 series heat detectors is 30 × 30 feet (9.1m × 9.1 m);
DMX50/50F manual stations, SMX50 short circuit loop isolator, SUX50/50H contact monitoring module.
For electric activated Deluge Sprinkler Systems, compatible solenoid valves are Minimax type 1/2-24 V/DC-2/2-Impulse, Minimax
P/N 84 0131. Standby batteries 24 V, 65 AH provide 90 hours of emergency battery backup supply.
Mircom Technologies Ltd, 25 Interchange Way, Vaughan, Ontario L4K 5W3, Canada
FR-320-D (or blank)-R(or W) programmable fire alarm releasing control panel. ICAC-306 Class A Converter Module is required to configure
the 6 initiating device circuits (IDC) for Class A, Style D operation. Provides 2 Class B releasing circuits. For deluge and preaction sprinkler
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-127
system release, compatible solenoid valves include ASCO Models T8210A107, R8210A107, 8210A107. For FM Approved combinations of
solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Primary power 120 or 240 V ac. 24 V dc secondary
supply consisting of batteries rated 10-26 AH provide required 90 hours of emergency operation. (See also description under AUTOMATIC
RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT.)
Pem-All Fire Extinguisher Corp, Div Pem Systems Inc, 39A Myrtle St, Cranford NJ 07016
PEM-2001 with operating system firmware revision level A. Including LED Interface Module (4XLM); Zone Relay Module (4XZM); Remote
Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four
output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition one regulated
and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for all extenal devices
not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system
release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid
for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves, refer to AUTOMATIC WATER
CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary
power failure, battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation.
FM Approvals
September 2007 — Approval Guide
1-128 Automatic Sprinkler Systems
Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146
PFC Series 100R Fire Control Panel provides one Style D initiating circuit, one Style B non-latching supervisory device circuit, one voltage
reversing Style Y indicating circuit rated 24 V dc, 500 mA, one voltage reversing releasing circuit rated 24 V dc, 1 A and one auxiliary power
supply circuit rated 24 V dc, 15 mA. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model
LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby
batteries rated 8 AH provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.)
PFC Series 2000RC Fire Control Panel. (See also LOCAL PROTECTIVE SIGNALING.) Uses Firmware Version 1.1 with release circuit
discharge times selectable (2 min. or continuous). Contains two signal initiating device circuits (field programmable for Style B or D operation),
two signal indicating circuits, one manual releasing circuit, and one polarized releasing device circuit (24 V dc, 1 A continuous, 3 A
momentary). The Style B and D initiating circuits are capable of cross-zone operation. Combined load of all external devices including
signaling devices not to exceed 3 A. For deluge and preaction sprinkler system release, compatible solenoid valves include ASCO Models
R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid actuator in Star Sprinkler Model D deluge valve solenoid
(P/N 5550). For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. In the
event of primary power failure, standby battery packs (24 V dc, 6.5, 8, 10, 12, or 15 AH) are available for 90 hours emergency power.
Model PFC-100RC Programmable Fire Control Panel. Provides one Style D alarm signal initiating device circuit, one Style B non-latching
supervisory signal initiating device circuit, one voltage reversing Style Y notification appliance circuit rated 24 V dc, 500 mA, one voltage
reversing releasing circuit rated 24 V dc, 1 A and one auxiliary power supply circuit rated 24 V dc, 15 mA. Compatible solenoid valves are
ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge
water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 8 AH provide 90 hours of emergency operation. (See
also LOCAL PROTECTIVE SIGNALING.)
Model PFC-4410 and PFC-4410A Programmable Fire Control Panel, using software Rev. 3.5. Provides four Class B (Style B) alarm signal
initiating device circuits, one Class B (Style B) supervisory signal initiating device circuit, four voltage reversing Class B (Style Y) program-
mable output circuits rated 24 V dc, 1 A, and one auxiliary power supply circuit rated 24 V dc, 50 mA with 12 AH standby batteries or 75 mA
with 17 AH standby batteries. CA2Z Class A initiating device module required to convert two Class B initiating device circuits to Class A (Style
D) operation. Up to two CA2Z modules may be used. Initiating device circuits are capable of cross-zone operation. Compatible solenoid
valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model 73218B4UNLVOC111C2. For FM Approved combinations
of solenoid and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 12 and 17 AH provide 90
hours of emergency operation. (See also LOCAL PROTECTIVE SIGNALING.)
Model PFC-4410-RC and PFC-4410A-RC Fire Alarm Controls, using software Rev. 4.14. Provides four Class B (Style B) alarm signal
initiating device circuits, one Class B (Style B) supervisory signal initiating device circuit, four voltage reversing Class B (Style Y) output
circuits rated 24 V dc, 1 A, and one auxiliary power supply circuit rated 24 V dc, 200 mA. CA2Z Class A initiating device module required to
convert two Class B initiating device circuits to Class A (Style D) operation. Up to two CA2Z modules may be used. Initiating device circuits
are capable of cross-zone operation. Compatible solenoid valves are ASCO Models R8210A107, T8210A107, 8210A107, Skinner Models
73218B4UNLVOC111C2 and 73212BN4TNLVNOC322C2, and Viking Model HV-274-060-001. For FM Approved combinations of solenoid
and deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 12 AH provide the required 90 hours of
emergency operation. (See also LOCAL PROTECTIVE SIGNALING.)
Pyrene Corp, 130 Esna Park Dr, Markham Ontario L3R 1E3 Canada
Fire Alarm and Extinguishment Control Panel Series 4000 configured with 40-3002 extinguishment module and other functional modules
as dictated by the needs of the installation (see listing for the Series 4000 control under LOCAL PROTECTIVE SIGNALING for other
functional modules). For deluge/preaction sprinkler system applications, the Series 4000 control must be configured to provide Class A (Style
D) initiating circuits. Initiating circuits can be configured for cross-zone operation. Release device circuits are rated at 2 A. Compatible solenoid
valves are ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and
deluge water valves, refer to AUTOMATIC WATER CONTROL VALVES. Standby batteries rated 16 AH are available to provide 90 hours
emergency power.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-129
Series Triton RPA Addressable Control System. Analog control panel with Software Revision Level 3.03 using programmed Notification
Appliance Circuits N3 or N4 on the Triton RPA SFI/O card. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil
supervision module which in turn is connected to a compatible 24 V dc actuation device. Optional TEPG-US Model 430657 or 431193
Suppression Release Peripheral connects to the SLCNet circuit and to a notification appliance circuit from either the Triton RPA fire alarm
control panel, or from the Triton EXT Notification Appliance Circuit Extender. This peripheral monitors the output releasing appliance circuit
wiring for opens and shorts. Each releasing appliance circuit must connect to a TEPG-US Model 430687 coil supervision module which in
turn is connected to a compatible 24 V dc solenoid or actuation device. For FM Approved combinations of solenoid and water control valves,
refer to the Automatic Water Control Valve listings that follow. SLCNet signaling line circuits must be configured for Class A, Style 6 wiring
for this application. 24 Vdc batteries rated 25-50 AH are available to provide 90 hours of emergency operation. For battery requirements
exceeding 25 AH, the TEPG-US Models 430548 or 430550 External Battery Charger must be used. (See Control Panel Description under
LOCAL PROTECTIVE SIGNALING.)
Control Panels (compatible for use with Automatic Water Control Valves)
Control Panel Group [(New group number to be assigned)]. These panels are compatible with Solenoid Groups [B]. MR2320 Series
programmable fire alarm releasing control panels.
Siemens Building Technologies Inc, Fire Safety, 8 Fernwood Rd, Florham Park NJ 07932
Automatic Release. ALS2 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are
via SIGA-REL-LG releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system
release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107,
821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and
71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL
VALVES. Standby batteries are available in 24 AH capacity to provide the required 90 hours of standby operation.
Automatic Release. ALS3 Fire Panel (see listing under LOCAL PROTECTIVE SIGNALING). Programmable control. Release circuits are
via SIGA-REL-LG releasing module. Used with model RELA-EOL polarized end of line resistor. For deluge and preaction sprinkler system
release, compatible solenoid valves include Skinner solenoid valve Model LV2LBX25; ASCO solenoid valves Model T821A107, R821A107,
821A107 and 8210G207; Skinner solenoid valves Model 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2, and
71395SN2ENJ1NOH111C2. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL
VALVES. Standby batteries are available in 65 AH capacity to provide the required 90 hours of standby operation.
System 3 Universal Alarm Control. Contains two initiating device circuits for ‘‘Class A’’ operation. FM Approved configuration consists of
CP-35 control panel, PS-35S power supply, BC-35 battery charger and the following modules: DC-35S filter/regulator, TC-30U battery
transfer, RM-30U or RM-30RU release, ZN-31U dual contact zone. Compatible solenoid valves are ASCO Models T8210A107, R8210A107,
8210A107 and Skinner Model LV2LBX25. For FM Approved combinations of solenoid and deluge water valves, refer to AUTOMATIC WATER
CONTROL VALVES. In the event of primary power failure, two 12 V 55 AH GC12550 batteries provide 90 hours of emergency power. See
LOCAL PROTECTIVE SIGNALING listing for other FM Approved modules.
MPC-6000 Fire Alarm Control Unit. Modular System made up of various combinations of devices and programmable configurations.
Enclosures are MPC6-ENC or MPC6-ENC-B with SFTK-6B or SFTK-6R trim kits. Minimum system configuration includes an MPC6-MB2
main terminal board which includes a regulated 24V power supply, MPC6-DB2 display board with firmware version 7.01, an X1 Addressable
Device Circuit with a capacity for 252 Addresses, four independent Class B (Style Y) notification appliance circuits (NACs) which can be
combined in pairs for Class A (Style Z) operation, a Serial Interface Circuit that will drive 16 remote LCD annunicators and up to 8 Serial Relay
Units and Serial Annuicator Units, four Form C relay contacts each rated at 1A @ 28Vdc and an RJ-11 Programming Port and MPC-REL
Releaseing Module with RPT-1 Releasing Power Transformer. 90 hours of secondary power provided by two 12Vdc (38Ah) batteries mounted
in an external BE-1 battery box. An optional external BE-1 battery box is available to allow connection of batteries up to 38Ah. For FM
Approved combinations of solenoid control valves, refer to Automatic Water Control Valve listings. [See complete MPC-6000 system
description under LOCAL PROTECTIVE SIGNALING].
MXL Programmable Modular Fire Alarm System. Uses Version 10.06 operating system and field programming software CSG-M Version
10.03. Requires CSM-4 signal module (configured for releasing service) compatible with Skinner Model LV2LBX25 and ASCO Models
8210A107 (with R or T suffixes) and Alarm-Saf Model AS/PS5-BFS-24-UL power supply. 24 V dc standby batteries rated (15-55 AH) are
available for MXL control and Alarm-Saf power supply (31 AH) to provide 90 hours of emergency operation. (See also LOCAL PROTECTIVE
SIGNALING.)
MXL-IQ Programmable Modular Fire Alarm System. Uses Version. 6.06 operating system and field programming software CSG-M Version
10.03. Requires CSM-4 signal module (configured for releasing service) compatible with Skinner Model LV2LBX25 and ASCO Models
8210A107 (with R or T suffixes) and Alarm-Saf Model AS/PS5-BFS-24-UL power supply. 24 V dc standby batteries rated (15-55 AH) are
available for MXL-IQ control and Alarm-Saf power supply (31 AH) to provide 90 hours of emergency operation. (See also LOCAL
PROTECTIVE SIGNALING.)
FireFinder XLS Fire Alarm Control System. Modular System made up of various combinations of devices and programmable configurations.
Any of the CAB1, CAB2 or CAB3 Cabinet Enclosures may be used with CAB-MP mounting plate, CAB-TK trim kit and card cages CC-2 or
CC-5. Any combination system must house a PMI [Person-Machine Interface] considered the main processor with a firmware level at 3.04;
a Zone Indicating Card [ZIC-4A] which is equipped with four programmable (Class B) Style Y, or (Class A) Style Z circuits. These output
circuits are rated 4A each and must be configured as releasing circuits. A Device Loop Card [DLC] allows a basic system to connect up to
252 addressable analog devices. The DLC has one programmable (Class B) Style 4.0 or (Class A) Style 6 signaling line circuit. Only the
(Class A) Style 6 signaling line circuit is permitted for this releasing application. Any combination of the following compatible devices
may be connected to the DLC: Manual Pull Stations HMS/S & D, HMS-M, HMS-2S, and HMS-SA; Photoelectric and Thermal sensor HFP-11
with 3.0%/ft nominal obscuration sensitivity and 135F/57C temperature sensor, Thermal sensor HFPT-11 rated at 135F/57C thermal sensi-
tivity suitable for a listed spacing of 20 x 20 feet (6.1 x 6.1 m) with any of the following bases: RL-HC, DB-HR, ADB-11, or ADBX-11;
Addressable Switch Interface Module [HTRI-S, -D, -M, or –R]; Loop Isolator Module [HLIM]; Two-wire Smoke Interface Module [HZM] which
is compatible with Models DI-3/3H, DI-A3/A3H, DI-B3/B3H, DT-3P-135, DT-11, PB-1191, PE-3, and PE-11/11T detectors. The HZM must be
converted to (Class A) Style D wiring performance for this releasing application. Each system must be provided with a PSC-12 power
supply which provides 120/240 V ac primary and 24 V dc secondary power. The power supply is provided with four Form C relays each rated
4A @120 V ac. Two 12 V dc (15-100 AH) batteries connect to the PSC-12 to provide 90 hours of back up. Optional Power Supply Extender
[PSX-12], may be connected to provide additional 24 V dc (12 A) power. For Approved combinations of solenoid and water control valves,
refer to the Automatic Water Control Valve listings that follow. [See further description under LOCAL PROTECTIVE SIGNALING].
FS-250 Fire Seeker Fire Alarm Control Unit. Modular System made up of various combinations of devices and programmable configura-
tions. Enclosures are FS-250-ENCL-R or FS-250-ENCL with FS-SFT or FS-SFT-R trim kits. Minimum system configuration includes an
FS-250-MB2 main terminal board which includes a regulated 24 V power supply, FS-250-DB2 display board with firmware version 7.01, an
FM Approvals
September 2007 — Approval Guide
1-130 Automatic Sprinkler Systems
FS-DLC device loop card with a P2 Addressable Device Circuit and capacity for 252 Addresses, four independent Class B (Style Y) notification
appliance circuits (NACs) which can be combined in pairs for Class A (Style Z) operation, a Serial Interface Circuit that will drive 16 remote
LCD annunciators and up to 8 Serial Relay Units and Serial Annunciator Units, four Form C relay contacts each rated at 1A @ 28 V dc and
an RJ-11 Programming Port and FS-REL Releasing Module with FS-RPT Releasing Power Transformer. 90 hours of secondary power
provided by two 12 V dc (38Ah) batteries mounted in an external CAB-BATT battery box. For Approved combinations of solenoid control
valves, refer to Automatic Water Control Valve listings. [See complete FS-250 system description under LOCAL PROTECTIVE SIGNALING].
Siemens Switzerland Ltd, Building Technologies Group, Gubelstrasse 22, CH-6301 Zug Switzerland
ALGORex Fire Detection System. NOTE: This system may not comply with all requirements of NFPA 72-1999 which would be
applicable to FM Approval if the equipment were to be marketed in North America. Programmable fire alarm panel (CSCI1145). 24 V
dc panel operable on primary voltage rating of 240 V ac. (See CS1140 system description under LOCAL PROTECTIVE SIGNALING.)
Preaction and deluge system control requires optional E3G060 I/O module release provides outputs rated at 24 V dc at 2 A max per output,
4 A total per module, alarm horn and illuminated warning panel outputs rated at 24 V dc at 2 A max per output for preaction-deluge releasing
and E3M 071 (DS112V3 NLV 1.2) interactive detection line wired Class A Style 7 for alarm initiation. The E3G080 (CS1140/V7.1) provides
two release outputs rated at 24 V dc at 2 A max, alarm horn and illuminated warning panel outputs rated at 24 V dc at 2 A max, five monitored
detection lines for manual actuation, stop or blocking button (abort), signal contact ‘‘loss of extinguishing agent’’, signal contact ‘‘extinguishing
blocked’’ and signal contact ‘‘extinguishing actuated’’. Additionally, there is a LON interface (Class B signaling line circuit) for connection to
the B3Q440 operating unit ‘‘extinguishing’’ (Firmware B3Q440/27C256-LON/V1.01). The B3Q440 provides indications and controls for a
single extinguishing system. It may be located in the CS1140 enclosure or remotely mounted in a separate enclosure. Indications are provided
for alarm, extinguishing command, extinguishing activated, trouble, power on, automatic actuation of extinguishing blocked and manual
actuation of extinguishing blocked. Controls provided, in addition to a key switch to inhibit their operation, are: automatic actuation of
extinguishing blocked, manual actuation of extinguishing blocked, switch off alarm horn and switch off illuminated warning panel. The B3Q440
also requires a 24 V dc supply from the control unit. (See also LOCAL PROTECTIVE SIGNALING and Automatic Release of Extinguishing
Systems)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-131
System Sensor, Div of Honeywell, 3825 Ohio Ave, Saint Charles IL 60174
PDRP-1001 with operating system firmware revision level A. Including LED Interface Module (4XLM); Zone Relay Module (4XZM); Remote
Annunciator (RZA-4X). Panel provides four input circuits: one detector; one manual release/detector; one waterflow; one supervisory and four
output circuits: one alarm/waterflow bell; one waterflow/supervisory bell; one release; one supervisory bell/release. In addition one regulated
and one unregulated 24 V auxiliary power output; one alarm and one trouble relay output are provided. Combined load for external devices
not to exceed 2.25 A. Field programmable using dip switches for either cross zone or dual zone. For deluge and preaction sprinkler system
release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25 and solenoid
for Star Sprinkler Model D deluge valve. For FM Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER
CONTROL VALVES. Transmitter Module (4XTM) provides a local energy municipal tie for auxiliary protective signaling. In the event of primary
power failure battery packs (24 V dc, 12, 15 AH) are suitable for 90 hours of standby operation.
Viking Electronic Services LLC, 620 Allendale Rd, King of Prussia PA 19406
e-LAN and e-LAN Lite Fire Alarm Control Panels. Basic system consists of a 4 Amp power supply module (P/N VF8115-00), Control Unit
Board (P/N VF1500-00) and Panel Annunciator Board (P/N VF1501-00). Release circuit requires a 2.7K end-of-line device for Squibb
supervision (Not required for solenoid operation) and SRM solenoid release module (P/N VF6006-00). For deluge and preaction sprinkler
system release, compatible solenoid valves include ASCO Models R8210A107, T8210A107, 8210A107 and Skinner Model LV2LBX25. For
Approved combinations of solenoid and water control valves refer to AUTOMATIC WATER CONTROL VALVES. Standby battery (24 V dc,
60 AH) provides 90 hour standby operation. (See control panels descriptions under LOCAL PROTECTIVE SIGNALING).
FM Approvals
September 2007 — Approval Guide
1-132 Automatic Sprinkler Systems
Electric
Dry Pilot Pneu-
Wet Pilot Sprinkler matic Hydraulic Solenoid Control
Sprinkler Line & Rate-of- Rate-of- Release Panel Detec-
Manufacturer Water Valve Designation & Size Line Actuator‡ Rise# Rise# Groups† Groups+ tors
Anber Globe *Model A 21⁄2 in. NPS X X [E] X [E] X [1] X [2]
Av de Las Flores 13, Models B, BX. 4, 6 in. NPS; 100, X X [E] X [E] X [1] X [2]
Parque Ind El Molino, 150 mm NPS
28970 Humanes de Madrid,
Madrid Spain
Grinnell Corp, Grinnell or Gem Model A-4. 4, 6 X X [D-1] X X [A] X [1] X [2]
3 Tyco Park, in. NPS X [B] X [2]
Exeter NH 03833 X [D] X [1] X [2]
X [E] X [1] X [2]
*Grinnell or Gem Model B. 2 in. X X [D-1] X [A] X [1] X [2]
NPS X [B] X [2]
X [D] X [E] X [1] X [2]
Grinnell or Gem Model C. 21⁄2, 6 X
in. NPS
Grinnell or Gem Model F445. 21⁄2 X X [D-1] X [A] X [1] X [2]
in. NPS X [D] X [1] X [2]
Angle Body X [E] X [1] X [2]
X [B] X [2]
Any device listed under ELECTRICAL SIGNALING, unless listed for signaling or special application only.
Grinnell or Gem Model F446. 21⁄2 X X [D-1] X X [F] X [4]
in. NPS
Angle Body. 250 psi (1725 kPa)
*Grinnell or Gem Thermal Control X
Valve
Model F430. 1, 11⁄2 in. NPS.
Wormald Model A1. 100, 150 mm X X [A] X [A] X [1] X [2]
(4, 6 in.)
Central Sprinkler Co, Model DL. 2 in. X
451 N Cannon Ave, Model A. 4, 6 in. NPS X X [DP-1] X [A] X [1] X [2]
Lansdale PA 19446 Model B, 4 in. X X [E} X [2]
Model B, 3, 6 in. NPS X X [AA-R] X [A] X [E] X [1] X [2]
Model C, 3, 6, in. NPS X X [AA-R]
X indicates FM Approved or compatible. ‡DRY PILOT ACTUATOR — Compatible models are shown in brackets in the table.
#See DELUGE, PREACTION or REFRIGERATED AREA SPRINKLER SYSTEM listings. Open brackets [ ] indicate none required.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-133
Deluge System
Only Deluge or Preaction System
Pneu-
Dry Pilot matic Electric
Wet Pilot Sprinkler Rate- Hydraulic Solenoid Control
Sprinkler Line & of- Rate-of- Release Panel Detec-
+
Manufacturer Water Valve Designation & Size Line Actuator‡ Rise #
Rise# Groups† Groups tors
Mil Ltd, INBAL Model 799-DG-01. 3, 4, 6, X X
17 Moshe Beker St, 8 in. NPS. 6 in. NPS. 300 psi
Box 15200, Rishon (2070 kPa) rated working pressure.
Lezion 75051, Israel INBAL Model 799-DG-04-A, 3, 4,
6, 8 in. NPS. 300 psi (2070 kPa) X X
rated working pressure.
INBAL Model 799-DG-04-B, 3, 4,
6, 8 in. NPS. 300 psi (2070 kPa) X X
rated working pressure.
INBAL Model 799-DG-04-C, 3, 4,
6, 8 in. NPS. 300 psi (2070 kPa)
rated working pressure. X[D] X [E] X [1] X [2]
Minimax GmbH & Co KG, Model FSX Deluge Valves. Sizes X X X [L] X [11]
Box 1260, 50, 80, 100 and 150 mm [Minimax
Industriestrasse 10-12, 232 (16 bar) RWP 20 9353-E]
D-23849 Bad Oldesloe,
Germany
Any device listed under ELECTRICAL SIGNALING, unless listed for signaling or special application only.
Reliable Automatic Sprinkler *Model A. 21⁄2 in. NPS X X [A] X [E] X X [1] X [2]
Co Inc, Models B, BX. 4, 6 in. NPS; 100, X X [A] [D] X [1] X [2]
1470 Smith Grove Road, 150 mm NPS X [E] X
Liberty SC 29657-0313 [D]
Star Sprinkler Inc, Model A. 3, 4, 6 in. NPS X X [AA-R] X [A][E] X [1] X [2]
7071 S 13th, Suite 103, Model B. 2 in. NPS X [DP-1] X X [1] X [2]
Oak Creek WI 53154 X [DP-1] [A][D][E] X [2]
Model D. 3, 6 in. NPS X X [B] X [3]
Model G. 3, 4, 6 in. NPS X X [AA-R] X [C] X [1] X [2]
Model A-1. 3, 4, 6 in. NPS [DP-1] X [A][E] X [4]
250 psi (1725 kPa) X X [DP-1] X [F] X [4]
Model G-1. 3, 4, 6 in. NPS X [F]
250 psi (1725 kPa) X [DP-1]
Total Walther GmbH, Model EKFV. DN 200 mm (8 in.). X
Feuerschutz und Sicherheit, A spool piece containing a 2 in.
Waltherstrasse 51, 51069 (51 mm) drain valve is attached to
Köln, Germany the inlet flange of each valve.
Tyco Fire Products, Model DV-1. 4, 6 in. NPS X X [DP-1] X [A] X [1] X [2]
451 N Cannon Ave, X [B] X [2]
Lansdale PA 19446 X [D] X [1] X [2]
X [E] X [1] X [2]
Model DV-3. 21⁄2 in. NPS. X X [DP-1] X [A] X [1] X [2]
Angle Body. X [D] X [1] X [2]
X [E] X[1] X [2]
X [B] X [2]
Model DV-3HP. 21⁄2 in. NPS. X X [DP-1] X X [F] X [4]
Angle Body.
250 psi (1725 kPa)
*Tyco Model DV- 2. 2 in. NPS X X [DP-1] X [A] X [1]
X [B] X [2]
X [D] X [2]
X [E] X [1]
X [2]
Model DV-5, 11⁄2, 2, 3, 4, 6, 8 in. X X [DP-1] X[F] X[4]
NPS
(40, 50, 80, 100, 150, 200 mm DN)
250 psi (1725 kPa).
Tyco Fire Products systems are dual rated and are FM Approved only as a complete Deluge or
Preaction System. (See appropriate listing.) System ratings are dependent on the solenoid valve
used. Only major electrical components listed above may be interchanged.
Victaulic Company, Series 758 FireLock 11⁄2, 2, 21⁄2, 3, X X [753A] X [B] X [1] X [2]
Box 31, 4, 6 and 8 in. grv × grv; 175 psi X X [D]
Easton PA 18044 (1205); [776LPA]
4, 6 and 8 in. available in flange X [I]
inlet × grv outlet; 300 psi (2070 X
kPa). [776LPA] X [I] X [I] X [2]
Series 769 FireLock 11⁄2, 2, 21⁄2, 3,
4, 6 and 8 in. grv x grv; 300 psi
(2070 kPa)
The Viking Corp, *Model E-3, E-4. 11⁄2 in. NPT. X X X X X [F] X [4] X [8]
210 N Industrial Park Rd, *Model E-1, E-2. 2 in. NPT. X [J] X [K] X [1] X [2]
Hastings MI 49058 **Model E-1, E-2. 3, 4, 6 in. NPS.
Available with FxF and FxG.
Model F-1, F-2: 11⁄2, 2, 21⁄2, 3, 4,
6, 8 in. NPS. Available with GxG,
FxF and FxG and screwed ends
(see system description) Above
systems: 250 psi (1725 kPa)
Viking systems are dual rated and are FM Approved only as a complete Deluge or Preaction Sys-
tem. (See appropriate listing.) Only major electrical components listed above may be inter-
changed. Solenoid Groups J and K used in Viking Sure-Fire Fail/Safe Systems.
X indicates FM Approved or compatible. ‡DRY PILOT ACTUATOR — Compatible models are shown in brackets in the table.
#See DELUGE, PREACTION or REFRIGERATED AREA SPRINKLER SYSTEM listings. Open brackets [ ] indicate none required.
FM Approvals
September 2007 — Approval Guide
1-134 Automatic Sprinkler Systems
The automatic-opening valves on the opposite page are FM Approved for controlling the flow of water to
sprinklers, spray nozzles or mechanical foam-making equipment when supervised as required. Unless otherwise
noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Valves identified in the listing by a single asterisk (*) have screwed connections only; valves identified by a double
asterisk (**) are available with flanged inlet and cut-grooved outlet connections; others have flanged inlet and outlet
connections.
See DELUGE SPRINKLER SYSTEMS or PREACTION SPRINKLER SYSTEMS listings for detailed information.
Footnotes to the Table follow.
†SOLENOID RELEASE VALVES — Compatible valve groups are shown in brackets in the table. Empty
brackets [ ] indicate none required.
Skinner solenoid valve Model LV2LBX25, 24 V dc, 11 WATTS, 458 mA, 1⁄2 in. NPS, 1⁄2 in. orifice.
ASCO solenoid valve Model T8210A107, 24 V dc, 16.8 WATTS, 700 mA, 1⁄2 in. NPS, 5⁄8 in. orifice.
ASCO solenoid valve Model R8210A107, 24 V dc, 16.8 WATTS, 700 mA, 1⁄2 in. NPS, 5⁄8 in. orifice.
ASCO solenoid valve Model 8210A107, 24 V dc, 16.8 WATTS, 700 mA, 1⁄2 in. NPS, 5⁄8 in. orifice.
Star Sprinkler Corp. Solenoid P/N 5550, 24 V dc, part of Model D deluge valve.
ASCO solenoid valve Model 8210G207, 24 V dc, 10.6 WATTS, 440 mA, 1⁄2 in. NPS, 1⁄2 in. orifice.
Skinner solenoid valve Model 73218BN4UNLVNOC111C2, 24 V dc, 10 WATTS, 420 mA, 1⁄2 in. NPS, 5⁄8 in. orifice.
Skinner solenoid valve Model 73212BN4TN00N0C111C2, 24 V dc, 10 WATTS, 420 mA, 1⁄2 in. orifice, 5-300 psi rated working pressure.
Skinner solenoid valve Model 73212BN4TNLVNOC322C2, 24 V dc, 22 WATTS, 1⁄2 in. NPS, 0.92 A, 250 psi (1725 kPa), 1⁄2 in. orifice.
Skinner solenoid valve Model 71395SN2ENJ1NOH111C2, 24 V dc, 10 WATTS, 420 mA, 1⁄4 in. NPS, 1⁄16 in. orifice, 250 psi (1725 kPa) rated
working pressure.
Victaulic Series 753-E solenoid valve, 24 V dc, 8.7 WATTS, 1⁄2 in. NPS, 364 mA, 300 psi (2069 kPa), 1⁄2 in. orifice.
Viking Model No. 11591 and 11592 (explosion proof) normally closed (NC) solenoid valve, 24 V dc, 10 WATTS, 1⁄2 in. NPS, 300 psi
(2069 kPa), 4.1 Cv.
Viking Model No. 11595 and 11596 (explosion proof) normally open (NO) solenoid valve, 24 V dc, 10 WATTS, 1⁄2 in. NPS, 300 psi
(2069 kPa), 4.1 Cv.
Viking Model No. 11601 and 11602 (explosion proof) normally closed (NC) solenoid valve, 24 V dc, 9 WATTS, 1⁄2 in. NPS, 250 psi
(1725 kPa), 6.2 Cv.
Viking Model No. 13215 normally open (NO) solenoid valve, 24 V dc, 9 WATTS, 1⁄2 in. NPS, 250 psi (1725 kPa), 4.1 Cv.
Minimax part no. 84 0131 impulse type solenoid valve. The valve shifts position (open or closed) when a voltage pulse is applied to the coil.
After shifting position it remains there without electrical power being applied, even if the supply voltage is disconnected. Only when the polarity
of the voltage is reversed will the valve shift to the other position. It is the electrical release for the Minimax Model FSX Deluge Valves. In these
deulge systems, it is installed in the NC (normally closed) position upon initial set-up.
Nominal voltage of 24 Vdc, operating voltage of 18-28 Vdc, 11 WATTS, 460 mA,1⁄2 in. NPS, 13 mm (1⁄2 in.) orifice dia.
+CONTROL PANELS. Details for panels are listed under AUTOMATIC RELEASES. Panels must have
appropriately sized battery to provide required 90 hours of emergency power.
Control Panel Group [1]. These panels are only compatible with Solenoid Groups [A], [D], [E], [G], [I], [J] and [K]:
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-135
Control Panel Group [2]. These panels are compatible with Solenoid Groups [A], [B], [D], [E], [G], [I], [J] and [K]:
ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486
Unimode-640 Fire Alarm Control Panel.
Buckeye Fire Equipment Co, 110 Kings Road, King Mountain NC 28086
Shield-SZ Fire Alarm Control Panel.
FM Approvals
September 2007 — Approval Guide
1-136 Automatic Sprinkler Systems
Pem-All Fire Extinguisher Corp, Div Pem Systems Inc, 39A Myrtle St, Cranford NJ 07016
PEM-2001 Preaction/Deluge Control System.
Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146
PFC Series 100R, PFC 2000RC.
Models PFC-100RC, PFC-4410, PFC-4410A.
Pyrene Corp, 130 Esna Park Dr Markham Ontario L3R 1E3 Canada
Fire Alarm Control Panel Series 4000.
Siemens Building Technologies Inc, Fire Safety, 8 Fernwood Rd, Florham Park NJ 07932
FireFinder XLS Fire Alarm Control System housing a PMI main processor with a firmware level at 3.04.
MPC-6000 Fire Alarm Control Unit.
MXL Programmable Modular Fire Alarm System.
System 3 Universal Alarm Control.
FS-250 Fire Seeker Fire Alarm Control Unit
System Sensor, Div of Honeywell, 3825 Ohio Ave Saint Charles IL 60174
PDRP-1001 Preaction/Deluge Control System.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-137
Control Panel Group [3]. These panels are compatible with Solenoid Group [C].
ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486
Unimode-640 Fire Alarm Control Panel.
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Micro 1001 Preaction/Deluge Control System.
Pem-All Fire Extinguisher Corp, Div Pem Systems Inc, 39A Myrtle St, Cranford NJ 07016
PEM-2001 Preaction/Deluge Control System.
Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146
PFC 2000RC.
System Sensor, Div of Honeywell, 3825 Ohio Ave Saint Charles IL 60174
PDRP-1001 Preaction/Deluge Control System.
Control Panel Group [4]. This panel is compatible with Solenoid Group [F].
ADT Security Services Inc, One Town Center Rd, Boca Raton FL 33486
Unimode-640 Fire Alarm Control Panel.
FM Approvals
September 2007 — Approval Guide
1-138 Automatic Sprinkler Systems
Potter Electric Signal Company, 2081 Craig Road, Saint Louis MO 63146
PFC 2000RC.
Control Panel Group [5]. This system is only compatible with Solenoid Group [E].
Siemens Switzerland Ltd, Building Technologies Group, Gubelstrasse 22, CH-6301 Zug Switzerland
CS1140/1145 AlgoRex Fire Detection System.
Control Panel Group [6]. These panels are only compatible with Solenoid Groups [A] and [B].
Control Panel Group [7]. These panels are compatible with solenoid Groups [A], [B], [C], [D], [E], [F] and [G].
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-139
Control Panel Group [8]. These panels are compatible with Solenoid Group [F] and [H].
Siemens Building Technologies Inc, Fire Safety, 8 Fernwood Rd, Florham Park NJ 07932
FireFinder XLS Fire Alarm Control System housing a PMI main processor with a firmware level at 3.04.
MPC-6000 Fire Alarm Control Unit.
FS-250 Fire Seeker Fire Alarm Control Unit
Control Panel Group [9]. These panels are compatible with Solenoid Groups [A], [B], [D], [E], [F] and [G]:
Control Panel Group [10]. These panels are compatible with Solenoid Groups [B], [D], [E], [F] and [G]:
Control Panel Group [11]. This electrical control panel is compatible with Solenoid Group [L]:
Minimax GmbH & Co KG, Box 1260 Industriestrasse 10-12, D-23840 Bad Oldsloe, Germany
Minimax FMZ 4100 GAB 32 Preaction Deluge Control System.
PRESSURE GAUGES
Gauges for sprinkler systems and fire pumps are designed for use with air or water. These gauges are usually of
the Bourdon tube type. The moving parts are fabricated of appropriate corrosion-resistant materials.
When installed on the air side of a dry pipe system, a retard type gauge may be used. This gauge is assembled
with a tube appropriate to the unretarded pressure range of the gauge and is provided with a spring to resist the full
scale load.
The two common sizes are 41⁄2 and 31⁄2 in. diameter. These gauges can be calibrated with a hydraulic testing unit
by adjusting the dial pointer to read correctly at known pressures. Accuracy requirements are that the gauge be
correct within 2% over the center third of its scale and within 3% over the remaining two-thirds. Dial marking
subdivisions correspond to the maximum accuracy of the gauge.
For service on fire pumps where the suction may be taken under a lift, compound pressure vacuum gauges are
available graduated in pressure units over both the pressure and vacuum scales, and are designed not to be injured
by vacuum.
To minimize possible damage and provide maximum accuracy, gauges should be selected with scales of about
twice the maximum system pressure.
FM Approvals
September 2007 — Approval Guide
1-140 Automatic Sprinkler Systems
Brecco Corp, 4433 W Van Buren St, Suite #5, Phoenix AZ 85043-3925
Pressure Gauge. Model W-101, Air/Water; 0-300 psi (0-2070 kPa). 31⁄2 in.
Retard Pressure Gauge. Model W-102, air; 0-80-250 psi (0-550-1725 kPa). 31⁄2 in.
Kujawska Fabryka Manometrow ‘‘KFM’’ S.A., uL. Legska 29/35, 87-800 Wloclawek, Poland
Model 111.10.100. Plastic or steel case with a 1⁄4 in. male NPT bottom connection, 4 in. (100 mm) size.
Model 111.12.100. Steel case and a 1⁄4 in. male NPT rear connection, 4 in. (100 mm) size.
Measuring Ranges:
Psi kPa
-15 to 0 -1 to 0
-15 to 150 -1 to 9
0 to 150 0 to 10
0 to 250 0 to 16
0 to 400 0 to 25
0 to 600 0 to 40
WIKA ALEXANDER WIEGAND GmbH & Co, Alexander-Wiegand-Straße, 63911 Klingenberg, Germany
Pressure Gauge. Model 111.10.100. Plastic or steel case, 31⁄2 in size (100 mm).
Pressure Gauge. Model 111.12.100. Steel case only, 31⁄2 in size (100 mm).
Measuring Ranges:
Psi kPa Bar
-15 to 0 -100 to 0 -1 to 0
-15 to 150 -100 to 900 -1 to 9
0 to 150 0 to 1000 0 to 10
0 to 250 0 to 1600 0 to 16
0 to 400 0 to 2500 0 to 25
0 to 600 0 to 4000 0 to 40
Outside screw and yoke gate valves are recommended for service indoors and in pits outdoors. They are not
recommended for throttling service. The stem indicates at a glance whether or not the valve is open. Smaller sizes,
3⁄4 through 2 in. NPS inclusive, are of bronze. Large sizes, 21⁄2 through 14 in. NPS inclusive, are of iron, bronze
mounted. One manufacturer makes valves of bronze up through the 3 in. size. Unless otherwise noted in the listing,
these valves have 175 psi (1205 kPa) rated working pressure.
AVK Saudi Valves Manufacturing Co Ltd, Phase 4, Street No. LO 404, Jeddah, KSA 21443
‡Series 45 Resilient Seated Gate Valves. 21⁄2 through 12 in. NPS. Valves have a rated working Pressure of 250 psi (1725 kPa).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-141
Series 45 Resilient Seated Gate Valves. 3 through 8 in. NPS valves have a rated working pressure of 250 psi (1725 kPa). 4, 6, and 8 in.
NPS sizes only, available with AISI 304 Stainless Steel stems as an alternate material to bronze stems.
3, 4, 6, 8 Grooved Ends
3, 4, 6, 8 Flanged by Grooved Ends
American Darling Valve, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202
All Series 2500-1 ‡. All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure.
American Flow Control, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202
Series 2500. Resilient Seated Gate Valves. 2 through 12 in. NPS valves have a rated working pressure of 250 psi (1725 kPa). 14 and 16 in.
NPS valves have a rated working pressure of 200 psi (1380 kPa). Available with the following end connections:
Series 2500. Resilient Seated Gate Valves. 250 psi (1725 kPa) rated working pressure. Available with the following end connections:
Clow Canada, a Div of Canada Pipe, 254 Henry St, Brantford, Ontario N3T 5T7, Canada
Fig. 459. 1⁄2 through 2 in. NPS.
Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577
Series F-6100. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
Model No. Size End Connections
Model 2638. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
4, 6, 8, 10, 12 Flanged
4, 6, 8, 10, 12 Flanged × Groove
4, 6, 8, 10, 12 Flanged × Mechanical Joint
4, 6, 8, 10, 12 Flanged × Tyton
4, 6, 8, 10, 12 Grooved
4, 6, 8, 10, 12 Mechanical Joint × Mechanical Joint
4, 6, 8, 10, 12 Mechanical Joint × Tapping
4, 6, 8 PVC
4, 6, 8, 10, 12 Tyton
Model 2639 Resilient Seated Gate Valves. Sizes 21⁄2 through 3 in. NPS. 250 psi (1725 kPa) rated working pressure. Sizes 4 through 12 in.
NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:
FM Approvals
September 2007 — Approval Guide
1-142 Automatic Sprinkler Systems
Model 2640. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC
Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
2, 3, 4, 6, 8, 10, 12 Flanged
Model 722U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 722H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 722G. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 722GF. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Fivalco (Qingdao) Co Ltd, 11 Shuangyuan Road, Chengyang Qingdao, Shandong PRC 266111
Model GVOSY-1161-200PSI. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure.
Available with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)
Model GVOSY-1161-250PSI. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available
with the following end connections:
‡Resilient seat.
Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901
Figure 66. Sizes 1⁄2 through 2 in. NPS. Available with the following end connections:
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-143
Figure 67. Sizes 21⁄2 through 6 in. NPS. Available with the following end connections:
21⁄2, 3, 4, 6 Threaded
Model Ken-Seal II. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with
the following end connections:
Model KS-FW. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
Model KS-RW. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
4, 6, 8, 10, 12 Flanged
21⁄2, 3, 4, 6, 8 Flanged x Grooved
21⁄2, 3, 4, 6, 8 Grooved
Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd,
Wolverhampton WV4 WTX, United Kingdom
Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
2, 3, 4, 6, 8, 10, 12 Flanged
Model 722U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 722H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 722G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end
connections:
3, 4, 6 Grooved
Lien Hwa Iron Works Co Ltd, 112 Sec 2 Kuang Fu Rd, Sanchung Taipei Hsien 24113, Taiwan ROC
Fig. 101F. 21⁄2 through 10 in. NPS. Flanged.
Fig. 151RB‡. 21⁄2 through 8 in. NPS. Flanged.
‡Resilient seat.
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)
‘‘United’’ Model 5100. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with
the following end connections:
4, 6, 8, 10, 12 Flanged
4, 6, 8, 10, 12 Mechanical Joint
‡Resilient seat.
Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151
Model 2885FP. Metal to Metal Seated Gate Valve. 21⁄2 through 8 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
21⁄2, 3, 4, 6, 8 Flanged
FM Approvals
September 2007 — Approval Guide
1-144 Automatic Sprinkler Systems
Figure 118. Metal to Metal Seated Gate Valve. 1 through 2 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the following
end connections:
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
Quikcoup Style 400. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with
the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)
Quikcoup Style 425. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with
the following end connections:
Series 2079. Resilient Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.
A-2079-6 4, 6, 8, 10 Flanged
A-2079-16 4, 6, 8, 10 Flanged by Mechanical Joint
A-2079-23 4, 6, 8, 10 Mechanical Joint
A-2079-24 4, 6, 8, 10 A/C Pipe Ends
A-2079-26 4, 6, 8, 10 Flanged by A/C Pipe End
A-2079-53 4, 6 Flanged by Grooved
Figure 2360*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure 2361*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure 2362*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure 2460. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. Available with the following end connections:
21⁄2, 3, 4, 6, 8 Compression Ends
21⁄2, 3, 4, 6, 8, 10, 12 Flanged
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping Flange
4, 6, 8 Mechanical Joint (Cut In/D-150)
4, 6, 8, 10, 12 Slip – On
2 1⁄ 2, 3 Threaded
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-145
Figure 2462. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. Available with the following end connections:
21⁄2, 3, 4, 6, 8 Compression Ends
21⁄2, 3, 4, 6, 8, 10, 12 Flanged
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping Flange
4, 6, 8 Mechanical Joint (Cut In/D-150)
4, 6, 8, 10, 12 Slip – On
2 1⁄ 2, 3 Threaded
*Bonnet with indicator post flange.
**Rated Working Pressure 250 psi (1724 kPa).
AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end
connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.
‡Resilient seat.
National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE
Model NF-OSY175U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with
the following end connections:
Model NF-OSY200U. Resilient Seated Gate Valve. 2 1⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
Model NF-OSY250H. Resilient Seated Gate Valve. 2 1⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the
following end connections:
Model NF-OSY250G. Resilient Seated Gate Valve. 3 through 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
2, 3, 4, 6, 8, 10, 12 Flanged
Model 722U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 722H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 722G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end
connections:
3, 4, 6 Grooved
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model RELOSY-200-RW. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available
with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)
Model RELOSY-250-RW. Resilient Seated Gate Valves. Sizes 4, 6 and 8 in. NPS 250 psi (1725 kPa) rated working pressure. Available with
the following end connections:
Shanghai Karon Valves Machinery Co Ltd, No 815 Deyuan Road Nanxiang, Jiading District Shanghai, PRC
Series RRHX. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 232 psi (1600 kPa) rated working pressure. Available with the
following end connections:
FM Approvals
September 2007 — Approval Guide
1-146 Automatic Sprinkler Systems
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Model 762U. Metal to Metal Seated Gate Valve. 2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
Model 722U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 722H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Model 722G. 3, 4 and 6 in. NPS. Grooved ends. Resilient Seated. 200 psi (1380 kPa).
Siam Cast Iron Works Co Ltd, Samutsakorn Industrial Estate, Soi 7, 1/12 Moo 2, Rama II Rd, Tahsai, Muang,
Samutsakorn 74000, Thailand
Model 105U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477
No. G-610. 21⁄2 through 12 in. Flanged, 200 psi (1380 kPa).
No. B-133. 1 through 2 in. NPS.
No. G-633. 21⁄2 through 6 in. NPS. Screwed.
No. G-634. 21⁄2 through 14 in. NPS. Flanged.
No. F-670. 2 through 10 in. NPS, flanged, 300 psi (2070 kPa) working pressure; 12 in. NPS, flanged, 250 psi (1725 kPa) working pressure.
Tong Kwang Valve Industrial Co Ltd, No. 1-1 Ming Chuan Rd, Ming-Sheng Li Tansui, Taipei Hsien, Taiwan ROC
Model 073U. 2, 21⁄2, 3, 4, 6, 8, 10 and 12 in. NPS. Flanged.
‡Resilient seat.
Tyco Water Valve (Shanghai) Co Ltd, No. 399 Jiu Ye Road, Qing Pu Industrial Zone, Shanghai China 201700
Series TM Resilient Seated Gate Valves. Rated working pressure 232 psi (1600 kPa). Available with the following end connections:
2, 21⁄2, 3, 4, 5, 6, 8, 10, 12
TMRX-XXXX Flanged × Flanged (ANSI, ISO, JIS)
50, 65, 80, 100, 125, 150, 200, 250, 300
2, 21⁄2, 3, 4, 5, 6, 8, 10, 12
TMRG-XXXX Grooved × Grooved
50, 65, 80, 100, 125, 150, 200, 250, 300
2, 21⁄2, 3, 4, 5, 6, 8, 10, 12,
TMRT-XXXX Flanged × Grooved
50, 65, 80, 100, 125, 150, 200, 250, 300
United States Pipe & Foundry Co, 3300 First Ave N, Birmingham AL 35222
Metroseal Series*. 4, 6, 8, 10, 12, 14 and 16 in. NPS. 250 psi (1725 kPa) working pressure. Double flanged, double mechanical joint ends
and flanged by mechanical joint ends through 16 in. nominal size, Tyton ends through 12 in. nominal size and TR Flex ends in 16 in. nominal
size only.
*Resilient seat.
Figure USP0*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-147
Figure USP1*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure USP2*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end
connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.
3, 4, 6, 8 Grooved
Figure 771H. Resilient Seated Gate Valve. Sizes 21⁄2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure.
Available with the following end connections:
Figure 771F. Resilient Seated Gate Valve. Sizes 21⁄2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure.
Available with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI Class 125, BS10 Table E, BS4505 DIN PN10, JIS B2212, JIS B2213)
FIREKING – Fig. No. OF250-####. Resilient Seated Gate Valves. Sizes 4 through 8 in. NPS. 250 psi (1725 kPa) rated working pressure.
Available with the following end connections:
4, 6, 8 Flanged × Flanged (ANSI Class 125, BS10 Table E, BS4505 DIN PN10 & PN16, JIS B2212, JIS B2213)
#### Valve size in millimeters
Waterous Co, 125 Hardman Ave So, South Saint Paul MN 55075-1191
All Series 2500-1 ‡. All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure. Available in the following end connections:
Series 2500‡. Resilient Seated Gate Valves. 2 through 3 in. NPS OS&Y valves have a rated working pressure of 250 psi (1725 kPa).
Available with the following end connections:
FM Approvals
September 2007 — Approval Guide
1-148 Automatic Sprinkler Systems
Model 409. Resilient Seated Gate Valves. Sizes 2 through 10 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
Inside screw gate valves are used underground with indicator posts attached or as roadway box valves (curb box
installation). FM Approved valves are available with a variety of end connections as indicated in the listings.
Valves having Ring-Tite, Fluid-Tite or Tyton-Joint connections should be anchored in place during installation.
Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
AVK Saudi Valves Manufacturing Co Ltd, Phase 4, Street No. LO 404, Jeddah, KSA 21443
Series 45. Resilient seat gate valves, with or without Indicator Post Flange. 250 psi (1725 kPa) working pressure.
Series 45 Resilient Seated Gate Valves. 3 through 8 in. NPS valves have a rated working Pressure of 250 psi (1725 kPa). 4, 6 and 8 in.
NPS sizes only, available with AISI 304 Stainless Steel stems as an alternate material to bronze stems. 4 through 8 in. available with or without
3, 4, 6, 8 Grooved Ends
3, 4, 6, 8 Flanged by Grooved Ends
American Darling Valve, Div American Cast Iron Pipe Co (ACIPCO), Box 2727 Birmingham AL 35202
Series 2500-1‡. All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure and 4 through 12 in. sizes are available with or
without an indicator post flange.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-149
American Flow Control, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202
Series 2500. Resilient Seated Gate Valves. 2 through 12 in. NPS valves have a rated working pressure of 250 psi (1725 kPa). 14 and 16
in. NPS valves have a rated working pressure of 200 psi (1380 kPa). Available with the following end connections:
4, 6, 8, 10, 12 Flanged
4, 6, 8 Tyton Joint
4, 6, 8, 10, 12 Slip-On for PVC Pipe
*Bonnet with indicator post flange.
†Bonnet without indicator post flange.
‡Resilient seat.
Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577
Series F-5700. Metal to Metal Seated Gate Valves. Sizes 21⁄2 through 14 in. NPS. 200 psi (1380 kPa) rated working pressure. Available
with the following end connections:
Model No. Size End Connections
Series F-6100. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
Model No. Size End Connections
Model 2638. Resilient Seated Gate Valves. 4 through 16 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 2639 Resilient Seated Gate Valves. Sizes 2 through 3 in. NPS. 250 psi (1725 kPa) rated working pressure. Sizes 4 through 12 in.
NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end connections:
FM Approvals
September 2007 — Approval Guide
1-150 Automatic Sprinkler Systems
Model 2640. Resilient Seated Gate Valves. 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
East Jordan Iron Works Inc, 301 Spring Street, East Jordan MI 49727
Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC
Model 710U. Metal to Metal Seated Gate Valve. 21⁄2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
Model 721U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 721H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 721G. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. All valves are available with
an operating nut or indicator post flange with operating nut. Available with the following end connections:
Model 721GF. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. All valves are available
with an operating nut or indicator post flange with operating nut. Available with the following end connections:
Fivalco (Qingdao) Co Ltd, 11 Shuangyuan Road Chengyang, Qingdao Shandong, PRC 266111
Model GVNRS-1161-200PSI†. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure.
Available with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged ANSI, BS10, BS4505, JIS B2212, JIS B2213)
†Available with or without indicator post flange.
Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901
KS-FW. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available with the following
end connections.
KS-RW. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available with the following
end connections.
4, 6, 8, 10, 12 Flanged
4, 6, 8, 10, 12 Mechanical Joint
4, 6, 8, 10, 12 Mechanical Joint x Flanged
4, 6, 8, 10, 12 Mechanical Joint x Tapping Flange
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-151
4, 6, 8, 10, 12 Push - On
4, 6, 8, 10, 12 Push - On x Flanged
4, 6, 8 Push - On for PVC
Ken-Seal D†. Resilient Seated Gate Valves. 4 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Ken-Seal II†. Resilient Seated Gate Valves. 2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
2, 21⁄2, 3, 4, 6, 8, 10, 12 Flanged
3, 4, 6, 8, 10, 12 Flanged by Standardized Mechanical Joint
4, 6, 8, 10, 12 Flanged by Push-On
2, 3, 4, 6, 8, 10, 12 Standardized Mechanical Joint
4, 6, 8, 10, 12 Standardized Mechanical Joint by Flanged
4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping
4, 6, 8, 10, 12 Push-On
2, 21⁄2, 3, 4, 6, 8, 10, 12 Push-On for PVC
2, 2 1⁄ 2, 3 Threaded
Model 2620†. 14 in. NPS. Available with standardized mechanical joint and flanged ends.
Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd,
Wolverhampton WV4 WTX, United Kingdom
Model 710U. Metal to Metal Seated Gate Valve. 21⁄2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
Model 721U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 721H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 721G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end
connections:
3, 4, 6 Grooved
Lien Hwa Iron Works Co Ltd, 112 Sec 2 Kuang Fu Rd, Sanchung Taipei Hsien 24113, Taiwan ROC
Fig. 253RB‡. 4 through 8 in. NPS. Flanged.
Fig. 263RB‡. 4 through 8 in. NPS. Standardized mechanical joint.
‡Resilient seat.
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)
†Available with or without indicator post flange.
4, 6, 8, 10, 12 Flanged
4, 6, 8, 10, 12 Mechanical Joint
4, 6, 8, 10, 12 Mechanical Joint × Flange
4, 6, 8, 10, 12 Mechanical Joint × Tapping
4, 6, 8, 10, 12 Push-on Joint
4, 6, 8, 10, 12 Push-on × Flange
FM Approvals
September 2007 — Approval Guide
1-152 Automatic Sprinkler Systems
Series 7000. Resilient Seated Gate Valves. Sizes 4 through 12 in. NPS. 200 psi (1380 kPa) rated working Pressure. All available with or
without indicator post flange. Available with the following end connections:
4, 6, 8, 10, 12 Flanged
4, 6, 8, 10, 12 Mechanical Joint
4, 6, 8, 10, 12 Mechanical Joint × Flange
4, 6, 8, 10, 12 Mechanical Joint × Tapping
4, 6, 8, 10, 12 Push-on Joint
4, 6, 8, 10, 12 Push-on × Flange
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
Quikcoup Style 450†. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available
with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged × Flanged (ANSI, BS10, BS4504, JIS B2212, JIS B2213)
†Available with or without indicator post flange.
Series 2052*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.
Figure No. Size End Connections
Series 2074. Resilient Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.
Figure No. Size End Connections
Series 2075*. Resilient Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Available with the following end connections.
Figure No. Size End Connections
Series 645*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Tapping Valve. Available with the following end
connections.
Figure No. Size End Connections
Series 698*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Tapping Valve. Available with the following end
connections.
Series 699*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Tapping Valve. Available with the following end
connections.
Series 876*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Cut-in valve with duck-tipped rubber gaskets. Available
with the following end connections.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-153
Series 877*. Metal Seated Gate Valves. 175 psi (1205 kPa) rated working pressure. Cut-in valve with plain rubber gaskets. Available with
the following end connections.
Figure 2360*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure 2361*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure 2362*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure 2460. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. All valves are available with an operating nut or
indicator post flange with operating nut. Available with the following end connections:
21⁄2, 3, 4, 6, 8 Compression Ends
21⁄2, 3, 4, 6, 8, 10, 12 Flanged
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping Flange
4, 6, 8 Mechanical Joint (Cut In/D150)
4, 6, 8, 10, 12 Slip – On
2 1⁄ 2, 3 Threaded
Figure 2461. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. All valves are available with an operating nut or
indicator post flange with operating nut. Available with the following end connections:
4, 6, 8, 10, 12 Flanged
4, 6, 8, 10, 12 Standardized Mechanical Joint
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping Flange
4, 6, 8, 10, 12 Slip – On
Figure 2462. Resilient Seated Gate Valves. 250 psi (1724 kPa) rated working pressure. All valves are available with an operating nut or
indicator post flange with operating nut. Available with the following end connections:
AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end
connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.
FM Approvals
September 2007 — Approval Guide
1-154 Automatic Sprinkler Systems
Figure F609RW. Resilient Seated Gate Valves. 250 psi (1725 kPa) rated working pressure. All valves are available with an operating nut
or indicator post flange with operating nut. Available with the following end connections:
4, 6, 8, 10, 12 Flanged (ANSI)
4, 6, 8, 10, 12 Standardized Mechanical Joint
4, 6, 8, 10, 12 Standardized Mechanical Joint by Flange
National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE
Model NF-NRS175U. Metal to Metal Seated Gate Valve. 21⁄2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with
the following end connections:
Model NF-NRS200U. Resilient Seated Gate Valve. 2 1⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
Model NF-NRS250H. Resilient Seated Gate Valve. 2 1⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the
following end connections:
Model NF-NRS250G. Resilient Seated Gate Valve. 3 through 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the
following end connections:
3, 4, 6, 8, Grooved
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
Model 710U. Metal to Metal Seated Gate Valve. 21⁄2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
Model 721U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 721H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Model 721G. Resilient Seated Gate Valve. 3, 4 and 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end
connections:
3, 4, 6 Grooved
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model RELNRS-200-RW. Resilient Seated Gate Valves. Sizes 21⁄2 through 12 in. NPS 200 psi (1380 kPa) rated working pressure. Available
with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12 Flanged 1 × Flanged (ANSI, BS10, BS4505, JIS B2212, JIS B2213)
†Available with or without indicator post flange.
Series Euro 20. Resilient Seated Gate Valves. Sizes 11⁄2 through 8 in. NPS, 235 psi (1620 kPa) rated working pressure. Sizes 10 and 12 in.
NPS, 200 psi (1380 kPa). Available with the following end connections:
Model No. Size End Connections
Shanghai Karon Valves Machinery Co Ltd, No. 815 Deyuan Road Nanxiang, Jiading District Shanghai, PRC
Series RVCX. Resilient Seated Gate Valves. Sizes 2 through 12 in. NPS. 232 psi (1600 kPa) rated working pressure. Available with the
following end connections:
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-155
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Model 710U. Metal to Metal Seated Gate Valve. 21⁄2 through 12 in. NPS. 175 psi (1205 kPa) rated working pressure. Available with the
following end connections:
Model 721U. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following
end connections:
Model 721H. Resilient Seated Gate Valve. 21⁄2 through 12 in. NPS. 250 psi (1725 kPa) rated working pressure. Available with the following
end connections:
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Model 721G. Resilient Seated Gate Valve. 3 through 6 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end
connections:
3, 4, 6 Grooved
Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477
G-600. 4 through 12 in. Flanged with indicator post flange. 200 psi (1380 kPa).
G-601. 4 through 12 in. Standardized mechanical joint, with indicator post flange. 200 psi (1380 kPa).
G-602. 4 through 12 in. NPS. Flanged by mechanical joint end, with indicator post flange. 200 psi (1380 kPa).
G-603. 4 through 12 in. Tyton joint, with indicator post flange. 200 psi (1380 kPa).
G-604. 4 through 12 in. Flanged by Tyton pipe end, with indicator post flange. 200 psi (1380 kPa).
G-605. 4 through 12 in. Flanged. 200 psi (1380 kPa).
G-606. 4 through 12 in. Standardized mechanical joint, flanged. 200 psi (1380 kPa).
G-607. 4 through 12 in. Tyton ends. 200 psi (1380 kPa).
G-616. 4 through 12 in. Flanged by mechanical joint end. 200 psi (1380 kPa).
G-617. 4 through 12 in. Flanged by Tyton end. 200 psi (1380 kPa).
No. G-632. 4 through 12 in. NPS. Flanged.
No. G-635. 4 through 14 in. NPS. Standardized mechanical joint.
No. G-638. 4 through 14 in. NPS. Ring-Tite.
†Resilient seat.
Tyco Water Valve (Shanghai) Co Ltd, No. 399 Jiu Ye Road, Qing Pu Industrial Zone, Shanghai China 201700
Series TM Resilient Seated Gate Valves. Rated working pressure 232 psi (1600 kPa) Available with the following end connections:
Model No. Size End Connections
FM Approvals
September 2007 — Approval Guide
1-156 Automatic Sprinkler Systems
United States Pipe & Foundry Co, 3300 First Ave N, Birmingham AL 35222
Metroseal Series*. 4, 6, 8, 10, 12, 14 and 16 in. NPS. 250 psi (1725 kPa) working pressure. Double flanged, double mechanical joint ends
and flanged by mechanical joint ends through 16 in. nominal size, Tyton ends through 12 in. nominal size and TR Flex ends in 16 in. nominal
size only. With and without indicator post flange.
*Resilient seat.
Figure USP0*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
21⁄2, 3, 4, 6, 8 Compression Ends
21⁄2, 3, 4, 6, 8, 10, 12 Flanged
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint
4, 6, 8, 10, 12 Standardized Mechanical Joint by Flanged
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping Flange
4, 6, 8 Mechanical Joint (Cut In/D150)
4, 6, 8 Mechanical Joint by Standardized Mechanical Joint (Cut In/D150)
4, 6, 8, 10, 12 Slip – On
4, 6, 8, 10, 12 Slip – On by Flange
2 1⁄ 2, 3 Screwed
Figure USP1*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
Figure USP2*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end
connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.
Figure 772H. Resilient Seated Gate Valve. Sizes 21⁄2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure.
All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved
Figure 772F. Resilient Seated Gate Valve. Sizes 21⁄2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure.
All valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:
21⁄2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved × Flanged
Waterous Co, 125 Hardman Ave So, South Saint Paul MN 55075-1191
Series 2500-1 ‡. All Series 2500-1 valves have a 250 psi (1725 kPa) working pressure and 4 through 12 in. sizes are available with or
without an indicator post flange. Available in the following end connections:
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-157
Series 2500‡. Resilient Seated Gate Valves. 2 through 3 in. NPS NRS valves have a rated working pressure of 250 psi (1725 kPa). 14 and
16 in. NPS valves have a rated working pressure of 200 psi (1380 kPa). Available with the following end connections:
Design features provide a dependable visible indication of the open position even at a distance. If excessive force
is applied to the handle, weakness-joints will break so as to preserve correct orientation between indicator and valve
position. Valve and indicator parts are so designed that they can be assembled only one way, always to give correct
indication. All FM Approved indicating valves turn clockwise to shut. They are small, lightweight, and, because of a
resilient seat, are easy to operate. They are not subject to sticking or dropped gates. They are not recommended for
throttling service. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Model Product Nominal Pipe Rated Working Remarks
Number Type Size Pressure, psi
in./ mm (kPa)
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Model Product Nominal Pipe Rated Working Remarks
Number Type Size Pressure, psi
in. / mm (kPa)
DANFOSS SOCLA S.A.S., 365, rue du Lieutenant Putier, 71530 Virey-Le-Grand, France
Model Product Nominal Pipe Rated Working Remarks
Number Type Size, mm Pressure, psi
(kPa)
BOMBYX Butterfly Valve, 32, 40, 50, 65, 80, 100, 232 a, b, c
Wafer Style with, 125, 150, 200, 250, 300 (1600)
centering lugs,
Lugged Body
Remarks:
FM Approvals
September 2007 — Approval Guide
1-158 Automatic Sprinkler Systems
Global Safety Products Inc, 970 E Orangethorpe Ave, Unit B, Anaheim CA 92801
Model Product Nominal Pipe Rated Working Remarks
Number Type Size, in. Pressure, psi
(mm) (kPa)
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Model Product Nominal Pipe Rated Working Remarks
Number Type Size Pressure, psi
(kPa)
Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901
Model Product Nominal Pipe Rated Working Remarks
Number Type Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-159
Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151
Model Product Nominal Pipe Rated Working Remarks
Number Type Size, in. Pressure, psi
(kPa)
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
Model 200 Wafer body (for mounting between bolted flanges). 21⁄2, 3, 4, 6, 8 in. NPS and 65, 80, 100, 150 and 200 mm NPS.
Model 100. Grooved inlet and outlet connections. 21⁄2, 3, 4, 6, 8 in. NPS and 65 and 150 mm NPS.
Model 500-T. Threaded connections. 1, 11⁄4, 11⁄2, 2, 21⁄2 in. NPS.
Model 500-G. Grooved inlet and outlet connections. 2, 21⁄2 in. NPS.
Valves are FM Approved for aboveground indoor use only.
Valves are available with two supervisory switches.
FM Approvals
September 2007 — Approval Guide
1-160 Automatic Sprinkler Systems
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Model Product Nominal Pipe Rated Working Remarks
Number Type Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-161
Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477
Fig. LD-52-UF, Fig. LG-52-UF. Wafer body (for mounting between bolted ANSI flanges). 4, 5, 6, 8, 10, 12 in. NPS.
Fig. LD-62-UF, Fig. LG-62-UF. Drilled lug body. 4, 5, 6, 8, 10, 12 in. NPS.
Fig. LD-72-UF, Fig. LG-72-UF. Drilled and tapped lug body, 4, 5, 6, 8, 10, 12 in. NPS.
Fig. LD-82-UF, Fig. LG-82-UF. Cut grooved inlet and outlet body connections. 4, 6, 8 in. NPS.
All valves are FM Approved for aboveground use only. Valves are available with one or two supervisory switches.
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Model Product Nominal Pipe Rated Working Remarks
Number Type Size, in. Pressure, psi
(kPa)
Tyco Fire and Building Products, 1467 Elmwood Ave, Cranston RI 02910
Fig No. Product Nominal Pipe Rated Working Remarks
Type Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-162 Automatic Sprinkler Systems
Remarks:
INDICATOR POSTS
Indicator posts are controls, extending aboveground, for operating underground sprinkler system valves. As an
important feature of their design, a target or indicator, visible through an opening in the post, shows whether the valve
is open or shut.
The indicator post generally consists of a cast iron barrel, an extension flange which allows the height of the barrel
to be regulated, and a wrought iron or mild steel stem which operates the underground valve and simultaneously
moves the target. A telescoping union permits turning the stem from a constant height.
Indicator posts are available for installation on non-rising stem gate valves. Unless otherwise specified, indicator
posts are Approved for use on 4 through 14 in. NPS non-rising stem gate valves with an indicator post flange.
In all new fire protection system installations, buried valves must open in a counterclockwise direction regardless
of the direction the valves of the public water system open. An exception to this is when all other buried valves in a
plant yard open in a clockwise direction. Then all new valves should open clockwise also.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-163
When some buried valves in a system open one way and some the other, all new valves should open
counterclockwise. There may be exceptions to this when most valves in an extensive yard system open clockwise.
In such cases, FM Global should be consulted regarding the proper direction of opening.
American Darling Valve, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202
Model IP-71. Fixed barrel.
American Flow Control, Div American Cast Iron Pipe Co (ACIPCO), Box 2727, Birmingham AL 35202
Model A240. Buried type, two-piece adjustable.
Model A278. Floor-mounted type.
Models A280, A281, A282. Wall type, various mounting configurations.
Model A279. Miter gearing wall-mounted assembly.
Model A-193-1, -2, -3. Coupling. For use with FM Approved post indicator valves.
Model IP-71. Fixed barrel.
Clow Canada, Div Canada Pipe Co Ltd, 245 Industrial Dr, Grandview Industrial Park, Saint John, New Brunswick
E2R 1A4 Canada
‘‘McAvity’’ Cat. Fig. 2945. Nonadjustable Type. Vertical.
‘‘McAvity’’ Cat. Fig. 2945A. Adjustable Type. Vertical.
Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577
Style 2945. Nonadjustable type.
Style 2945A. Adjustable type.
Style F5765K. Wall type.
Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien Taiwan ROC
Fig. 800
Fig. 800 W. Wall type.
Fivalco (Qingdao) Co Ltd, 11 Shuangyuan Road Chengyang, Qingdao Shandong, PRC 266111
Model IP888. Vertical type.
Model WP999. Wall Post.
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
Model 800. Adjustable barrel. Vertical.
Model 810. Wall type.
Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901
Fig. 641-S. Wall post.
Fig. 551. Right angle gear for use with Fig. 641-S.
Fig. 641-14. Pit style post. Floor mounted.
Fig. 2945. Vertical nonadjustable type post.
Fig. 2945A. Vertical adjustable type post.
Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd,
Wolverhampton WV4 WTX, United Kingdom
Fig. 800
Fig. 800 W. Wall Type.
Lien Hwa Iron Works Co Ltd, 112 Sec 2 Kuang Fu Rd, Sanchung Taipei Hsien 24113, Taiwan ROC
Fig. 130. Wall type.
Fig. 135.
Mueller Canada Inc, 8069 Lawson Rd, Milton, Ontario L9T 5C4, Canada
Model C20806. Vertical adjustable type.
Model C20808. Vertical nonadjustable type.
Model C20813. Horizontal wall mounted.
National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE
Fig. NF-PI800A.
Fig. NF-PI800W. Wall Type.
FM Approvals
September 2007 — Approval Guide
1-164 Automatic Sprinkler Systems
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
Model 800. Adjustable barrel. Vertical.
Model 810. Wall type.
Figure 800.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model RELPI-WALL. Wall Indicator Post.
Model RELPI-UP. Indicator Post, Upright, Adjustable.
Shanghai Karon Valves Machinery Co Ltd, No 815 Deyuan Road Nanxiang, Jiading District Shanghai, PRC
Model RBLX Vertical Indicator Post, Adjustable.
Model RWHX Wall type.
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Fig. 800.
Fig. 800 W. Wall Type.
Stockham Valves & Fittings, 2129 3rd Ave SE, Cullman AL 35055-5477
Cat. Figs. G-950, G-950-A. Wall type.
Cat. Figs. G-951, G-951-A.
Waterous Co, 125 Hardman Ave So, South Saint Paul MN 55075-1191
No. A240. Buried type, two-piece adjustable.
No. A278. Floor-mounted type.
No. A-193-1, -2, -3. Coupling. For use with FM Approved post indicator valves.
Post indicator valve assemblies are used to control waterflow to fire protection systems. The assembly consists
of a buried, quarter-turn valve and an above grade indicator operator. It is not necessary for the weekly inspector to
‘‘try’’ these valves to make sure they are open, thus saving time. Built-in design features provide a dependable
‘‘open’’ signal which can be seen at considerable distance.
If excessive force is applied to the handle, weakness-joints will break so as to preserve correct orientation between
indicator and valve position. Parts are so designed that they can be assembled only one way, always to give correct
indication. In case the post is broken off above grade, fail-safe features will keep the valve intact, and it will
automatically remain in place or move into the wide open position. All FM Approved valves turn clockwise to shut.
Their rubber seats make them easy to operate. Their compactness and light weight permit quick installation in small
space. The valves are not subject to sticking or to dropped gates.
This device is available only as a factory-assembled unit with true orientation guaranteed by the manufacturer. By
means of standard adapters, the valve can be used with all types of pipe joints. When ordering, it is necessary to
specify depth to which it is buried. Unless otherwise noted in the listing, this valve assembly has 175 psi (1205 kPa)
rated working pressure.
Manually operated ball valves are used to control water to small open-head extinguishing systems or in the trim
on waterflow alarm valves, dry pipe valves or automatic water control valves.
The friction loss through these valves should be considered when they are used in hydraulically calculated
extinguishing systems. Consult the manufacturer for details. Unless otherwise noted in the listing, these valves have
175 psi (1205 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-165
1⁄ 2, 3⁄ 4, 175
221 Ball Valve 1, 11⁄4, 11⁄2, 2 f
(1205)
1⁄ 2, 3⁄ 4, 175
222 Ball Valve 1 b, f
(1205)
1⁄ 2, 3⁄ 4, 175
226 Ball Valve 1, 11⁄4, 11⁄2, 2 g
(1205)
1⁄ 2, 3⁄ 4, 175
227 Ball Valve 1 b, g
(1205)
1⁄ 2, 3⁄ 4, 175
553 Ball Valve 1, 11⁄4, 11⁄2, 2 f
(1205)
1⁄ 2, 3⁄ 4, 175
9241 Ball Valve 1, 11⁄4, 11⁄2, 2 a
(1205)
1⁄ 2, 3⁄ 4, 175
9242 Ball Valve 1 a, b
(1205)
1⁄ 2, 3⁄ 4, 175
9246 Ball Valve 1, 11⁄4, 11⁄2, 2 c
(1205)
1⁄ 2, 3⁄ 4, 175
9247 Ball Valve 1 b, c
(1205)
1⁄ 2, 3⁄ 4, 175
9276 Ball Valve 1, 11⁄4, 11⁄2, 2 d, e
(1205)
1⁄ 2, 3⁄ 4, 175
9277 Ball Valve 1 b, d, e
(1205)
1⁄ 2, 3⁄ 4, 175
9551 Ball Valves 1, 11⁄4, 11⁄2, 2 a
(1205)
Remarks:
Compass Asia Inc, 11FL, No 165, Sec 4, Nanjing E Rd, Taipei 105, Taiwan
FM Approvals
September 2007 — Approval Guide
1-166 Automatic Sprinkler Systems
Remarks:
Crane Supply, 615 Dixon Rd, Toronto, Ontario M9W 1H9, Canada
1⁄ 2, 3⁄ 4, 600
CSC-9322 Ball Valve 1, 11⁄4, 11⁄2, 2 b
(4135)
Remarks:
Enolgas Bonomi SpA, Via Europa 227, 25062 Concesio (BS), Italy
Remarks:
Fire Protection Products Inc, 6241 Yarrow Drive, Suite A, Carlsbad CA 92011
Remarks:
Fortune Manufacturing Company Ltd, 11F No 222 Sec 5, Nanking E Rd, Taipei, Taiwan ROC
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-167
1⁄ 2, 3⁄ 4, 600
220-CC Ball Valve 1, 11⁄4, 11⁄2, 2 b
(4135)
1⁄ 2, 3⁄ 4, 600
FBVS-3C Ball Valve 1, 11⁄4, 11⁄2, 2 b
(4135)
Remarks:
Fratelli Pettinaroli SpA, Via Pianelli 38, 28017 San Maurizio d’Opaglio Novara, Italy
Model T-100N-E. 1⁄4 through 2 in.; 1⁄4 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated
working pressure. Female pipe thread end connections, brass valve stem and ball.
Model T-100-C; 1⁄2 through 2 in.; 1⁄2 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated
working pressure. Female pipe thread end connections.
Model T-100-SSN-E. 1⁄2 through 2 in.; 1⁄4 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated
working pressure. Female pipe thread end connections, 316 stainless steel valve stem and ball.
Model S-100N-E. 1⁄2 through 2 in.; 1⁄2, 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working
pressure. Tube by tube end connections, brass valve stem and ball.
Model S-100-C. 1⁄2 through 2 in.; 1⁄2, 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working
pressure. Tube by tube end connections, brass valve stem and ball.
All above 5 Models are available with:
a) steel handle - 90° to open or close.
b) aluminum tee handle - 90° to open or close.
c) plastic ‘‘top ball’’ handle with one full turn to open or close.
Model T-100. 1⁄4 through 1 in.; 1⁄4 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 in., 500 psi (3450 kPa) rated working pressure.
Female pipe thread end connections, brass valve stem and ball.
Model T-100-C. 1⁄2 through 2 in.; 1⁄2 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated
working pressure. Female pipe thread end connections.
Model T-100-SS. 1⁄2 through 1 in.; 1⁄4 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 in., 500 psi (3450 kPa) rated working
pressure. Female pipe thread end connections, 316 stainless steel valve stem and ball.
Model S-100. 1⁄2 through 1 in.; 1⁄2, 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 in., 500 psi (3450 kPa) rated working pressure. Tube
by tube end connections, brass valve stem and ball.
Model S-100-C. 1⁄2 through 2 in.; 1⁄2, 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working
pressure. Tube by tube end connections, brass valve stem and ball.
All above with aluminum tee handle - 90° to open or close.
Model T-100. 1⁄4 through 2 in.; 1⁄4 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working
pressure. Female pipe thread end connections, brass valve stem and ball.
Model T-100-C. 1⁄2 through 2 in.; 1⁄2 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated
working pressure. Female pipe thread end connections.
Model T-100-SS. 1⁄2 through 2 in.; 1⁄4 through 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated
working pressure. Female pipe thread end connections, 316 stainless steel valve stem and ball.
Model S-100. 1⁄2 through 2 in.; 1⁄2, 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working
pressure. Tube by tube end connections, brass valve stem and ball.
Model S-100-C. 1⁄2 through 2 in.; 1⁄2, 3⁄4 in., 600 psi (4140 kPa) rated working pressure. 1 through 2 in., 500 psi (3450 kPa) rated working
pressure. Tube by tube end connections, brass valve stem and ball.
All above with plastic ‘‘top ball’’ handle with one full turn to open or close.
Fu San Machinery Co Ltd, 22 Lane 89, Sec 4 Chang-Mei Road, Ho-Mei Town Chang-Hua, Taiwan ROC
Fig. F1361FP. Ball type valves. 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 in. Rated working pressure 600 psi (4130 kPa).
Fu San Valve (Suzhou) Limited, No. 1, Cheng Hu Zhong Rd, Wuzhong Economic Development Zone, Suzhou City,
Jiangsu Province, China
Remarks:
a. Valves are available with threads to ANSI/ASME B1.20.1 and BS21 Pipe Thread Standards.
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Model R250D. 1⁄2, 3⁄4 in., 600 psi (4135 kPa) rated working pressure; 1 through 2 in., 500 psi (3445 kPa) rated working pressure.
Model R850. 1⁄2 through 2 in., 600 psi (4135 kPa) rated working pressure. NPT end connections.
Model R858. 1⁄2 through 2 in., 600 psi (4135 kPa) rated working pressure. Solder joint end connections.
Model R910. 1⁄2 through 2 in., 600 psi (4135 kPa) rated working pressure. NPT end connections.
Model R918. 1⁄2 through 2 in., 600 psi (4135 kPa) rated working pressure. Solder joint end connections.
Model R850PR. 1⁄2 through 2 in., 600 psi (4135 kPa) rated working pressure. NPT end connections.
Model R858PR. 1⁄2 through 2 in., 600 psi (4135 kPa) rated working pressure. Solder joint end connections.
FM Approvals
September 2007 — Approval Guide
1-168 Automatic Sprinkler Systems
Remarks:
IVR Valvole a sfera spa, Via Brughiera III n°1, Loc. Piano Rosa, 28010 Boca (NO), Italy
Remarks:
a. Female pipe thread end connections with Standard Steel Handle – 90° to open or close.
1⁄ 2, 6 00
S-100 Ball Valve ¾ b, c, e
(4140)
500
S-100 Ball Valve 1 b, c, e
(3450)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-169
500
T-100-C Ball Valve 1, 11⁄4, 11⁄2, 2 c, f
(3450)
600
T-100-SS Ball Valve ¼, 1⁄2, 3⁄4 c, f, h
(4140)
500
T-100-SS Ball Valve 1 c, f, h
(3450)
600
T-100 Ball Valve ¼, 1⁄2, 3⁄4 b, d, f
(4140)
500
T-100 Ball Valve 1, 11⁄4, 11⁄2, 2 b, d, f
(3450)
500
T-100-C Ball Valve 1, 11⁄4, 11⁄2, 2 d, f
(3450)
600
T-100-SS Ball Valve ¼, 1⁄2, 3⁄4 d, f, h
(4140)
500
T-100-SS Ball Valve 1, 11⁄4, 11⁄2, 2 d, f, h
(3450)
Remarks:
a. Valves supplied with female NPT threaded end connections and BS21 Pipe Thread Standards.
b. Brass valve stem and ball.
c. All above with Aluminum Tee Handle – 90° to open or close.
d. All above with Plastic ‘‘Slo-Ball’’ Handle with one full turn to open or close.
e. Tube by tube end connections.
f. Female pipe thread end connections.
g. All above with Standard Steel Handle – 90° to open or close.
h. 316 stainless steel valve stem and ball.
Karl DUNGS Inc, 524 Apollo Dr, Suite 10-30, Lino Lakes MN 55014
Model KH01/6, sizes 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 and 2 in. Female pipe thread end connections. 250 psi (1725 kPa) rated working pressure.
Legend Valve & Fitting, 51245 Filomena Drive, Shelby Township MI 48315
FM Approvals
September 2007 — Approval Guide
1-170 Automatic Sprinkler Systems
Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151
Pressure
Product Nominal Pipe
Description Rating, psi Remarks
Designation Size, in.
(kPa)
Remarks:
NIGO Industrial Co Ltd, No 9 Lane 93, Chang Lu Road, Changhua, Taiwan R.O.C.
Remarks:
Ningbo Zhiqing Industrial Co Ltd, No. 12 Wai Huan (W.) Road, Yuelong Street, Ninghai County,
Ningbo, 315600, China
1⁄ 2, 3⁄ 4, 600
Q61F-600TL Ball Valve 1, 11⁄4, 11⁄2, 2 b
(4135)
1⁄ 2, 3⁄ 4, 600
Q61F-600TL2 Ball Valve 1, 11⁄4, 11⁄2, 2 b
(4135)
Potter-Roemer Inc, 15125 Proctor Avenue, Box 3527, City of Industry CA 91744-0527
Models 4405; 4407. 1⁄2, 3⁄4 in.; 600 psi (4135 kPa) rated working pressure.
Models 4410, 4412, 4415, 4420. 1, 11⁄4, 11⁄2, 2 in.; 500 psi (3445 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-171
1⁄ 2, 3⁄ 4, 600
5044A Ball Valve 1, 11⁄4, 11⁄2, 2 a
(4135)
1⁄ 2, 3⁄ 4, 600
5044F Ball Valve 1, 11⁄4, 11⁄2, 2 a
(4135)
1⁄ 2, 3⁄ 4, 600
5544 Ball Valve 1, 11⁄4, 11⁄2, 2 a
(4135)
Rubinetterie Bresciane Bonomi SpA, Via Industralie 30, Box 31, 25065 Lumezzane SS Brescia, Italy
1⁄ 2, 3⁄ 4, 400
16 Ball Valve, Threaded Ends 1, 11⁄4, 11⁄2, 2 a
(2760)
Remarks:
Rubinetterie Italiane Valvole, Via Dell Acacie 8-ZI, D4 28075 Grignasco NO, Italy
Series 4201. Sizes 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 in. NPS. 600 psi (4140 kPa) maximum rated working pressure. Size 2 in. NPS, 400 psi (2760 kPa)
maximum rated working pressure. Female NPT end connections.
Rubinetterie Utensilerie Bonomi, Via Padana Superiore 27/29, Ciliverghe Di Mazzano, Brescia 25080, Italy
Model S.92. 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 and 2 in. 400 psi (2760 kPa) rated working pressure. Brass and chrome-plated finishes. NPT M×F
and F×F end threaded.
Model S.95. 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 and 2 in. 400 psi (2760 kPa) rated working pressure. Brass and chrome-plated finishes. NPT F×F
end threaded.
Toyo Valve Co Ltd, TT-2 Bldg, 8-1, 3-Chome, Nihonbashi-Ningyocho, Chuo-Ku, Tokyo 103-0013 Japan
VIR Valvoindustria Ing Rizzio SpA, Via Circonvallazione 10, 13018 Valduggia, Italy
1⁄ 2, 3⁄ 4, 600
340T Ball Valve 1, 11⁄4, 11⁄2, 2 a
(4135)
FM Approvals
September 2007 — Approval Guide
1-172 Automatic Sprinkler Systems
1⁄ 2, 3⁄ 4, 600 b
FBVS-3C Ball Valve 1, 11⁄4, 11⁄2, 2
(4135)
Remarks:
Single check valves are used in fire protection systems to allow waterflow in one direction only. Typical applications
are at connections between public water supplies and private fire service systems, at the discharge from fire pumps,
at gravity tank connections and at fire service pumper connections.
Valves identified in the listing by a single asterisk (*) have side covers; valves identified by a double asterisk (**)
have no removable covers; others have top covers. Clearance must be provided for side-cover valves to permit
clapper removal. Valves without covers must be removed from the system for clapper replacement or repair. Unless
otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Remarks:
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Remarks:
Ban Chang Hardware Co Ltd, No 168, Lane 432, Sec 3, Lu Ho Road, LuKang ChangHua Hsien 505, Taiwan
250
B120G 4 a
(1725)
a. Resilient seat.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-173
Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577
a. Metal Seat.
b. Resilient Seat.
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
a. Metal seat.
b. Resilient seat.
c. No removable covers.
Fire Protection Products Inc, 6241 Yarrow Drive, Suite A, Carlsbad CA 92009-1541
Product Description Nominal Pipe Pressure Remarks
Designation Size, in. Rating, psi
(kPa)
b. Resilient Seat.
c. No removable covers.
FM Approvals
September 2007 — Approval Guide
1-174 Automatic Sprinkler Systems
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
a. Resilient seat.
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
a. Metal Seat.
Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-175
b. Resilient seat.
Lichfield Fire & Safety Equipment Co Ltd, 2nd Floor, Suite 4, Saturn Centre, Spring Rd, Ettingshall Rd,
Wolverhampton WV4 WTX, United Kingdom
Model 763UM. 3 through 12 in. NPS, flanged swing check with bronze seat. 200 psi (1380 kPa) rated working pressure.
Model 763UR. 3 through 12 in. NPS, flanged swing check with rubber faced clapper. 200 psi (1380 kPa) rated working pressure.
Model 453UF**. 3, 4 and 6 in. NPS, flanged dual plate, rubber seat. 250 psi (1725 kPa) rated working pressure.
Model 453UG**. 3, 4, 6 and 8 in. NPS, grooved end dual plate, rubber seat. 200 psi (1380 kPa) rated working pressure.
Lien Hwa Iron Works Co Ltd, 112 Section 2 Kuang Fu Rd, Sanchung, Taipei Hsien 24113, Taiwan ROC
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
a. Resilient Seat.
Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151
Series 1400. 2 through 10 in. NPS. Wafer style.
Series 1800. 21⁄2 through 12 in. NPS. Globe style-flanged.
Series 8800. 2 through 12 in. NPS. Oval disc-wafer style.
a. Metal Seat
b. Resilient Seat.
National Fire Fighting Mfg, FZCO, Box 17014, Jebel Ali Free Zone, Dubai, UAE
Model Number Description Nominal Pipe Max Working Remarks
Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-176 Automatic Sprinkler Systems
a. Bronze seat.
b. Rubber seat.
c. Dual Plate.
d. No removable covers.
Max Working
Product Nominal Pipe
Description Pressure, psi Remarks
Designation Size, in.
(kPa)
a. Resilient Seat.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Nominal Pipe Max Working
Product Size Pressure, psi
Designation Description in./ mm (kPa) Remarks
Ritepro Corporation, 12200 Albert Hudon, Montreal Quebec, H1G 3K7, Canada
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Model Description Nominal Pipe Max Working Remarks
Number Size, in. Pressure, psi
(kPa)
a. Bronze seat.
b. Rubber seat.
c. Dual Plate.
d. No removable covers.
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
a. Resilient Seat.
b. No removable covers.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-177
Siam Cast Iron Works Co Ltd, Samutsakorn Industrial Estate, Soi 7, 1/12 Moo 2, Rama II Rd, Tahsai, Muang,
Samutsakorn 74000, Thailand
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
c. Resilient Seat.
d. Clearance must be provided to permit hinge pin removal.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
a. Resilient Seat.
a. Metal Seat.
Tong Kwang Valve Industrial Co Ltd, No. 1-1 Ming Chuan Rd, Ming-Sheng Li, Tansui, Taipei Hsien, Taiwan ROC
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
a. Resilient Seat.
a. Resilient Seat.
b. For use in horizontal and vertical installations.
Val-Matic Valve & Mfg Corp, 905 Riverside Dr, Elmhurst IL 60126
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-178 Automatic Sprinkler Systems
Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-179
a. Resilient Seat.
b. Clearance must be provided to permit hinge pin removal
Wilson & Cousins, 4390 Paletta Court, Burlington, Ontario L7L 5R2, Canada
Product Description Nominal Pipe Max Working Remarks
Designation Size, in. Pressure, psi
(kPa)
Fire-protective systems in high buildings sometimes experience severe water hammer from backflow of a pressure
tank when the automatic control shuts down the fire pump. These special check valves are FM Approved only for use
in the discharge of a fire pump where conditions may be expected to cause serious water hammer with the usual
swing type valve. However, the friction loss through these valves is generally higher than that of a conventional single
check valve. Available friction loss data is tabulated in the listings below. The flow rates shown are the maximum
flows anticipated for the corresponding valve sizes. Lower flow rates will result in comparably lower losses. Unless
otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Series 300
304.3, 304.4, 304.5, 304.6 4 750 9.8
(2840) (67.5)
306.3, 306.4, 306.5, 306.6 6 1500 6.5
(5680) (45.0)
308.3, 308.4, 308.5, 308.6 8 3000 8.2
(11 355) (56.5)
310.3, 310.4, 310.5, 310.6 10 5000 9.3
(18 925) (64.0)
Series 600
604.3, 604.4, 604.5, 604.6 4 750 7.4
(2840) (51.0)
606.3, 606.4, 606.5, 606.6 6 1500 5.7
(5680) (39.5)
608.3, 608.4, 608.5, 608.6 8 3000 7.4
(11 355) (51.0)
610.3, 610.4, 610.5, 610.6 10 5000 8.5
(18 925) (58.5)
612.3, 612.4, 612.5, 612.6 12 7000 8.0
(26 500) (55.0)
618.1, 618.2 18 13,000 4.3
(49 210) (29.5)
FM Approvals
September 2007 — Approval Guide
1-180 Automatic Sprinkler Systems
Series 9000*
9004.1, 9204.1* 4 750 7.8
(2840) (53.5)
9006.1, 9206.1* 6 1500 4.3
(5680) (29.5)
9008.1, 9208.1* 8 3000 4.3
(11 355) (29.5)
9010.1, 9210.1* 10 5000 3.9
(18 925) (27.0)
9012.1, 9212.1* 12 7000 3.5
(26 500) (24.0)
*250 psi (1725 kPa) working pressure.
Ban Chang Hardware Co Ltd, No 168, Lane 432, Sec 3, Lu Ho Road, LuKang ChangHua Hsien 505, Taiwan
Product Nominal Pipe Flow Rate, gal/min Friction Loss, psi
Description Size, in. (L/min) (kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-181
8 3000 5.4
(11 355) (37)
10 5000 6.5
(18 925) (45)
12 7000 6.5
(26 500) (45)
2 200 8.7
(755) (60)
21⁄2 250 5.6
(945) (39)
3 400 5.6
(1515) (39)
4 750 5.6
(2840) (39)
5 1000 3.5
(3785) (24)
6 1500 3.5
(5680) (24)
8 3000 3.7
(11 355) (26)
10 5000 3.7
(18 925) (26)
12 7000 3.2
(26 500) (22)
*200 psi (1380 kPa) reated working pressure.
Clow Valve Co, Div McWane Inc, 902 S 2nd St, Oskaloosa IA 52577
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Crane Stockham Valve Ltd, 6 Alexander Rd, Cregagh, Belfast Northern Ireland BT6 9HJ
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
FM Approvals
September 2007 — Approval Guide
1-182 Automatic Sprinkler Systems
10 5000 2.0
(18 925) (14.0)
12 7000 2.0
(26 500) (14.0)
250 psi (1725 kPa) working pressure.
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Available with male inlet x female outlet threaded end connections and threaded male inlet x cut groove outlet end connections. 250 psi
(1725 kPa) rated working pressure.
Fire Protection Products Inc, 6241 Yarrow Drive, Suite A, Carlsbad CA 92009-1541
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Available with grooved × grooved, male × female threaded and male threaded × grooved end connections. Resilient seat. 300 psi
(2070 kPa) rated working pressure.
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Available with male inlet x female outlet threaded end connections and threaded male inlet x cut groove outlet end connections. 250 psi
(1725 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-183
Groeniger & Co, 27750 Industrial Blvd, Box 3629, Hayward CA 94545
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Kennedy Valve, Div McWane Inc, 1021 E Water St, Elmira NY 14901
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Milwaukee Valve Company Inc, 16550 West Stratton Drive, New Berlin WI 53151
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
FM Approvals
September 2007 — Approval Guide
1-184 Automatic Sprinkler Systems
Fig. A-2103-52. 2 through 12 in. NPS. Cut groove. 250 psi (1725 kPa) rated working pressure.
Mueller Steam Specialty, Div Core Industries Inc, RR2 Box 44 Saint Pauls NC 28384
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
71* 2 200 11
(755) (76.0)
21⁄2 300 25
(1135) (172.5)
3 450 6
(1705) (41.5)
4 750 4.5
(2840) (31.0)
5 1000 3
(3785) (20.5)
6 1500 3.5
(5680) (24.0)
8 3000 4
(11 355) (27.5)
10 5000 4.5
(18 925) (31.0)
12 7000 3.5
(26 500) (24.0)
14 9500 5
(35 960) (34.5)
16 13,000 3
(49 210) (20.5)
72† 2 200 11
(755) (76.0)
2 1⁄ 2 300 25
(1135) (172.5)
3 450 6
(1750) (41.5)
4 750 4.5
(2840) (31.0)
5 1000 3
(3785) (20.5)
6 1500 3.5
(5680) (24.0)
8 3000 4
(11 355) (27.5)
10 5000 4.5
(18 925) (31.0)
12 7000 3.5
(26 500) (24.0)
14 9500 5
(35 960) (34.5)
101-AP 4 750 6.2
(2840) (42.5)
5 1000 5.1
(3785) (35.0)
6 1500 5.8
(5680) (40.0)
8 3000 7.8
(11 355) (54.0)
10 5000 8.7
(18 925) (60.0)
105-AP 4 750 5.1
(2840) (35.0)
5 1000 5.1
(3785) (35.0)
6 1500 4.4
(5680) (30.5)
8 3000 4.7
(11 355) (32.5)
10 5000 8.7
(18 925) (60.0)
12 7000 11.2
(26 500) (77.0)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-185
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Ritepro Corporation, 12200 Albert Hudon, Montreal, North Quebec H1G 3K7, Canada
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
FM Approvals
September 2007 — Approval Guide
1-186 Automatic Sprinkler Systems
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
90 4 750 4.5
(2840) (31.0)
6 1500 3.8
(5680) (26.0)
8 3000 7.0
(11 355) (48.5)
67* 4 750 5.5
(2840) (38.0)
Val-Matic Valve & Mfg Corp, 905 Riverside Dr, Elmhurst IL 60126
Product Valve Flow Rate,gal/min Friction Loss, psi
Designation Size, in. (dm3/min) (kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-187
FM Approvals
September 2007 — Approval Guide
1-188 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-189
Surge arresters or dampers are used to moderate the potentially destructive effects of pressure surges or water
hammer due to pump starting and stopping and valve opening and closing. They are employed when an
anti-waterhammer check valve, alone, proves inadequate to control the problem, but should always be used in
conjunction with such a valve.
These hydropneumatic devices absorb pressure surges into a precalculated volume of captive gas and return the
absorbed water volume to the system in a controlled fashion. Surge arresters are installed on the system side of the
fire pump discharge check valve and as close to the valve as possible. Because of the complex effects of system
variables on satisfactory performance, each surge arrester installation should be engineered by the manufacturer for
best results.
Young Engineering Mfg Inc, 560 W Terrace Dr, San Dimas CA 91773-2914
BACKFLOW PREVENTERS
Backflow preventers are used in connections between public water supplies and fire protection systems to prevent
reverse flow. Where health authorities require the installation of backflow preventers, FM Approved models should
be used.
FM Approvals
September 2007 — Approval Guide
1-190 Automatic Sprinkler Systems
These backflow preventers have been evaluated for reliability from a fire protection standpoint. No attempt has
been made to determine their suitability to ensure the public health.
Unless otherwise noted in the listing, these devices have 175 psi (1205 kPa) rated working pressure and are
limited to horizontal installations.
A double check type backflow preventer is an assembly of two check valves and two FM Approved resilient seated
NRS or OS&Y gate valves.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-191
FM Approvals
September 2007 — Approval Guide
1-192 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-193
FM Approvals
September 2007 — Approval Guide
1-194 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-195
FM Approvals
September 2007 — Approval Guide
1-196 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-197
FM Approvals
September 2007 — Approval Guide
1-198 Automatic Sprinkler Systems
*Model Nos. 870 and 870v (in the n-shaped configuration) are available with optional FLGxFLG (21⁄2, 3, 4, 6, 8 and 10 in.); MJ×MJ (3, 4, 6, 8 and 10 in.) or FLGxMJ
(3, 4, 6, 8 and 10 in.) Valve Setter Elbows. The above friction loss data was obtained by assemblies which employed Valve Setter Elbows.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-199
Hersey Meters, Division of Mueller Group Inc, Hwy 70 Box 128 Cleveland NC 27013
FM Approvals
September 2007 — Approval Guide
1-200 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-201
FM Approvals
September 2007 — Approval Guide
1-202 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-203
FM Approvals
September 2007 — Approval Guide
1-204 Automatic Sprinkler Systems
Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-205
FM Approvals
September 2007 — Approval Guide
1-206 Automatic Sprinkler Systems
A reduced-pressure principle type backflow preventer is an assembly of two internally loaded check valves, which
are separated by an intermediate chamber equipped with an automatic relief valve for venting to atmosphere, and
two FM Approved resilient seated NRS or OS&Y gate valves.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-207
FM Approvals
September 2007 — Approval Guide
1-208 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-209
FM Approvals
September 2007 — Approval Guide
1-210 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-211
FM Approvals
September 2007 — Approval Guide
1-212 Automatic Sprinkler Systems
*Model Nos. 880 and 880v (in the n-shaped configuration) are available with optional FLGxFLG (21⁄2, 3, 4, 6, 8 and 10 in.); MJ×MJ (3, 4, 6, 8 and 10 in.) or
FLGxMJ (3, 4, 6, 8 and 10 in.) Valve Setter Elbows. The above friction loss data was obtained by assemblies which employed Valve Setter Elbows.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-213
FM Approvals
September 2007 — Approval Guide
1-214 Automatic Sprinkler Systems
Hersey Meters, Division of Mueller Group Inc, Hwy 70 Box 128, Cleveland NC 27013
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-215
FM Approvals
September 2007 — Approval Guide
1-216 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-217
FM Approvals
September 2007 — Approval Guide
1-218 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-219
Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446
FM Approvals
September 2007 — Approval Guide
1-220 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-221
A double check-detector check type backflow preventer is an assembly of two internally loaded check valves, a
metered, internally loaded double check by-pass and two FM Approved resilient seated NRS or OS&Y gate valves.
FM Approvals
September 2007 — Approval Guide
1-222 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-223
FM Approvals
September 2007 — Approval Guide
1-224 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-225
FM Approvals
September 2007 — Approval Guide
1-226 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-227
FM Approvals
September 2007 — Approval Guide
1-228 Automatic Sprinkler Systems
*Model Nos. 876 and 876v (in the n-shaped configuration) are available with optional FLGxFLG (21⁄2, 3, 4, 6, 8 and 10 in.); MJ×MJ (3, 4, 6, 8 and 10 in.) or FLGxMJ
(3, 4, 6, 8 and 10 in.) Valve Setter Elbows. The above friction loss data was obtained by assemblies which employed Valve Setter Elbows.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-229
Hersey Meters, Division of Mueller Group Inc, Hwy 70 Box 128 Cleveland NC 27013
FM Approvals
September 2007 — Approval Guide
1-230 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-231
FM Approvals
September 2007 — Approval Guide
1-232 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-233
FM Approvals
September 2007 — Approval Guide
1-234 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-235
Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446
FM Approvals
September 2007 — Approval Guide
1-236 Automatic Sprinkler Systems
A reduced-pressure principle – detector check type backflow preventer is an assembly of two internally loaded
check valves, which are separated by an intermediate chamber equipped with an automatic relief valve for venting
to atmosphere in addition to a metered, internally loaded double check by-pass, and two FM Approved resilient
seated NRS or OS&Y gate valves.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-237
FM Approvals
September 2007 — Approval Guide
1-238 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-239
FM Approvals
September 2007 — Approval Guide
1-240 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-241
FM Approvals
September 2007 — Approval Guide
1-242 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-243
FM Approvals
September 2007 — Approval Guide
1-244 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-245
Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446
FM Approvals
September 2007 — Approval Guide
1-246 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-247
Where local waterworks authorities require the installation of full registration metering devices on public water
connections to private fire protection systems, meters especially designed for fire protection service should be used.
Unless otherwise noted in the listing, these meters have 175 psi (1205 kPa) rated working pressure.
ABB Ltd, Oldends Lane, Stonehouse, Gloucestershire GL10 3TA, United Kingdom
Aquamaster FS (Fire Service) Model Code MM/GFabcdefgUh4Aijklmn Full Bore Fire Service Meter Assembly 3, 4, 6 and 8 in. NPS. (80,
100, 150 and 200 mm). 95-240 VAC and/or battery powered display. 225 psi (1550 kPa) rated working pressure.
a = Language code.
b = 0080, 0100, 0150 or 0200 bore diameter (mm).
c = Display and sensor configuration.
d = 0, A, B, C, D or L power supply.
e = 2 or C enclosure options.
f = Cable length.
g = Label type.
h = Cable connection type.
i = Electrode material.
j = Options.
k = Communication protocol.
l = Data protocol.
m = Pressure transducer option.
n = Pressure span.
Aquamaster FC (Fire Service Coned) Model Code MM/GAabcdefgUh4Aijklmn Reduced Throat Bore Fire Service Meter Assembly 3, 4, 6,
8 and 10 in. NPS (80, 100, 150, 200, and 250 mm). 95-240 VAC and/or battery powered display. 175 psi (1205 kPa) rated working pressure.
a = Language code.
b = 0080, 0100, 0150, 0200, or 0250 bore diameter (mm).
c = Display and sensor configuration.
d = 0, A, B, C, D, or L power supply.
e = 2 or C enclosure options.
f = Cable length.
g = Label type.
h = Cable connection type.
I = Electrode material.
j = Options.
k = Communication protocol.
l = Data protocol.
m = Pressure transducer option.
n = Pressure span.
FM Approvals
September 2007 — Approval Guide
1-248 Automatic Sprinkler Systems
Where the waterworks authorities require metering devices on connections used only for fire service, there are
instances where the indication of waterflow is considered of greater importance than knowing the actual amount of
water used. When acceptable to the authorities, supervision of a fire service connection is best accomplished by
means of a FM Approved waterflow detector check valve. Unless otherwise noted in the listing, these valves have
175 psi (1205 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-249
FM Approvals
September 2007 — Approval Guide
1-250 Automatic Sprinkler Systems
10 3000 1.9
(11 355) (13.0)
4000 1.9
(15 140) (13.0)
5000 2.5
(18 925) (17.0)
Hersey Meters, Division of Mueller Group Inc, Hwy 70, Box 128, Cleveland NC 27013
DC 2 140 1.1
(530) (8.0)
175 1.4
(660) (10.0)
220 1.7
(835) (12.0)
3 250 1.0
(945) (7.0)
400 1.9
(1515) (13.0)
600 4.6
(2270) (32.0)
EDC 4 500 1.7
(1895) (12.0)
750 2.5
(2840) (17.0)
1000 3.3
(3785) (23.0)
6 1000 1.6
(3785) (11.0)
1500 2.2
(5680) (15.0)
2000 2.6
(7570) (18.0)
8 2000 1.7
(7570) (12.0)
3000 2.4
(11 355) (16.5)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-251
4000 3.1
(15 140) (21.5)
10 2250 1.6
(8515) (11.0)
4500 2.2
(17 035) (15.0)
6750 2.6
(25 550) (18.0)
EDC II 8 2000 1.7
(7570) (12.0)
3000 2.4
(11 355) (16.5)
4000 3.1
(15 140) (21.5)
EDC III 4 500 2.5
(1905) (17.0)
750 2.6
(2840) (18.0)
1000 2.0
(3785) (14.0)
6 1000 2.5
(3785) (17.0)
1500 3.0
(5700) (21.0)
2000 4.0
(7550) (27.5)
8 1500 1.8
(5700) (12.5)
2000 2.0
(7550) (14.0)
2500 2.0
(9455) (14.0)
10 2250 1.6
(8515) (11.0)
4500 1.5
(17 035) (10.5)
6000 1.6
(22 710) (11.0)
EDC IV 3 200 2.6
(757) (18.1)
400 3.0
(1514) (20.9)
600 2.4
(2270) (16.8)
800 3.0
(3030) (20.9)
4 500 1.1
(1893) (7.9)
750 2.5
(2839) (16.9)
1000 4.1
(3785) (28.6)
6 1000 1.8
(3785) (12.2)
1500 1.9
(5678) (12.9)
2000 3.2
(7570) (22.1)
8 1500 3.2
(5678) (22.1)
3000 2.4
(11 355) (16.5)
4000 3.9
(15 140) (26.9)
10 2250 2.9
(8516) (20.0)
4500 2.5
(16 843) (17.2)
6750 4.9
(25 550) (33.8)
E 4 500 3.7
(1905) (26)
750 4.7
(2840) (32)
1000 8.1
(3785) (56)
6 1000 2.7
(3785) (18)
FM Approvals
September 2007 — Approval Guide
1-252 Automatic Sprinkler Systems
1500 3.2
(5700) (22)
2000 4.5
(7550) (31)
8 2000 2.2
(7570) (15)
2500 2.4
(9465) (17)
3000 2.6
(11 355) (18)
10 2250 1.6
(8515) (11)
4500 2.4
(17 035) (16)
6750 2.9
(25 550) (20)
Wilkins Operation, Zurn Industries Inc, 1747 Commerce Way, Paso Robles CA 93446
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-253
Suction pressure regulating valves are used with booster pumps in fire protection systems when local authorities
require that a minimum suction pressure be maintained. The valve is installed in the discharge line of the booster
pump. The pump suction pressure is monitored through a pressure line to the controlling mechanism of the
regulating valve.
50B-5KG 3 400 14
(1500) (100)
50B-5KG 4 750 20
(2800) (140)
50B-5KG 6 1500 21
(5700) (145)
50B-5KG 8 3000 20
(11 400) (140)
Size 3 in. available with NPT ends rated at 400 psi (2760 kPa).
Sizes 3, 4, 6, 8 in. available with 150 lb F.F. flanges rated at 250 psi (1725 kPa).
Sizes 3, 4, 6, 8 in. available with 300 lb R.F. flanges rated at 400 psi (2260 kPa).
Sizes 80, 100, 150, 200 mm available with ISO PN10, PN16, PN25 flanges rated at 12, 16, 25 bar (175, 232, 363 psi) respectively.
All above models available with white epoxy coating on body. Add suffix -KC to model no.
Available ANSI flanged body connections are as follows:
Class 300 inlet, Class 150 outlet; 250 psi rated working pressure,
Class 300 inlet, Class 300 outlet; 400 psi rated working pressure,
Class 150 inlet, Class 150 outlet; 250 psi rated working pressure.
Friction Loss:
3 400 16
(110)
4 750 13
(90)
6 1500 11
(76)
8 3000 16
(110)
3 400 9
(62)
4 750 7
(48)
6 1500 5
(35)
8 3000 9
(62)
116-1FM 4 750 17
(2800) (115)
6 1500 16
(5700) (110)
8 3000 14
(11 400) (100)
Sizes 4 and 6 in. NPS valves available with ANSI Class 125 and 250 rated flanges. 8 in. NPS valves available with ANSI Class 125 rated
flanges only. ANSI Class 125 valves have a rated working pressure of 175 psi (1205 kPa). ANSI Class 250 valves have a rated working
pressure of 300 psi (2070 kPa).
FM Approvals
September 2007 — Approval Guide
1-254 Automatic Sprinkler Systems
PV60GFM 4 750 17
(2800) (115)
6 1500 16
(5700) (110)
8 3000 14
(11 400) (100)
Sizes 4 and 6 in. NPS valves available with ANSI Class 125 and 250 rated flanges. 8 in. NPS valves available with ANSI Class 125 rated
flanges only. ANSI Class 125 valves have a rated working pressure of 175 psi (1205 kPa). ANSI Class 250 valves have a rated working
pressure of 300 psi (2070 kPa).
A fire service pumper connection, located outside buildings, permits the fire service to pump water into a sprinkler
system from a nearby public hydrant or reservoir. Water supplied at high pressure will aid automatic sprinklers to
control a fire. The connection may also be used to supply building standpipes.
FM Approved connections are made of bronze and consist of two inlet couplings threaded for standard fire hose
and siamesed into an outlet pipe connection. A check valve is provided in each inlet so that either connection may
be used separately. The connections are available in straight, 45° or 90° patterns. Unless otherwise noted in the
listing, these connections have 175 psi (1205 kPa) rated working pressure.
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Ban Chang Hardware Co Ltd, 17 Lane 620, Sec 3 Lu Ho Rd, Lu Kang Chang Hua, Taiwan ROC
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Straightway Single
86A 21⁄2×21⁄2×4
Clapper
These connections have a 300 psi (2070 kPa) rated working pressure.
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Model 614. Sprinkler System Alarm Tester. 1 and 11⁄4 in. NPT female threaded inlet with male threaded outlet. 1⁄2 in. nominal orifice. 175 psi
(1205 kPa) rated working pressure.
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Straightway Single
86A 21⁄2×21⁄2×4
Clapper
These connections have a 300 psi (2070 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-255
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Double Check,
Model 21-132 21⁄2×21⁄2×4
Straightway Siamese
Double Check,
Model 21-203 21⁄2×21⁄2×4
Straightway Siamese
Double Check,
Model 21-133 21⁄2×21⁄2×4
90° Siamese
Double Check,
Model 21-207 21⁄2×21⁄2×4
90° Siamese
Single Check,
Model 21-201* 21⁄2×21⁄2×4
Straightway Siamese
Straightway Siamese
Model 21-132** 3×3×4
Dual Clapper
90° Siamese Dual
Model 21-133** 3×3×4
Clapper
**These connections are FM Approved for hose threads conforming to the standard for hose coupling screw threads, ANSI B2.4 or the Engineering Division, Dept.
of Purchase, City of New York, Specification No. 2103b, and outlet conforming to 8 threads per in. per ANSI B2.1.
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Single Check,
‘‘Powhatan’’ Model 21-201* 21⁄2×21⁄2×4
Straightway Siamese
Double Check,
‘‘Powhatan’’ Model 21-132 21⁄2×21⁄2×4
Straightway Siamese
Double Check,
‘‘Powhatan’’ Model 21-203 21⁄2×21⁄2×4
Straightway Siamese
Straightway Siamese
‘‘Powhatan’’ Model 21-132** 3×3×4
Dual Clapper
Double Check,
‘‘Powhatan’’ Model 21-133 21⁄2×21⁄2×4
90° Siamese
Double Check,
‘‘Powhatan’’ Model 21-207 21⁄2×21⁄2×4
90° Siamese
90° Siamese Dual
‘‘Powhatan’’ Model 21-133** 3×3×4
Clapper
**These connections are FM Approved for hose threads conforming to the standard for hose coupling screw threads, ANSI B2.4 or the Engineering Division, Dept.
of Purchase, City of New York, Specification No. 2103b, and outlet conforming to 8 threads per in. per ANSI B2.1.
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Fire Protection Products Inc, 6241 Yarrow Dr, Suite A, Carlsbad CA 92009-1541
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
FM Approvals
September 2007 — Approval Guide
1-256 Automatic Sprinkler Systems
A Giacomini SpA, Strada Per Alzo 39, 28017 S Maurizio d’Opaglio, Italy
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Grinnell or Gem
21⁄2×21⁄2×4
1682 Straightway
3×3×4
1683 45°Connection 21⁄2×21⁄2×4
Potter-Roemer Inc, 15125 Proctor Avenue, Box 3527, City of Industry CA 91744-0527
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Shuenn Cherng Industrial Co Ltd, 113 Tsao-Kang Lane, Tsao-Jong Lee Lukang, Chang Hua Hsien 505,
Taiwan ROC
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Wilson & Cousins Interior Fire Protection, 4390 Paletta Court, Burlington, Ontario L7L 5R2 Canada
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Straightway
IE-33S Single Clapper 21⁄2×21⁄2×4
Female Connection
90° Single Clapper
IE-34S 21⁄2×21⁄2×4
Female Connection
Zhejiang Slion Brass-Craft Manufacturing Co Ltd, 256 Chuyou South Rd Chumen, Yuhuan, Zhejiang, China 317605
Nominal Size,
Fig. No. Component Description
Inlets×Outlet, in.
Straightway
8511030 Single Clapper 21⁄2×21⁄2×4
Female Connection
90° Single Clapper
8511031 21⁄2×21⁄2×4
Female Connection
These connections have a 300 psi (2070 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-257
BALL DRIPS
Ball drips are designed to automatically drain off water which may leak into piping that must be kept free of water.
A common use is on fire service pumper connections or the trim of dry pipe valves. The ball drip is normally open
and closes when the flow of water through is between 4 and 10 gal/min (15 through 40 dm3/min). Unless otherwise
noted in the listing, these ball drips have a rated working pressure of 175 psi (1205 psi).
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Model A. 1⁄2 in. NPS.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model C. 1⁄2, 3⁄4 in. NPS.
Water motor gongs give a locally audible alarm signal when the automatic sprinkler system operates. They may
be used with waterflow alarm, dry pipe, or automatic water control valves.
Angus Fire Sprinklers, Thame Park Rd, Oxfordshire OX9 3RT, United Kingdom
Model D.
Model E. Limited to installations where freezing temperatures are not anticipated.
Model F. Available with British Standard threads.
Dixon Valve & Coupling Company, 800 High Street, Chestertown MD 21620
‘‘Automatic’’ Model 168.
‘‘Automatic’’ Model 168-200.
Globe Fire Sprinkler Corp, 4077 Air Park Dr, Standish MI 48658
Models C, E, F.
Model WM. Single gong.
Model WM-2. Double gong.
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
Model No. PM 12 3569 93, AG2.
Reliable Automatic Sprinkler Co Inc, 1470 Smith Grove Road, Liberty SC 29657-0313
Model C.
Star Sprinkler Inc, 7071 S 13th St, Suite 103, Oak Creek WI 53154
Model CD.
Venus Fire Protection Ltd, 4105 Portland Blvd, Sherbrooke, Quebec J1L 1X9, Canada
Astra Model E.
FM Approvals
September 2007 — Approval Guide
1-258 Automatic Sprinkler Systems
Hubless pipe couplings are used with hubless cast iron or steel pipe in drain, waste, vent, sewer, rainwater or
storm drain systems. These couplings may be used above ground when the piping system is adequately supported
and braced, and below ground when the system is laid on a continuous firm bed, concrete or other adequate
supports. Any required clamps, restraints or supports should be installed or framed prior to careful placement of
backfill and should conform to the requirements of the authority having jurisdiction.
Clamp-All Products Corp, c/o Torca Products Inc, 2430 E Walton Blvd, Auburn Hills MI 48326
CLAMP-ALL ‘‘Hi-Torq-125.’’ Stainless steel band style clamp with neoprene sleeve. 11⁄2, 2, 3, 4, 5, 6, 8, 10, 12 and 15 in. Nominal sizes.
15 psi (105 kPa) working pressure.
CLAMP-ALL ‘‘Hi-Torq-80.’’ Stainless steel band style clamp with neoprene sleeve. 11⁄2, 2, 3, 4, 5, 6, 8, 10 in. Nominal sizes. 15 psi (105 kPa)
working pressure. Four largest sizes may require restraint per manufacturer’s instructions.
GROOVED COUPLINGS
Grooved couplings are used to join pipe and fittings in both wet and dry sprinkler systems. Unless otherwise noted,
these couplings are intended to provide some flexibility in piping systems. Typical applications are in sprinkler risers,
in feed mains passing through walls from one building area to another, in locations subject to earthquakes, in the
discharge line from aboveground pump suction tanks, in new connections to existing feed mains and in air or water
fire service lines subject to excessive vibration or difficult alignment.
Unless otherwise noted, these couplings are limited to use with rolled or cut groove-ended pipe, valves and fittings,
at a minimum rated working pressure of 175 psi (1205 kPa) and are suitable for aboveground service. Higher rated
pressures are noted in the text of the listing. Selection of pipe schedules for use with grooved pipe couplings should
be made according to applicable FM Global Property Loss Prevention Data Sheets installation standards. These
pipe schedules determine system pressure ratings and may take precedence over the higher rated working
pressures listed for some couplings.
Installation must be made according to the manufacturer’s instructions and requirements. Where couplings are
used to join FM Approved pipe, the pipe manufacturer’s installation instructions and requirements must also be
observed. Grooves should be made according to ANSI/AWWA C606 (latest edition), ‘‘Grooved and Shouldered
Joints’’, unless otherwise specified.
FM Approved grooved pipe couplings joining steel pipe may be used in underground service, subject to the
installation restrictions placed upon the pipe and to the coupling manufacturer’s recommendations and requirements.
Unless otherwise stated in the listing, these couplings have been evaluated for a maximum ambient temperature
of 225°F (107°C), suitable for use in normal warehouse protection. For special applications, temperatures, or
environments, the manufacturer’s recommendations and requirements are to be followed.
These couplings join pipe, valves or fittings having equal nominal-sized diameters.
ATUSA empresarial SL, Aptd. Correos 8, Poligono Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-259
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
1-6 ‘‘ b, c, w 500
(3445)
8 ’’ b, c, w 400
(2760)
10 ‘‘ b, c, w 450
(3105)
12 ’’ b, c, w 350
(2415)
76.1 mm Cut Groove c, h 500
165.1 mm Rolled Groove (3445)
216 mm, Rolled Groove c, l 500
267 mm (3445)
318 mm ’’ c, l 400
(2760)
7001E 10, 12 Cut Groove a, b, c, w 175
Rolled Groove (1205)
7000E 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5 Cut Groove a, b, c, d, i, k, t, w 300
Rolled Groove (2070)
76, 165 mm Cut Groove c, h 300
Rolled Groove (2070)
6, 8 Cut Groove a, b, c, w 175
Rolled Groove (1205)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket Grade E (green stripe), Grade E Type A (violet stripe), and Grade E Type A Dri-Seal™ (violet stripe). Flush gap gasket in 11⁄2-12 in. nominal
sizes are interchangeable with standard gasket.
d. Min schedule pipe to be joined: 3 in. or smaller – Allied Tube & Conduit FM Approved ‘‘XL’’, ‘‘Super-XL’’ and ‘‘Super-40’’ Thinwall pipe.
e. Min schedule pipe to be joined: Allied Tube ‘‘Dyna-Flow’’ Lightwall pipe, 11⁄4-4 in. 300 psi (2070 kPa).
f. Min schedule pipe to be joined: Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall pipe, 11⁄4-4 in. 300 psi (2070 kPa).
h. Metric Pipe: Equivalent to 76.1, 108, 133, 139.7, 159 and 165.1 mm. British Standard 1387, medium or equal.
j. Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
k. Tex-Tube Co. ‘‘Tex-Flow’’ non-threadable Lightwall pipe.
l. JIS Schedule 20 pipe or heavier.
m. For use with Northwest ‘‘EZ-Flow’’ in 3 through 6 in. sizes.
n. Youngstown Tube ‘‘Fire-Flo’’ Non-Threadable Lightwall Sprinkler Pipe.
p. IDOD Systems Gal-5 and All-Gal, Bull Moose Ultra-Eddy, and Wheatland WST Schedule 5 Pipes.
r. IDOD Systems Gal-7 and Gal-flo pipe.
s. Western International Fire Line Flow or Fire Line Thread Light pipe.
t. Wheatland Mega-Flow, Mega-thread, MLT, GL, and WLS pipe.
u. Bull Moose EDDY-flow, EDDY-lite pipe.
v. For use with Yieh Phui SPS Flow Pipe in 11⁄4 through 4 in. NPS.
w. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.
FM Approvals
September 2007 — Approval Guide
1-260 Automatic Sprinkler Systems
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Pipe Ends Remarks Max Working
Designation Size, in. Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S, 8 in. NPS and larger, 0.188 in. (5 mm) wall.
c. With EPDM gasket using standard gasket lubricant or dry lubricant.
d. For use with Allied Tube and Conduit ‘‘Super-Flo’’ and ‘‘Dyna-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
e. For use with Northwest Pipe ‘‘EZ-Flow’’ Lightwall steel sprinkler pipe in size 4 in. NPS.
f. For use with Allied Tube and Conduit ‘‘XL’’, ‘‘XL-II’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
g. For use with Allied Tube and Conduit ‘‘Super-XL’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
h. For use with Allied Tube and Conduit ‘‘Super-40’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
i. For use with Allied Tube and Conduit ‘‘BLT’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
k. For use with Wheatland Tube ‘‘WLS’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
l. For use with Western International Forest Products ‘‘Fire-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 3, and 4 in. NPS.
m. Available with flush gap gasket, 11⁄2-12 in. NPS.
n. For use with Tex-Tube ‘‘Tex-Flow’’ Lightwall steel sprinkler pipe in sizes: 3 and 4 in. NPS.
o. For use with Bull Moose ‘‘Ultra-Eddy’’ Schedule 5 steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
p. For use with Wheatland Tube ‘‘Mega-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 3, and 4 in. NPS.
q. For use with Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
r. For use with BS 1387 Medium or Heavy steel pipe in sizes: 76 and 165 mm NPS.
s. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.
Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan
Industrial Base, Shunyi District, Beijing, P. R. China
Product Pipe Size, Pipe Max Working
Designation mm Ends Remarks Pressure, psi
(kPa)
Dong Yang Bend Co Ltd, 37-3, Songma-Ri, Daegot-Myeon, Gimpo-Si, Gyeonggi-do, Korea
Product Pipe Actual Size Pipe Max Working
Designation mm/in. Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-261
Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien, Taiwan ROC
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang, Tsun Ta Liau Shiang Kaohsiung Hsien,
Taiwan ROC
DUCCO Brand Couplings
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
FireShield Series 300 Products.
FM Approvals
September 2007 — Approval Guide
1-262 Automatic Sprinkler Systems
JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan
Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin, Jinan, 250400 China
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
d. Approved for use with GB/T3092 regular and extra heavy pipe, ISO 4200, and BS 1387 medium and heavy pipe.
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-263
07 2, 21⁄2, 3 ’’ c, d, f, j 300
(2070)
11⁄2-6 ’’ a, b, c, f, j 500
(3445)
8 Rolled Groove b, c, j 400
(2760)
8 Cut Groove a, c, j 500
(3445)
76, 139.7 mm Cut Groove c, g, h, j 500
Rolled Groove (3445)
75 11⁄4-8 Cut Groove, a, b, c, d, f, j 500
Rolled Groove (3445)
76.1, 108, 133, 139 Rolled Groove c, g, j 290
159, 165 mm (2000)
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
FireShield Series 300 Products.
FM Approvals
September 2007 — Approval Guide
1-264 Automatic Sprinkler Systems
2 ’’ c, q 300
(2070)
Style 11 11⁄4-3 Cut Groove, c, l 300
Rolled Groove (2070)
11⁄4-4 ’’ c, d, m 300
(2070)
11⁄4-2 ’’ c, g 300
(2070)
11⁄4-4 ’’ a, b, c 300
(2070)
11⁄4-8 ’’ a, b, c 500
(3445)
Style 12 11⁄4-3 ’’ c, l 175
(1205)
11⁄4-4 ’’ c, d, m 175
(1205)
11⁄4-2 ’’ c, g, o 175
(1205)
11⁄4-8 ’’ a, b, c 175
(1205)
11⁄4-2 Rolled Groove c, q, r 175
(1205)
3 ’’ c, r 175
(1205)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With standard EPDM gasket, or dry lubricant EPDM gasket.
d. Allied ‘‘Dyna-Flow.’’
g. Bull Moose ‘‘EDDY-Lite.’’
k. British Standard BS 1387 Pipe.
l. Allied ‘‘XL.’’
m. Allied ‘‘Super-Flo.’’
o. With Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
p. Tex-Tube Co. ‘‘Tex-Flow’’ non-threadable Lightwall pipe.
q. Western International Forest Products ‘‘Fire Thread’’ threadable Thinwall pipe.
r. Western International Forest Products ‘‘Fire Flow’’ non-threadable Lightwall pipe.
Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao,
China
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 or 10 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with GB/T 3091-93 or GB/T 8163-99 Pipe.
Robor Pipe Systems, Box 1098, Isando, Gauteng 1600, South Africa
Style ‘‘STEELGRO F75’’ Grooved.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-265
f. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe, Allied ‘‘BLT’’, and Wheatland ‘‘WLS.’’
j. For use with Bull Moose Tube EDDY-Flow pipe.
k. For use with BS 1387 medium and heavy pipe, or equal.
SCE Company Ltd, Unit E&F, 20/F., CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong
Max Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, in. Ends Remarks (kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
SPT Metal Corp, 19-1 Da Y/eh St, Da Liao Hsiang, Kaóhsiung Hsien, Taiwan ROC
300
505 1-4 Rolled Groove c, e, f, g, h, i, j, n
(2070)
1, 11⁄4, 11⁄2, 2, 21⁄2, Cut Groove 300
505 a, b, c, n
3, 4, 5, 6, 8 Rolled Groove (2070)
300
505 76.1, 165.1 mm Rolled Groove c, d, n
(2070)
300
505 11⁄4 through 4 ’’ c, m, n
(2070)
175
505 11⁄4 through 4 ’’ c, n
(1205)
300
507 11⁄2-6 ’’ c, e, f, g, h, i, j, n
(2070)
175
507 11⁄2 through 4 ’’ c, n
(1205)
Cut Groove 300
507 11⁄2 through 14 a, b, c, n
Rolled Groove (2070)
175
507 16 through 24 ’’ a, b, c, n
(1205)
2, 21⁄2, 3, Cut Groove 300
505 Stainless Steel c, k, p
4, 5, 6, 8, 10 Rolled Groove (2070)
Cut Groove 250
505 Stainless Steel 12 c, k, p
Rolled Groove (1720)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For metric pipe per BS 1387 medium or equal.
e. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe, 1-2 in. only.
f. For use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size.
i. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
j. For use with Bull Moose Tube EDDY-Flow pipe.
k. For use on Schedule 40 Cut Groove and Rolled Groove only.
m. For use with Wheatland ″Mega-Flow″ non-threadable Thinwall pipe.
n. Ductile Iron
p. Stainless Steel.
Shanghai Recomb Piping System Co Ltd, No. 270 Yixian Rd, Shanghai 200434, Peoples Republic China
Product Pipe Actual Pipe Max Working
Designation Size mm Ends Remarks Pressure, psi
(kPa)
XGQT2 33.7, 42, 48, 60, 73, 76, 89, Rolled Groove, a, b, c 300
108, 114, 133, 140, 141.3, Cut Groove (2070)
159, 165, 168 and 219
FM Approvals
September 2007 — Approval Guide
1-266 Automatic Sprinkler Systems
Shanghai Vision Mechanical Joint Co Ltd, Jinlan Road, Loutang Industrial Park, Jiading District,
Shanghai 201807 PRC
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Product Nominal Pipe Fitting Max Working
Designation Size, in. Description Remarks Pressure, psi
(kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 and 10 in.-0.188 in. wall; 12 in.-0.250 in. wall.
c. Allied ‘‘Super-Flo’’, Allied ‘‘Dyna-Flow’’, 4 in. or smaller.
d. Allied ‘‘Super 40’’ and ‘‘Super-XL’’, 1 through 3 in.
e. Bull Moose ‘‘EDDY-Lite’’, 1 through 2 in.
f. BS 1387 medium or heavy grade, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 6 in.
g. Bull Moose Tube EDDY-Flow pipe, 11⁄2 through 4 in.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-267
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 or 10 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green Stripe).
d. For use with Korean KS D3507 pipe.
f. For use with metric OD pipe.
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-268 Automatic Sprinkler Systems
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket using standard gasket lubricant or dry lubricant.
d. For use with Allied Tube & Conduit ‘‘Dyna-Light’’ Schedule 5 non-threadable Lightwall pipe.
f. Also available with Tri-Seal EPDM gasket. Recommended by the manufacturer for dry systems. For use with standard gasket lubricant or dry lubricant.
g. For use with Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe.
h. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’ and ‘‘Super-Flo’’ non-threadable Lightwall pipe.
i. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
j. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
k. For use with BS1387 medium or heavy pipe.
n. For use with Bullmoose Tube Co. ‘‘Ultra-EDDY’’ Schedule 5 non-threadable Lightwall pipe.
o. For use with Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe.
p. For use with IDOD Systems Schedule 5 non-threadable Lightwall pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
s. For use with Allied ‘‘XL’’ pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. For use with Youngstown Tube Co. ‘‘Fire-Flo’’ non-threadable Lightwall steel sprinkler pipe.
w. For use with Youngstown Tube Co. ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe.
x. For use with IDOD’s Gal-7 and Gal-Flo pipe.
y. For use with Bullmoose Tube Co. ‘‘EDDY-flow’’ non-threadable Lightwall pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-269
77 1-12 ’’ a, c, e, aa 500
(3445)
14 ’’ a, c, e 300
(2070)
1-4 ’’ o, aa 175
(1205)
1, 11⁄4, 11⁄2, 2 ’’ e, h, aa 300
(2070)
1, 11⁄2, 2, 21⁄2, 3, 4 ’’ a, e, g, w, z, aa 300
(2070)
11⁄4, 11⁄2, 2, 21⁄2, 3, 4 ’’ a, e, j, k, u, aa 300
(2070)
1-4 ’’ q, y, aa 300
(2070)
21⁄2, 3, 4 ’’ e, s, aa 300
(2070)
6 ’’ e, s, aa 175
(1205)
6 ’’ a, e, z, aa 300
(2070)
1-12 ’’ a, d, e, aa 450
(3105)
11⁄2-3 ’’ a, e, aa 175
(1205)
14 ’’ a, d, e 300
(2070)
3-8 ’’ a, e, i, v, aa 300
(2070)
165 mm ’’ b, e, n, aa 450
(3105)
3⁄4-2 ’’ a, e, p, aa 175
(1205)
1, 11⁄4, 11⁄2, 2 ’’ a, e, l, t, y, aa 300
(2070)
76, 108, 133, ’’ a, b, n, aa 175
139.7, 159 mm (1205)
11⁄4, 11⁄2, 2 ’’ a, e, r, aa 300
(2070)
77 267, 318 mm Rolled Groove e, ff 175
Cut Groove (1205)
FM Approvals
September 2007 — Approval Guide
1-270 Automatic Sprinkler Systems
Victaulic Company of Japan Limited (The), IINO Building 3F, 1-1, Uchisaiwaicho 2-Chome, Chiyoda-Ku,
Tokyo 100-0011, Japan
Product Nominal Pipe Pipe Remarks Max Working
Designation Size, in. Ends Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-271
a. Also available with Style 77FS gasket. Recommended by manufacturer for use with dry pipe systems.
b. For steel pipe having metric sized outside dia. (ref. DIN 2448 & 2458).
c. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
d. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
e. With gasket E (green stripe), H (white stripe) or L (solid red).
i. With gasket M.
l. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe.
m. Joins rolled or cut groove steel pipe, per note d to cut groove iron pipe per note i.
n. For steel pipe having outside dia. sized per British Standard 1387, medium or equal.
o. All FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
p. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.
q. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
s. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 and 6 in. nominal size.
t. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
u. For use with Bull Moose Tube EDDY-Flow pipe.
v. For use with Wheatland ‘‘Mega-Flow’’ up to 4 in. nominal size.
w. For use with Wheatland ‘‘MLT’’ up to 2 in. nominal size.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For metric pipe per BS 1387 medium or heavy.
FM Approvals
September 2007 — Approval Guide
1-272 Automatic Sprinkler Systems
Weifang 100tong Casting Co Ltd, No. 1919 Jinchang South Road, Weicheng District, Weifang, Shandong, PR China
261052
Rated Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, mm Ends Remarks (kPa)
GCQT2 33, 42, 48, 60, 76, 89, 108, Cut Groove or a, b, c, d, e, f 230
114, 133, 140, 159, 165, 168, Rolled Groove (1600)
219
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with BS 1387 medium or equal metric pipe.
e. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000,
Schedule 40 pipe (8 in. NPS – Schedule 30).
f. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40
pipe (8 in. NPS – Schedule 30).
AJS Co Ltd, 1001 Namsung Plaza #345-30, Gasan-dong, Geumcheon-gu, Seoul 153-782 Korea
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000,
Schedule 40 pipe (8 in. NPS – Schedule 30).
e. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40
pipe (8 in. NPS – Schedule 30).
ATUSA empresarial SL, Aptd. Correos 8, Poligono Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain
Product Nominal Pipe Pipe Remarks Max Working
Designation Size, in. Ends Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Fitting Max Working
Designation Size, in. Description Remarks Pressure, psi
(kPa)
Gruvlok HPR*
7004 2-8 Cut Groove, a, c 750
Rolled Groove (5170)
2-3 ’’ c, d 300
(2070)
2-8 Rolled Groove b, c, w 300
(2070)
Rigidlite 7400* 1-8 Rolled Groove, a, b, c, d, e, 300
Cut Groove f, j, l, p, r, s, t, w (2070)
21⁄2-4 Rolled Groove c, n, w 300
(2070)
6 ’’ c, n, w 175
(1205)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-273
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket Grade E (green stripe), Grade E Type A (violet stripe), and Grade E Type A DriSeal™ (violet stripe). Flush gap gasket in 11⁄2-12 in. nominal
sizes are interchangeable with standard gasket.
d. Min schedule pipe to be joined: 3 in. or smaller – Allied Tube & Conduit FM Approved ‘‘XL’’, ‘‘Super-XL’’ and ‘‘Super-40’’ Thinwall pipe.
e. Min schedule pipe to be joined: Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe, 1-4 in.
f. Min schedule pipe to be joined: Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall pipe, 1-4 in.
h. Metric Pipe: Equivalent to 76.1, 108, 133, 139.7, 159 and 165.1 mm. British Standard 1387, medium or equal.
j. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
l. Min schedule rolled groove pipe to be joined: Bull Moose EDDY-Lite, 2 in. and EDDY-flow, 11⁄2-4 in.175 psi (1205 kPa).
m. Min schedule rolled groove pipe to be joined: Bull Moose Ultra-EDDY, 1-2 in., IDOD Systems Gal-5 and All-Gal, and Wheatland WST Schedule 5 pipes.
n. For use with Tex-Tube ‘‘Tex-Flow’’ Lightwall pipe 21⁄2 to 6 in.
o. For use with Youngstown Tube ‘‘EZ-Thread’’ Threadable Thinwall Sprinkler Pipe.
p. For Use with Northwest ‘‘EZ-Flow’’ pipe in 3 thru 6 in. sizes.
r. IDOD Systems Gal-7 and Gal-flo pipe.
s. Western International Fire Line Flow or Fire Line Thread Light.
t. Wheatland Mega-Flow, Mega-thread, MLT, GL, and WLS pipe.
w. EPDM Grade E (green stripe) flush gap gaskets in 1-12 in. nominal sizes are interchangeable with standard EPDM gaskets.
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Pipe Remarks Max. Working
Designation Size, in. Ends Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S, 8 in. NPS and larger, 0.188 in. (5 mm) wall.
FM Approvals
September 2007 — Approval Guide
1-274 Automatic Sprinkler Systems
Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan
Industrial Base, Shunyi District, Beijing, P. R. China
Product Pipe Size, Pipe Max Working
Designation mm Ends Remarks Pressure, psi
(kPa)
Dong Yang Bend Co Ltd, 37-3, Songma-Ri, Daegot-Myeon, Gimpo-Si, Gyeonggi-do, Korea
Product Pipe Actual Size Pipe Max Working
Designation mm/in. Ends Remarks Pressure, psi
(kPa)
Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang Tsun Ta Liau Shiang Kaohsiung Hsien,
Taiwan ROC
DUCCO Brand Couplings
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-275
a. Min schedule cut groove pipe to be joined: 6 in. or smaller — Schedule 40.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller — Schedule 10.
c. With EPDM gasket.
d. For use with Schedule 5 pipe.
e. For use with Allied Super-Flo or Dyna-Flow pipe.
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
FireShield Series 300 Products.
Max Working
Product Nominal Pipe Pressure, psi
Designation Size, in. Remarks (kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket, and flush-seal gasket.
d. Allied ‘‘Dyna-Flow’’
g. Bull Moose ‘‘EDDY-Lite’’
l. Allied ‘‘XL’’
m. Allied ‘‘Super-Flo’’
n. BS 1387 pipe, Med. or Heavy.
o. IDOD Gal-7
p. Tex-Tube Tex-flow
r. Western International Fire-Thread and Fire-Flow
s. Northwest EZ-Flow
t. Welded Tube – Berkeley, LLC Steady-Flow
u. Wheatland Sch. 5 and IDOD Gal-5
JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10.
c. Allied ‘‘Super-Flo’’, Allied ‘‘Dyna-Flow’’, 4 in. or smaller.
d. Allied ‘‘Super 40’’, Bull Moose ‘‘Ultra-Eddy’’, 3 in. or smaller.
e. Bull Moose ‘‘EDDY-LITE’’, 11⁄4 through 2 in.
f. BS 1387 medium or heavy grade, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 6 in.
g. Bull Moose Tube EDDY-FLOW pipe, 11⁄2-4 in.
h. American Tube ‘‘BLT’’, 11⁄4 through 2 in.
j. American Tube ‘‘Dyna-Thread’’ 11⁄4 through 2 in.
k. ‘‘Super-XL’’, 11⁄4 through 3 in.
l. Allied Tube ‘‘XL-II’’, 11⁄4 through 3 in.
m. Central ‘‘TL’’, 11⁄4 through 2 in.
p. Wheatland WST, 11⁄4 through 2 in.
Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin, Jinan, 250400 China
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
FM Approvals
September 2007 — Approval Guide
1-276 Automatic Sprinkler Systems
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
d. Approved for use with GB/T3092 regular and extra heavy pipe, ISO 4200, and BS 1387 medium and heavy pipe.
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in areas subject to earthquake.
a. Minimum schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 Wall (5 mm Wall).
c. With EPDM ‘‘EP’’ gasket (green stripe).
d. For use with DIN 2448 and 2458 steel pipe.
e. For use with all FM Approved Thinwall steel sprinkler pipe.
f. With EPDM ‘‘EA’’ gasket (violet stripe).
g. For installation with cast rigid insert placed in the bolt pocket, according to the manufacturer’s instructions.
h. With EPDM ‘‘EP’’ gasket with pre-lubricated material.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe.
e. FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
f. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe, Allied ‘‘BLT’’ and Wheatland ‘‘WLS.’’
i. For use on Northwest EZ Flow non-threadable Lightwall pipe in 4 in. nominal size.
j. For use with Bull Moose Tube EDDY-Flow pipe.
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
FireShield Series 300 Products.
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-277
2-8 ’’ a, b, c 175
(1205)
3-8 Rolled Groove c, n 175
(1205)
2 ’’ c, o, p 175
(1205)
*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With standard EPDM gasket, or dry lubricant EPDM gasket.
d. Allied ‘‘Dyna-Flow.’’
g. Bull Moose ‘‘EDDY-Lite.’’
l. Allied ‘‘XL.’’
m. Allied ‘‘Super-Flo.’’
n. Tex-Tube ‘‘Tex-Flow’’ Lightwall pipe.
o. Western International Forest Products ‘‘Fire Thread’’ threadable Thinwall pipe.
p. Western International Forest Products ‘‘Fire Flow’’ non-threadable Lightwall pipe.
Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao,
China
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 or 10 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with GB/T 3091-93 or GB/T 8163-99 Pipe.
Robor Pipe Systems, Box 1098 Isando, Gauteng 1600, South Africa
Style ‘‘STEELGRO R75’’ Grooved.
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe.
e. FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
f. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe, Allied ‘‘BLT’’ and Wheatland ‘‘WLS.’’
i. For use on Northwest EZ Flow non-threadable Lightwall pipe in 4 in. nominal size.
j. For use with Bull Moose Tube EDDY-Flow pipe.
k. For use with BS 1387 medium and heavy pipe, or equal.
SCE Company Ltd, Unit E&F, 20/F., CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong
Max Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, in. Ends Remarks (kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
FM Approvals
September 2007 — Approval Guide
1-278 Automatic Sprinkler Systems
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
SPT Metal Corp, 19-1 Da Yeh St, Da Liao Hsiang, Kaóhsiung Hsien, Taiwan ROC
*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. British Standard Pipe
e. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe, 1-2 in. only.
f. For use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size.
i. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
j. For use with Bull Moose Tube EDDY-Flow pipe.
k. For use on Schedule 40 Cut Groove and Rolled Groove only.
m. For use with Wheatland ‘‘Mega-Flow’’ non-threadable Thinwall pipe.
Shanghai Recomb Piping System Co Ltd, No. 270 Yixian Rd, Shanghai 200434, P.R. China
Product Pipe Actual Pipe Remarks Max Working
Designation Size mm Ends Pressure, psi
(kPa)
XGQT1 33.7, 42, 48, 60, 73, 76, 89, 108, 114, 133, Rolled Groove, a, b, c 300
140, 141.3, 159, 165, 168 and 219 Cut Groove (2070)
XGQT1 273 and 325 Rolled Groove, a, b, c 175
Cut Groove (1205)
Shanghai Vision Mechanical Joint Co Ltd, Jinlan Road, Loutang Industrial Park, Jiading District,
Shanghai 201807 PRC
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-279
001 45, 57, 76, 108, 133, 159, Cut Groove a, b, c, d, e 300
165 mm Rolled Groove (2070)
Remarks:
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000,
Schedule 40 pipe (8 in. NPS – Schedule 30).
e. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40
pipe (8 in. NPS – Schedule 30).
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10.
c. Allied ‘‘Super-Flo’’, Allied ‘‘Dyna-Flow’’, 4 in. or smaller.
d. Allied ‘‘Super 40’’, ‘‘Super-XL’’, 11⁄4 through 3 in.
e. Bull Moose ‘‘EDDY-LITE’’, 11⁄4 through 2 in.
f. BS 1387 medium or heavy grade, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6 in.
g. Bull Moose Tube EDDY-Flow pipe, 11⁄4 through 4 in.
h. American Tube ‘‘BLT’’, 11⁄4 through 2 in.
i. For use with copper tubing in ‘‘K’’ type pipe.
j. American Tube ‘‘Dyna-Thread’’ 11⁄4 through 2 in.
k. ‘‘Super-XL’’, 11⁄4 through 3 in.
l. Allied Tube ‘‘XL-II’’, 11⁄4 through 3 in.
m. Central ‘‘TL’’, 11⁄2 through 2 in.
p. Wheatland WST, 11⁄4 through 2 in.
q. ‘‘Fire-Thread’’, 11⁄2 through 2 in.
r. ‘‘Fire-Flow’’, 11⁄4, 11⁄2, 4 in.
s. EPDM gasket.
FM Approvals
September 2007 — Approval Guide
1-280 Automatic Sprinkler Systems
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 or 10 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green Stripe)
d. For use with Korean KS D3507 pipe.
f. For use with metric OD pipe.
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green or violet stripe).
d. Min schedule pipe to be joined: 3 in. or smaller – Allied Tube & Conduit FM Approved ‘‘XL’’, ‘‘Super-XL’’ and ‘‘Super-40’’ Thinwall pipe.
e. Min schedule pipe to be joined: Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe, 1-3 in.
f. Min schedule pipe to be joined: Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall pipe, 1-4 in.
h. Metric Pipe: Equivalent to 76.1, 108, 133, 139.7, 159 and 165.1 mm. British Standard 1387, medium or equal.
j. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
n. Tex-Tube ‘‘Tex-Flow’’ Lightwall pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-281
11⁄4-2 ’’ c, e, g, h, r, s, t 300
(2070)
11⁄4-4 ’’ c, p 300
(2070)
5, 6 ’’ b, c, e 300
(2070)
8 ’’ b, c, e 400
(2760)
5 Cut Groove a, c, e 300
(2070)
6 ’’ a, c, e 400
(2760)
8 ’’ a, c, e 450
(3105)
10, 12 Cut Groove a, b, c, e 250
Rolled Groove (1725)
76, 165 mm Cut Groove c, e, n 300
Rolled Groove (2070)
*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green stripe). For use with standard lubricant or dry lubricant.
e. Also available with Tri-Seal EPDM gasket. Recommended by the manufacturer for dry systems. For use with standard lubricant or dry lubricant.
f. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’, Northwest ‘‘EZ-Flow’’ and Allied ‘‘Super-Flo’’ non-threadable Lightwall pipe, in sizes up to 4 in. NPS.
g. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe, in 6 in. NPS size.
h. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
i. For use with Wheatland WLS.
j. For use with Bull Moose ‘‘Ultra-EDDY’’ Schedule 5 pipe.
l. For use with Northwest ‘‘EZ-flow’’ Pipe in 6 in. NPS size.
m. For use with IDOD Systems Sch. 5 Pipe.
n. For use with BS 1387 medium and heavy wall pipe.
o. For use with Youngstown Tube Co. ‘‘Fire-Flo’’ non-threadable Lightwall steel sprinkler pipe.
p. For use with Youngstown Tube Co. ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. For use with IDOD’s Gal-7 and Gal-Flo pipe.
w. For use with Bull Moose ‘‘EDDY-flow’’ non-threadable Lightwall pipe.
FM Approvals
September 2007 — Approval Guide
1-282 Automatic Sprinkler Systems
a. Also available with Style 77FS gasket. Recommended by manufacturer for use with dry pipe systems.
b. For steel pipe having metric sized outside dia. (ref. DIN 2448 & 2458).
c. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
d. For use with Youngstown Tube ‘‘Fire-Flo’’ non-threadable Lightwall steel sprinkler pipe.
e. With gasket E (green stripe), H (white stripe) or L (solid red), using standard gasket lubricant or Vic-Plus dry lubricant.
f. For use with JIS steel pipe.
g. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
h. For use with Schedules 10 and 40 stainless steel pipe.
i. For use with Welded Tube–Berkeley LLC ‘‘Steady Flow’’ non-threadable Lightwall steel sprinkler pipe in sizes 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
j. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe.
k. With gasket E, Grade A (violet stripe) with or without dry lubricant .
l. For use with Allied Tube & Conduit ‘‘XL’’ and ″BLT″ threadable Thinwall pipe.
m. For use with Welded Tube–Berkeley LLC ‘‘Steady Thread’’ threadable Thinwall steel sprinkler pipe in sizes 1, 11⁄4, 11⁄2, and 2 in. NPS.
n. For steel pipe having outside dia. sized per British Standard 1387, medium or equal.
o. For use on Allied Tube & Conduit ‘‘Dyna-Flow’’ and ″Super-flo″ non-threadable Lightwall pipe.
p. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-283
q. For use with IDOD Systems Gal-7 and Gal-flo pipe, 11⁄4-2 in. sizes.
r. For use on Wheatland ‘‘Mega-Flow’’ pipe.
s. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 and 6 in. nominal size.
u. For use with Bull Moose Tube EDDY-Flow pipe.
v. For use on Schedules 10 and 40 pipe with end seal grooves only. Not for use with standard rolled or cut grooves. Not for use with hydrocarbon based fluids.
x. For use with IDOD Systems Gal-5 and All-Gal pipe, 11⁄4-2 in. sizes at 175 psi.
y. Tex-Tube ‘‘Tex-Flow’’ Lightwall pipe.
z. For use with Western ‘‘Fire-Flow’’ and ‘‘Fire-Thread’’ pipe.
aa. For use with VicMax EPDM Gaskets in 2 through 8 in. and 76 and 165 mm sizes.
aaa. = For use with ‘‘EDDY-lite’’ and ‘‘EDDY-thread’’ pipe made by Bull Moose Tube.
bb. = For use with ‘‘GL’’, ‘‘WLS’’ and ‘‘MLT’’ pipe made by Wheatland Tube.
cc. = For use with ‘‘WST’’ pipe at 175 psi, as made by Wheatland Tube.
dd. = For use with ‘‘Ultra-EDDY’’ pipe at 175 psi, as made by Bull Moose Tube.
ee. = For use with ‘‘Dyna-light’’ pipe at 175 psi, as made by Allied Tube & Conduit.
ff. = For use with Allied Tube & Conduit ‘‘Dyna-thread’’ threadable Thinwall pipe.
gg. = For use with Wheatland Tube ‘‘Mega-thread’’ threadable Thinwall pipe.
*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.
a. Also available with Style 77FS gasket. Recommended by manufacturer for use with dry pipe systems.
b. For steel pipe having metric sized outside dia. (ref. DIN 2448 & 2458).
c. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
e. With gasket E (green stripe), H (white stripe) or L (solid red).
g. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
k. With gasket E, Grade A (violet stripe).
FM Approvals
September 2007 — Approval Guide
1-284 Automatic Sprinkler Systems
l. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe.
n. For steel pipe having outside dia. sized per British Standard 1387, medium or equal.
o. All FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
p. For Schedule 5 non-threadable Lightwall pipe as manufactured by Bull Moose Tube Co.
q. When joining Allied Tube & Conduit ″Super-flo″ non-threadable Lightwall pipe.
s. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size.
t. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
u. For use with Bull Moose Tube EDDY-Flow pipe.
*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For metric pipe per BS 1387 medium or heavy.
e. For use on Wheatland ‘‘Mega-Flow’’ pipe.
f. All FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ and ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size at 250 psi (1725 kPa).
j. For use with Bull Moose Tube ‘‘EDDY-Flow’’ pipe.
Weifang 100tong Casting Co Ltd, No. 1919 Jinchang South Road, Weicheng District, Weifang, Shandong, PR China
261052
Rated Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, mm Ends Remarks (kPa)
GCQT1 33, 42, 48, 60, 76, 89, 108, Cut Groove or a, b, c, d, e, f 230
114, 133, 140, 159, 165, 168, Rolled Groove (1600)
219
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with BS 1387 medium or equal metric pipe.
e. For use with Chinese Standard GB/T 3091-1993, GB/T 3092-1993 welded steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000,
Schedule 40 pipe (8 in. NPS – Schedule 30).
f. For use with Chinese Standard GB/T 17395-1998 seamless steel pipe with pipe wall thicknesses comparable to same size ASME B16.10M-2000, Schedule 40
pipe (8 in. NPS – Schedule 30).
These couplings join pipe, valves or fittings having different nominal pipe diameters.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-285
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. Allied ‘‘Dyna-Flow.’’
g. Bull Moose ‘‘EDDY-Lite.’’
l. Allied ‘‘XL.’’
m. Allied ‘‘Super-Flo.’’
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Fitting Max Working
Designation Size, in. Description Remarks Pressure, psi
(kPa)
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Pipe Ends Remarks Max Working
Designation Size, in. Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S, 8 and 10 in. NPS, 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with Allied Tube and Conduit ‘‘Super-Flo’’ and ‘‘Dyna-Flow’’, ‘‘Dyna-thread’’, and ‘‘BLT’’ Lightwall steel sprinkler pipe.
e. For use with Northwest Pipe ‘‘EZ-Flow’’ Lightwall steel sprinkler pipe.
f. For use with Allied Tube and Conduit ‘‘XL’’, ‘‘XL-II’’, ‘‘Super XL’’, and ‘‘Super 40’’ threadable Thinwall steel sprinkler pipe.
i. For use with Wheatland Tube ‘‘WLS’’, ‘‘Mega-flow’’, ‘‘GL’’, ‘‘MLT’’, ‘‘Mega-thread’’ threadable Thinwall steel sprinkler pipe.
k. For use with Bull Moose Tube ‘‘EDDY-Flow’’, ‘‘EDDY-thread’’, ‘‘EDDY-Light’’ Lightwall steel sprinkler pipe.
l. For use with Western International Forest Products ‘‘Fire Line Flow’’, ‘‘Fire Line Thread’’ Lightwall steel sprinkler pipe.
m. For use with Western International Forest Products ‘‘Rapid-Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄2 and 2 in. NPS.
n. For use with Welded Tube–Berkeley LLC ‘‘Steady Flow’’ and ‘‘Steady-thread’’ Lightwall steel sprinkler pipe.
o. Tex-Tube Co. ‘‘Tex-flow’’ Pipe in 21⁄2, 3, and 4 in. at 300 psi, and 6 in. at 175 psi.
p. IDOD Systems Gal 7 and Gal-flow pipe.
r. Yieh Phui Enterprise ‘‘SPS’’ Pipe.
s. Youngstown Tube ‘‘Fire Flow’’ and ‘‘Fire-thread’’ pipe.
t. Approved for use with Schedule 5 pipe.
FM Approvals
September 2007 — Approval Guide
1-286 Automatic Sprinkler Systems
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang Tsun Ta Liau Shiang Kaohsiung Hsien,
Taiwan ROC
DUCCO Brand Couplings
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
FireShield Series 300 Products.
JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-287
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
Remarks:
a. Minimum schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 Wall (5 mm Wall).
c. With EPDM ‘‘EP’’ gasket (green stripe).
d. For use with DIN 2448 and 2458 steel pipe.
e. With EPDM ‘‘EP’’ gasket with pre-lubricated material.
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
FireShield Series 300 Products.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. Allied ‘‘Dyna-Flow.’’
g. Bull Moose ‘‘EDDY-Lite.’’
k. British Standard BS 1387 Pipe.
l. Allied ‘‘XL.’’
m. Allied ‘‘Super-Flo.’’
SPT Metal Corp, 19-1 Da Yeh St, Da Liao, Hsiang, Kaóhsiung Hsien Taiwan, ROC
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
e. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe, 1-2 in. only.
f. All FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size.
i. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
j. For use with Bull Moose Tube EDDY-Flow pipe.
FM Approvals
September 2007 — Approval Guide
1-288 Automatic Sprinkler Systems
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
a. Min schedule cut groove pipe to be joined: 8 in. or smaller – Schedule 40.
b. Min schedule Rolled groove pipe to be joined: 8 in. or smaller – Schedule 10.
c. British Standard BS 1387 medium or heavy grade pipe.
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green stripe).
d. 3 in. and smaller connections can be made to rolled grooved Allied Tube & Conduit FM Approved ‘‘XL’’, ‘‘Super-XL’’ and ‘‘Super-40’’ Thinwall pipe.
e. Min pipe Schedule Pipe to be joined: a) Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe; b) Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-289
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green stripe). For use with standard lubricant or dry lubricant.
e. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
d. For use with BS 1387 medium and heavy pipe.
f. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
g. For use with Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
i. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
j. For use with Central 7 non-threadable Thinwall pipe.
k. For use with Schedule 5 pipe, including IDOD Systems galv. coated pipe.
l. For use with Central 7 pipe.
m. For use with 4 in. Northwest ‘‘EZ-Flow’’ pipe.
n. For use with Welded Tube – Berkeley LLC Steady-flow pipe.
o. For use with Youngstown ‘‘Fire-Flo’’ Pipe.
p. For use with Youngstown ‘‘EZ-Thread’’ Pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. For use with IDOD’s Gal-7 and Gal-Flo pipe.
w. For use with ISO 4200 steel sprinkler pipe.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green stripe). For use with standard lubricant or dry lubricant.
e. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
f. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
g. For use with Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
m. For use with 4 in. Northwest ‘‘EZ-Flow’’ pipe.
n. For use with Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ pipe.
o. For use with Youngstown ‘‘Fire-Flo’’ Pipe.
p. For use with Youngstown ‘‘EZ-Thread’’ Pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. For use with IDOD’s Gal-7 and Gal-Flo pipe.
w. For use with Bull Moose Tube Co. ‘‘EDDY-flow’’ non-threadable Lightwall pipe.
x. For use with BS 1387 Medium and Heavy pipe.
y. For use with ISO 4200 steel sprinkler pipe.
FM Approvals
September 2007 — Approval Guide
1-290 Automatic Sprinkler Systems
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
c. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
d. With gasket E (green stripe), H (white stripe) or L (solid red), using standard gasket lubricant or Vic-Plus dry lubricant.
f. When joining Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall non-threadable pipe, up to 4 in. dia., 200 psi (1380 kPa) limit.
g. With Allied Tube & Conduit ‘‘Dyna-Flow.’’
h. For use with Central 7 pipe.
i. For use with Western ‘‘Fire-Flow’’ and ‘‘Fire-Thread’’ pipe.
j. For use with Bull Moose ‘‘EDDY-Flow’’ pipe.
k. For use on Wheatland ‘‘Mega-Flow’’ pipe.
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
c. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
d. With gasket E (green stripe), H (white stripe) or L (solid red).
f. When joining Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall non-threadable pipe, up to 4 in. dia., 200 psi (1380 kPa) limit.
g. With Allied Tube & Conduit ‘‘Dyna-Flow.’’
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-291
Grooved couplings only allow installation of a perpendicular branch line of reduced size, while joining inline pipes
of equal diameters. Mechanical tees bolt over a hole in the run pipe, and allow installation of a perpendicular branch
line of reduced size. For both couplings and fittings the maximum branch line size is one pipe size reduced from the
run pipe size.
ATUSA empresarial SL, Aptd. Correos 8, Poligono Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain
Product Fitting Nominal Pipe Remarks Max Rated
Designation Description Size, in. Pressure, psi
(kPa)
Style 15G Snap-Tee Branch Outlet. For working pressure of 300 psi (2070 kPa) for the 3, 4 in. run sizes and working pressure of 250 psi
(1725 kPa) for 6 in. run size. For use on Schedule 10 or heavier pipe. Grooved outlet connection clamps over hole in pipe wall.
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Gruvlok Clamp-T. For use with Schedule 10S or heavier pipe*†, in 6 in. or smaller sizes and 0.188 in. (5 mm) wall or heavier pipe, in the
8 in. size. With EPDM gasket (green stripe) only.
FM Approvals
September 2007 — Approval Guide
1-292 Automatic Sprinkler Systems
FM Approved with ANSI NPT thread or ISO thread as appropriate for the outlet pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-293
a. For use with FM Approved Schedule 10 and 40 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6, and 8 in. NPS.
b. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
c. For use with Allied Tube and Conduit ‘‘XL’’ and ‘‘XL-II’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
d. For use with Sawhill Tubular ‘‘SLS’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
e. For use with Wheatland Tube ‘‘WST’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
f. For use with Tex-Tube ‘‘Tex-Flow’’ Lightwall steel sprinkler pipe in sizes: 3, 4, and 6 in. NPS.
g. For use with Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3. In addition, the MT-4 is FM Approved for use with
4 in. NPS ‘‘Steady-Flow’’.
h. For use with Wheatland Tube ‘‘Mega Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
i. For use with Northwest Pipe ‘‘EZ-Flow’’ Lightwall steel sprinkler pipe in sizes: 4 and 6 in. NPS.
j. For use with Youngstown Tube ‘‘Fire-Flo’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
k. For use with Bull Moose Tube ‘‘Ultra – EDDY’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
l. For use with Bull Moose ‘‘EDDY Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
m. For use with Allied Tube and Conduit ‘‘BLT’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
n. For use with Bull Moose Tube ‘‘EDDY-Lite’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
p. For use with Western International Forest Products ‘‘Rapid-Thread’’ steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
q. For use with Wheatland Tube ‘‘WLS’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
r. For use with Western International Forest Products ‘‘Fire Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 3, and 4 in. NPS.
s. For use with Allied Tube and Conduit ‘‘Dyna Flow’’ and ‘‘Super-Flo’’ Lightwall sprinkler pipe in sizes: 11⁄2, 2, 2 1⁄2, 3, 4, and 6 in. NPS.
t. For use with BS1387 Medium or Heavy steel pipe.
FM Approvals
September 2007 — Approval Guide
1-294 Automatic Sprinkler Systems
Sizes of the Figure 7049 Clamp Tee Crosses can be formed with any combination of the sizes shown of Figure 7047 or 7048 Clamp Tee
Crosses having the same run size.
‡Allied Tube & Conduit ‘‘Super-Flo’’, 2 in. and Allied Tube & Conduit ‘‘Dyna-Flow’’, 2 in. 175 psi (1205 kPa). Allied Tube & Conduit ‘‘Super-Flo’’, 21⁄2-4 in. and Allied
Tube & Conduit ‘‘Dyna-Flow’’, 21⁄2-3 in. 300 psi (2070 kPa). Tex-Tube Co. ‘‘Tex-Flow’’. 3-8 in. 300 psi (2070 kPa). Youngstown Tube ‘‘Fire-Flo’’ 11⁄2-4 in., and
Youngstown Tube ‘‘EZ-Thread’’ 1-2 in., 300 psi (2070 kPa).
§Except 2 in. run sized items and 21⁄2×1⁄2, 3⁄4, 1 in. sized branch connections.
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Product Nominal Pipe Fitting Remarks Rated Working
Designation Size, in. Description Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-295
a. For use with FM Approved Schedule 10 and 40 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6, and 8 in. NPS.
b. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
c. For use with Allied Tube and Conduit ‘‘XL’’ and ‘‘XL-II’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
d. For use with Sawhill Tubular ‘‘SLS’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
e. For use with Wheatland Tube ‘‘WST’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
f. For use with Tex-Tube ‘‘Tex-Flow’’ Lightwall steel sprinkler pipe in sizes: 3, 4, and 6 in. NPS.
g. For use with Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3. In addition, the MT-4 is FM Approved for use with
4 in. NPS ‘‘Steady-Flow’’.
h. For use with Wheatland Tube ‘‘Mega Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
i. For use with Northwest Pipe ‘‘EZ-Flow’’ Lightwall steel sprinkler pipe in sizes: 4 and 6 in. NPS.
j. For use with Youngstown Tube ‘‘Fire-Flo’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
k. For use with Bull Moose Tube ‘‘Ultra – EDDY’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
l. For use with Bull Moose ‘‘EDDY Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
m. For use with Allied Tube and Conduit ‘‘BLT’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
n. For use with Bull Moose Tube ‘‘EDDY-Lite’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
p. For use with Western International Forest Products ‘‘Rapid-Thread’’ steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
q. For use with Wheatland Tube ‘‘WLS’’ threadable thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
r. For use with Western International Forest Products ‘‘Fire Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 3, and 4 in. NPS.
s. For use with Allied Tube and Conduit ‘‘Dyna Flow’’ and ‘‘Super-Flo’’ Lightwall sprinkler pipe in sizes: 11⁄2, 2, 2 1⁄2, 3, 4, and 6 in. NPS.
t. For use with BS1387 Medium or Heavy steel pipe.
Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan
Industrial Base, Shunyi District, Beijing, P. R. China
Product Pipe Size, Fitting Max Working
Designation mm Description Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-296 Automatic Sprinkler Systems
Style 16 Snap-Tee Branch Outlet. For working pressures up to 300 psi (2070 kPa). For use on Schedule 10 or heavier pipe. NPT internal
outlet connection to Schedule 40 or heavier pipe. Clamps over hole in pipe wall.
Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang Tsun Ta Liau Shiang Kaohsiung Hsien,
Taiwan ROC
Side Outlet Coupling. For working pressures up to 300 psi (2070 kPa). For use on Schedule 10 or heavier pipe. NPT internal outlet
connection to Schedule 40 or heavier pipe. Roll grooved outlet for Schedule 10 or heavier pipe. Clamps over hole in pipe wall.
Product Nominal Pipe Max Working
Designation Size, in. Pressure, psi
(kPa)
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
Style 13 Mechanical Branch Outlet. For use on Schedule 10 or heavier pipe. NPT internal threaded outlet. Clamps over predrilled hole in
pipe wall. 300 psi (2070 kPa) rated working pressure.
Style 15 Snap-Tee Branch Outlet. Grooved outlet connection. Clamps over hole in pipe wall
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-297
2 × 11⁄4 – 4 × 3 ’’ c, d, m 300
(2070)
2 × 11⁄4 – 6 × 4 ’’ a, b, c, n 300
(2070)
8×2–8×4 ’’ a, b, c 300
(2070)
165 × 11⁄4 – 165 × 4 ’’ c, k 300
76 mm × 11⁄2 (2070)
139.7 × 11⁄4-3
a. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
b. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40. 8 in. or larger – Sch. 30
c. With EPDM gasket.
d. Allied ‘‘Dyna-Flow.’’
k. British Standard BS 1387 Pipe, Med. and Heavy.
l. Allied ‘‘XL.’’
m. Allied ‘‘Super-Flo.’’
n. Northwest ‘‘EZ-Flow’’
Style 16 Snap-Tee Branch Outlet. NPT internal outlet connection to Schedule 40 or heavier pipe. Clamps over hole in pipe wall.
Style 16 2 × 1⁄ 2 – 3 × 2 c, l, p 300
(2070)
2× 1⁄ 2 –4×3 c, d, m, o, p 300
(2070)
2 × 1⁄2 – 2 × 11⁄2 c, g, p 300
(2070)
2 × 1⁄ 2 – 6 × 4 a, b, c, o, p 300
(2070)
76 mm × 1⁄2 to 11⁄2 c, k 300
139 × 11⁄4 to 4 (2070)
165 × 2 to 4 c, k 300
(2070)
a. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
b. Min schedule cut groove pipe to be joined: 6 in. or smaller - Schedule 40; 8 in. or larger – Schedule 30.
c. With EPDM gasket.
d. Allied ‘‘Dyna-Flow’’
g. Bull Moose ‘‘EDDY-Lite’’
k. British Standard BS 1387 Pipe, Med. and Heavy.
l. Allied ‘‘XL’’
m. Allied ‘‘Super-Flo’’
o. Northwest ‘‘EZ Flow’’
p. Central Sprinkler ‘‘TL’’
JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan
Product Nominal Pipe Fitting Max Working
Designation Size, in. Description Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-298 Automatic Sprinkler Systems
21⁄2×1,
C-7 11⁄2×1⁄2, Type of Outlet * 300
Outlet Coupling 11⁄2×3⁄4, F (2070)
11⁄2×1, 2×1⁄2, F
2×3⁄4, 2×1, F
2×1 F
21⁄2×1⁄2, M/G
2 ⁄2×3⁄4,
1 F
21⁄2×1, F
21⁄2×11⁄4, F
21⁄2×11⁄2, M/G
3×3⁄4, 3×1, M/G
3×1, 3×11⁄2, F
4×3⁄4, 4×1, M/G
4×11⁄2, 4×2, F
6×1, 6×11⁄2, M/G
6×11⁄2, 6×2 F
M/G
* F = Female Threaded
* M = Male Threaded
* G = Grooved
Mechanical Branch Outlet. For use on Schedule 10 or heavier pipe. NPT internal thread outlet. Clamps over predrilled hole in pipe wall.
175 psi (1207 kPa) rated working pressure.
The Model 723 Mechanical Tee may be used with Schedule 10 and heavier, plus:
Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin, Jinan, 250400 China
139.7×2, 21⁄2, 3
5×11⁄4, 11⁄2, 2, 21⁄2, 3
165×2, 21⁄2, 3
6×11⁄4, 11⁄2, 2, 21⁄2, 3, 4
139.7×2, 21⁄2, 3
5×11⁄4, 11⁄2, 2, 21⁄2, 3
165×2, 21⁄2, 3
6×11⁄4, 11⁄2, 2, 21⁄2, 3, 4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-299
Branch Connection for attachment to pipe by welding. For use with ISO 4200, DIN2440 and 2448, Schedule 10 or 40 Steel Sprinkler Pipe.
Requires pre-cutting of hole on pipe. Rated Working Pressure is 20 bar (290 psi).
FM Approvals
September 2007 — Approval Guide
1-300 Automatic Sprinkler Systems
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
Model Nominal Size, mm
(in.)
Rated working pressure 16 BAR (232 psi). FM Approved for use with Schedules 10 and 40 pipe, DIN 2448 and 2458 pipe, ISO 4200 pipe
and BS 1387 medium and heavy pipe for use in valve trim, and accessories, and in sprinkler system branch lines.
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
‘‘Quik-Tee’’ Branch Outlet or Cross with NPT internal threaded or grooved outlet connections for use with Schedule 10 or heavier pipe to
clamp over precut hole in pipe. 500 psi (3445 kPa) rated working pressure.
‘‘QUIK-T’’ Branch Outlet or Cross with NPT external threaded or grooved outlet connections for use with Schedule 10 or heavier pipe to
clamp over precut hole in pipe. 250 psi (1725 kPa) rated working pressure.
‘‘QUIK-HOOK’’ Style 09 Sprinkler Outlet. For use on Schedule 10 or heavier pipe. 175 psi (1205 kPa) rated working pressure. NPT internal
outlet connection. Clamps over hole in pipe wall.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-301
Style 09 ‘‘Quik-Hook’’ Sprinkler Outlet. For use on Schedule 10 or heavier pipe. NPT internal outlet connection. Clamps over hole in pipe
wall.
Product Fitting Nominal Run Pipe Nominal Outlet Pipe
Designation Description Size, in. Size, in.
Outlet
Connection
Style 99 Sprinkler Outlet. For use on Schedule 10 or heavier pipe, or DIN pipe. NPT internal outlet connection. Clamps over hole in pipe
wall.
Product Fitting Nominal Run Pipe Nominal Outlet Pipe
Designation Description Size, in. Size, in.
Style 13 Mechanical Branch Outlet. For use on Schedule 10 or heavier pipe. NPT internal threaded outlet. Clamps over predrilled hole in
pipe wall. 175 psi (1207 kPa) rated working pressure.
Style 15 Snap-Tee Branch Outlet. For working pressure of 300 psi (2070 kPa) for the 3, 4 in. run sizes and working pressure of 250 psi
(1725 kPa) for 6 in. run size. For use on Schedule 10 or heavier pipe. Grooved outlet connection. Clamps over hole in pipe wall.
Style 16 Snap-Tee Branch Outlet. For working pressures up to 300 psi (2070 kPa). For use on Schedule 10 or heavier pipe. NPT internal
outlet connection to Schedule 40 or heavier pipe. Grooved outlet connection clamps over hole in pipe wall.
Snap-Tee Branch Outlet. NPT internal outlet connection to Schedule 40 or heavier pipe. Clamps over hole in pipe wall.
FM Approvals
September 2007 — Approval Guide
1-302 Automatic Sprinkler Systems
Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao,
China
Branch Outlet 20
Figure 16T 57×1⁄2, 3⁄4, 1 a, b, c, d
(NPT) (90)
20
″ ″ 2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 a, b, c
(90)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-303
20
″ ″ 76×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 a, b, c, d
(90)
20
″ ″ 3×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 a, b, c
(90)
20
″ ″ 4×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 3 a, b, c, d
(90)
20
″ ″ 133×11⁄4, 11⁄2, 2, 3 a, b, c, d
(90)
20
″ ″ 139×1, 11⁄4, 11⁄2, 2, 3 a, b, c, d
(90)
20
″ ″ 159×1, 11⁄4, 11⁄2, 2, 3, 4 a, b, c, d
(90)
20
″ ″ 165×1, 11⁄4, 11⁄2, 2, 3, 4 a, b, c, d
(90)
20
″ ″ 6×2, 3, 4 a, b, c, d
(90)
20
″ ″ 8×11⁄4, 11⁄2, 2, 3, 4 a, b, c, d
(90)
Branch Outlet 20
Figure 16T 57×1⁄2, 3⁄4, 1 a, b, c, d
(ISO) (90)
20
″ ″ 2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 a, b, c
(90)
20
″ ″ 76×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 a, b, c, d
(90)
20
″ ″ 3×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 a, b, c
(90)
20
″ ″ 4×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 76, 3 a, b, c, d
(90)
20
″ ″ 133×11⁄4, 11⁄2, 2, 76, 3 a, b, c, d
(90)
20
″ ″ 139×1, 11⁄4, 11⁄2, 2, 76, 3 a, b, c, d
(90)
20
″ ″ 159×1, 11⁄4, 11⁄2, 2, 76, 3, 4 a, b, c, d
(90)
20
″ ″ 165×1, 11⁄4, 11⁄2, 2, 76, 3, 4 a, b, c, d
(90)
20
″ ″ 6×2, 76, 3, 4 a, b, c, d
(90)
20
″ ″ 8×11⁄4, 11⁄2, 2, 76, 3, 4 a, b, c, d
(90)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 or 10 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with GB/T 3091-93 or GB/T 8163-99 Pipe.
SCE Company Ltd, Unit E&F, 20/F., CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong
Max Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, in. Ends Remarks (kPa)
FM Approvals
September 2007 — Approval Guide
1-304 Automatic Sprinkler Systems
Max Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, in. Ends Remarks (kPa)
SPT Metal Corp, 19-1 Da Yeh St, Da Liao Hsiang, Kaóhsiung Hsien, Taiwan ROC
Mechanical Tee Branch Outlet. NPT internal outlet connection. Clamps over hole in pipe wall.
Mechanical Tee Branch Outlet. Grooved outlet connection. Clamps over hole in pipe wall.
3×11⁄2, 3×2
Mechanical Branch 4×11⁄2, 2, 21⁄2, 3 300
522 Tee a, b, c
Outlet (Grooved) 6×11⁄2, 2, 21⁄2, 3, 4 (2070)
8×21⁄2, 3, 4
Mechanical Branch 3×11⁄2, 2 300
522 Tee c, f, g, h, j
Outlet (Grooved) 4×1, 11⁄2, 2, 21⁄2, 3 (2070)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
e. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe, 1-2 in. only.
f. All FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size.
i. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
j. For use with Bull Moose Tube EDDY-Flow pipe.
m. For use with Wheatland ‘‘Mega-Flow’’ non-threadable Thinwall pipe.
Shanghai Recomb Piping System Co Ltd, No. 270 Yixian Rd, Shanghai, 200434 P. R. China
Product Pipe Actual Size Fitting Remarks Max Working
Designation mm Description Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-305
XGQT3 60×42, 60×48, 73×42, 73×48, 73×60, 76×42, 76×48, Outlet Coupling a, b, c 300
89×42, 89×48, 89×60, 108×60, 108×76, (Grooved) (2070)
114×42, 114×48, 114×60, 114×73, 114×76, 114×89, 133×60, 133×76,
133×89, 140×60, 140×76, 140×89,
159×60, 159×76, 159×89, 159×108, 159×114, 165×42, 165×48,
165×60, 165×76, 165×89, 165×114, 168×42, 168×48, 168×60,
168×73, 168×76, 168×89, 168×108, 168×114, 219×60, 219×73,
219×76, 219×89, 219×108 219×114, 5×11⁄4, 5×11⁄2, 5×2, 5×21⁄2A, 5×3
XGQT3 273×60, 273×76, 273×89, 273×108 and 273×114 Outlet Coupling a, b, c 175
(Grooved) (1205)
XGQT3U 42×G1⁄2, 42×G3⁄4, 42×G1, 48×G1⁄2, 48×G3⁄4, 48×G1, Strap Tee a, b, c 235
60×G1⁄2, 60×G3⁄4, 60×G1, (Threaded) (1620)
73×G1⁄2, 73×G3⁄4, 73×G1, 76×G1⁄2, 76×G3⁄4, 76×G1
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
FM Approvals
September 2007 — Approval Guide
1-306 Automatic Sprinkler Systems
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Product Fitting Nominal Pipe Remarks Max. Working
Designation Description Size, in. Pressure psi
(kPa)
a. For use with FM Approved Schedule 10 and 40 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6, and 8 in. NPS.
b. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
c. For use with Allied Tube and Conduit ‘‘XL’’ and ‘‘XL-II’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
d. For use with Sawhill Tubular ‘‘SLS’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
e. For use with Wheatland Tube ‘‘WST’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
f. For use with Tex-Tube ‘‘Tex-Flow’’ Lightwall steel sprinkler pipe in sizes: 3, 4, and 6 in. NPS.
g. For use with AMS Tube ‘‘Steady-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3.
h. For use with Wheatland Tube ‘‘Mega Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
i. For use with Northwest Pipe ‘‘EZ-Flow’’ Lightwall steel sprinkler pipe in sizes: 4 and 6 in. NPS.
j. For use with Youngstown Tube ‘‘Fire-Flo’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
k. For use with Bull Moose Tube ‘‘Ultra - EDDY’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
l. For use with Bull Moose ‘‘EDDY Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 2 1⁄2, 3, and 4 in. NPS.
m. For use with Allied Tube and Conduit ‘‘BLT’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
n. For use with Bull Moose Tube ‘‘EDDY-Lite’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
p. For use with Western International Forest Products ‘‘Rapid-Thread’’ steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
q. For use with Wheatland Tube ‘‘WLS’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
r. For use with Western International Forest Products ‘‘Fire Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 3, and 4 in. NPS.
s. For use with Allied Tube and Conduit ‘‘Dyna Flow’’ and ‘‘Super-Flo’’ Lightwall sprinkler pipe in sizes: 11⁄2, 2, 2 1⁄2, 3, 4, and 6 in. NPS.
t. For use with BS 1387 Medium or Heavy steel pipe.
Grinnell Clamp-T. For use with Schedule 10S or heavier pipe*†, in 6 in. or smaller sizes and 0.188 in. (5 mm) wall or heavier pipe, in the
8 in. size. With EPDM gasket (green stripe) only.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-307
FM Approved with ANSI NPT thread or ISO thread as appropriate for the outlet pipe.
FM Approvals
September 2007 — Approval Guide
1-308 Automatic Sprinkler Systems
Sizes of the Figure 7049 Clamp Tee Crosses can be formed with any combination of the sizes shown of Figure 7047 or 7048 Clamp Tee
Crosses having the same run size.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-309
‡Allied Tube & Conduit ‘‘Super-Flo’’, 2 in. and Allied Tube & Conduit ‘‘Dyna-Flow’’, 2 in. 175 psi (1205 kPa). Allied Tube & Conduit ‘‘Super-Flo’’, 21⁄2-4 in. and Allied
Tube & Conduit ‘‘Dyna-Flow’’, 21⁄2-3 in. 300 psi (2070 kPa). Tex-Tube Co. ‘‘Tex-Flow’’. 3-8 in. 300 psi (2070 kPa).
§Except 2 in. run sized items and 21⁄2×1⁄2, 3⁄4, 1 in. sized branch connections.
Mechanical Tee or Cross Branch Outlet. NPT internal outlet connection. Clamps over hole in pipe wall.
Product Fitting Nominal Pipe Max. Working
Designation Description Size, in. Remarks Pressure psi
(kPa)
a. Min schedule cut groove pipe: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 m) wall.
c. With EPDM gasket (green stripe) Grade E or (purple stripe) Grade A.
d. Min schedule pipe: 3 in. or smaller – Allied Tube & Conduit Corp Approved ‘‘BLT’’, ‘‘XL’’, ‘‘XL-II’’, ‘‘Super- XL’’ and ‘‘Super-40’’ Thinwall pipe.
e. Min schedule pipe: Allied Tube ‘‘Dyna-Flow’’ and ‘‘Super-flo’’ Lightwall pipe, 300 psi (2070 kPa).
f. IDOD Gal-5 and All-Gal pipe, 11⁄4 to 2 in. sizes, 175 psi (1205 kPa).
g. IDOD Gal-7 and Gal-Flo pipe, 11⁄4 to 2 in. sizes.
h. Allied Tube ‘‘Dyna-Light’’ pipe, 1 to 2 in. sizes, 175 psi (1205 kPa).
j. Bull Moose ‘‘EDDY-Lite‘‘ pipe, 1-2 in. sizes.
k. Bull Moose ‘‘Ultra-EDDY’’ pipe at 175 psi (1205 kPa), 1-2 in. sizes.
l. Bull Moose ‘‘EDDY-Flo’’ pipe, 175 psi (1205 kPa).
m. BS 1487 pipe, medium and heavy wall at 300 psi (2070 kPa), and ISO 4200 pipe.
n. For use with Welded Tube–Berkeley LLC Steady-Flow pipe.
p. WIFP Fire Line Flow & Rapid-Thread Light Pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ and ‘‘SL’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ and ‘‘GL’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe at 175 psi (1205 kPa).
v. Youngstown Tube Fire-Flo and EZ-Thread Pipe.
Mechanical Tee or Cross Branch Outlet. NPT internal outlet connection or grooved outlet. Clamps over hole in pipe wall.
FM Approvals
September 2007 — Approval Guide
1-310 Automatic Sprinkler Systems
Mechanical Tee Branch Outlet. BSP internal outlet connection or grooved outlet. Clamps over hole in pipe wall.
Grinnell Figure 40-5 Mechanical Outlet Tee. 11⁄4, 11⁄2, 2 and 21⁄2 in. plus 76 mm nominal run size, each with 1⁄2, 3⁄4 or 1 in. NPT outlets.
Approved for use with Schedule 5, 10 and 40 pipe. Also, Allied ‘‘Dyna-Flow’’ and ‘‘Dyna-Thread’’, Allied ‘‘Super-Flo’’ and ‘‘XL’’, Central Grooved
Piping Products ‘‘TL’’, Bull-Moose ‘‘EDDY-Lite’’ and Wheatland ‘‘WLS’’, ‘‘MLT’’, ‘‘WST’’ and MEGA-flow Steel Sprinkler Pipes. Approved for use
with Central Grooved Piping Products ‘‘Central 7’’ and Welded Tube–Berkeley LLC Steady-flow pipes. Approved for use with Youngstown
‘‘Fire-flo’’ and ‘‘EZ-Thread’’ pipe.
Grinnell Figure 40-5 Mechanical Outlet Tee. 11⁄4, 11⁄2, 2 and 21⁄2 in. nominal run size, each with 1⁄2, 3⁄4 or 1 in. BSP outlets. Approved for
use with the following run pipes: Schedules 5, 10 and 40 pipe. Allied ‘‘Dyna-Flow’’ and ‘‘Dyna-Thread’’, Allied ‘‘Super-Flow’’ and ‘‘XL’’, Central
Sprinkler ‘‘TL’’, Bull-Moose ‘‘EDDY-Lite’’ and Wheatland ‘‘WLS’’, ‘‘MLT’’, ‘‘WST’’ and MEGA-flow Steel Sprinkler Pipes. Approved for use with
Youngstown ‘‘Fire-flo’’ and ‘‘EZ-Thread’’ pipe. Approved for use with IDOD’s Gal-7 and Gal-Flo pipe.
Style 300 Ease-Tee. Mechanical fittings with NPT internal outlet connections for use with Schedule 40 pipe to clamp over 1 in. (25 mm)
drilled hole. 300 psi (2070 kPa) rated working pressure.
Product Fitting Nominal Pipe
Designation Description Size, in.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-311
21⁄2×1⁄2, 3⁄4, 1
Mek-Tee Mechanical Tee or Cross Branch Outlet. For use on Schedule 10 or heavier pipe. NPT internal outlet connection. Clamps over
hole in pipe wall.
Mechanical Tee or Cross Branch Outlet. NPT internal outlet connection. Clamps over hole in pipe wall.
Mechanical Tee or Cross Branch Outlet. NPT internal outlet connection or grooved outlet. Clamps over hole in pipe wall.
FM Approvals
September 2007 — Approval Guide
1-312 Automatic Sprinkler Systems
Mechanical Tee Branch Outlet. BSP internal outlet connection or grooved outlet. Clamps over hole in pipe wall.
a. For use with Allied Tube & Conduit ‘‘Dyna-Light’’ Schedule 5 Lightwall pipe.
b. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’ and ‘‘Super-Flo’’ non-threadable Lightwall pipe.
c. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
d. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
g. For use with Schedule 10S or heavier steel sprinkler pipe.
h. Mechanical fittings with NPT internal outlet connections to clamp over 1 in. (25 mm) drilled hole.
j. Branch line sprinkler installation 1 in. outlet size only.
k. For use with Bull Moose ’’Ultra-EDDY‘‘ Schedule 5 Lightwall steel sprinkler pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-313
m. For use with BS 1387 pipe, medium and heavy wall steel sprinkler pipe.
n. For use with Allied Tube & Conduit ‘‘XL’’ and ‘‘Super-XL’’ threadable Thinwall steel sprinkler pipe.
o. For use with Allied Tube & Conduit ‘‘Super-40’’ threadable Thinwall steel sprinkler pipe.
p. Min schedule cut groove pipe: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
q. Min schedule rolled groove pipe: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 m) wall.
r. With EPDM gasket (green stripe).
s. For use with Youngstown Tube ‘‘Fire-Flo’’ non-threadable Lightwall steel sprinkler pipe.
t. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe.
u. For use with IDOD’s Gal-7 and Gal-Flo pipe.
v. For use with ISO 4200 steel sprinkler pipe.
Model 40-5 Mechanical Outlet Tee. 11⁄4, 11⁄2, 2 and 21⁄2 in. plus 76 mm nominal run size, each with 1⁄2, 3⁄4 or 1 in. NPT outlets. FM Approved
for use with Schedule 5, 10 and 40 pipe. Also, Allied ‘‘Dyna-Flow’’ and ‘‘Dyna-Thread’’, Allied ‘‘Super-Flo’’ and ‘‘XL’’, Central Grooved Piping
Products ‘‘TL’’, Bull-Moose ‘‘EDDY-Lite’’ and Wheatland ‘‘WLS’’, ‘‘MLT’’, ‘‘WST’’ and MEGA-flow Steel Sprinkler Pipes. FM Approved for use
with Central Grooved Piping Products ‘‘Central 7’’, and Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ pipes. FM Approved for use with
Youngstown ‘‘Fire-flo’’ and ‘‘EZ-Thread’’ pipe.
Model 40-5 Mechanical Outlet Tee. 11⁄4, 11⁄2, 2 and 21⁄2 in. nominal run size, each with 1⁄2, 3⁄4 or 1 in. BSP outlets. FM Approved for use with
the following run pipes: Schedules 5, 10 and 40 pipe. Allied ‘‘Dyna-Flow’’ and ‘‘Dyna-Thread’’, Allied ‘‘Super-Flow’’ and ‘‘XL’’, Central Sprinkler
‘‘TL’’, Bull-Moose ‘‘EDDY-Lite’’ and Wheatland ‘‘WLS’’, ‘‘MLT’’, ‘‘WST’’ and MEGA-flow Steel Sprinkler Pipes. FM Approved for use with
Youngstown ‘‘Fire-flo’’ and ‘‘EZ-Thread’’ pipe. FM Approved for use with IDOD’s Gal-7 and Gal-Flo pipe.
Mechanical
c, d, e, f, 175
073 Branch Outlet 21⁄2×3⁄4
g, h, i, j (1205)
(FNPT)
Mechanical
300
920 Branch Outlet 4×21⁄2, 3 c, k
(2070)
(Grooved Outlet)
Mechanical
165 mm x 76 mm 300
920 Branch Outlet c
165 mm × 89 mm (2070)
(Grooved Outlet)
Mechanical
165 mm x 76 mm 400
920 Branch Outlet c
165 mm × 89 mm (2760)
(FNPT or ISO or BSP)
Mechanical
300
920 Branch Outlet 6×4, 3 c, m
(2070)
(FNPT)
Mechanical
300
920 Branch Outlet 6×4, 3 c, m
(2070)
(Grooved Outlet)
Mechanical
300
920N Branch Outlet 2×1, 11⁄4, 11⁄2 c, k, l
(2070)
(Grooved Outlet)
21⁄2×1, 11⁄4,
Mechanical
1 1⁄ 2, 2 300
920N Branch Outlet c, k
3×1, 11⁄4, (2070)
(Grooved Outlet)
1×1⁄2, 2
2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2;
Mechanical 21⁄2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2;
300
920N Branch Outlet 3×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2; c, m
(2070)
(FNPT) 4×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2;
6×2, 11⁄4
2×11⁄4, 11⁄2;
Mechanical 21⁄2×11⁄4, 11⁄2
300
920N Branch Outlet 3×11⁄4, 11⁄2, 2; c, m
(2070)
(Grooved Outlet) 4×11⁄4, 11⁄2, 2;
6×2, 11⁄4
a. Use limited to a min of Schedule 10S pipe in 6 in. or smaller sizes and 0.188 in. (5 mm) wall pipe in 8 in. or larger sizes.
b. For use with Schedule 40 pipe in 6 in. or smaller, and Schedule 30 pipe for 8 in. NPS steel sprinkler pipe.
c. With gasket E (green stripe), H (white stripe) or L (solid red).
d. For use with Allied Tube ‘‘XL’’, ‘‘Super-XL’’ and ‘‘Super-40’’ threadable Thinwall pipe.
e. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
f. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
g. For use with Allied Tube & Conduit ‘‘Super-Flo’’ or ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
h. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall steel sprinkler pipe.
i. For use with Bull Moose ‘‘Ultra-EDDY’’ non-threadable Lightwall steel sprinkler pipe.
j. For use with Bull Moose ‘‘EDDY-Flow’’ non-threadable Lightwall steel sprinkler pipe.
k. For use with Youngstown Tube ‘‘Fire-Flo’’ non-threadable Lightwall steel sprinkler pipe.
l. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe.
m. For use with Wheatland Tube ‘‘Mega Flow’’ non-threadable Lightwall steel sprinkler pipe.
Style 920 Mechanical-T Branch Outlet or Cross. For working pressures up to 400 psi (2760 kPa). Branch is available with either grooved
or NPT internal connection, except as noted. Use limited to a min of Schedule 10S pipe in 6 in. or smaller sizes and 0.188 in. (5 mm) wall
pipe in 8 in. or larger sizes. 6×3, 4 and 8×3, 4 in. sizes are limited to a pressure rating of 250 psi (1725 kPa) when used with Schedule 10S
pipe, and limited to pressure rating of 300 psi (2070 kPa) for 6×3, 4 on Schedule 40, and for 8×3, 4 on Schedule 30. Limited to pressure rating
FM Approvals
September 2007 — Approval Guide
1-314 Automatic Sprinkler Systems
of 300 psi (2070 kPa) up to and including 4×3 on Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe. For use with Northwest ‘‘EZ-Flow’’ 4 and
6 in. non-threadable Lightwall pipe. For use with Central Sprinkler ‘‘TL’’ pipe in 1-2 in. sizes. For use with Wheatland ‘‘MLT’’ up to 2 in. nominal
size. For use with Central 7 pipe in 11⁄2-4 in. sizes. For use with Western ‘‘Fire-Flow’’ pipe.
Product Nominal Outlet Nominal Pipe
Designation Size, in. Size, in.
Style 920 Mechanical-T Branch Outlet or Cross. For working pressures up to 175 psi (1205 kPa). Branch is provided with a British Standard
internal taper pipe thread. Run pipes must be Schedule 10 or heavier wall in sizes up to 6 in. and 0.188 in. (4.8 mm) min wall in larger sizes.
Branch pipes must be Schedule 40 or heavier.
Style 920N Mechanical-T Branch Outlet or Cross. For working pressure up to 400 psi (2760 kPa). Branch is available with NPT female outlet
connection. Use limited to Schedule 10 and 40 pipe in 6 in. or smaller sizes at 400 psi (2760 kPa). For working pressure up to 300 psi
(2070 kPa) on Super-Flo, Dyna-Flow, Super XL, Super 40, XL, BLT, TL, Gal-flo and Gal-7, EZ-Flow and EDDY-Flow.
Style 920N Mechanical-T Branch Outlet or Cross. For working pressure up to 400 psi (2760 kPa). Branch is available with BSP female outlet
connection. Use limited to BS 1387 Medium or Heavy run pipe, or DIN 2458, or ISO 4200 run pipe.
Use limited to Schedule 10 and 40 pipe at 400 psi (2760 kPa). 31⁄2 by 2
Use limited to BS 1387 Medium or Heavy Run Pipe, or Din 2458, or ISO 4200 pipe. 76 mm by 11⁄4, 11⁄2
Style 920N Mechanical-T Branch Outlet or Cross. For working pressure up to 400 psi (2760 kPa). Branch is available with grooved outlet
connection. Use limited to Schedule 10 and 40 pipe in 6 in. or smaller sizes at 400 psi (2760 kPa). For working pressure up to 300 psi
(2070 kPa) on Super-Flo, Dyna-Flow, Super XL, Super 40, XL, BLT, TL, EZ-Flow and EDDY-Flow.
Style 921 Mechanical-T Branch Outlet. For working pressures up to 300 psi (2070 kPa). NPT internal connection branch only. Use limited
to a min of Schedule 10S pipe in 6 in. or smaller sizes and 0.188 in. (5 mm) wall pipe in 8 in. or larger sizes. 4 in. size is limited to a pressure
rating of 250 psi (1725 kPa) when used with Schedule 10S pipe. For working pressure up to 300 psi (2070 kPa) up to and including 4 × 1
size on Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe. For use with Northwest ‘‘EZ-Flow’’ 4 in. non-threadable Lightwall pipe. For use with
Wheatland ‘‘MLT’’ up to 2 in. nominal size and ‘‘Mega-Flow’’ up to 4 in. nominal size. For use with Central 7 pipe in 11⁄2-4 in. sizes. For use
with Western ‘‘Fire-Flow’’ and ‘‘Fire-Thread’’ pipe. For use with Yieh Phui SPS Flow Pipe, 11⁄4 through 4 in. NPS.
‡300 psi (2070 kPa) on Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall sprinkler pipe and Tex-Tube ‘‘Tex-Flow’’ pipe.
Style 921 Mechanical-T Branch Outlet. For working pressures up to 175 psi (1205 kPa). British Standard internal taper pipe thread branch
connections only. Run pipe must be Schedule 10 or heavier. Branch pipe must be Schedule 40, or heavier.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-315
Style 922 Sprinkler Outlet, for use with Schedule 10 and 40 pipe in 11⁄4 through 21⁄2 in. NPS sizes. Also FM Approved for use with Allied
XL and Dyna-flow, Bull Moose Ultra-EDDY and EDDY-flow, Welded Tube–Berkeley LLC Steady-Flow, Wheatland WLS, WST, and Mega-flow,
IDOD Gal-5 and All-Gal. Clamps over hole in pipe wall. No gasket lubricant required.
Pressure rating 175 psi (1205 kPa) on Schedule 5 Pipe, 300 psi (2070 kPa) on all other heavier pipe schedules.
Style 925 Snaplet Sprinkler Outlet. For use on Allied Tube & Conduit ‘‘Dyna-Flow’’, Schedule 5, 10 and 40 Sprinkler pipe. NPT internal outlet
connection. Clamps over hole in pipe wall. Designed specifically for sprinkler heads. 1’’ outlet size may be used for branch connections. For
use with Central Sprinkler ‘‘TL’’ pipe in 11⁄4-2 in. sizes; Allied Tube ‘‘XL’’ and ‘‘Super-Flo’’ pipes; Central 7 pipe in 11⁄2-21⁄2 in. sizes; and IDOD
Systems Gal-5 pipe, and Bull Moose ‘‘EDDY-Flow’’ pipe and Wheatland ‘‘Mega-Flow’’ pipe.
Style 927 Sprinkler Outlet. For use on Schedule 10 and 40 Sprinkler pipe. DIN internal outlet connection. Clamps over hole in pipe wall.
Designed specifically for sprinkler heads. 1’’ outlet size may be used for branch connections.
Style 920 Mechanical-T Branch Outlet or Cross. For working pressures up to 400 psi (2760 kPa). Branch is available with either grooved
or NPT internal connection, except as noted. Use limited to a min of Schedule 10S pipe in 6 in. or smaller sizes and 0.188 in. (5 mm) wall
pipe in 8 in. or larger sizes. 6×3, 4 and 8×3, 4 in. sizes are limited to a pressure rating of 250 psi (1725 kPa) when used with Schedule 10S
pipe, and limited to pressure rating of 300 psi (2070 kPa) for 6×3, 4 on Schedule 40, and for 8×3, 4 on Schedule 30. Limited to pressure rating
of 300 psi (2070 kPa) up to and including 4 x 3 on Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe. For use with Northwest ‘‘EZ-Flow’’ 4 in.
non-threadable Lightwall pipe. For use with Central Sprinkler ‘‘TL’’ pipe in 1-2 in. sizes.
Style 920 Mechanical-T Branch Outlet or Cross. For working pressures up to 175 psi (1205 kPa). Branch is provided with a British Standard
internal taper pipe thread. Run pipes must be Schedule 10 or heavier wall in sizes up to 6 in. and 0.188 in. (4.8 mm) min wall in larger sizes.
Branch pipes must be Schedule 40 or heavier.
Style 921 Mechanical-T Branch Outlet. For working pressures up to 300 psi (2070 kPa). NPT internal connection branch only. Use limited
to a min of Schedule 10S pipe in 6 in. or smaller sizes and 0.188 in. (5 mm) wall pipe in 8 in. or larger sizes. 4 in. size is limited to a pressure
rating of 250 psi (1725 kPa) when used with Schedule 10S pipe. For working pressure up to 300 psi (2070 kPa) up to and including 4×1 size
on Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall pipe. For use with Northwest ‘‘EZ-Flow’’ 4 in. non-threadable Lightwall pipe.
FM Approvals
September 2007 — Approval Guide
1-316 Automatic Sprinkler Systems
‡300 psi (2070 kPa) on Allied Tube & Conduit ‘‘Dyna-Flow’’ Lightwall sprinkler pipe.
Style 921 Mechanical-T Branch Outlet. For working pressures up to 175 psi (1205 kPa). British Standard internal taper pipe thread branch
connections only. Run pipe must be Schedule 10 or heavier. Branch pipe must be Schedule 40, or heavier.
Style 922 Hooker Sprinkler Outlet. For use on Lightwall pipe, Schedule 10S, or heavier pipe. NPT internal outlet connection. Clamps over
hole in pipe wall. Designed specifically for sprinkler heads. 1’’ outlet size may be used for branch connections.
Style 925 Snaplet Sprinkler Outlet. For use on Allied Tube & Conduit ‘‘Dyna-Flow’’, Schedule 5, 10 and 40 Sprinkler pipe. NPT internal outlet
connection. Clamps over hole in pipe wall. Designed specifically for sprinkler heads. 1’’ outlet size may be used for branch connections. For
use with Central Sprinkler ‘‘TL’’ pipe in 11⁄4-2 in. sizes. For use with Allied Tube ‘‘XL’’ and ‘‘Super-Flo’’ pipes.
Style 927 Sprinkler Outlet. For use on Schedule 10 and 40 Sprinkler pipe. DIN internal outlet connection. Clamps over hole in pipe wall.
Designed specifically for sprinkler heads. 1’’ outlet size may be used for branch connections.
8×21⁄2, 3, 4;
Mechanical Tee Branch Outlet. Grooved outlet connection. Clamps over hole in pipe wall.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-317
3×11⁄4,11⁄2, 2; c, e, f, h, j 300
4×11⁄4, 11⁄2, 2, 21⁄2, 3 (2070)
Virotec Rohrtechnik GmbH & Co KG, Meininger Weg 8, D-36132 Eiterfield, Germany
Model Virotec-T. Mechanical fittings with NPT internal outlet connections. For use with Schedule 10 or heavier pipe to clamp over 1 in.
(25 mm) drilled hole. 175 psi (1205 kPa) pressure rating.
Weifang 100tong Co Ltd, No. 1919 Jinchang South Road, Weicheng District, Weifang,
Shandong, PR China 261052
Rated Working
Product Fitting Nominal Pipe Pressure, psi
Designation Description Size, mm Remarks (kPa)
These couplings allow installation of a perpendicular branch line of reduced size, while joining inline pipes of equal
diameters. These fittings bolt over a hole in the run pipe, and allow installation of a perpendicular branch line of
reduced size.
FM Approvals
September 2007 — Approval Guide
1-318 Automatic Sprinkler Systems
Weifang 100tong Co Ltd, No. 1919 Jinchang South Road, Weicheng District, Weifang,
Shandong, PR China 261052
Rated Working
Product Fitting Nominal Pipe Pressure, psi
Designation Description Size, mm (kPa)
GCQT3 Mechanical Tee Grooved 108x60, 108x76, 114x60, 114x76, 140x60, 140x76, 140x89, 230
159x76, 159x89, 159x108, 159x114, 165x60, 165x76, 165x89, (1600)
165x114, 219x57, 219x60, 219x76, 219x89, 219x114,
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-319
Split Flanged—These fittings join pipe, valves or fittings having equal diameters.
ATUSA empresarial SL, Aptd. Correos 8, Poligono Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain
Product Fitting Nominal Pipe Max Rated
Designation Description Size, in. Remarks Pressure, psi
(kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
d. Approved when supplied with an ISO PN10 bolt pattern.
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
a, b, c, d, e, f, g,
Cut Groove 300
7012 2, 21⁄2, 3, 4, 5, 6, 8, 10, 12 h, i, j, k,m, n, q, r,
Rolled Groove (2070)
s, t, u, v, w, x, z, A
60, 76, 89, 114, 139, 165, Cut Groove 300
7012E c, C
168, 219, 273 and 324 mm Rolled Groove (2070)
Cut Groove 175
7012T 2, 21⁄2, 3, 4, 5, 6, 8 a, b, c, C
Rolled Groove (1205)
Cut Groove 500
7013 2, 21⁄2, 3, 4 a, c, g
Rolled Groove (3445)
Cut Groove 500
5, 6, 8, 10, 12 a, c
Rolled Groove (3445)
Cut Groove 300
5, 6, 8, 10, 12 b, c
Rolled Groove (2070)
Remarks:
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S, 8 in. and 10 NPS, 0.188 in. (5 mm) wall.
c. With EPDM gasket
d. For use with Allied Tube and Conduit ‘‘Super-Flo’’ and ‘‘Dyna-Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 in. NPS.
e. For use with Allied Tube and Conduit “BLT” thinwall steel sprinkler pipe in size 2 inch NPS.
f. For use with Allied Tube and Conduit “Dyna-Thread” thinwall steel sprinkler pipe in size 2 inch NPS.
g. For use with Allied Tube and Conduit ‘‘XL’’, ‘‘XL-II’’, “Super-40”, and ‘‘Super-XL’’ Thinwall steel sprinkler pipe in sizes: 2, 21⁄2, and 3 inch NPS at 300 psi.
h. For use with AMS Tube ‘‘Steady Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 in. NPS.
i. For use with Bull Moose Tube “EDDY-Lite” Thinwall steel sprinkler pipe in size 2 inch NPS.
j. For use with Bull Moose Tube “EDDY-Thread” Thinwall steel sprinkler pipe in size 2 inch NPS.
k. For use with Bull Moose Tube ‘‘EDDY Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 inch NPS.
l. For use with Bull Moose Tube “Ultra-EDDY” Schedule 5 steel sprinkler pipe in size 2 inch NPS.
m. For use with IDOD Systems “Gal-7” Lightwall steel sprinkler pipe in size 2 inch NPS.
n. For use with IDOD Systems “Gal-Flo” Lightwall steel sprinkler pipe in size 2 inch NPS.
o. For use with IDOD Systems “Gal-5” Schedule 5 steel sprinkler pipe in size 2 inch NPS.
p. For use with IDOD Systems “All-Gal” Schedule 5 steel sprinkler pipe in size 2 inch NPS.
q. For use with Northwest Pipe “EZ-Flow” Lightwall steel sprinkler pipe in sizes: 3 and 4 inch NPS.
r. For use with Tex-Tube “Tex-Flow” Lightwall steel sprinkler pipe in sizes: 21⁄2, 3, 4, and 6 inch NPS.
s. For use with Wheatland Tube “Mega-Flow” Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 inch NPS.
t. For use with Western International Forest Products “Rapid Thread” Thinwall steel sprinkler pipe in size 2 inch NPS.
u. For use with Wheatland Tube “WLS” Thinwall steel sprinkler pipe in size 2 inch NPS.
v. For use with Wheatland Tube “Mega-Thread” Thinwall steel sprinkler pipe in size 2 inch NPS.
w. For use with Wheatland Tube “MLT” Thinwall steel sprinkler pipe in size 2 inch NPS.
x. For use with Wheatland Tube “GL” Thinwall steel sprinkler pipe in size 2 inch NPS.
y. For use with Wheatland Tube “WST” schedule 5 steel sprinkler pipe in size 2 inch NPS.
z. For use with Youngstown Tube “EZ-Thread” Thinwall steel sprinkler pipe in 2 inch NPS.
A. For use with Youngstown Tube “Fire-Flo” Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 inch NPS.
B. Schedule 40 only.
C. For use with BS1387 medium or heavier pipe, or EN 10255 pipe, or ISO 4200 pipe.
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
FM Approvals
September 2007 — Approval Guide
1-320 Automatic Sprinkler Systems
Remarks:
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S, 8 and 10 in. NPS, 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with Allied Tube and Conduit ‘‘Super-Flo’’ and ‘‘Dyna-Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 in. NPS.
e. For use with Allied Tube and Conduit “BLT” thinwall steel sprinkler pipe in size 2 inch NPS.
f. For use with Allied Tube and Conduit “Dyna-Thread” thinwall steel sprinkler pipe in size 2 inch NPS.
g. For use with Allied Tube and Conduit ‘‘XL’’, ‘‘XL-II’’, and ‘‘Super-XL’’ Thinwall steel sprinkler pipe in sizes: 2, 21⁄2, and 3 inch NPS.
h. For use with AMS Tube ‘‘Steady Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 2-1⁄2, 3, and 4 in. NPS.
i. For use with Bull Moose Tube “EDDY-Lite” Thinwall steel sprinkler pipe in size 2 inch NPS.
j. For use with Bull Moose Tube “EDDY-Thread” Thinwall steel sprinkler pipe in size 2 inch NPS.
k. For use with Bull Moose Tube ‘‘EDDY Flow’’ Lightwall steel sprinkler pipe in sizes: 2, 21⁄2, 3, and 4 inch NPS.
l. For use with Bull Moose Tube “Ultra-EDDY” Schedule 5 steel sprinkler pipe in size 2 inch NPS.
m. For use with IDOD Systems “Gal-7” Lightwall steel sprinkler pipe in size 2 inch NPS.
n. For use with IDOD Systems “Gal-Flo” Lightwall steel sprinkler pipe in size 2 inch NPS.
o. For use with IDOD Systems “Gal-5” Schedule 5 steel sprinkler pipe in size 2 inch NPS.
p. For use with IDOD Systems “All-Gal” Schedule 5 steel sprinkler pipe in size 2 inch NPS.
q. For use with Northwest Pipe “EZ-Flow” Lightwall steel sprinkler pipe in sizes: 3 and 4 inch NPS.
r. For use with Tex-Tube “Tex-Flow” Lightwall steel sprinkler pipe in sizes: 2-1⁄2, 3, 4, and 6 inch NPS.
s. For use with Wheatland Tube “Mega-Flow” Lightwall steel sprinkler pipe in sizes: 2, 2-1⁄2, 3, and 4 inch NPS.
t. For use with Western International Forest Products “Rapid Thread” Thinwall steel sprinkler pipe in size 2 inch NPS.
u. For use with Wheatland Tube “WLS” Thinwall steel sprinkler pipe in size 2 inch NPS.
v. For use with Wheatland Tube “Mega-Thread” Thinwall steel sprinkler pipe in size 2 inch NPS.
w. For use with Wheatland Tube “MLT” Thinwall steel sprinkler pipe in size 2 inch NPS.
x. For use with Wheatland Tube “GL” Thinwall steel sprinkler pipe in size 2 inch NPS.
y. For use with Wheatland Tube “WST” schedule 5 steel sprinkler pipe in size 2 inch NPS.
z. For use with Youngstown Tube “EZ-Thread” Thinwall steel sprinkler pipe in 2 inch NPS.
A. For use with Youngstown Tube “Fire-Flo” Lightwall steel sprinkler pipe in sizes: 2, 2-1⁄2, 3, and 4 inch NPS.
B. Schedule 40 only.
Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan
Industrial Base, Shunyi District, Beijing, P. R. China
Product Pipe Size, Pipe Max Working
Designation mm Ends Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-321
Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang Tsun Ta Liau Shiang Kaohsiung Hsien,
Taiwan ROC
GT-425 Adapter Flanges for use with pipe conforming to the following min schedules. Cut groove: Schedule 40, 6 in. or smaller;
Schedule 30, 8 in. or larger. Rolled groove: Schedule 10S, 6 in. or smaller; 0.188 in. (5 mm) wall, 8 in. or larger.
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
FireShield Series 300 Products.
Product Nominal Pipe Max Working
Designation Size, in. Remarks Pressure, psi
(kPa)
Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin, Jinan, 250400 China
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
d. Approved when supplied with an ISO PN10 bolt pattern.
e. Approved when used with GB/T3092 regular and extra heavy pipe, ISO 4200, and BS 1387 Medium and Heavy pipe.
Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao,
China
16
2, 3, 4, 5, 8, 10 a, b, c, d
(232)
14 Grooved Split Flange
16
76, 108, 133, 139, 159, 165 mm c, d
(232)
Remarks:
a. Min schedule cut groove pipe to be joined: 6 in. NPS or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. NPS or smaller – Schedule 10S; 8 or 10 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with GB/T 3091-93 or GB/T 8163-99 Pipe.
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
‘‘QUIKFLANGE’’ Style 90, grooved flange, for working pressure up to 250 psi (1725 kPa). For use with pipe conforming to the following min
schedules:
90 QUIKFLANGE* 2, 3, 4, 6, 8 in.,
76, 89, 114, 168, 219 mm
FM Approvals
September 2007 — Approval Guide
1-322 Automatic Sprinkler Systems
*For use with roll groove Allied Tube & Conduit ‘‘Dyna Flow’’ at 175 psi (1205 kPa) rating. 2, 3, 4 in.
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
FireShield Series 300 Products.
Product Nominal Pipe Max Working
Designation Size, in. Remarks Pressure, psi
(kPa)
Style 14 2 to 8 a, b, c 175
Split Flange (1205)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
SCE Company Ltd, Unit E&F, 20/F., CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong
Max Working
Product Nominal Pipe Pipe Pressure, psi
Designation Size, in. Ends Remarks (kPa)
a. Minimum schedule cut groove pipe to be joined: 6 in. NPS and smaller – Schedule 40; 8 in. NPS and larger – Schedule 30.
b. Minimum schedule rolled groove pipe to be joined: 6 in. NPS and smaller – Schedule 10S; 8 in. NPS and larger 0.188 in. (5 mm) wall.
c. Approved when supplied with EPDM gasket.
d. Approved when supplied with an ISO PN10 bolt pattern.
SPT Metal Corp, 19-1 Da Yeh St, Da Liao, Hsiang, Kaóhsiung Hsien, Taiwan ROC
c, e, f, g, h, i, j 300
Split Flange 2-6
c, d (2070)
300
Split Flange 165.1 mm c, d
(2070)
Style 61
250
Split Flange 8 a, b, c
(1725)
175
Split Flange 10, 12 a, b, c
(1205)
Rigid Flange, 300
Style 62 2, 21⁄2, 3, 4, 5, 6, 8 a, c
Adaptor Flange (2070)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For metric pipe per BS 1387 medium or equal.
e. When joining Allied Tube & Conduit ‘‘XL’’ threadable Thinwall pipe, 1-2 in. only.
f. All FM Approved for use on Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
g. When joining Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use on Northwest ‘‘EZ-Flow’’ non-threadable Lightwall pipe in 4 in. nominal size.
i. For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe.
j. For use with Bull Moose Tube EDDY-Flow pipe.
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Product Fitting Nominal Pipe Max Working
Designation Description Size, in. Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-323
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Grinnell Flange. For use with pipe conforming to the following min schedules, at the pressure ratings indicated.
a. Cut groove-ended: 6 in. or smaller - Schedule 40, 300 psi (2070 kPa); 8 in. or larger - Schedule 30, 300 psi (2070 kPa).
b. Rolled groove-ended: 2, 21⁄2, 3 in. NPS - Allied Tube & Conduit FM Approved ‘‘XL’’, ‘‘Super-40’’ and ‘‘Super-XL’’ Lightwall pipe, 300 psi (2070 kPa).
c. Rolled groove-ended: 6 in. or smaller - Schedule 10; 8 in. or larger - 0.188 in. (5 mm) wall, 300 psi (2070 kPa).
d. Rolled groove-ended: Allied Tube & Conduit ‘‘Dyna-Flow.’’ 2, 21⁄2, 3 in., 300 psi (2070 kPa); Allied Tube & Conduit ‘‘Super-Flo.’’ 2-4 in., 300 psi (2070 kPa). Gruvlok
standard grooved-end fittings for use with Gruvlok couplings.
e. Metric pipe: equivalent to 76.1, 108, 133, 139.7, 165.1 and 323.9 mm British Standard 1387, medium or equal.
Cut groove-ended: 6 in. or smaller - Schedule 40, 300 psi (2070 kPa); 8 in. or larger – Schedule 30, 300 psi (2070 kPa).
Rolled groove-ended: 2, 21⁄2, 3 in. NPS – Allied Tube & Conduit FM Approved ‘‘XL’’, ‘‘Super-40’’ and ‘‘Super-XL’’ Lightwall pipe, 300 psi
(2070 kPa).
Rolled groove-ended: 6 in. or smaller – Schedule 10, 300 psi (2070 kPa); 250 psi (1725 kPa) or Schedule 30, 8 in. or larger – 0.188 in.
(5 mm) wall, 300 psi (2070 kPa).
Rolled groove-ended: Allied Tube & Conduit ‘‘Dyna-Flow.’’ 2, 21⁄2, 3 in., 300 psi (2070 kPa); Allied Tube & Conduit ‘‘Super-Flo.’’ 2-4 in.,
300 psi (2070 kPa).
Product Fitting Nominal Pipe Remarks Max. Working
Designation Description Size, in. Pressure psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-324 Automatic Sprinkler Systems
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket.
d. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
e. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
f. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
g. For use with Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
j. For use with Bull Moose ‘‘Ultra-EDDY’’ pipe and IDOD Systems Sch. 5 pipe.
k. For use with Allied ‘‘XL’’, Wheatland ‘‘WLS’’ Thinwall pipe.
l. For use with 3 through 6 in. Northwest ‘‘EZ-Flow’’ pipe.
m. For use with Youngstown ‘‘Fire-flo’’, ‘‘EZ-Thread’’ pipe, and Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. BS 1387 pipe, medium and heavy wall or ISO 4200 pipe.
Style 742 Vic-Flange. For rated working pressures up to 250 psi (1725 kPa) joining Schedule 30 cut groove-ended pipe.
Style 743 Vic-Flange. For working pressures up to 500 psi (3445 kPa). For use with pipe conforming to the following min schedules:
Cut or rolled groove-ended - Schedule 40, 6 in. or smaller; Schedule 30, 8 in. or larger.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-325
Style 744 Vic-Flange. For working pressures up to 175 psi (1205 kPa). For use with pipe conforming to the following min schedules:
Cut groove-ended - Schedule 40, 6 in. or smaller; Schedule 30, 8 in. or larger.
Rolled groove-ended - Schedule 10S, 6 in. or smaller; 0.188 in. (5 mm) wall, 8 in. or larger.
Also FM Approved for use on Allied ‘‘XL’’, Dyna-Flow, EZ-Flow and Super-Flo Lightwall pipe in appropriate sizes.
PIPE FITTINGS
These fittings are suitable for interconnecting piping, valves and other components in both wet and dry automatic
sprinkler systems. Installation should be according to applicable sprinkler system fabrication rules. These rules limit
the minimum size of sprinkler piping to 1 in., nominal. FM Approved pipe fittings of smaller sizes are intended for use
as valve trim, gauge connections, and for other peripheral service. The water flow path of the sprinkler system cannot
be designed using smaller sizes than 1 in., nominal. Unless otherwise noted in the listing, these fittings have 175 psi
(1205 kPa) rated working pressure.
Threaded connections on fittings can be made to FM Approved threadable thinwall pipe or to Schedule 40 pipe.
The Table on page provides a summary of pipes which are FM Approved for threaded connections. Also refer to the
specific listings under the heading ‘‘Steel Pipe.’’
The fittings manufacturer’s installation instructions must be observed in all cases. When connections are made to
FM Approved pipe, the pipe manufacturer’s installation instructions must also be followed.
Unless otherwise stated below, the maximum ambient temperature to which these fittings should be subjected is
225°F (107°C).
FM Approvals
September 2007 — Approval Guide
1-326 Automatic Sprinkler Systems
AJS Co Ltd, 1001 Namsung Plaza #345-30, Gasan-dong, Geumcheon-gu, Seoul 153-782 Korea
ATUSA empresarial SL, Aptd. Correos 8, Poligono, Industrial Agurain S/N, 01200 Salvatierra, Álava, Spain
1 Long Sweep Bend, M/F 1⁄8, 1⁄4, 3⁄8, 1⁄2, 3⁄4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
1A Short Bend, M/F 1⁄ 4, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
2 Long Sweep Bend, F/F 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 450
11⁄4, 11⁄2, 2, 21⁄2 (3100)
2A Short Bend, F/F 3⁄8, 1⁄2, 3⁄4, 1, 450
11⁄4, 11⁄2, 2, 21⁄2 (3100)
3 Long Sweep Bend, M/M 1⁄ 4, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
40 45° Long Sweep Bend, M/F 1⁄ 4, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
41 45° Long Sweep Bend, F/F 1⁄ 4, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
90 Elbow, F/F 1⁄ 8, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
90R Reducing Elbow, F/F 3⁄ 8 × 1⁄ 4, 450
1⁄2 × 1⁄4, 3⁄8 (3100)
3 ⁄ 4 × 3⁄ 8, 1⁄ 2
1 x 1⁄2, 3⁄4
1 ⁄4 × 1⁄2, 3⁄4, 1
1
95 Union Elbow, Flat Seat, F/F 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 450
(3100)
96 Union Elbow, Taper Seat, F/F 1⁄ 4, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
97 Union Elbow, Flat Seat, M/F 3⁄8, 1⁄2, 3⁄4, 450
1, 11⁄4, 11⁄2, 2 (3100)
98 Union Elbow, Taper Seat, M/F 1⁄ 4, 3⁄ 8, 1⁄ 2, 3⁄ 4, 450
1, 11⁄4, 11⁄2, 2, 21⁄2 (3100)
120 45° Elbow, F/F 3⁄8, 1⁄2, 3⁄4, 1, 450
11⁄4, 11⁄2, 2, 21⁄2 (3100)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-327
1 × 11⁄4, 11⁄2
11⁄4 × 11⁄2, 2
1 1⁄ 2 x 2
2 × 21⁄2
130R Tee, Branch Reducing, 1⁄ 2 × 3⁄ 8 x 3⁄ 8 450
Run Reducing, F 3⁄4 × 3⁄8 × 1⁄2, 3⁄4 x 1⁄2 × 3⁄8, (3100)
3⁄4 × 1⁄2 x 1⁄2, 1 × 3⁄8 × 3⁄4,
1 × 1⁄ 2, 3⁄ 4
11⁄4 × 1⁄2, 3⁄4, 1
11⁄2 x 3⁄4, 1, 11⁄4
2 × 1, 11⁄4, 11⁄2
21⁄2 × 2
FM Approvals
September 2007 — Approval Guide
1-328 Automatic Sprinkler Systems
1 x 1⁄2, 3⁄4
11⁄4 × 1⁄2, 3⁄4, 1
11⁄2 × 3⁄4, 1, 11⁄4
2 x 1, 11⁄4, 11⁄2
21⁄2 × 11⁄2, 2
270 Socket, F/F 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
271 Right and Left Socket, F/F 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 450
(3100)
280 Hex Nipple, M/M 3⁄ 8, 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
281 Right and Left Hex Nipple, M/M 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 450
(3100)
290 Plug, M 3⁄ 8, 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
291 Plain Plug, M 3⁄ 8, 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
294 Plug, M 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
300 Cap, F 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
330 Union, Flat Seat, F/F 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
331 Union, Flat Seat, M/F 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 450
(3100)
340 Union, Taper Seat, F/F 1⁄8, 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
341 Union, Taper Seat, M/F 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
344 Union, Taper Seat, M/M 1⁄4, 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 450
(3100)
526 Extension Tube, M/F 3⁄8 × 30, 1⁄2 × 30, 450
3⁄ 8× 40, 1⁄2 × 50, 3⁄4 × 50 (3100)
529A Extension Tube, M/F 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 450
(3100)
531 Internal Nipple, M/M 3⁄ 8, 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2, 21⁄2 450
(3100)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-329
Action Fire Fab & Supply Inc, 1600 W Linne Rd, Tracy CA 95376
FM Approvals
September 2007 — Approval Guide
1-330 Automatic Sprinkler Systems
Sch. 40
Fig. 600, 600A Grooved Welding 11⁄4×1; 300
Nipple 11⁄2×1, 11⁄4; (2070)
Sch. 10 2×1, 11⁄4, 11⁄2;
21⁄2×1, 11⁄4, 11⁄2, 2;
3×1, 11⁄4, 11⁄2, 2, 21⁄2;
4×1, 11⁄4, 11⁄2, 2,
21⁄2, 3, 31⁄2;
5×1, 11⁄4, 11⁄2, 2,
2 ⁄2, 3, 31⁄2, 4;
1
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-331
1 1⁄ 4 11⁄2-8
3F Female Thread 1 1⁄ 2 2-8
2 21⁄2-8
2 1⁄ 2 3-8
3 31⁄2-8
3 1⁄ 2 4-8
4 5-8
Standard groove-ended fittings for use with flexible couplings. 500 psi (3445 kPa) rated working pressure.
Product Nominal
Designation Description Pipe Size, in.
Fittings for use on Schedule 10 or heavier plain end pipe. NPT internal threaded branch connection.
FM Approvals
September 2007 — Approval Guide
1-332 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-333
Rated Working
Fitting Nominal Pressure,
Description Pipe Size End Conn. psi (kPa)
The Schedule 40 grooved, threaded, and flanged fittings have a rated working pressure as tabulated below:
Rated Working
Fitting Nominal Pressure,
Description Pipe Size End Conn. psi (kPa)
FM Approvals
September 2007 — Approval Guide
1-334 Automatic Sprinkler Systems
Rated Working
Fitting Nominal Pressure,
Description Pipe Size End Conn. psi (kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-335
Rated Working
Fitting Nominal Pressure,
Description Pipe Size End Conn. psi (kPa)
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
125 lb threaded Cast Iron Fittings.
175 psi (1205 kPa) rated pressure.
Flanged by threaded
356 45° Elbow 1⁄4-6
Flanged by threaded
356a 221⁄2° Elbow 3⁄ 4
to 21⁄2
352 90° Reducing Elbow 1⁄ 2by 1⁄4, 3⁄8;
3⁄4 by 1⁄2;
1 by 1⁄2, 3⁄4;
11⁄4 by 1⁄2, 3⁄4, 1;
11⁄2 by 1⁄2, 3⁄4, 1, 11⁄4;
2 by 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2;
21⁄2 by 1, 11⁄4, 11⁄2, 2;
3 by 11⁄4, 11⁄2, 2, 21⁄2;
31⁄2 by 3;
4 by 2, 21⁄2, 3, 31⁄2;
5 by 21⁄2, 3, 4;
6 by 3, 4, 5
358 Tee 1⁄4 to 6
FM Approvals
September 2007 — Approval Guide
1-336 Automatic Sprinkler Systems
1 by 1⁄2, 3⁄4;
11⁄4 by 1⁄2, 3⁄4, 1;
11⁄2 by 1⁄2, 3⁄4, 1, 11⁄4;
2 by 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2;
21⁄2 by 11⁄2, 2;
3 by 3⁄4, 2, 21⁄2;
4 by 2, 21⁄2, 3
368 Eccentric Reducer 3⁄4 by 1⁄2;
1 by 1⁄2, 3⁄4;
11⁄4 by 1⁄2, 3⁄4, 1;
11⁄2 by 1⁄2, 3⁄4, 1, 11⁄4;
2 by 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2;
21⁄2 by 1, 11⁄4,11⁄2, 2;
3 by 1, 11⁄4, 11⁄2, 2, 21⁄2;
31⁄2 by 2, 3;
4 by 1, 11⁄4, 11⁄2, 2, 21⁄2, 3
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-337
1 by 1⁄2, 3⁄4;
11⁄4 by 1⁄2, 3⁄4, 1;
11⁄2 by 1⁄2, 3⁄4, 1, 11⁄4;
2 by 1⁄2, 1, 11⁄4, 11⁄2;
21⁄2 by 11⁄4, 11⁄2, 2;
3 by 11⁄4, 11⁄2, 2, 21⁄2;
31⁄2 by 21⁄2;
4 by 2, 21⁄2, 3
387 Sq. Hd. Plug, Cored 1⁄2 to 4
250 lb Standard Threaded CI Fittings. Rated working pressure is 400 psi (2760 kPa)
1 by 1 by 1⁄2, 3⁄4;
11⁄4 by 11⁄4 by 3⁄4, 1;
11⁄2 by 11⁄2 by 3⁄4, 1/ 11⁄4;
2 by 2 by 3⁄4, 1, 11⁄4, 11⁄2
125 lb Standard Flanged CI Fittings. Rated working pressure is 175 psi (1205 kPa)
FM Approvals
September 2007 — Approval Guide
1-338 Automatic Sprinkler Systems
250 lb Standard Flanged CI Fittings. Rated working pressure is 400 psi (2760 kPa).
841 Tee 3 to 6
842 Reducing Tee 3 by 3 by 2, 21⁄2;
4 by 4 by 2, 21⁄2, 3;
5 by 5 by 4;
6 by 6 by 3, 4
150 lb Standard Threaded Malleable Iron Fittings. Rated working pressure is 300 psi (2070 kPa).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-339
300 lb Standard Threaded Malleable Iron Fittings. Rated working pressure as follows:
Product Fitting Nominal Pipe
Description Description Size, in.
1 by 1⁄2, 3⁄4;
11⁄4 by 3⁄4, 1;
11⁄2 by 1, 11⁄4;
2 by 11⁄4, 11⁄2;
21⁄2 by 2;
3 by 21⁄2
1163 Cap 1⁄4 to 3
FM Approvals
September 2007 — Approval Guide
1-340 Automatic Sprinkler Systems
463 300 1⁄ 4 to 3
(2070)
554 400 1⁄ 4 to 4
(2760)
459 600 1⁄ 4 to 4
(4135)
551 600 1⁄ 2 to 2
(4135)
552 600 3⁄ 8 to 1
(4135)
J-3 600 1⁄ 4 to 2
(4135)
Dart (0832) 600 3⁄ 8 to 2
(4135)
Segmentally welded pipe fittings for use with flexible or rigid grooved pipe couplings, plain end fittings, welded or threaded joints, or flanges.
Working pressures of 300 psi (2070 kPa) for non-threadable Thinwall pipe up to 4 in. NPS, Schedules 10 and 40 up to 8 in. NPS, and 250
psi (1725 kPa) for 10 and 12 in. NPS.
Prefix 7 in model no. means made from non-threadable Thinwall pipe.
Prefix 10 in model no. means made from Schedule 10 pipe.
Prefix 40 in model no. means made from Schedule 40 pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-341
Gruvlok standard grooved-end fittings for use with Gruvlok couplings. Rated working pressure is 500 psi (3445 kPa) unless otherwise
noted.
Product Fitting Nominal Pipe Pressure
Designation Description Size, in. Rating, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-342 Automatic Sprinkler Systems
12 350
(2415)
7053 111⁄4° Elbow 1-10 500
(3445)
12 350
(2415)
7055 90° Adapter Elbow 1-10 500
(3445)
12 350
(2415)
7056 45° Adapter Elbow 1-10 500
(3445)
12 350
(2415)
7060 Tee 1-10 500
(3445)
12 350
(2415)
76, 108, 133, 139, 175
159, 165 mm (1205)
216, 267 mm 500
(3445)
318 mm 400
(2760)
7060S Tee 11⁄4-8 300
(2070)
7060SR Shurjoint Radius 2-6 175
Tee Grooved (1205)
7060T Grooved Tee 11⁄4-8 175
(1205)
7061 Reducing Tee 1-10 500
(3445)
12 350
(2415)
7061T Grooved 2×11⁄2, 21⁄2×2, 3×2, 175
Reducing Tee 3×21⁄2, 4×2, 4×21⁄2, (1205)
4×3, 6×3, 6×4
7062 Bull Head Tee 5×5×8 500
(3445)
6×6×8 500
(3445)
7063 Tee With Threaded 1-10 500
Branch (3445)
12 350
(2415)
7064 Reducing Tee With 1-10 500
Threaded Branch (3445)
12 350
(2415)
7065 Stand Pipe Tee 4×4×21⁄2 500
(3445)
6×6×21⁄2 500
(3445)
7066 Tee Wyes 2×2×2 - 500
10×10×10 (3445)
12×12×3, 4, 350
6, 8, 10, 12 (2415)
7067 Reducing Tee Wyes 4×3×3- 500
8×6×8 (3445)
7068* Cross 1-10 500
(3445)
12 400
(2760)
7068T Grooved Cross 2, 21⁄2, 3, 4, 5, 6 175
(1205)
7069 45° Lateral 1-10 500
(3445)
12 350
(2415)
7070* Reducing Lateral 3×3×2 - 500
12×12×6 (3445)
12×12×8, 400
12×12×10 (2760)
7071 90° True Wye 1-10 500
(3445)
12 350
(2415)
7072 Concentric Reducer 11⁄2×1-10×8 500
(3445)
12×6, 8, 10 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-343
21⁄2×1
2-6
7095* 90° Elbow 11⁄2×1 250
Reducing (1725)
Groove × NPT
7097 Eccentric Reducer 11⁄2×1-10×8 500
Threaded Small End (3445)
12×4, 6, 8, 10 350
(2415)
*Fabricated fittings FM Approved with rolled or cut-grooved ends.
**Male threaded outlets.
FM Approvals
September 2007 — Approval Guide
1-344 Automatic Sprinkler Systems
Gruvlok Sock-It quick connect fittings for plain-end pipe. Pressure rating of 300 psi (2070 kPa) for all items except those having one or more
2 in. (51 mm) connections. 2 in. (51 mm) items rated at 250 psi (1725 kPa). Pressure rating is 175 psi (1205 kPa) for all items when used
with FM Approved Allied Tube & Conduit ‘‘XL’’, ‘‘Super-40’’ and ‘‘Super-XL’’ pipe, Allied ‘‘Super-Flo’’ pipe or Allied Tube & Conduit ‘‘Dyna-Flow’’
pipe, or IDOD ‘‘Gal-7’’ or ‘‘Gal-flo’’. 21⁄2 in. fittings rated at 175 psi for all pipes.
Product Fitting Nominal Pipe
Designation Description Size, in.
1×3⁄4×1⁄2, 1×1⁄2×1,
11⁄4×11⁄4×1,
11⁄4×11⁄4×3⁄4,
11⁄4×11⁄4×1⁄2,
11⁄4×1×11⁄4, 11⁄4×1×1,
11⁄4×1×3⁄4, 11⁄4×1×1⁄2,
1×1×11⁄4,
11⁄2×11⁄2×11⁄4,
11⁄2×11⁄2×1,
11⁄2×11⁄2×3⁄4,
11⁄2×11⁄2×1⁄2,
11⁄2×11⁄4×11⁄2,
11⁄2×11⁄4×1,
i1105R Screwed Fitting 11⁄2×11⁄4×3⁄4, 300
Reducing Tees 11⁄2×11⁄4×1⁄2, (2070)
11⁄2×1×11⁄2,
11⁄2×1×1, 11⁄2×1×3⁄4,
11⁄2×1×1⁄2, 1×1×11⁄2,
11⁄4×11⁄4×11⁄2,
11⁄4×1×11⁄2,
2×2×11⁄2, 2×2×11⁄4,
2×2×1,
2×2×3⁄4, 2×2×1⁄2,
2×11⁄2×2,
2×11⁄2×11⁄2, 2×11⁄2×1,
2×11⁄2×3⁄4, 2×11⁄2×1⁄2,
2×11⁄4×2, 2×1×2,
11⁄2×11⁄2×2,
11⁄2×11⁄4×2, 21⁄2×2×3⁄4,
2×2×21⁄2
i1125 Screwed Fitting 3⁄4×1⁄2, 1×3⁄4, 1×1⁄2, 300
Reducer 1 ⁄4×1, 11⁄2×1,
1 (2070)
11⁄2×11⁄4, 2×1, 2×11⁄4,
2×11⁄2, 21⁄2×2
i1107 Screwed Fitting 1, 11⁄4, 11⁄2, 2, 11⁄4×1, 300
Cross 11⁄2×1, 2×1 (2070)
i1121 Screwed Fitting 1⁄2, 3⁄4, 1, 11⁄4, 300
Straight Coupling 11⁄2, 2, 21⁄2 (2070)
i388 Screwed Fitting 1⁄2, 3⁄4, 1, 11⁄4, 300
Square Head Plug 11⁄2, 2 (2070)
i1124 Screwed Fitting 1⁄2, 3⁄4, 1, 11⁄4, 300
Cap 11⁄2, 2 (2070)
i1133 Screwed Fitting 1⁄2×11⁄2L, 1⁄2×2L, 300
Extension Piece 3⁄4×11⁄2L, 3⁄4×2L (2070)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-345
AnvilStar LLC, Division of Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
1×11⁄4-11⁄2
1×11⁄2-2
1×2-21⁄2
1×21⁄2-3
1×3-4
1×5-8
11⁄4×11⁄2-2
11⁄4×2-21⁄2
11⁄4×21⁄2-3
11⁄4×3-4
11⁄4×5-8
11⁄2×2
11⁄2×21⁄2
11⁄2×3-4
11⁄2×4
11⁄2×5-8
2×21⁄2
2×3
2×4
2×6
2×8
MT-40 1⁄2×11⁄4-11⁄2 Welded Branch Outlet e, k 175
1⁄2×11⁄2-2 Fitting, NPT (1205)
3⁄4×1-11⁄4
3⁄4×11⁄4-11⁄2
3⁄4×11⁄2-2
1×11⁄4-11⁄2
1×11⁄2-2
11⁄4×11⁄2-2
11⁄2×2
FM Approvals
September 2007 — Approval Guide
1-346 Automatic Sprinkler Systems
Cast Iron Threaded 1, 11⁄4, 11⁄2, 2, 21⁄2 C.I. 90° Elbow 300
Pipe Fittings (2070)
1, 1 1⁄ 4, 11⁄2, 2, 21⁄2 C.I. 45° Elbow 300
(2070)
1, 11⁄4, 11⁄2, 2, 21⁄2 C.I. Equal Tee 300
(2070)
1, 11⁄4, 11⁄2, 2 C.I. Equal Cross 300
(2070)
1×1⁄2, 3⁄4 C. I. Reducing Elbow 300
11⁄4×1⁄2, 3⁄4,1 (2070)
11⁄2×1⁄2, 3⁄4, 1, 11⁄4
2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
1×1⁄2×1, 1×3⁄4×1, C.I. Reducing Tee 300
1×1×1⁄2, 3⁄4, 11⁄4, 11⁄2 (2070)
11⁄4×1×1⁄2, 3⁄4, 11⁄4, 11⁄2
11⁄4×11⁄4×1⁄2, 3⁄4, 1, 11⁄2, 2
1 ⁄2×1×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
1
a. For use with FM Approved Schedule 10 and 40 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 6, and 8 in. NPS.
b. For use with Youngstown Tube ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
c. For use with Allied Tube and Conduit ‘‘XL’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
d. For use with Sawhill Tubular ‘‘SLS’’ threadable Thinwall steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
e. For use with Wheatland Tube ‘‘WST’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
f. For use with Tex-Tube ‘‘Tex-Flow’’ Lightwall steel sprinkler pipe in sizes: 3, 4, and 6 in. NPS.
g. For use with Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
h. For use with Wheatland Tube ‘‘Mega Flow’’ Lightwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
i. For use with Northwest Pipe ‘‘EZ-Flow’’ Lightwall steel sprinkler pipe in sizes: 4 and 6 in. NPS.
j. For use with Youngstown Tube ‘‘Fire-Flo’’ Lightwall steel sprinkler pipe in sizes: 11⁄2, 2, 21⁄2, 3, and 4 in. NPS.
k. For use with Bull Moose Tube ‘‘Ultra – EDDY’’ Schedule 5 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
l. For use with Allied Tube & Conduit ‘‘XL-II’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
m. For use with Allied Tube & Conduit ‘‘Super-XL’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
n. For use with Allied Tube & Conduit ‘‘Super 40’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, 2, 21⁄2, and 3 in. NPS.
o. For use with Allied Tube and Conduit ‘‘BLT’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
p. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
q. For use with Bull Moose Tube ‘‘EDDY-Lite’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
r. For use with Bull Moose Tube ‘‘EDDY-Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
t. For use with Western International Forest Products ‘‘Rapid Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
u. For use with Wheatland Tube ‘‘WLS’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
v. For use with Wheatland Tube ‘‘Mega Thread’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
w. For use with Wheatland Tube ‘‘MLT’’ threadable Thinwall steel sprinkler pipe in sizes: 11⁄4, 11⁄2, and 2 in. NPS.
Segmentally welded pipe fittings for use with flexible or rigid grooved pipe couplings, plain end fittings, welded or threaded joints, or flanges.
Working pressures of 300 psi (2070 kPa) for non-threadable Thinwall pipe up to 4 in. NPS, Schedules 10 and 40 up to 8 in. NPS, and 250 psi
(1725 kPa) for 10 and 12 in. NPS.
Prefix 7 in model no. means made from non-threadable Thinwall pipe.
Prefix 10 in model no. means made from Schedule 10 pipe.
Prefix 40 in model no. means made from Schedule 40 pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-347
Tri-flex Loops
The model numbers of the Tri-flex Loops contain a digit, which represents the amount of flex in inches that each assembly will tolerate in
each principal plane of motion. The size of each assembly increases in proportion to the amount of flex required for each installation. Consult
the manufacturer for overall dimensions of each loop.
Max Working
Product Nominal Pipe Assembly Pressure, psi
Designation Size, in. Ends Remarks (kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
c. The digit in the Series number is the amount of flex in inches that the assembly will withstand in each cardinal direction.
FM Approvals
September 2007 — Approval Guide
1-348 Automatic Sprinkler Systems
B&K Industries Inc, 2600 Elmhurst Road, Elk Grove Village IL 60007
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-349
241 Bushing 1⁄ 2
× 1⁄ 4, 3⁄ 8 500 psi
× 3⁄ 8, 1⁄ 2
3⁄ 4 (3445 kPa)
1 × 1⁄ 2, 3⁄ 4
11⁄4 × 1⁄2, 3⁄4, 1
11⁄2 × 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4
2 × 3⁄8, 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
21⁄2 × 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2
3 × 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2
31⁄2 × 21⁄2, 3
4 × 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 31⁄2
5 × 2, 3, 4 300
6 × 2, 21⁄2, 3, 31⁄2, 4, 5 (2070)
FM Approvals
September 2007 — Approval Guide
1-350 Automatic Sprinkler Systems
BMI Canada Inc, 3437 Grande Allee Blvd, Boisbriand, Quebec J7H 1H5, Canada
Product Fitting Nominal Pipe Pressure
Designation Description Size, in. Rating, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-351
Beijing Tian Ning Yi He Pipe System Equipment Co Ltd, No. 2, North Road, Ju Yuan, Ma Pa Ju Yuan
Industrial Base, Shunyi District, Beijing, P. R. China
FM Approvals
September 2007 — Approval Guide
1-352 Automatic Sprinkler Systems
China Changchun Rongxia Tube Co Ltd, XinLiCheng Town 54, Village Changchun China 130119
Standard threaded branch outlet connections for attachment to pipe by welding. For use with schedule 10 and 40 steel sprinkler pipe.
Requires precutting of hole on pipe. NPT internal threaded branch connection conforming to ANSI B1.20.1.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-353
Standard groove-ended fittings for use with grooved couplings. 250 psi (1725 kPa) rated working pressure.
Standard groove-ended fittings for use with grooved couplings. 175 psi (1205 kPa) rated working pressure.
FM Approvals
September 2007 — Approval Guide
1-354 Automatic Sprinkler Systems
Dibu S.L., Ctra. Parla a Pinto, Km 2, 800, Parla (Madrid) E-28980, Spain
Product Fitting Nominal Nominal Pipe
Designation Description Outlet Size, in. Size, in.
Branch connections for attachment to pipe by welding. For use with ISO 4200, DIN 2440 and DIN 2448 steel sprinkler pipe. Requires
precutting of hole on pipe. Rated working pressure 20 bar (290 psi).
Ever Metal Industry Co Ltd, 853 Kwang Fu Rd, Pa Teh City, Tao Yuen Hsien Taiwan ROC
Standard grooved-end fittings for use with flexible couplings with Schedule 40 or heavier and Schedule 10S or heavier cut or rolled
groove-end pipe. 300 psi (2070 kPa) rated working pressure.
Ductile Iron Screwed Fittings — 300 psi (2070 kPa) rated working pressure.
11⁄4x1⁄2, 3⁄4, 1;
11⁄2x3⁄4, 1, 11⁄4;
2x3⁄4, 1, 11⁄4, 11⁄2
D6 Reducing Couplings 3⁄4x1⁄2; 1x1⁄2, 3⁄4
1x1⁄2x1⁄2, 3⁄4, 1;
1x3⁄4x1⁄2, 3⁄4, 1;
1x1x1⁄2, 3⁄4, 11⁄4, 11⁄2, 2;
11⁄4x1⁄2x1, 11⁄4;
11⁄4x3⁄4x3⁄4, 1, 11⁄4;
11⁄4x1x1⁄2, 3⁄4, 1, 11⁄4;
11⁄4x11⁄4x1⁄2, 3⁄4, 1, 11⁄2, 2;
11⁄2x1⁄2x11⁄2;
11⁄2x3⁄4x11⁄2;
11⁄2x1x1, 11⁄4, 11⁄2;
1 ⁄2x1 ⁄4x ⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2;
1 1 1
11⁄4x3⁄4, 1;
11⁄2x3⁄4, 1, 11⁄4;
2x3⁄4, 1, 11⁄4, 11⁄2
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-355
The model numbers of the Tri-flex Loops contain a digit, which represents the amount of flex in inches that each assembly will tolerate in
each principal plane of motion. The size of each assembly increases in proportion to the amount of flex required for each installation. Consult
the manufacturer for overall dimensions of each loop.
Max Working
Product Nominal Pipe Assembly Pressure, psi
Designation Size, in. Ends Remarks (kPa)
FM Approvals
September 2007 — Approval Guide
1-356 Automatic Sprinkler Systems
Max Working
Product Nominal Pipe Assembly Pressure, psi
Designation Size, in. Ends Remarks (kPa)
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10; 8 in. or larger – 0.188 in. (5 mm) wall.
Steel Fittings
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-357
Product Nominal
Designation Description Pipe Size, in.
316 S. S. ‘‘Press-Fit’’ Couplngs. To be installed with Geberit Mapress pressing tools EFP-2, EFP-3, or HCDS only. FM Approved for use with Geberit
Mapress Stainless Steel Schedule 5 pipe in wet or dry pipe systems in 25-100 mm nominal sizes, and for use with valve trim and accessories in 20 mm
nominal size.
Gentler Industrial Co Ltd, 178-10A Chung Chang Rd, Chung Chang Tsun Ta Liau Shiang Kaohsiung Hsien
Taiwan ROC
Standard grooved-end fittings for use with grooved couplings: 300 psi (2070 kPa) rated working pressure.
Product Fitting Nominal Pipe
Designation Description Size, in.
FM Approvals
September 2007 — Approval Guide
1-358 Automatic Sprinkler Systems
Georg Fischer Fittings GmbH, Mariazeller Strauße 75, A-3160 Traisen Austria
Standard malleable iron (W400-05) threaded pipe fittings to ISO 49, and BS EN 10242. Threads in accordance with ISO 7-1 (taper external,
parallel internal threads where sealing is achieved on the threads), and ISO 228 (parallel internal threads where sealing is not achieved on
the threads). Rated working pressure 450 psi (3100 kPa).
11⁄2×3⁄4, 1, 11⁄4,
2×1, 11⁄4, 11⁄2
92 Equal Elbow 1⁄ 2, 3⁄ 4,
1, 11⁄4, 11⁄2, 2 450
(3100)
92 Elbow Reducing 1⁄2×3⁄8, 450
External Thread 3⁄4×1⁄2, (3100)
1×3⁄4,
11⁄4×3⁄4, 1,
11⁄2×1, 11⁄4
92 Elbow, 3⁄8×1⁄2, 1⁄2×3⁄4, 3⁄4×1, 450
Reducing 1×11⁄4 (3100)
Internal Thread
94 Elbow 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
120 45° Elbow 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
121 45° Elbow 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
130 Equal Tee 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
130 Tee Branch 1⁄2×3⁄4, 1, 450
Increasing 3⁄4×1, (3100)
1×11⁄4,11⁄2,
11⁄4×11⁄2, 2,
11⁄2×2
130 Elbow Branch 1⁄2×1⁄4, 3⁄8, 450
Reducing 3⁄4×1⁄4, 3⁄8, 1⁄2, (3100)
1×1⁄4, 3⁄8, 1⁄2, 3⁄4,
11⁄4×3⁄8, 1⁄2, 3⁄4, 1,
11⁄2×1⁄2, 3⁄4, 1, 11⁄4
2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-359
1×1⁄2×1⁄2, 3⁄4,
1×3⁄4×1⁄2, 3⁄4,
1×1×3⁄8, 1⁄2, 3⁄4,
1×11⁄4×3⁄4,
11⁄4×1⁄2×1,
11⁄4×3⁄4×3⁄4, 1,
11⁄4×1×3⁄4, 1,
1 ⁄4×11⁄4×1⁄2, 3⁄4, 1,
1
11⁄4×11⁄2×1,
11⁄2×1⁄2×11⁄4,
11⁄2×3⁄4×11⁄4,
11⁄2×1×1,
11⁄2×11⁄4×1, 11⁄4,
11⁄2×11⁄2×1⁄2, 3⁄4, 1, 11⁄4,
11⁄2×2×11⁄4,
2×1⁄2×11⁄2,
2×3⁄4×11⁄2,
2×1×11⁄2,
2×11⁄4×11⁄2,
2×11⁄2×11⁄2,
2×2×1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
133 Tee 1⁄2, 3⁄4, 1 450
(3100)
134 Tee 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
135 Tee 1⁄2, 3⁄4, 1 450
(3100)
180 Equal Cross 1⁄ 2, 3⁄ 4, 1, 11⁄4, 11⁄2, 2 450
(3100)
180 Cross Reducing 3⁄4×1⁄2, 450
1×1⁄2, 3⁄4, (3100)
11⁄4×1,
11⁄2×3⁄4, 1,
2×1
240 Reducers 1⁄2×3⁄8, 3⁄4×1⁄2, 450
1×3⁄4, 11⁄4×1, (3100)
11⁄2×11⁄4, 2×11⁄2
240 Reducers 3⁄4×3⁄8, 450
1×1⁄2, (3100)
11⁄4×1⁄2, 3⁄4,
11⁄2×1⁄2, 3⁄4, 1,
2×1⁄2, 3⁄4, 1, 11⁄4
241 Reducing Bush 1⁄2×3⁄8, 3⁄4×1⁄2, 450
1×3⁄4, 11⁄4×1, (3100)
11⁄2×11⁄4, 2×11⁄2
241 Reducing Bush 3⁄4×3⁄8, 450
1×1⁄2, (3100)
11⁄4×1⁄2, 3⁄4,
11⁄2×1⁄2, 3⁄4, 1,
2×1⁄2, 3⁄4, 1, 11⁄4
246 Socket 1⁄2×3⁄8, 450
3⁄4×3⁄8, 1⁄2, (3100)
1×1⁄2, 3⁄4,
11⁄4×1⁄2, 3⁄4, 1,
1 ⁄2× ⁄2, 3⁄4, 1, 11⁄4,
1 1
FM Approvals
September 2007 — Approval Guide
1-360 Automatic Sprinkler Systems
Hyspan Precision Products Inc, 1685 Brandywine Ave, Chula Vista CA 91911
Ball joints for sprinkler system piping. Can be used singly or in multiples to connect sprinkler systems on mobile structures to stationary
water supplies. Requires proper installation geometry for free movement. Consult manufacturer for design information. FM Approved with
Type 11/11N packing.
Model Configuration Size
Interfit India Ltd, SF No 112 / 3D, Part Mathapur Road, Kaniyur Village, Coimbatore 641 659, India
Standard groove-ended fittings for use with grooved couplings and grooved pipe as noted.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-361
Threaded Fittings
65 Reducing Tee 3⁄ 4
× 3⁄4 × 1⁄2 to 300
2 × 11⁄4 × 2 (2070)
FM Approvals
September 2007 — Approval Guide
1-362 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-363
4×1-31⁄2;
5×1-4;
6×1-4
85, 86 Reducing on Run and or Outlet 21⁄2×2×1-21⁄2;
Tee with Female NPT Side 3×2×1-3;
Outlet 3×21⁄2×1-3;
3 ⁄2×2×1-31⁄2;
1
31⁄2×21⁄2×1-31⁄2;
31⁄2×3×1-31⁄2;
4×2-31⁄2×1-4;
5×2-4×1-4;
6×2-5×1-4;
8×2-6×1-4
EL 90° Elbow 11⁄4 through 8
60° Elbow
45° Elbow
EL 30° Elbow
221⁄2° Elbow
91⁄2° Elbow
111⁄4° Elbow
40 Reducing on Run and 21⁄2×2×2;
Outlet Tee 3×2×2, 21⁄2;
3×21⁄2×2, 21⁄2;
31⁄2×2-3×2-3;
4×2-31⁄2×2-31⁄2;
5×2-4×2-4;
6×2-5×2-5;
8×2-6×2-6
RT1-RT5 Riser Tee 21⁄2 through 8*
*All size riser tees have a rated working pressure of 250 psi (1725 kPa).
Branch connections for attachment to pipe by welding. For use with Schedule 10S or heavier pipe unless otherwise noted. Requires
precutting of hole in pipe. Rated working pressure 300 psi (2070 kPa)
Branch connections for attachment to pipe by welding. For use with Schedule 10 or heavier pipe. Requires precutting of hole on pipe. Rated
working pressures: Schedule 40 pipe, 500 psi (3445 kPa); Schedule 10 pipe, 300 psi (2070 kPa).
40CG Cut Grooved Outlet 1, 11⁄4, 11⁄2, 2, 21⁄2, 11⁄4, 11⁄2, 2, 21⁄2,
3, 4, 5, 6 3, 4, 5, 6, 8
40RG Roll Grooved Outlet 1, 11⁄4, 11⁄2, 2, 21⁄2, 11⁄4, 11⁄2, 2, 21⁄2,
3, 4, 5, 6 3, 4, 5, 6, 8
40MT Male Thread Outlet 1, 11⁄4, 11⁄2, 2, 21⁄2, 11⁄4, 11⁄2, 2, 21⁄2,
3, 4, 5, 6 3, 4, 5, 6, 8
40BW 371⁄2 Bevel for 1, 11⁄4, 11⁄2, 2, 21⁄2, 11⁄4, 11⁄2, 2, 21⁄2,
Butt Welding 3, 4, 5, 6 3, 4, 5, 6, 8
FM Approvals
September 2007 — Approval Guide
1-364 Automatic Sprinkler Systems
Standard groove-ended fittings for use with flexible couplings. 300 psi (2070 kPa) rated working pressure.
JFE Pipe Fitting Mfg Co Ltd, 153 Tajime-Cho, Kishiwada Osaka, Japan
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-365
11⁄2×11⁄2×1⁄2, 11⁄2×11⁄4×11⁄2,
DI, Reducing 11⁄2×11⁄4×1, 11⁄2×11⁄4×3⁄4, ’’ 300
Tees 11⁄2×11⁄4×1⁄2, 11⁄2×1×11⁄2, (2070)
11⁄2×1×1, 11⁄2×1×3⁄4,
11⁄2×1×1⁄2, 1×1×11⁄2,
11⁄4×11⁄4×11⁄2, 11⁄4×1×11⁄2,
2×2×11⁄2, 2×2×11⁄4, 2×2×1,
2×2×3⁄4, 2×2×1⁄2, 2×11⁄2×2,
2×11⁄2×11⁄2, 2×11⁄2×1,
2×11⁄2×3⁄4, 2×11⁄2×1⁄2,
2×11⁄4×2, 2×1×2, 11⁄2×11⁄2×2,
11⁄2×11⁄4×2, 21⁄2×2×3⁄4,
2×2×21⁄2
DI, Reducing 1×3⁄4, 1×1⁄2 ’’ 300
Couplings (2070)
DI, Reducing 1⁄2×11⁄2 L, 1⁄2×2 L, ’’ 300
Coupling (2070)
Extension 3⁄4×11⁄2 L, 3⁄4×2 L ’’ 300
Pieces (2070)
DI, Crosses 1, 11⁄4, 11⁄2, 2, 11⁄4×1, ’’ 300
11⁄2×1, 2×1 (2070)
DI, Straight 1⁄2, 3⁄4, 1, 1 ⁄4, 11⁄2, 2, 21⁄2
1 ’’ 300
Coupling (2070)
DI, Caps 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 ’’ 300
(2070)
DI, Hex. 1×3⁄4, 1×1⁄2, 11⁄4×1, 11⁄4×3⁄4, ’’ 300
Bushings 11⁄4×1⁄2, 11⁄2×11⁄4, 11⁄2×1, (2070)
11⁄2×3⁄4, 11⁄2×1⁄2, 2×11⁄2,
2×11⁄4, 2×1, 2×3⁄4, 2×1⁄2
DI, Face 11⁄4×1, 11⁄2×11⁄4, 11⁄2×1, ’’ 300
Bushings 2×11⁄2, 2×11⁄4 (2070)
DI, Brass 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 ’’ 300
Seat Union (2070)
a. 21⁄2, 4 in. British Standard BS 1387 medium or heavy pipe.
b. Min schedule cut groove pipe to be joined: 8 in. or smaller – Schedule 40.
c. Min schedule rolled groove pipe to be joined: 8 in. or smaller – Schedule 10.
Jinan Meide Casting Co Ltd, No. 3 Nanmen Road, Pingyin Jinan Shandong 250400, China
Product Fitting Nominal Pipe Max Working
Designation Description Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-366 Automatic Sprinkler Systems
240N Concentric Reducer, Groove × Female NPT 2×3⁄4, 1, 11⁄4, 11⁄2, 500
21⁄2×1, 11⁄4, 11⁄2, 2, (3450)
3×3⁄4, 1, 11⁄2, 2, 21⁄2,
4×1, 11⁄2, 2, 21⁄2, 3,
5×3, 4,
6×2, 21⁄2, 3, 4, 5,
8×21⁄2, 3, 4, 5, 6
240W Concentric Reducer, Groove × Male NPT 2×3⁄4, 1, 11⁄4, 11⁄2, 500
21⁄2×1, 11⁄4, 11⁄2, 2, (3450)
3×3⁄4, 1, 11⁄2, 2, 21⁄2,
4×1, 11⁄2, 2, 21⁄2, 3,
5×3, 4,
6×2, 21⁄2, 3, 4, 5,
8×21⁄2, 3, 4, 5, 6
35C D.I. Cap, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
35CP D.I. Straight Coupling, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
35E D.I. 90° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
35F D.I. 45° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-367
2×11⁄4×2
2×1×2
21⁄2×21⁄2×3⁄4, 1, 11⁄4, 11⁄2, 2, 3
35T D.I. Equal Tee, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
37E C.I. 90° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 300
(2070)
37F C.I. 45° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 300
(2070)
2×11⁄4×21⁄2,
2×1×21⁄2,
2×3⁄4×21⁄2,
21⁄2×1⁄2×2, 21⁄2
FM Approvals
September 2007 — Approval Guide
1-368 Automatic Sprinkler Systems
5, 6 300
(2070)
90R Reducing Elbows, 90 1⁄2×1⁄4 thru 4×3 500
(3445)
92 Street Elbows, 90 1⁄ 2 thru 4 500
(3445)
6 300
(2070)
120 Elbow, 45 1⁄ 2 thru 4 500
(3445)
5, 6 300
(2070)
121 Street Elbow, 45 1⁄ 2 thru 4 500
(3445)
1221 Side Outlet Elbows 1⁄ 2 thru 2 500
(3445)
130 Tees 1⁄ 2 thru 4 500
(3445)
5, 6 300
(2070)
130R Reducing Tees 1⁄2×1⁄2×1⁄4, 3⁄8 500
1⁄2×1⁄4×1⁄2 (3445)
1⁄2×3⁄8×1⁄2
3⁄4×3⁄4×1⁄4, 3⁄8, 1⁄2
3⁄4×1⁄2×1⁄2, 3⁄4
1×1×11⁄4, 11⁄2, 2
11⁄4×11⁄4×11⁄2, 2
11⁄2×11⁄2×2
2×2×21⁄2
134 Service Tee 1⁄2 thru 2 500
(3445)
165 Lateral Y Branch 1⁄ 2 thru 4 500
(3445)
180 Cross 1⁄ 2 thru 4 500
(3445)
5, 6 300
(2070)
180R Reducing Cross 3⁄4×1⁄2 500
1×3⁄4 (3445)
11⁄4×3⁄4, 1
11⁄2×3⁄4, 1/11⁄4
2×3⁄4, 1/11⁄4, 11⁄2
21⁄2×1, 11⁄4, 11⁄2, 2
3×1, 11⁄4, 11⁄2, 2, 21⁄2
4×21⁄2, 3
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-369
FM Approvals
September 2007 — Approval Guide
1-370 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-371
Merit Manufacturing, Division of Anvil International Inc, 110 Corporate Dr, Suite 10, Portsmouth NH 03801
Product Fitting Nominal Pipe
Designation Description Size, in.
The above fittings have a 500 psi (3445 kPa) rated working pressure.
Product Fitting Nominal Pipe
Designation Description Size, in.
Eliminator II
A-922-1 Cast Reducer 1×1⁄2
A-922-2 Cast Reducer 1×3⁄4
The above fittings have a 300 psi (2070 kPa) rated working pressure.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working
pressure 300 psi (2070 kPa). For use with pipes as noted above, in sizes as appropriate.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working
pressure 175 psi (1205 kPa). For use with pipes as noted above, in sizes as appropriate.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working pressure 300 psi
(2070 kPa). For use with pipes as noted above, in sizes as appropriate.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working pressure 175 psi
(1205 kPa). For use with pipes as noted above, in sizes as appropriate.
FM Approvals
September 2007 — Approval Guide
1-372 Automatic Sprinkler Systems
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working pressure 300 psi
(2070 kPa). For use with pipes as noted above, in sizes as appropriate.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working
pressure 175 psi (1205 kPa). For use with pipes as noted above, in sizes as appropriate.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working
pressure 300 psi (2070 kPa). For use with pipes as noted above, in sizes as appropriate.
Branch connections for attachment to pipe by welding. Requires precutting of hole on pipe and removal of coupon. Rated working
pressure 175 psi (1205 kPa). For use with pipes as noted above, in sizes as appropriate.
Notes:
Modgal Metal (99) Ltd, Box 63, Rosh Pina 12000, Israel
‘‘QUIKCOUP’’ standard grooved ended fittings for use with grooved couplings.
Max Working
Product Fitting Nominal Pipe
Remarks Pressure, psi
Designation Description Size, in./ mm
(kPa)
500
02 End Cap (Blind) 11⁄4 through 8 –
(3445)
175
02 End Cap (Blind) 10 –
(1205)
End Cap
500
02D (3⁄4 in. NPT 3 through 8 –
(3445)
Tapped Vent Hole)
76, 108, 133, 140 290
02 End Cap (Blind) –
159, 165 mm (2000)
End Cap 76, 108, 133, 290
02D –
(Tapped 11⁄2 in. BSP) 159, 165 mm (2000)
500
04 ‘‘QUIKBEND’’ 45° Elbow 11⁄2 through 8 –
(3445)
500
05 Tee 11⁄4 through 8 –
(3445)
290
05 Tee 76, 108, 159 mm –
(2000)
200
05 Tee 10 –
(1380)
500
06 ‘‘QUIKBEND’’ 90° Elbow 11⁄4 through 8 –
(3445)
290
06 ‘‘QUIKBEND’’ 90° Elbow 76, 108, 159 mm –
(2000)
200
06 ‘‘QUIKBEND’’ 90° Elbow 10 –
(1380)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-373
Max Working
Product Fitting Nominal Pipe
Remarks Pressure, psi
Designation Description Size, in./ mm
(kPa)
500
06D 90° Drain Elbow 3, 4, 6, 8 –
(3445)
11⁄2×11⁄4; 2×11⁄2
Concentric 500
15 3×2, 21⁄2; 4×2, 3 –
Reducer (3445)
6×2, 3, 4; 8×4, 6
Concentric 175
15 10×8 –
Reducer (1205)
76×60 mm,
114×76 mm,
Concentric 140×89, 114 mm, 500
15 –
Reducer 165×60, 89 mm, (3445)
114, 140 mm,
168×140 mm
Concentric 175
15 219×140 mm –
Reducer (1205)
Reducing Adapter,
250
24 Groove × Female BSP 11⁄2×1 –
(1725)
Thread
Sprinkler Adapter,
175
25 Groove × Female NPT 11⁄2×1 –
(1205)
Thread
21⁄2×21⁄2×2;
3×3×2; 4×4×2;
Cast Straight 500
55 4×4×21⁄2; 4×4×3; –
Reducing Tee (3445)
6×6×11⁄2, 2,
21⁄2, 3, 4
Short Radius Tees, 60, 76, 89, 114, 139, 165, 300
65 –
Grooved Ends 168, 219 mm (2070)
90° Short Elbow, 60, 76, 89, 114, 139, 165, 300
66 –
Grooved Ends 168, 219 mm (2070)
500
60, 76, 89, 114, 139, 165,
(3450)
91 Flange x Grooved Adapter 168, 219 mm –
300
273, 324 mm
(2070)
500
91 Flange Adapter 3, 4 g
(3445)
175
91 Flange Adapter 6, 8, 10 g
(1205)
175
91 Flange Adapter 165 mm g
(1205)
300
Elbow 221⁄2° Segmentally Welded 11⁄2, 2, 3, 4, 6, 8 –
(2070)
FM Approvals
September 2007 — Approval Guide
1-374 Automatic Sprinkler Systems
Max Working
Product Fitting Nominal Pipe
Remarks Pressure, psi
Designation Description Size, in./ mm
(kPa)
300
Elbow 221⁄2° Segmentally Welded 76, 140 mm –
(2070)
300
Elbow 111⁄4° Segmentally Welded 11⁄2, 2, 3, 4, 6, 8 –
(2070)
300
Elbow 111⁄4° Segmentally Welded 76, 140 mm –
(2070)
232
280 Coupling, Plain End 1, 11⁄4, 11⁄2, 2 a, b, c, d, e
(1600)
232
282 End Cap 1, 11⁄4, 11⁄2, 2 –
(1600)
232
285 Equal Tee, Plain End 1, 11⁄4, 11⁄2 a, b, c, d, e
(1600)
232
286 Elbow, 90°, Plain End 1, 11⁄4, 11⁄2 a, b, c, d, e
(1600)
1×1⁄2, 3⁄4, 1
Reducing Tee, Plain 11⁄4×1⁄2, 3⁄4, 1 232
289 a, b, c, d, e, f
End × Threaded Branch 11⁄2×1⁄2, 3⁄4, 1 (1600)
2×1⁄2, 3⁄4, 1
Remarks:
a. Approved for use with Schedule 10 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
b. Approved for use with Schedule 40 steel sprinkler pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
c. Approved for use with DIN 2458 steel sprinkler pipe.
d. Approved for use with ISO 65 steel pipe in sizes: 1, 11⁄4, 11⁄2, and 2 in. NPS.
e. Approved when supplied with EPDM gasket.
f. Approved when supplied with ISO 7/1 threaded connections.
g. Adapters are used for connecting traditional PN16 flanges to grooved piping systems.
National Fittings Inc, 295 East Swedesford Road #280, Wayne PA 19087-1462
Nominal Pipe Outlet
Run Sizes, in. Size, in./ mm
Series T3F-NPT
1 1⁄ 4 1⁄2, 3⁄4, 1
1 1⁄ 2 1⁄2, 3⁄4, 1, 11⁄4
2 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
Series T3F-BSP
11⁄4 1⁄2, 3⁄4, 1
1 1⁄ 2 1⁄2, 3⁄4, 1, 11⁄4
2 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2
Series T3G
1 1⁄ 4 1
1 1⁄ 2 1, 11⁄4
2 1, 11⁄4, 11⁄2
21⁄2 1, 11⁄4, 11⁄2, 2
3 1, 11⁄4, 11⁄2, 2, 21⁄2
4 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 76.1 mm
5 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 76.1 mm
6 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 76.1 mm
8 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6, 76.1 mm, 165.1 mm
76.1 mm 1, 11⁄4, 11⁄2, 2, 21⁄2
165.1 mm 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6, 76.1 mm
Standard groove-ended fittings for use with grooved couplings and grooved pipe as noted.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-375
Slip-on and Blind Flanges. 4-12 in. sizes in accordance with AWWA-C207.
Standard threaded pipe fittings conforming to ASTM A-126. Grade A cast iron. ANSI B2.1 NPT internal threads. Rated working pressure
175 psi (1205 kPa).
FM Approvals
September 2007 — Approval Guide
1-376 Automatic Sprinkler Systems
Standard threaded pipe fittings conforming to ASTM A-536 (Grade 65-45-12) ductile iron, ANSI B2.1 taper threads according to NPT. Rated
working pressure 300 psi (2070 kPa).
Product Fitting Nominal Pipe
Designation Description Size, in.
North Alabama Pipe Corp, New Industrial Park, Box 750, Guntersville AL 35976
NAP300 Welded Outlets. Rated working pressure 300 psi (2070 kPa).
Product Nominal Outlet Nominal Pipe
Designation Size, FNPT Size, in.
NAP300 1⁄ 2, 3⁄ 4 11⁄4-8
1, 11⁄4 11⁄2-8
1 1⁄ 2 2-8
2 21⁄2-8
2 1⁄ 2 3-8
Qingdao V-Cart Piping Systems Co Ltd, JuiZhao Road, NanGuan Industry Zone, JiaoZhou City, Qingdao, China
34
2, 3, 57, 76
(495)
27
100 90° Elbow 4, 108
(390)
5, 6, 8, 20
133, 139, 141, 159, 165 (290)
34
2, 3, 57, 76
(495)
27
101 45° Elbow 4, 108
(390)
5, 6, 8, 20
133, 139, 141, 159, 165 (290)
2 through 8 20
110 Straight Tee
57, 76, 108, 133, 139, 141, 159, 165 (290)
2 through 6 20
112 Equal cross
57, 76, 108, 133, 139, 141, 159, 165 (290)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-377
34
2 by 11⁄4 through 4 by 3
Concentric Reducers (495)
140G
G by G 20
139 by 2 through 12 by 10 in.
(290)
34
Concentric Reducers 2 by 1⁄2 through 4 by 3
(495)
140T G by T
NPT Threads 20
133 by 1 through 165 by 4 in.
(290)
34
Concentric Reducers 2 by 1⁄2 through 4 by 3
(495)
140T G by T
ISO Threads 20
133 by 1 through 165 by 4 in.
(290)
2 through 12 in., 16
190 Flange×Groove Adapter
76, 108, 133, 139, 159, 165 mm (32)
13062 2×2
130715 3×11⁄2
13072 3×2
130724 3×2
130915 4×11⁄2
13092 4×2
130924 4×2
130925 4×21⁄2
13093 4×3
131115 6×11⁄2
13112 6×2
131124 6×2
131125 6×21⁄2
13113 6×3
13114 6×4
13115 6×5
13132 8×2
131324 8×2
13133 8×3
13134 8×4
13135 8×5
13136 8×6
13163 10×3
13164 10×4
13165 10×5
13166 10×6
13168 10×8
13194 12×4
13196 12×6
13198 12×8
131190 12×10
Rigid Industries Co Ltd, 8 Mei-Chung Rd, Niao-Song Kaohsiung Hsien, 83301 Taiwan
The following fittings are suitable for use on Schedule 10 and 40 pipe.
FM Approvals
September 2007 — Approval Guide
1-378 Automatic Sprinkler Systems
SCE Company Ltd, Unit E&F, 20/F, CDW Building, 388 Castl Peak Road, Tsuen Wan, N.T., Hong Kong
SPT Metal Corp, 19-1 Da Yeh St, Da Liao Hsiang, Kaohsiung Hsien, Taiwan ROC
Cast Grooved Fittings.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-379
Shanghai Vision Mechanical Joint Co Ltd, Jinlan Road, Loutang Industrial Park, Jiading District,
Shanghai 201807 PRC
FM Approvals
September 2007 — Approval Guide
1-380 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-381
FM Approvals
September 2007 — Approval Guide
1-382 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-383
Shanghai Recomb Piping System Co Ltd, No. 270 Yixian Rd, Shanghai 200434, P. R. China
Standard grooved and threaded pipe fittings conforming to ASTM A-536 (Grade 65-45-12) ductile iron, ANSI B2.1 taper threads according
to NPT.
Product Pipe Actual Fitting Max Working
Designation Size mm Description Pressure, psi
(kPa)
XGQT01 42, 48, 60, 73, 76, 89, 108, 114, 133, 90° Elbow 300
140, 141.3, 159, 165, 168 and 219 (2070)
XGQT02 42, 48, 60, 73, 76, 89, 108, 114, 133, 45° Elbow 300
141.3, 140, 159, 165, 168 and 219 (2070)
FM Approvals
September 2007 — Approval Guide
1-384 Automatic Sprinkler Systems
XGQT03 42, 48, 60, 73, 76, 89, 108, 114, 133, Tee 300
141.3, 140, 159, 165, 168 and 219 (2070)
XGQT05 60, 76, 89, 108, 114, 133, 140, Cross 300
159, 165, 168 and 219 (2070)
XGQT05 273 and 325 mm Cross 175
(1205)
XGQT06 42, 48, 60, 73, 76, 89, 108, 114, 133, Cap 300
141.3, 140, 159, 165, 168 and 219 (2070)
XGQT07 60x42, 60x48, 73x48.3, 73x60.3, 76x42, 76x48, 76×60, Concentric Reducer 300
89x42, 89x48, 88.9x73, 89×60, 89×76, (Grooved) (1205)
108×76, 108×89, 114x42, 114x48, 114x60,
114.3x73, 114×76, 114×89, 133×76, 133×89, 133×108,
133×114, 140x60,140×76, 140×89,
140×114, 141.3x60.3, 141.3x73, 141.3x88.9, 141.3x114.3,
159×76, 159×89, 159×108, 159×114, 159×133, 159×140,
165x60, 165×76, 165×89, 165×114, 165×140, 168x60,
168×76, 168×89, 168×108, 168×114,
168×133, 168×140, 168.3x73, 168.3x141.3,
219×76, 219×89, 219×108, 219×114, 219×133, 219×140,
219×159, 219×165, 219×168, 219.1x73 and 219.1x141.3
XGQT07 89x60P, 89x76P, 114x76P, 114x89P, 165x76P, 165x89P, Eccentric Reducer 300
165x114P, 219x114P and 219x165P (2070)
XGQT07 273x219P Eccentric Reducer 175
(1205)
XGQT08 60, 73, 76, 89, 108, 114, 133 140, Flange 300
141.3, 159, 165, 168 and 219 (2070)
XGQT08 60, 73, 89, 114, 141.3, 168 and 219 ANSI 150 Flange 300
American Standard (2070)
(2, 21⁄2, 3, 4, 5, 6 and 8 in.)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-385
XGQT10 42, 48, 60, 73, 76, 89, 114, 22.5° Elbow 300
140, 165, 168 and 219 (2070)
Shanxi Jinbaote Machinery Industry Co Ltd, International Foundry Park, Eco. Development Area, Jincheng, Shanxi,
China 048000
Product Fitting Nominal Pipe Rated Working
Designation Description Size, mm Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-386 Automatic Sprinkler Systems
Shield Fire, Safety and Security Ltd, 28th Floor Regus Suite, One Canada Square, Canary Wharf, London E14 5DY,
United Kingdom
Product Fitting Nominal Pipe Max Working
Designation Description size, mm Pressure, psi
(kPa)
Model SDG100 90° Elbow, Grooved Ends 11⁄4, 11⁄2, 2, 21⁄2, 500
3, 4, 5, 6, 8 (3450)
Model SDG200 45° Elbow, Grooved Ends 11⁄4, 11⁄2, 2, 21⁄2, 3, 500
4, 5, 6, 8, 10, 12 (3450)
Model SDG200 45° Elbow, Grooved Ends 76.1, 165 mm 500
(3450)
Model SDG12 Equal Tee, Grooved Ends 11⁄4, 11⁄2, 2, 21⁄2, 3, 500
4, 5, 6, 8, 10, 12 (3450)
Model SDG12 Equal Tee, Grooved Ends 76.1, 165 mm 500
(3450)
Model SDG53 Reducing Tee, Grooved Ends 2×11⁄2, 500
3×1, 11⁄2, 2, 21⁄2, (3450)
4×1, 2, 21⁄2, 3,
5×2, 3, 4,
6×2, 21⁄2, 3, 4, 5,
8×2, 3, 4, 5, 6
Model SDG13 Equal Cross, Grooved Ends 11⁄4, 11⁄2, 2, 21⁄2, 3, 500
4, 5, 6, 8, 10, 12 (3450)
Model SDG13 Equal Cross, Grooved Ends 76.1, 165 mm 500
(3450)
Model SDG35 Concentric Reducer, Grooved Ends 2×3⁄4, 1, 11⁄4, 11⁄2, 500
21⁄2×1, 11⁄4, 11⁄2, 2, (3450)
3×3⁄4, 1, 11⁄2, 2, 21⁄2,
4×1, 11⁄2, 2, 21⁄2, 3,
5×3, 4,
6×1, 2, 21⁄2, 3, 4, 5,
1
8×2 ⁄2, 3, 4, 5, 6
Model SDG37 Concentric Reducer, Groove×Female NPT 2×3⁄4, 1, 11⁄4, 11⁄2, 500
21⁄2×1, 11⁄4, 11⁄2, 2, (3450)
3×3⁄4, 1, 11⁄2, 2, 21⁄2,
4×1, 11⁄2, 2, 21⁄2, 3,
5×3, 4,
6×2, 21⁄2, 3, 4, 5,
8×21⁄2, 3, 4, 5, 6
Model SDG39 Concentric Reducer, Groove×Male NPT 2×3⁄4, 1, 11⁄4, 11⁄2, 500
21⁄2×1, 11⁄4, 11⁄2, 2, (3450)
3×3⁄4, 1, 11⁄2, 2, 21⁄2,
4×1, 11⁄2, 2, 21⁄2, 3,
5×3, 4,
6×2, 21⁄2, 3, 4, 5,
8×21⁄2, 3, 4, 5, 6
Model SDG14 Grooved End Cap 11⁄4, 11⁄2, 2, 21⁄2, 3, 4, 5, 6, 8, 500
10, 12 (3450)
Model SDG14 Grooved End Cap 76.1, 165 mm 500
(3450)
Model SDG16 Flange×Groove Adapter 2, 21⁄2, 3, 4, 5, 6, 8 500
(3450)
Model SDG16 Flange×Groove Adapter 76.1, 165mm 500
(3450)
Model SDT14 D.I. Cap, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
Model SDT22 D.I. Straight Coupling, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
Model SDT100 D.I. 90° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
Model SDT200 D.I. 45° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
Model SDT57 D.I. Bushings, Threaded 1×1⁄2, 3⁄4 500
11⁄4×3⁄4 (3450)
2×1
Model SDT30 D.I. Concentric Reducer, Threaded 1×1⁄2, 3⁄4 500
11⁄4×3⁄4 (3450)
2×1
Model SDT101 D.I. 90° Reducing Elbow, Threaded 3⁄4×1⁄2 500
1×1⁄2, 3⁄4 (3450)
11⁄4×1⁄2, 3⁄4, 1
1 ⁄2×3⁄4, 1, 11⁄4
1
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-387
2×11⁄4×2
2×1×2
21⁄2×21⁄2×3⁄4, 1, 11⁄4, 11⁄2, 2, 3
Model SDT51 D.I. Reducing Cross, Threaded 11⁄4×1, 11⁄2×1, 2×1 500
(3450)
Model SDT55 D.I. Square Head Pipe Plug 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 500
(3450)
Model SDT12 D.I. Equal Tee, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 500
(3450)
Model SDT59 D.I. Union, Threaded 1, 11⁄4, 11⁄2, 2 500
(3450)
Model SDT13 D.I. Cross, Threaded 1, 11⁄4, 11⁄2, 2 500
(3450)
Model SDC100 C.I. 90° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 300
(2070)
Model SDC200 C.I. 45° Elbow, Threaded 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 300
(2070)
Model SDC30 C.I. Concentric Reducer, Threaded 1×1⁄2, 3⁄4 300
2×1 (2070)
Model SDC101 C.I. 90° Reducing Elbow, Threaded 1×1⁄2, 3⁄4, 300
11⁄4×1⁄2, 3⁄4, 1, (2070)
11⁄2×1⁄2, 3⁄4, 1, 11⁄4,
2× ⁄2, 3⁄4, 1, 11⁄4, 11⁄2,
1
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Product Nominal Pipe Fitting Max Rated
Designation Size, in. Description Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
1-388 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-389
Standard threaded pipe fittings conforming to ASTM A-536 (Grade 65-45-12) ductile iron, ANSI B2.1 taper threads according to NPT. Unless
otherwise noted in the listing, these fittings are ductile iron.
FM Approvals
September 2007 — Approval Guide
1-390 Automatic Sprinkler Systems
4 5, 6, 8
74 Universal Threaded Outlet Fitting, 1⁄ 2 1, 11⁄2, 2, 21⁄2, 300
Welded Outlet Fitting 3, 4, 5, 6, 8 (2070)
3⁄ 4 11⁄4, 11⁄2, 2, 21⁄2,
3, 4, 5, 6, 8
1 11⁄4, 11⁄2, 2, 21⁄2,
3, 4, 5, 6, 8
7150M 11⁄2×1, 2×11⁄4,2×11⁄2, 21⁄2×11⁄4, 21⁄2×11⁄2, 21⁄2×2, 3×11⁄4, Reducing Nipple 300
3×11⁄2, 3×2, 4×11⁄2, 4×2, 4×21⁄2, 5×11⁄2, 6×11⁄2, 6×2, (2070)
6×21⁄2, 6×4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-391
FM Approvals
September 2007 — Approval Guide
1-392 Automatic Sprinkler Systems
Threaded Ductile Iron Fittings. Rated working pressure is 500 psi (3445 kPa)
1 by 3⁄4, 3⁄4;
11⁄4 by 3⁄4, 3⁄4, 1;
1 ⁄2 by 3⁄4, 1, 11⁄4;
1
1, 11⁄4, 11⁄2, 2, 3;
35X Cross 1 to 2
35RC Concentric Reducer 1 by 3⁄4, 3⁄4;
1 ⁄4 by 3⁄4;
1
2 by 1
35HB Bushing 1 by 3⁄4, 3⁄4;
1
1 ⁄4 by 1;
11⁄2 by 1, 11⁄4;
2 by 1, 11⁄4, 11⁄2;
35U Union 1 thru 2
35C End Cap 3⁄4 thru 21⁄2
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-393
Rated Working Pressure of the Coop-let Series Weldolets is 300 psi (2070 kPa) when used with Schedule 10, Schedule 40, or
non-threadable lightwall pipe.
When used with Schedule 5 pipe, the rated working pressure is 175 psi (1205 kPa).
FM Approvals
September 2007 — Approval Guide
1-394 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-395
Branch connections for attachment to pipe by welding. For use with Schedule 10S or heavier pipe unless otherwise noted. Requires
precutting of hole in pipe. Rated working pressure 11⁄4 through 5 in., 300 psi (2070 kPa). Rated working pressure 6 and 8 in. 250 psi
(1725 kPa).
Product Fitting Nominal Outlet Nominal Pipe
Designation Description Size, in. Size, in.
Tyco Fire Products, 1550 Valley Center Pkwy, Suite 135, Bethlehem PA 18017
Fig. No. Description Sizes (in.)
2 by 2 by 11⁄2
817 Cross 1⁄2 thru 21⁄2
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Max Rated
Product Fitting Nominal Pipe Pressure, psi
Designation Description Size, in. (kPa)
FM Approvals
September 2007 — Approval Guide
1-396 Automatic Sprinkler Systems
Max Rated
Product Fitting Nominal Pipe Pressure, psi
Designation Description Size, in. (kPa)
Standard threaded pipe fittings conforming to ASTM A-536 (Grade 65-45-12) ductile iron, ANSI B2.1 taper threads according to NPT. Rated
working pressure 300 psi (2070 kPa).
11⁄4×1⁄2,3⁄4, 1;
11⁄2×3⁄4, 1, 11⁄4;
2×3⁄4, 1, 11⁄2;
21⁄2×2
813 45° Elbow 1⁄2 through 21⁄2
1×1⁄2×1;
1×3⁄4×1⁄2,3⁄4, 1;
1 ⁄4×1×1⁄2,3⁄4, 1;
1
11⁄4×1×11⁄4;
11⁄2×11⁄4×1⁄2,3⁄4, 1;
11⁄2×1×1⁄2,3⁄4, 1, 11⁄2,
2×1×2;
2×11⁄4, 11⁄2;
2×11⁄2×1⁄2,3⁄4, 1, 11⁄2, 2;
2×2, 11⁄4, 11⁄2;
21⁄2×2×3⁄4;
815 Bullhead Tee 1×1×11⁄4, 11⁄2;
11⁄4×1×11⁄2;
11⁄4×11⁄4×11⁄2;
11⁄2×11⁄2×2;
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-397
2×2×21⁄2
831 90° Street Elbow 1×1⁄2, 1
832 California Fitting 1×1⁄2×1
1×1×1
816 Reducing Couplings 3⁄4×1⁄2, 1×1⁄2, 1×3⁄4
Max Rated
Product Fitting Nominal Pipe Pressure, psi
Designation Description Size, in. (kPa)
Segmentally welded fittings, made from Schedule 40 pipe. Rated working pressure 300 psi. Roll grooved ends unless otherwise specified.
FM Approvals
September 2007 — Approval Guide
1-398 Automatic Sprinkler Systems
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
Product Fitting Nominal Pipe Max Rated
Designation Description Size, in. Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-399
Standard threaded pipe fittings conforming to ASTM A-536 (Grade 65-45-12) ductile iron, ANSI B2.1 taper threads according to NPT. Rated
working pressure 300 psi (2070 kPa).
11⁄4×1⁄2, 3⁄4, 1;
11⁄2×3⁄4, 1, 11⁄4;
2×3⁄4, 1, 11⁄2;
21⁄2×2
813 45° Elbow 1⁄2 through 21⁄2
1×1⁄2×1;
1× ⁄4×1⁄2, 3⁄4, 1;
3
11⁄4×1×1⁄2, 3⁄4, 1;
11⁄4×1×11⁄4;
11⁄2×11⁄4×1⁄2, 3⁄4, 1;
11⁄2×1×1⁄2, 3⁄4, 1, 11⁄2,
2×1×2;
2×11⁄4, 11⁄2;
2×11⁄2×1⁄2, 3⁄4, 1, 11⁄2, 2;
2×2, 11⁄4, 11⁄2;
21⁄2×2×3⁄4;
815 Bullhead Tee 1×1×11⁄4, 11⁄2;
11⁄4×1×11⁄2;
11⁄4×11⁄4×11⁄2;
11⁄2×11⁄2×2;
2×2×21⁄2
816 Reducing Couplings 3⁄4×1⁄2, 1×1⁄2, 1×3⁄4
1, 11⁄4, 11⁄2, 2
FM Approvals
September 2007 — Approval Guide
1-400 Automatic Sprinkler Systems
Segmentally welded fittings, made from Schedule 40 pipe. Rated working pressure 300 psi. Roll grooved ends unless otherwise specified.
Branch Connection for attachment to pipe by welding. Requires pre-cutting of hole on pipe and removal of coupon. Rated Working Pressure
300 psi (2070 kPa).
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30. Standard schedule 10 rolled groove pipe: 6 in. or smaller –
8 in. or 10 in. – 0.188 in. (5 mm) wall.
b. For use with Allied Dyna-thread, Dyna-flow, Super-flo, and BLT pipe.
c. For use with Tex-Tube Tex-flow Pipe.
d. For use with Wheatland Tube SL pipe, WLS, Mega-flow, MLT, and Mega-thread.
e. For use with Bull Moose Tube EDDY-lite, EDDYthread 40, and EDDY-flow.
f. For use with Northwest Pipe EZ-flow pipe.
g. For use with WIFP Fire Flow and Rapid-thread pipe.
h. For use with Youngstown Pipe Fire-flo and EZ-Thread pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-401
Branch Connection for attachment to pipe by welding. Requires pre-cutting of hole on pipe and removal of coupon. Rated Working Pressure
300 psi (2070 kPa).
a. Min schedule cut groove pipe to be joined: 6 in. or smaller – BS1387 Heavy; 8 in. – Schedule 30. Standard BS1387 Medium rolled groove pipe: 6 in. or
smaller – 8 in. – 0.188 in. (5 mm) wall Schedule 10 pipe.
Vandewater 11⁄4;
NPT Weldable 1⁄2
Tee-Let 11⁄2 through 21⁄2;
Branch Outlet Fitting
Cericeo Series 21⁄2 through 8
Rated working pressure of the Cericeo Series Tee-lets is 300 psi (2070 kPa).
FM Approved for use with Schedule 10 and 40 Run pipes, Steady-flow, 11⁄2 thru 4 in., Super-flo, 1 thru 4 in., Dyna-flow, 1 thru 4 in.,
EDDY-flow, 11⁄2 thru 4 in., Gal-flo and Gal-7, 11⁄4 thru 2 in., EZ-flow, 3 thru 6 in., Tex-flow, 21⁄2 thru 6 in., Fire-flow, 11⁄4 thru 3 in., Mega-flow
11⁄4 thru 4 in., and Fire-Flo, 11⁄2 thru 4 in.
FM Approvals
September 2007 — Approval Guide
1-402 Automatic Sprinkler Systems
5×8;
21 Bullhead Tee
6×8
2×3⁄4, 1, 21⁄2×1;
3×1, 2;
25 Reducing Tee 4×1, 11⁄2, 2, 21⁄2, 3;
5 by 21⁄2
165 mm×114 mm
Standpipe Tee
27 4×21⁄2; 6×21⁄2
(NPT Branch)
3⁄4 through 4;
2×3⁄4, 1, 21⁄2×1;
Adapter Tee 3×1, 2;
29
(NPT Branch) 4×1, 11⁄2, 2, 21⁄2, 3;
5×21⁄2
6×2, 3
30 Lateral 2, 3, 4, 8
2, 3, 4
35 Cross
76, 165 mm
11⁄2×1, 11⁄4;
2×3⁄4, 1, 11⁄4, 11⁄2;
2 ⁄2×11⁄4, 11⁄2, 2;
1
11⁄2×1;
2×3⁄4, 1, 11⁄4, 11⁄2
Reducer, Grooved Large End, 21⁄2×2;
52
Threaded Small End 3×1, 2, 21⁄2;
4×1, 2, 21⁄2, 3;
6×1, 2, 21⁄2, 3
3⁄4 through 12
60 End Cap
76, 108, 133, 140, 159, 165 mm
11⁄4×1⁄2, 3⁄4, 1,
Grooved End×Threaded (NPT) 11⁄2×1⁄2, 3⁄4, 1, 500
67
Outlet Reducing Elbow 2×1⁄2, 3⁄4, 1, (3450)
21⁄2×1⁄2, 3⁄4, 1
80 Female Adapter 2, 3, 4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-403
Style 500 Series ‘‘Press-Fit’’ Couplngs. To be installed with Victaulic pressing tools, Type EPU or PFT 505, only. FM Approved for use with
Allied Tube & Conduit ‘‘Dyna-Light’’, Bull Moose ‘‘Ultra-EDDY’’ or Wheatland ‘‘WST’’ Schedule 5 pipe in wet pipe systems in sizes 1 through
2 in., and for use with valve trim and accessories in 3⁄4 in. size; FM Approved for use with IDOD Systems Gal-5 pipe in 11⁄4-2 in. sizes.
11⁄2×1⁄2, 3⁄4, 1;
2×1⁄2, 3⁄4, 1
520 Tee Reducing Branch 11⁄4×1×1⁄2, 3⁄4;
and Run (P×P×F) 11⁄2×11⁄4×1⁄2, 3⁄4;
2×11⁄2×1⁄2, 3⁄4
520 Tee Reducing Branch 11⁄4×1×1
and Run (P×P×P) 11⁄2×11⁄4×1;
2×11⁄2×1
520 End of Line 1×1×3⁄4;
Fitting (P×C×F) 11⁄4×11⁄4×1⁄2, 3⁄4;
11⁄2×11⁄2×3⁄4, 1;
2×2×1⁄2, 3⁄4, 1
520 End of Line 1×1×3⁄4;
Fitting 11⁄4×11⁄4×3⁄4;
P×C×P 11⁄2×11⁄2×3⁄4, 1;
2×2×3⁄4, 1, 11⁄2
535 Equal Cross 3⁄4, 1, 11⁄4, 11⁄2, 2
FM Approvals
September 2007 — Approval Guide
1-404 Automatic Sprinkler Systems
1×1⁄2, 3⁄4, 1
580 Adapter-Male (P×M) 3⁄4×1⁄2, 3⁄4, 1;
1×3⁄4, 1;
11⁄4×11⁄4;
11⁄2×11⁄2;
2×2
Style 96 Fast Installation Technique (FIT) Reducing Tee§. NPT internal threaded branch connection. Run connects two plain end Lightwall,
Thinwall, 10S or heavier pipes. With Grade E (green stripe) or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 929 Mechanical Tee with Fast Installation Technique (FIT) Branch Outlet§. Clamps over hole in run pipe. Also for use as crosses in
any possible combination. With grade E (green stripe) or L (solid red) gasket material. Also FM Approved with Allied ‘‘Dyna-Flow’’ Lightwall
pipes. Not FM Approved for Schedule 5 pipe.
Style 960 Fast Installation Technique (FIT) Coupling§. Connects two plain end Lightwall, Thinwall, 10S or heavier pipes. With Grade E
(green stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 961 Fast Installation Technique (FIT) Elbow§. Connects two plain end Lightwall, Thinwall, 10S or heavier pipes. With Grade E (green
stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 963 Fast Installation Technique (FIT) Straight Tee§. Connects three plain-end Lightwall, Thinwall, 10S or heavier pipes for branch
connection. With Grade E (green stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 966 Fast Installation Technique (FIT) Reducing Elbow§. NPT internal threaded drop nipple or sprigs. Connects plain end Lightwall,
Thinwall, 10S or heavier pipes. With Grade E (green stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 969 Fast Installation Technique (FIT) Reducing Tee§. NPT internal threaded branch connection. With Grade E (green stripe) or L (solid
red) gasket material. Connects plain end Lightwall, Thinwall, 10S or heavier pipe. With Grade E (green stripe), or L (solid red) gasket material.
Not FM Approved for Schedule 5 pipe.
Fast Installation Technique (FIT) pipe fittings. Connects two plain end Lightwall, Thinwall, 10S or heavier pipes as listed below. Not FM
Approved for Schedule 5 pipe.
Product Fitting Nominal Pipe Max Working
Designation Description Size, in. Remarks Pressure, psi
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-405
3, 41⁄4, 51⁄4,
51⁄2, 61⁄4 and 6.5
12 221⁄2° Elbow 4
13 111⁄4° Elbow 2, 3, 4, 6, 8
18 90° Adapter Elbow 3⁄4 through 6
3, 41⁄4, 51⁄4,
51⁄2, 61⁄4 and 6.5
21 Bullhead Tee 5×8;
6×8
25 Reducing Tee 2×3⁄4, 1;
3×1, 2;
4×1, 2, 21⁄2, 3
27 Standpipe Tee 4×21⁄2;
(NPT Branch) 6×21⁄2
29 Adapter Tee 3⁄4 through 4;
Firelock Pipe Fittings. Cast ductile iron grooved-end fittings. 175 psi (1205 kPa).
Product Nominal Pipe
Designation Fitting Description Size, in.
FM Approvals
September 2007 — Approval Guide
1-406 Automatic Sprinkler Systems
Style 500 Series ‘‘Press-Fit’’ Couplngs. To be installed with Victaulic pressing tools, Type EPU or PFT 505, only. FM Approved for use with
Allied Tube & Conduit ‘‘Dyna-Light’’, Bull Moose ‘‘Ultra-EDDY’’ or Wheatland ‘‘WST’’ Schedule 5 pipe in wet pipe systems in sizes 1 through
2 in., and for use with valve trim and accessories in 3⁄4 in. size.
11⁄2×1⁄2, 3⁄4;
2×3⁄4
509 Short Radius Elbow (P×P) 1, 11⁄4, 11⁄2, 2
510 90° Elbow 1×1⁄2, 3⁄4;
Reducing (P×F) 11⁄4×1⁄2, 3⁄4;
11⁄2×1⁄2, 3⁄4
510 90° Elbow 11⁄4×1;
Reducing (P×P) 11⁄2×1;
11⁄2×11⁄4
510 90° Elbow (P×P) 3⁄4 through 2
2×3⁄4, 1
520 Tee Reducing Branch 1×1⁄2, 3⁄4, 1;
(P×P×F) 11⁄4×1⁄2, 3⁄4, 1;
11⁄2×1⁄2, 3⁄4, 1;
2×1⁄2, 3⁄4, 1
520 Tee Reducing Branch 11⁄4×1×1⁄2, 3⁄4;
and Run (P×P×F) 1 ⁄2×11⁄4×1⁄2, 3⁄4;
1
2×11⁄2×1⁄2, 3⁄4
520 Tee Reducing Branch 11⁄4×1×1
and Run (P×P×P) 11⁄2×11⁄4×1;
2×11⁄2×1
520 End of Line Fitting 2×3⁄4
535 Equal Cross 3⁄4, 1, 11⁄4, 11⁄2, 2
1×1⁄2, 3⁄4, 1
580 Adapter-Male (P×M) 3⁄4×1⁄2, 3⁄4, 1;
1×3⁄4, 1;
11⁄4×11⁄4;
11⁄2×11⁄2;
2×2
Style 96 Fast Installation Technique (FIT) Reducing Tee§. NPT internal threaded branch connection. Run connects three plain end
Lightwall, Thinwall, 10S or heavier pipes. With Grade E (green stripe) or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 929 Mechanical Tee with Fast Installation Technique (FIT) Branch Outlet§. Clamps over hole in run pipe. Also for use as crosses in
any possible combination. With grade E (green stripe) or L (solid red) gasket material. Also FM Approved with Allied ‘‘Dyna-Flow’’ Lightwall
pipes. Not FM Approved for Schedule 5 pipe.
Style 960 Fast Installation Technique (FIT) Coupling§. Connects two plain end Lightwall, Thinwall, 10S or heavier pipes. With Grade E
(green stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 961 Fast Installation Technique (FIT) Elbow§. Connects two plain end Lightwall, Thinwall, 10S or heavier pipes. With Grade E (green
stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 963 Fast Installation Technique (FIT) Straight Tee§. Connects three plain-end Lightwall, Thinwall, 10S or heavier pipes for branch
connection. With Grade E (green stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-407
2×2×2
Style 966 Fast Installation Technique (FIT) Reducing Elbow§. NPT internal threaded drop nipple or sprigs. Connects plain end Lightwall,
Thinwall, 10S or heavier pipes. With Grade E (green stripe), or L (solid red) gasket material. Not FM Approved for Schedule 5 pipe.
Style 969 Fast Installation Technique (FIT) Reducing Tee§. NPT internal threaded branch connection. With Grade E (green stripe) or L (solid
red) gasket material. Connects plain end Lightwall, Thinwall, 10S or heavier pipe. With Grade E (green stripe), or L (solid red) gasket material.
Not FM Approved for Schedule 5 pipe.
§For use with Central Sprinkler ‘‘TL’’ threadable Thinwall pipe, 1-2 in. sizes.
‘‘Uniking’’ Series
Fig. 6001 90° Long Radius Elbow 4, 6 500
(3445)
8 300
(2070)
Fig. 6010 90° Elbow 1-6 500
76, 108, 133, 139, 159, 165 mm (3445)
8-12 300
(2070)
6011 45° Elbow 1-6 500
76, 108, 133, 139, 159, 165 mm (3445)
8-12 300
(2070)
6020 Equal Tees 1-6 500
76, 108, 133, 139, 159, 165 mm (3445)
8-12 300
(2070)
6025 Reduced Tees 2×1 through 8×6 300
(2070)
6050 Concentric 2×11⁄4 through 12×10 300
Reducers (2070)
6060 End Cap 1 through 6 500
76, 108, 133, 139, 159, 165 mm (3445)
8-12 300
(2070)
‘‘Fireking’’ Series
Fig. 2010 90° Elbow 11⁄4-8 300
76, 139, 165 mm (2070)
Virotec Rohrtechnik GmbH & Co KG, Meininger Weg 8, D-36132 Eiterfield, Germany
Rotating U, Z and L shaped pipe unions for use as sprinkler drops below suspended ceilings.
Product
Designation End Connections Remarks
FM Approvals
September 2007 — Approval Guide
1-408 Automatic Sprinkler Systems
2×2×2
5060 Reducing Tee 2×2×1;
2×2×11⁄4;
2×2×11⁄2
5065 Bullhead Tee 11⁄2×11⁄2×2
Threaded Fittings.
175 psi,
1205 (kPa)
Nominal Size (unless otherwise
Fig. No. Description Range NPT specified)
through
8 by 6
14 C.I. Flanged Union 1⁄2-8
through
4 by 31⁄2
23 C.I. 45° Elbow 1⁄2-4
through
4 by 4 by 31⁄2
29 C.I. Reducer 11⁄4 by 3⁄4
through
3 by 2
30 C.I. Cap 21⁄2-6
30A C.I. Cross 1⁄2-2
through
3 by 2
48 M.I. 45° Elbow 1⁄2-4
through
3 by 3 by 21⁄2
53 M.I. Coupling 1⁄2-4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-409
Tee 2-12
Reducing Tee 3 by 2
through
12 by 10
Cross 2-12
Reducing Cross 12 by 3
through
12 by 10
Long Radius 90° El 4-12
90° Elbow 2-12
Reducing El 6 by 4
8 by 6
45° Elbow 2-12
221⁄2° Elbow 2-12
111⁄4° Elbow 2-12
Concentric Reducer 3 by 2
through
12 by 10
Eccentric Reducer 6 by 4
through
12 by 10
Weifang 100tong Co Ltd, No. 1919 Jinchang South Road, Weicheng District, Weifang,
Shandong, PR China 261052
Rated Working
Product Fitting Nominal Pipe Pressure, psi
Designation Description Size, mm (kPa)
GCPQT01 90° Elbow 60, 76, 89, 108, 114, 133, 140, 159, 165, 168, 219, 273, 325 230
(1600)
GCPQT02 45° Elbow 60, 76, 89, 108, 114, 133, 140, 159, 165, 168, 219, 273, 325 230
(1600)
GCPQT03 Tee 60, 76, 89, 108, 114, 133, 140, 159, 165, 168, 219, 273, 325 230
(1600)
GCPQT04 Grooved Reducing Tee 89×76, 108×76, 108×89, 114×76, 114×89, 140×76, 140×89, 230
140×114, 159×76, 159×89, 159×108, 159×114, 159×140, (1600)
165×76, 165×89, 165×108, 165×114, 165×133, 165×140
GCPQT08 Flange Adaptor 60, 76, 89, 108, 114, 133, 140, 159, 165, 219 230
(1600)
GCPQT06 Cap 60, 76, 89, 108, 114, 133, 140, 159, 165, 219, 273, 325 230
(1600)
GCPQT05 Cross 60, 76, 89, 108, 114, 140, 159, 165, 219, 273, 325 230
(1600)
GCPQT07s Reducer, Threaded 60×1’’, 60×11⁄4’’, 60×11⁄2’’, 76×1’’, 76×1 1⁄4’’, 76×11⁄2’’, 89×1’’, 230
89×11⁄4’’, 89×1 1⁄2’’, 89×2’’, 108×1’’, 108×11⁄4’’, 108×1 1⁄2’’, (1600)
108×2’’, 114×1’’, 114×11⁄4’’, 114×1 1⁄2’’, 114×2’’, 133×1’’,
133×11⁄4’’, 133×1 1⁄2’’, 133×2’’, 140×1’’, 140×11⁄4’’, 140×1 1⁄2’’,
140×2’’, 159×1’’, 159×11⁄4’’, 159×1 1⁄2’’, 159×2’’, 165×1’’,
165×11⁄4’’, 165×1 1⁄2’’, 165×2’’, 219×1’’, 219×11⁄4’’, 219×1 1⁄2’’,
219×2’’
GCPQT07 Reducer, Grooved 76×60, 89×60, 89×76, 108×76, 108×89, 114×76, 114×89, 230
133×76, 133×89, 133×108, 133×114, 140×76, (1600)
140×89,140×114, 159×76, 159×89, 159×108, 159×114,
159×133,165×76, 165×89, 165×108, 165×114,
165×140,219×76, 219×89, 219×108, 219×114,219×140,
219×159, 219×165, 273×108, 273×114, 273×159, 273×165,
273×219, 325×114, 325×140, 325×165,325×219, 325×273
These assemblies are used to simplify the installation of water based sprinkler systems by pre-installing the outlet
connections to the run pipe. These pipes are used as risers and branch lines in a sprinkler system. Installation shall
be according to applicable sprinkler system fabrication rules. These rules limit sprinkler system piping to a minimum
of 1 inch nominal. Outlets less than 1 inch nominal, are for installation of sprinkler heads, pressure gauges, or valve
connections, and for other peripheral service. Outlets 1 inch and larger may be used for joining multiple sprinkler pipe
assemblies, valves, or grooved end pipe fittings using FM Approved grooved end couplings.
Unless otherwise noted in the listing, the sprinkler pipe assemblies have a rated working pressure of 175 psi
(1205 kPa), and shall be installed aboveground, in installations with maximum ambient temperatures below 225°F
(107°C).
Tubasys S.L., Polı́gono Industrial de Carballo, Vial C, Parcelas G4 y G5, 15105 Carballo – La Coruña, Spain
Nominal Run Pipe Outlet Nominal Outlet Rated Working Pressure, Remarks
Size, in. Connection Size, in. psi (kPa)
FM Approvals
September 2007 — Approval Guide
1-410 Automatic Sprinkler Systems
Nominal Run Pipe Outlet Nominal Outlet Rated Working Pressure, Remarks
Size, in. Connection Size, in. psi (kPa)
STEEL PIPE
This pipe is FM Approved for use in automatic sprinkler systems. Unless otherwise noted in individual listings,
pressure rating is 175 psi (1205 kPa) and use is limited to wet-pipe systems.
In addition to certain specific FM Approvals requirements, Approval is based upon conformance to American
Society for Testing and Materials (ASTM) Standards. ASTM A-53 and A-135 are used for Schedule 40 pipe (and
Schedule 30 in larger sizes) and ASTM A-135 for Schedule 10 (0.188 in. (5 mm) wall pipe in larger sizes). Pipe
meeting ASTM A-795 is also approvable.
Generally, joining by threading or cut-grooving is limited to pipe of the ‘‘standard-weight’’ Schedules, 30 or 40.
Schedule 10 pipe is usually joined by roll-grooving. ‘‘Lightwall’’ pipe is non-threadable, is close to Schedule 5 in size,
but is non-standard in wall thickness. ‘‘Thinwall’’ pipe is threadable, is close to Schedule 10 in size, but is also
non-standard in wall thickness. The life expectancy of steel piping products varies widely depending on
characteristics such as the water conditions and pipe material, as well as wall thickness. Such factors should be
considered when selecting piping products. Approval of any piping product is not confirmation of equivalent field
longevity to any pipe schedule or material identified in this introductory section.
All FM Approved pipe is suitable for joining by welding or FM Approved plain end fittings where so listed. When
welding pipe products, close adherence to recognized welding procedures and the use of welders certified under
these procedures shall be followed. Pipe of other schedules or unusual joint design may be FM Approved if shown
to be of comparable performance to the traditional products. Approval of individual pipe fittings and couplings may
limit them to use with specific schedules of pipe or at specific pressure ratings. Use caution to ensure that a given
pipe fitting or coupling is FM Approved for use on a given schedule of pipe and that the rated working pressures are
compatible. In all cases, the installation instructions of both the pipe manufacturer and the pipe fitting or coupling
manufacturer should be observed.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-411
Pressure ratings of completed sprinkler systems are determined by the lowest pressure rated component in the
system.
Rated Working
Product Nominal Pipe
Manufacturer Pressure, Remarks
Description Size, in.
psi (kPa)
Remarks:
a. FM Approved for use with FM Approved pipe couplings on rolled or cut grooves.
b. FM Approved for use with FM Approved pipe fittings when threaded.
c. FM Approved for use in welded systems when supplied with standard bevel on ends.
Rated Working
Product Nominal Pipe
Manufacturer Pressure, Remarks
Description Size, in.
psi (kPa)
Mittal Canada
5870 Rue Saint Patrick 175
Schedule 40 1, 11⁄4, 11⁄2, 2 a, b, c, d, g
Montreal H4E 1B3 (1205)
Canada
Mittal Canada
5870 Rue Saint Patrick 1, 11⁄4, 11⁄2, 300
Schedule 40 a, b, c, d
Montreal H4E 1B3 2, 21⁄2, 3, 4 (2070)
Canada
FM Approvals
September 2007 — Approval Guide
1-412 Automatic Sprinkler Systems
Rated Working
Product Nominal Pipe
Manufacturer Pressure, Remarks
Description Size, in.
psi (kPa)
Tex-Tube Co
1503 North Post Oak Rd 300
Schedule 40 3, 4, 6, 8 a, b, c
(2070)
Houston TX 77255-5710
Wheatland Tube Co
1 Council Ave 3⁄4, 175
Schedule 40 1, 11⁄4, 11⁄2, 2 a, b, c, d, g
(1205)
Wheatland PA 16161
Youngstown Tube Co
401 Andrews Ave 175
Schedule 40 1, 11⁄4, 11⁄2, 2 a, b, c, g
(1205)
Youngstown OH 44505
Youngstown Tube Co
401 Andrews Ave 300
Schedule 40 1, 11⁄4, 11⁄2, 2 a, b, c
(2070)
Youngstown OH 44505
Remarks:
a. FM Approved for use with FM Approved pipe couplings on rolled or cut grooves.
b. FM Approved for use with FM Approved pipe fittings when threaded.
c. FM Approved for use in welded systems when supplied with standard bevel on ends.
d. When hot dip galvanized by factory, the sprinkler pipe is FM Approved for dry pipe systems.
g. FM Approved for use with plain-end fittings.
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-413
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Mittal Canada
5870 Rue Saint Patrick 175
Schedule 10 11⁄4, 11⁄2, 2 a, c, d, g
Montreal H4E 1B3 (1205)
Canada
Mittal Canada
5870 Rue Saint Patrick 11⁄4, 11⁄2, 2, 300
Schedule 10 a, c, d
Montreal H4E 1B3 21⁄2, 3, 4, 6 (2070)
Canada
Northwest Pipe Co
8154 Industrial Park Lane 300
Schedule 10 3, 4, 6, 8 a, c
Box 610 (2070)
Atchison KS 66002
Tex-Tube Co
1503 North Post Oak Rd 300
Schedule 10 21⁄2, 3, 4, 6, 8 a, c
(2070)
Houston TX 77255-5710
FM Approvals
September 2007 — Approval Guide
1-414 Automatic Sprinkler Systems
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Remarks:
Thinwall Pipe — Non-schedule — Normal connections are threaded, welded, rolled groove
or plain end
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-415
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Wheatland Tube Co
1 Council Ave 175
‘‘WLS’’ 1, 11⁄4, 11⁄2, 2 a, c, d, e, g
(1205)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 300
‘‘WLS’’ 1, 11⁄4, 11⁄2, 2 a, c, d, e
(2070)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 175
‘‘Mega-Thread’’ 1, 11⁄4, 11⁄2, 2 a, c, e, g
(1205)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 300
‘‘Mega-Thread’’ 1, 11⁄4, 11⁄2, 2 a, c, e
(2070)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 175
‘‘MLT’’ 1, 11⁄4, 11⁄2, 2 a, c, e, g
(1205)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 300
‘‘MLT’’ 1, 11⁄4, 11⁄2, 2 a, c, e
(2070)
Wheatland PA 16161
FM Approvals
September 2007 — Approval Guide
1-416 Automatic Sprinkler Systems
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Wheatland Tube Co
1 Council Ave 175
‘‘GL’’ 1, 11⁄4, 11⁄2, 2 a, c, e, g
(1205)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 300
‘‘GL’’ 1, 11⁄4, 11⁄2, 2 a, c, e
(2070)
Wheatland PA 16161
Youngstown Tube Co
401 Andrews Ave 175
‘‘EZ-Thread’’ 1, 11⁄4, 11⁄2, 2 a, c, e, g
(1205)
Youngstown OH 44505
Youngstown Tube Co
401 Andrews Ave 300
‘‘EZ-Thread’’ 1, 11⁄4, 11⁄2, 2 a, c, e
(2070)
Youngstown OH 44505
Remarks:
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-417
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Northwest Pipe Co
8154 Industrial Park Lane 300
‘‘EZ-Flow’’ 3, 4, 6 a, c, h
Box 610 (2070)
Atchison KS 66002
Tex-Tube Co
1503 North Post Oak Rd 300
‘‘Tex-Flow’’ 21⁄2, 3, 4, 6 a, c, h
(2070)
Houston TX 77255-5710
Wheatland Tube Co
1 Council Ave 175
‘‘Mega-Flow’’ 11⁄4, 11⁄2, 2 a, c, g, h
(1205)
Wheatland PA 16161
Wheatland Tube Co
1 Council Ave 11⁄4, 11⁄2, 2, 300
‘‘Mega-Flow’’ a, c, h
21⁄2, 3, 4, 6 (2070)
Wheatland PA 16161
FM Approvals
September 2007 — Approval Guide
1-418 Automatic Sprinkler Systems
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Remarks:
Rated Working
Product Nominal Pipe
Manufacturer Pressure, psi Remarks
Description Size, in.
(kPa)
Remarks:
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-419
j. 3⁄4 in. (20 mm) nominal size limited to use in valve trim.
k. FM Approved for use in dry sprinkler systems.
l. FM Approved for use when joined by FM Approved ‘‘Press-Fit’’ Couplings.
Plastic pipe and fittings are FM Approved for aboveground wet pipe fire protection systems for Light Hazard
Occupancy sprinkler systems only. Except where noted otherwise, all pipe and fittings must be completely separated
by nonremovable, fire resistant barriers from any area protected by the system. A nonremovable barrier cannot be
removed without substantial cosmetic damage. A fire-resistant barrier has a minimum finish fire rating of 15 minutes
when tested per ASTM E 119. Except for minimal exposure at a sprinkler connection, the intent is that the sprinkler
system will not be exposed to a fire environment. Rated working pressure is 175 psi (1205 kPa) at 120°F (49°C).
Manufacturer’s installation instructions must be strictly followed to ensure proper performance. The use of these
pipes and fittings is prohibited in areas where seismic protection is required.
Aleum Co Ltd, Champs-Elysee Center, A1413, 889-5, Daechi-Dong, Kangnam-Ku, Seoul, Korea 135-712
BLAZEMASTER. SDR 13.5 CPVC pipe and Schedule 40 and 80 fittings, joined by solvent cement method using FS-5 or equivalent
one-part CPVC primer and cement. For joints using threaded fittings (plastic to plastic, plastic to metal) Teflon tape is recommended to obtain
a good seal. Pressure ratings are 175 psi (1205 kPa) at 73°F (23°C) and 175 psi (1205 kPa) at 150°F (66°C).
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
Product Nominal
Description Pipe Size, in.
(Slip × FNPT)
(Slip × FNPT)
STR Sprinklerhead Adapter 3⁄4 × 1⁄2
1 × 1⁄2
(External Slip × FNPT)
Flange, Slip 3⁄4 through 2
FM Approvals
September 2007 — Approval Guide
1-420 Automatic Sprinkler Systems
Product Nominal
Description Pipe Size, in.
1 × 3⁄4 × 1;
1 × 3⁄4 × 3⁄4;
1 × 1 × 3⁄ 4;
11⁄4 × 11⁄4 × 3⁄4, 1, 11⁄2;
1 ⁄2 × 11⁄2 × 3⁄4, 1, 11⁄4, 2;
1
Durman Esquivel S.A., Camino La palma Estacion El Ahorcado Km 1.5, El Ahorcado, Pedro Escobedo,
Qro. C.p. 76700 Mexico
BLAZEMASTER CPVC SDR 13.5 CPVC Pipe. Joined by solvent cement method using BM-5 or TFP-500 One Step CPVC cement.
Pressure ratings 175 psi (1205 kPa) at 150°F (66°C). FM Approval limited to use with appropriate Approved BlazeMaster solvent cement type
fittings.
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
Product Nominal
Description Pipe Size, in.
Product Nominal
Designation Description Pipe Size, in.
PT07 Tee 3⁄ 4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-421
Product Nominal
Designation Description Pipe Size, in.
PL10 ’’ 1
PL12 ’’ 11⁄4
PL15 ’’ 11⁄2
PL20 ’’ 2
PSL0705 90° Sprinkler Head Elbow 3⁄4 × 1⁄2
(Soc × Soc)
PFL10 ’’ 1
PFL12 ’’ 11⁄4
PFL15 ’’ 11⁄2
PFL20 ’’ 2
PK07 Coupling 3⁄ 4
(Soc × Soc)
PK10 ’’ 1
PK12 ’’ 11⁄4
PK15 ’’ 11⁄2
PK20 ’’ 2
PRK1007 Reducing Coupling 1 × 3⁄ 4
(Soc × Soc)
PRK1210 ’’ 11⁄4 × 1
PRK1510 ’’ 11⁄2 × 1
PRK1512 ’’ 11⁄2 × 11⁄4
PRK2015 ’’ 2 × 11⁄2
PB1007 Flush Reducer Bushing 1 × 3⁄ 4
(Slip × Soc)
PB1207 ’’ 11⁄4 × 3⁄4
PB1210 ’’ 11⁄4 × 1
PB1507 ’’ 11⁄2 × 3⁄4
PB1510 ’’ 11⁄2 × 1
PB1512 ’’ 11⁄2 × 11⁄4
PB2007 ’’ 2 × 3⁄ 4
PB2010 ’’ 2×1
PB2012 ’’ 2 × 11⁄4
PB2015 ’’ 2 × 11⁄2
PGA12 Grooved Coupling Adapter 11⁄4 × 1.660
(Soc × Pipe OD)
PGA15 ’’ 11⁄2 × 1.900
PGA20 ’’ 2 × 2.375
PFA07 Female Adapter 3⁄4 × 3⁄4
FM Approvals
September 2007 — Approval Guide
1-422 Automatic Sprinkler Systems
Product Nominal
Designation Description Pipe Size, in.
PSFA1005 ’’ 1 × 1⁄ 2
PSFA1007 ’’ 1 × 3⁄ 4
PSHA0705 Spigot Sprinkler Head Adapter 3⁄4 × 1⁄2
PC10 ’’ 1
PC12 ’’ 11⁄4
PC15 ’’ 11⁄2
PC20 ’’ 2
Soc = Solvent Weld Socket
Spig = Spigot End
Fipt = Female Iron Pipe Thread
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
Product Nominal
Description Pipe Size, in.
IPEX Inc, 3 Place du Commerce, Suite 101, Ile-des-Soeurs Verdun, Quebec H3E 1H7, Canada
BLAZEMASTER CPVC SDR 13.5 pipe and Schedule 80 fittings, joined by solvent cement using BM-5 One Step CPVC solvent cement.
For joints using threaded fittings (plastic to plastic, metal to plastic) Teflon tape is recommended. Pressure rating is 175 psi (1205 kPa) at
150°F (66°C).
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
13404 ’’ 1
13406 ’’ 11⁄4
13415 ’’ 11⁄2
13411 ’’ 2
13416 ’’ 21⁄2
13417 ’’ 3
48473 ’’ 1 × 1⁄ 2
48474 ’’ 1 × 3⁄ 4
Sprinkler Head Adapter
48030 with Stl. Stl. Reinforced plastic threads 3⁄ 4 × 1⁄ 2
(Spig × Fipt)
Sprinkler Head Adapter
48024 with Stl. Stl. Reinforced plastic threads 1×1
(Soc × Fipt)
Sprinkler Head Adapter
48527 with Stl. Stl. Reinforced plastic threads 1 × 1⁄ 2
(Soc × Fipt)
Sprinkler Head Adapter
48026 with Stl. Stl. Reinforced plastic threads 3⁄ 4 × 1⁄ 2
(Soc × Fipt)
Spigot Sprinkler Head Adapter
48475 with brass thread insert 3⁄ 4 × 1⁄ 2
(Soc × Fipt)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-423
48476 ’’ 1 × 1⁄ 2
Sprinkler Head Tee
48477 with brass thread insert 3⁄ 4 × 3⁄4 × 1⁄2
(Soc × Soc × Fipt)
Sprinkler Head Adapter Tee
48012 with Stl. Stl. Reinforced plastic threads 1 × 1 × 1⁄2
(Soc × Soc Fipt)
Sprinkler Head Adapter Tee
48010 with Stl. Stl. Reinforced plastic threads 3⁄ 4 × 3⁄4 × 1⁄2
(Soc × Soc Fipt)
48478 ’’ 1 × 1 × 1⁄2
48484 ’’ 2 × 2 × 1⁄2
48495 ’’ 1 × 1 × 3⁄4
48497 ’’ 1 × 3⁄ 4 × 3⁄ 4
48498 ’’ 1 × 3⁄ 4 × 1
48506 ’’ 1 1⁄ 4 × 1 × 1
48513 ’’ 2 × 2 × 3⁄4
48514 ’’ 2×2×1
48515 ’’ 2 × 2 × 11⁄2
48517 ’’ 3×3×2
48518 ’’ 3 × 3 × 21⁄2
48428 ’’ 1 × 1⁄ 2
Female Adapter
48438 with brass thread insert 3⁄ 4
(Soc × Fipt)
48439 ’’ 1
48440 ’’ 11⁄4
FM Approvals
September 2007 — Approval Guide
1-424 Automatic Sprinkler Systems
48441 ’’ 11⁄2
48442 ’’ 2
48415 ’’ 1
48416 ’’ 11⁄4
48417 ’’ 11⁄2
48418 ’’ 2
48419 ’’ 21⁄2
48487 ’’ 1
48488 ’’ 11⁄4
48489 ’’ 11⁄2
48490 ’’ 2
48491 ’’ 21⁄2
48492 ’’ 3
48421 ’’ 1
48422 ’’ 11⁄4
48423 ’’ 11⁄2
48424 ’’ 2
48425 ’’ 21⁄2
48426 ’’ 3
48432 ’’ 1
48433 ’’ 11⁄4
48434 ’’ 11⁄2
48435 ’’ 2
48436 ’’ 21⁄2
48437 ’’ 3
48408 ’’ 1
48409 ’’ 11⁄4
48410 ’’ 11⁄2
48411 ’’ 2
48412 ’’ 21⁄2
48413 ’’ 3
48540 ’’ 11⁄2
48541 ’’ 2
48542 ’’ 21⁄2
48461 ’’ 11⁄4 × 1
48462 ’’ 1 1⁄ 2 × 3⁄ 4
48463 ’’ 11⁄2 × 1
48466 ’’ 2×1
48467 ’’ 2 × 11⁄4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-425
48468 ’’ 2 × 11⁄2
48469 ’’ 21⁄2 × 2
48470 ’’ 3×2
48471 ’’ 3 × 21⁄2
48401 ’’ 1
48402 ’’ 11⁄4
48403 ’’ 11⁄2
48404 ’’ 2
48405 ’’ 21⁄2
48406 ’’ 3
48444 ’’ 1
48445 ’’ 11⁄4
48446 ’’ 11⁄2
48447 ’’ 2
48448 ’’ 21⁄2
48449 ’’ 3
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
Equal Tee 3⁄ 4
5011
(Soc × Soc × Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
Reducing Tee 3⁄ 4
5011-R × 3⁄ 4 × 1
(Soc × Soc × Soc)
’’ 1 × 3⁄4 × 3⁄4
’’ 1 × 3⁄ 4 × 1
FM Approvals
September 2007 — Approval Guide
1-426 Automatic Sprinkler Systems
’’ 1 × 1 × 3⁄ 4
’’ 11⁄4 × 1 × 3⁄4
’’ 11⁄4 x 1 x 1
’’ 11⁄4 x 1 x 11⁄4
’’ 11⁄4 × 11⁄4 × 1
’’ 11⁄2 x 11⁄4 x 1
’’ 11⁄2 × 11⁄2 × 1
’’ 11⁄2 x 11⁄2 x 2
’’ 2 × 2 × 3⁄ 4
’’ 2×2×1
’’ 2 × 2 × 11⁄2
’’ 3×3×2
90° Elbow 3⁄ 4
5007
(Soc × Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
’’ 3
’’ 1 × 3⁄ 4
45° Elbow 3⁄ 4
5006
(Soc × Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
’’ 3
Coupling 3⁄ 4
5001
(Soc × Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
’’ 3
Reducing Coupling
5001-R 1 × 3⁄ 4
(Soc × Soc)
11⁄4 x 1
’’
11⁄2 × 3⁄4
’’ 11⁄2 × 1
’’ 11⁄2 × 11⁄4
’’ 2×1
’’ 2 × 11⁄2
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-427
Cap 3⁄ 4
5017
(Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
’’ 3
Reducing Bushing
5018 1 × 3⁄ 4
(Soc × Soc)
’’ 11⁄4 × 3⁄4
’’ 11⁄4 × 1
’’ 11⁄2 × 3⁄4
’’ 11⁄2 × 1
’’ 11⁄2 × 11⁄4
’’ 2 × 3⁄ 4
’’ 2×1
’’ 2 × 11⁄4
’’ 2 × 11⁄2
’’ 21⁄2 × 11⁄4
’’ 21⁄2 × 11⁄2
’’ 21⁄2 × 2
’’ 3×2
’’ 3 × 21⁄2
Cross 3⁄ 4
5035
(Soc × Soc × Soc × Soc)
’’ 1
’’ 11⁄4
’’ 1 × 3⁄4 × 1 × 3⁄4
Flange 3⁄ 4
5051-H
(Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
’’ 3
Blind Flange 3⁄ 4
5019-H
(Soc)
’’ 1
’’ 11⁄4
’’ 11⁄2
’’ 2
’’ 21⁄2
’’ 3
Female Adapter 1
5003-BI with brass thread insert 1 1⁄ 4
(Soc × Fipt) 11⁄2
2
FM Approvals
September 2007 — Approval Guide
1-428 Automatic Sprinkler Systems
Female Adapter 3⁄ 4
5003-2-BI with brass thread insert
1
(Spig × Fipt)
3⁄ 4
Male Adapter 1
5004-BI with brass thread insert 1 1⁄ 4
(Soc × Mipt) 11⁄2
2
Female Sprinkler Head Adapter 3⁄4x 1⁄ 2
5004-2-S-BI with brass thread insert
1 x 1⁄ 2
(Spig x Fipt)
Sprinkler Head Tee 3⁄ 4
× 3⁄4 × 1⁄2
5012-S-BI with brass thread insert 1 × 3⁄4 × 1⁄2
(Soc × Soc × Fipt) 1 × 1 × 1⁄ 2
’’ 1×1×1
’’ 1 × 1⁄ 2 × 1
’’ 1 1⁄ 4
x 11⁄4 x 1⁄2
’’ 11⁄2 x 11⁄2 x 1⁄2
’’ 2 x 2 x 1⁄ 2
Female Sprinkler Head Reducing 11⁄4 x 1 x 1⁄2
5012R-S-BI Tee with brass thread insert 11⁄2 x 11⁄4 x 1⁄2
(Soc x Soc x Fipt) 2 x 11⁄2 x 1⁄2
3⁄ 4
× 1⁄ 2
90° Sprinkler Head Elbow 1 × 1⁄ 2
5007-3-S-BI with brass thread insert 1 × 3⁄ 4
(Soc × Fipt) 1 1⁄ 4 x 1⁄ 2
Approved for exposed use when all of the following criteria are met:
1. Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
2. Sprinklers must have quick response thermal sensing elements.
3. Sprinkler systems must be wet pipe type.
4201-007 3⁄ 4
4201-010 1
4201-012 1 1⁄ 4
Equal Tee
4201-015 11⁄2
(Soc × Soc × Soc)
4201-020 2
4201-025 2 1⁄ 2
4201-030 3
4201-102 3⁄ 4
× 3⁄ 4 × 1
4201-125 1 × 3⁄ 4 × 3⁄ 4
4201-126 1 × 3⁄ 4 × 1
4201-131 1 × 1 × 3⁄4
4201-157 11⁄4 × 1 × 3⁄4
4201-158 11⁄4 × 1 × 1
4201-159 11⁄4 × 1 × 11⁄4
4201-167 11⁄4 × 11⁄4 × 3⁄4
4201-168 11⁄4 × 11⁄4 × 1
4201-169 11⁄4 × 11⁄4 × 11⁄2
4201-201 11⁄2 × 11⁄4 × 3⁄4
4201-202 Reducing Tee 11⁄2 × 11⁄4 × 1
4201-210 (Soc × Soc × Soc) 11⁄2 × 11⁄2 × 3⁄4
4201-211 11⁄2 × 11⁄2 × 1
4201-212 11⁄2 × 11⁄2 × 11⁄4
4201-213 11⁄2 × 11⁄2 × 2
4201-248 2 × 2 × 3⁄4
4201-249 2×2×1
4201-251 2 × 2 × 11⁄2
4201-289 2 ⁄2 × 21⁄2 × 1
1
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-429
4220-007 3⁄ 4
4220-010 1
4220-012 1 1⁄ 4
Equal Cross
4220-015 11⁄2
(All Socket)
4220-020 2
4220-025 2 1⁄ 2
4220-030 3
Reducing Cross
4220-131 1 × 1 × 3⁄4 × 3⁄4
(All Socket)
4206-007 3⁄ 4
4206-010 1
4206-012 1 1⁄ 4
90°Elbow
4206-015 11⁄2
(All Socket)
4206-020 2
4206-025 2 1⁄ 2
4206-030 3
4207-101 3⁄ 4
× 1⁄ 2
4207-130 Sprinkler Head 90°Elbow 1 × 1⁄ 2
4207-131 (Socket×Brass FIPT) 1 × 3⁄ 4
4207-166 11⁄4 × 1⁄2
4207-101SR 3⁄ 4
× 1⁄ 2
4207-130SR Sprinkler Head 90°Elbow 1 × 1⁄ 2
4207-131SR (Socket×SR FIPT) 1 × 3⁄ 4
4207-166SR 11⁄4 × 1⁄2
4217-007 3⁄ 4
4217-010 1
4217-012 1 1⁄ 4
45°Elbow
4217-015 11⁄2
(All Socket)
4217-020 2
4217-025 2 1⁄ 2
4217-030 3
4229-007 3⁄ 4
4229-010 1
4229-012 1 1⁄ 4
Coupling
4229-015 11⁄2
(Soc × Soc)
4229-020 2
4229-025 2 1⁄ 2
4229-030 3
4229-131 1 × 3⁄ 4
4229-167 11⁄4 × 3⁄4
4229-168 11⁄4 × 1
4229-210 1 1⁄ 2 × 3⁄ 4
4229-211 11⁄2 × 1
4229-212 Reducer Coupling 11⁄2 × 11⁄4
4229-248 (Soc×Soc) 2 × 3⁄ 4
4229-249 2×1
4229-250 2 × 11⁄4
4229-251 2 × 11⁄2
4229-291 21⁄2 × 11⁄2
4229-292 21⁄2 × 2
FM Approvals
September 2007 — Approval Guide
1-430 Automatic Sprinkler Systems
4237-131 1 × 3⁄ 4
4237-167 11⁄4 × 3⁄4
4237-168 11⁄4 × 1
4237-210 1 1⁄ 2 × 3⁄ 4
4237-211 11⁄2 × 1
4237-212 11⁄2 × 11⁄4
4237-248 2 × 3⁄ 4
Reducer Bushing
4237-249 2×1
(Spig × Soc)
4237-250 2 × 11⁄4
4237-251 2 × 11⁄2
4237-290 21⁄2 × 11⁄4
4237-291 21⁄2 × 11⁄2
4237-292 21⁄2 × 2
4237-338 3×2
4237-339 3 × 21⁄2
4233-012 11⁄4
Grooved Coupling Adapter
4233-015 11⁄2
(Grv × Soc)
4233-020 2
4235-007 3⁄ 4
4235-010 1
Female Adapters
4235-012 1 1⁄ 4
(Soc × brass FIPT)
4235-015 11⁄2
4235-020 2
4235-007SR 3⁄ 4
Female Adapters
4235-010SR 1
(Soc × SR FIPT)
4235-012SR 1 1⁄ 4
4247-007 3⁄ 4
4247-010 1
4247-012 1 1⁄ 4
4247-015 Cap (Soc) 11⁄2
4247-020 2
4247-025 2 1⁄ 2
4247-030 3
4251-007 3⁄ 4
4251-010 1
4251-012 1 1⁄ 4
4 Bolt Flange,
4251-015 11⁄2
ANSI 150 (Soc)
4251-020 2
4251-025 2 1⁄ 2
4254-030 3
4256-007 3⁄ 4
4256-010 1
4256-012 1 1⁄ 4
4 Bolt Flange, ANSI 150
4256-015 11⁄2
(Spig, Van Stone)
4256-020 2
4256-025 2 1⁄ 2
4256-030 3
4253-007 3⁄ 4
4253-010 1
4253-012 1 1⁄ 4
4 Bolt Blind Flange,
4253-015 11⁄2
ANSI 150
4253-020 2
4253-025 2 1⁄ 2
4253-030 3
4257-007 3⁄ 4
4257-010 1
Union
4257-012 1 1⁄ 4
(Soc×Soc)
4257-015 11⁄2
4257-020 2
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-431
4259-007BR 3⁄ 4
4259-010BR 1
Union
4259-012BR 1 1⁄ 4
(Soc×Brass FIPT)
4259-015BR 11⁄2
4259-020BR 2
Adapter, Sprinkler Head,
L4235-130 Long Body 1×1⁄2
(Soc×Brass FIPT)
Adapter, Sprinkler Head with
R4235-101 Positioning Ring 3⁄4×1⁄2
(Soc×Brass FIPT)
4235-101 3⁄4×1⁄2
Adapter, Sprinkler Head
4235-130 1×1⁄2
(Soc×Brass FIPT)
4235-131 1×3⁄4
4235-101SR 3⁄4×1⁄2
4235-130SR 1×1⁄2
Adapter, Sprinkler Head 3⁄4×1⁄2
Z4235-101SR
(Soc×SR FIPT)
Z4235-130SR 1×1⁄2
4235-131SR 1×3⁄4
4238-101SR Adapter, Sprinkler Head 3⁄4×1⁄2
4221-101SR 3⁄4×1⁄2
Sprinkler Head Cross
4221-130SR 1×1⁄2
(Soc×SR FIPT)
4221-131SR 1×3⁄4
4244-007 3⁄ 4
4244-010 1
Street Tee
4244-012 1 1⁄ 4
(Spig × Soc × Soc)
4244-015 11⁄2
4244-020 2
4209-007 3⁄ 4
4209-010 1
90° Street Elbow
4209-012 1 1⁄ 4
(Spig × Soc)
4209-015 11⁄2
4209-020 2
Tyco Fire and Building Products, 451 N Cannon Ave, Lansdale PA 19446
BLAZEMASTER. SDR 13.5 CPVC pipe and schedule 40 and 80 fittings, joined by solvent cement method using TFP-400 cement or
TFP-500 cement. For joints using threaded fittings (plastic to plastic, plastic to metal) Teflon tape is recommended to obtain a good seal.
Pressure rating of pipe and fittings is 175 psi (1205 kPa) at 150°F (66°C).
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
Pipe 3⁄ 4 through 3
3⁄4
× 1⁄ 2
STR Sprinklerhead Adapter 1 × 1⁄ 2
Both Schedule 40 and 80 1 × 3⁄ 4
(Slip × FNPT)
Elbow Sprinklerhead Adapter 3⁄ 4 × 1⁄2; 3⁄4 × 3⁄4; 1 × 3⁄4; 1 × 1
Schedule 40 (Slip × FNPT)
FM Approvals
September 2007 — Approval Guide
1-432 Automatic Sprinkler Systems
90° Elbow
Transition Coupling
11⁄4, 11⁄2, 2
(Slip × Cut Groove)
Sprinkler Head Adapter Tee 1 × 1 × 1, 11⁄2 × 11⁄2 × 1⁄2 NPT
Slip × 2 NPT
Female Adapter Assembly, Str. 2 Slip × 21⁄2 NPT
3 Slip × 3 NPT
(35⁄8) Dual Outlet Tee 1 by 1⁄2 (slip by NPT)
Approved for exposed use when all of the following criteria are met:
• Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
• Sprinklers must have quick response thermal sensing elements.
• Sprinkler systems must be wet pipe type.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-433
3⁄ 4
× 3⁄4 × 1⁄2
1 × 3⁄4 × 1⁄2
1 × 1 × 1⁄ 2
1×1×1
Sprinkler Head Tee 11⁄4 × 1 × 1⁄2
823
(Soc × Soc × SR FIPT) 1 ⁄4 × 11⁄4 × 1⁄2
1
1 × 3⁄4 × 3⁄4
1 × 3⁄ 4 × 1
1 × 1 × 3⁄ 4
11⁄4 × 1 × 3⁄4
11⁄4 × 1 × 1
11⁄4 × 1 × 11⁄4
1 ⁄4 × 11⁄4 × 3⁄4
1
11⁄4 × 11⁄4 × 1
Reducing Tee
825 11⁄4 × 11⁄4 × 11⁄2
(Soc × Soc × Soc)
11⁄2 × 11⁄4 × 3⁄4
11⁄2 × 11⁄4 × 1
11⁄2 × 11⁄2 × 3⁄4
11⁄2 × 11⁄2 × 1
11⁄2 × 11⁄2 × 11⁄4
11⁄2 × 11⁄2 × 2
2 × 2 × 3⁄ 4
2×2×1
2 × 2 × 11⁄2
1 × 3⁄ 4
11⁄4 × 3⁄4
11⁄4 × 1
11⁄2 × 3⁄4
11⁄2 × 1
831 Reducer Coupling (Soc × Soc)
11⁄2 × 11⁄4
2 × 3⁄ 4
2×1
2 × 11⁄4
2 × 1 1⁄ 2
11⁄4
832 Grooved Coupling Adapter (Grv × Soc) 11⁄2
2
3⁄ 4
1
835 Equal Cross (All Socket) 1 1⁄ 4
11⁄2
2
1 × 1
1 1⁄ 4 × 11⁄4
851 Union (Soc × Brass* FIPT) 1
1 ⁄2 × 11⁄2
2 × 2
1 × 3⁄ 4
11⁄4 × 3⁄4
11⁄4 × 1
11⁄2 × 3⁄4
11⁄2 × 1
852 Reducer Bushing (Spig × Soc)
11⁄2 × 11⁄4
2 × 3⁄ 4
2×1
2 × 11⁄4
2 × 1 1⁄ 2
FM Approvals
September 2007 — Approval Guide
1-434 Automatic Sprinkler Systems
Fire Resistant Barriers for Use with CPVC Pipe and Fittings in Light Hazard Occupancies
Fire resistant barriers FM Approved for use with CPVC pipe and fittings in Light Hazard Occupancies may be used
in place of a fire-resistant barrier with a minimum finish fire rating when tested per ASTM E119 as described under
‘‘Plastic Pipe and Fittings’’. These barriers are designed such that once assembled the barrier cannot be removed
with ordinary tools.
Soffi-Steel System Tyco Fire Products BlazeMaster CPVC Pipe and Fittings
Fire Resistant Barriers IPEX Inc., BlazeMaster CPVC Pipe anf Fittings
20 Gauge Harvel BlazeMaster CPVC Pipe
FM Approved to 10 feet (3.1 m) Spears Manufacturing Flameguard CPVC Fittings
Ceiling Height NIBCO Inc., BlazeMaster CPVC Fittings
Victaulic Company FireLock CPVC Pipe and Fittings
Above pipe and fittings Approved with the following Joint
Cements: TFP-500, BM-5, FS-5
Pipe, Fittings and Pipe Joints for Underground Fire Service Mains
Underground fire service mains are made from many different materials. Cast iron, ductile iron, stainless steel
pipe, Polyvinyl Chloride (PVC), Polyethylene (PE), and Fiber Reinforced Composite (FRP of Fiberglass) pipe and
fittings are acceptable when they are FM Approved.
Installation of these products should conform to FM Global Property Loss Prevention Data Sheets.
In-Building Risers
Designed to connect the underground fire service main to the building overhead sprinkler system. The fitting will
typically pass under the building foundation and extend up through the floor.
Ductile iron pipe and fittings should be installed and anchored according to the manufacturer’s instructions and
FM Global Property Loss Prevention Data Sheets. For underground use only.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-435
Ductile iron restraint gland for ductile iron pipe. Used to secure spigot ends of ductile iron pipe into standardized mechanical joint-ended
pipe, fittings or other components.
Rated Working
Product Nominal Pipe Pressure, psi
Description Size, in. (kPa)
FM Approvals
September 2007 — Approval Guide
1-436 Automatic Sprinkler Systems
ADMB622 6 350
(2415)
ADMB822 8 350
(2415)
ADMB1022 10 350
(2415)
ADMB1222 12 300
(2070)
ADMB1422 14 300
(2070)
ADMB1622 16 300
(2070)
ADMB311 111⁄4° Elbow 3 350
(2415)
ADMB411 4 350
(2415)
ADMB611 6 350
(2415)
ADMB811 8 350
(2415)
ADMB1011 10 350
(2415)
ADMB1211 12 300
(2070)
ADMB1411 14 300
(2070)
ADMB1611 16 300
(2070)
ADMR43 Reducer 4×3 350
(2415)
ADMR63 6×3 350
(2415)
ADMR64 6×4 350
(2415)
ADMR84 8×4 350
(2415)
ADMR86 8×6 350
(2415)
ADMR104 10 × 4 350
(2415)
ADMR106 10 × 6 350
(2415)
ADMR108 10 × 8 350
(2415)
ADMR124 12 × 4 300
(2070)
ADMR126 12 × 6 300
(2070)
ADMR128 12 × 8 300
(2070)
ADMR1210 12 × 10 300
(2070)
ADMR1410 14 × 10 350
(2415)
ADMR166 16 × 6 250
(1725)
ADMR168 16 × 8 250
(1725)
ADMR1610 16 × 10 350
(2415)
ADMR1612 16 × 12 250
(1725)
ADMR1614 16 × 14 350
(2415)
ADMK3 Solid Cap (M.J.) 3 350
(2415)
ADMK4 4 350
(2415)
ADMK6 6 350
(2415)
ADMK8 8 350
(2415)
ADMK10 10 350
(2415)
ADMK12 12 300
(2070)
ADMK14 14 350
(2415)
ADMK16 16 250
(1725)
ADMP3 Solid Plug (M.J.) 3 350
(2415)
ADMP4 4 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-437
ADMP6 6 350
(2415)
ADMP8 8 350
(2415)
ADMP10 10 350
(2415)
ADMP12 12 300
(2070)
ADMP14 14 350
(2415)
ADMP16 16 250
(1725)
ADTK3 Tapped Cap (M.J.) 3 350
(2415)
ADTK4 4 350
(2415)
ADTK6 6 350
(2415)
ADTK8 8 350
(2415)
ADTK10 10 350
(2415)
ADTK12 12 300
(2070)
ADTK16 16 250
(1725)
ADTP3 Tapped Plug (M.J.) 3 350
(2415)
ADTP4 4 350
(2415)
ADTP6 6 350
(2415)
ADTP8 8 350
(2415)
ADTP10 10 350
(2415)
ADTP12 12 300
(2070)
ADTP16 16 250
(1725)
ADMS3 Short Sleeve (M.J.) 3 350
(2415)
ADMS4 4 350
(2415)
ADMS6 6 350
(2415)
ADMS8 8 350
(2415)
ADMS10 10 350
(2415)
ADMS12 12 300
(2070)
ADMS14 14 350
(2415)
ADMS16 16 250
(1725)
ADML3 Long Sleeve (M.J.) 3 350
(2415)
ADML4 4 350
(2415)
ADML6 6 350
(2415)
ADML8 Long Sleeve (M.J.) 8 350
(2415)
ADML10 10 350
(2415)
ADML12 12 300
(2070)
ADML16 16 250
(1725)
ADG3 M.J. Gland 3 350
(2415)
ADG4 4 350
(2415)
ADG6 6 350
(2415)
ADG8 8 350
(2415)
ADG10 10 350
(2415)
ADG12 12 300
(2070)
ADG16 16 250
FM Approvals
September 2007 — Approval Guide
1-438 Automatic Sprinkler Systems
(1725)
ADMC43 Cross (M.J.) 4×3 350
(2415)
ADMC44 4×4 350
(2415)
ADMC64 6×4 350
(2415)
ADMC66 6×6 350
(2415)
ADMC84 8×4 350
(2415)
ADMC86 8×6 350
(2415)
ADMC88 8×8 350
(2415)
ADMC104 10 × 4 350
(2415)
ADMC106 10 × 6 350
(2415)
ADMC108 10 × 8 350
(2415)
ADMC1010 10 × 10 350
(2415)
ADMC124 12 × 4 300
(2070)
ADMC126 12 × 6 300
(2070)
ADMC128 12 × 8 300
(2070)
ADMC1210 12 × 10 300
(2070)
ADMC1212 12 × 12 300
(2070)
ADMO612 Offset 6 × 12 300
(2070)
ADMO126 12 × 6 300
(2070)
ADMH66 Hydrant Tee 6×6 350
(M.J. × M.J. × Swivel End) (2415)
ADMH86 8×6 350
(2415)
ADMH88 8x8 350
(2415)
ADMH106 10 × 6 350
(2415)
ADMH108 10x8 350
(2415)
ADMH126 12 × 6 300
(2070)
ADMH128 12 × 8 350
(2415)
ADMH146 14 × 6 300
(2070)
ADMH166 16 × 6 250
(1725)
ADMF44 Hydrant Tee 4×4 350
(M.J. × M.J. × Flanged End) (2415)
ADMF64 6x4 350
(2415)
ADMF66 6×6 350
(2415)
ADMF84 8x4 350
(2415)
ADMF86 8×6 350
(2415)
ADMF88 8×8 350
(2415)
ADMF104 10x4 350
(2415)
ADMF106 10 × 6 350
(2415)
ADMF108 10x8 350
(2415)
ADMF1010 10x10 350
(2415)
ADMF124 12x4 350
(2415)
ADMF126 12 × 6 300
(2070)
ADMT33 Hydrant Tee (M.J.) 3×3 350
(2415)
ADMT43 4×3 350
(2415)
ADMT44 4×4 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-439
FM Approvals
September 2007 — Approval Guide
1-440 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-441
APPR168 16 × 8 250
(1725)
APPR1612 16 × 12 250
(1725)
AMFA3 Adapter Flanged 3 350
End × M.J. (2415)
AMFA4 4 350
(2415)
AMFA6 6 350
(2415)
AMFA8 8 350
(2415)
AMFA10 10 350
(2415)
AMFA12 12 300
(2070)
ADTT3 Tapped Tees 3 350
(2415)
ADTT4 4 350
(2415)
ADTT6 6 350
(2415)
ADTT8 8 350
(2415)
ADTT10 10 350
(2415)
ADTT12 12 300
(2070)
ADTT16 16 250
(1725)
ADTC4 Tapped Cross 4 350
(2415)
ADTC6 6 350
(2415)
ADTC8 8 350
(2415)
ADTC10 10 350
(2415)
ADTC12 12 300
(2070)
ADTC16 16 250
(1725)
ADFB390 90° Elbow (Flanged) 3 250
ADFB490 4 (1750)
ADFB690 6
ADFB890 8
ADFB1090 10
ADFB1290 12
ADFB345 45° Elbow (Flanged) 3 250
ADFB445 4 (1750)
ADFB645 6
ADFB845 8
ADFB1045 10
ADFB1245 12
ADFB322 221⁄2° Elbow (Flanged) 3 250
ADFB422 4 (1750)
ADFB622 6
ADFB822 8
ADFB1022 10
ADFB1222 12
ADFB311 111⁄4° Elbow (Flanged) 3 250
ADFB411 4 (1750)
ADFB611 6
ADFB811 8
ADFB1011 10
ADFB1211 12
ADFB32 90° Reducing Elbow (Flanged) 3×2 250
ADFB43 4×3 (1750)
ADFB63 6×3
ADFB64 6×4
ADFB65 6×5
ADFB84 8×4
ADFB85 8×5
ADFB86 8×6
ADFB104 10 × 4
ADFB106 10 × 6
ADFB108 10 × 8
ADFB124 12 × 4
ADFB126 12 × 6
ADFB128 12 × 8
FM Approvals
September 2007 — Approval Guide
1-442 Automatic Sprinkler Systems
ADFB1210 12 × 10
ADFL390 90° Base Elbow (Flanged) 3 250
ADFL490 4 (1750)
ADFL690 6
ADFL890 8
ADFL1090 10
ADFL1290 12
ADFD3 90° Long Radius Elbow (Flanged) 3 250
ADFD4 4 (1750)
ADFD6 6
ADFD8 8
ADFD10 10
ADFD12 12
ADFT33 Equal Tee (Flanged) 3 250
ADFT44 4 (1750)
ADFT55 5
ADFT66 6
ADFT88 8
ADFT1010 10
ADFT1212 12
ADFT32 Reducing Tee (Flanged) 3×2 250
ADFT42 4×2 (1750)
ADFT425 4 × 21⁄2
ADFT43 4×3
ADFT62 6×2
ADFT63 6×3
ADFT64 6×4
ADFT84 8×4
ADFT86 8×6
ADFT104 10 × 4
ADFT106 10 × 6
ADFT108 10 × 8
ADFT124 12 × 4
ADFT126 12 × 6
ADFT128 12 × 8
ADFT1210 12 × 10
ADRT433 Reducing Tee (Flanged) 4×3×3 250
ADRT533 5×3×3 (1750)
ADRT544 5×4×4
ADRT633 6×4×4
ADRT644 6×4×4
ADRT646 6×4×6
ADRT864 8×6×4
ADRT866 8×6×6
ADRT868 8×6×8
ADFC33 Equal Cross (Flanged) 3 250
ADFC44 4 (1750)
ADFC55 5
ADFC66 6
ADFC88 8
ADFC1010 10
ADFC1212 12
ADFC32 Reducing Cross (Flanged) 3×2 250
ADFC42 4×2 (1750)
ADFC425 4 × 21⁄2
ADFC43 4×3
ADFC62 6×2
ADFC63 6×3
ADFC64 6×4
ADFC84 8×4
ADFC86 8×6
ADFC104 10 × 4
ADFC106 10 × 6
ADFC108 10 × 8
ADFC124 12 × 4
ADFC126 12 × 6
ADFC128 12 × 8
ADFC1210 12 × 10
ADFR32 Concentric Reducer (Flanged) 3×2 250
ADFR325 3 × 21⁄2 (1750)
ADFR42 4×2
ADFR425 4 × 21⁄2
ADFR43 4×3
ADFR62 6×2
ADFR625 6 × 21⁄2
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-443
ADFR63 6×3
ADFR64 6×4
ADFR65 6×5
ADFR84 8×4
ADFR85 8×5
ADFR86 8×6
ADFR104 10 × 4
ADFR106 10 × 6
ADFR108 10 × 8
ADFR124 12 × 4
ADFR126 12 × 6
ADFR128 12 × 8
ADFR1210 12 × 10
ADFE32 Eccentric Reducer (Flanged) 3×2 250
ADFE325 3 × 21⁄2 (1750)
ADFE42 4×2
ADFE425 4 × 21⁄2
ADFE43 4×3
ADFE62 6×2
ADFE625 6 × 21⁄2
ADFE63 6×3
ADFE64 6×4
ADFE84 8×4
ADFE85 8×5
ADFE86 8×6
ADFE104 10 × 4
ADFE106 10 × 6
ADFE108 10 × 8
ADFE124 12 × 4
ADFE126 12 × 6
ADFE128 12 × 8
ADFE1210 12 × 10
ADTF3 Blind Flange (tapped) 3 250
ADTF4 4 (1750)
ADTF6 6
ADTF8 8
ADTF10 10
ADTF12 12
ABDF3 Blind Flange (solid) 3 250
ABDF4 4 (1750)
ABDF6 6
ABDF8 8
ABDF10 10
ABDF12 12 250
(1750)
All above products used to join plain-end or mechanical joint or flanged ductile iron pipe to mechanical joint or flanged or plain end devices
as noted or to identical adapters in underground mains.
FM Approvals
September 2007 — Approval Guide
1-444 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-445
FM Approvals
September 2007 — Approval Guide
1-446 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-447
FM Approvals
September 2007 — Approval Guide
1-448 Automatic Sprinkler Systems
AXML6 6 350
(2415)
AXML8 8 350
(2415)
AXML10 10 350
(2415)
AXML12 12 350
(2415)
AXML14 14 350
(2415)
AXML16 16 350
(2415)
AXMK3 Cap 3 350
(2415)
AXMK4 4 350
(2415)
AXMK6 6 350
(2415)
AXMK8 8 350
(2415)
AXMK10 10 350
(2415)
AXMK12 12 350
(2415)
AXMK14 14 350
(2415)
AXMK16 16 350
(2415)
AXTK3 Tapped Cap 3 350
(2415)
AXTK4 4 350
(2415)
AXTK6 6 350
(2415)
AXTK8 8 350
(2415)
AXTK10 10 350
(2415)
AXTK12 12 350
(2415)
AXTK14 14 350
(2415)
AXTK16 16 350
(2415)
AXMP3 Plug 3 350
(2415)
AXMP4 4 350
(2415)
AXMP6 6 350
(2415)
AXMP8 8 350
(2415)
AXMP10 10 350
(2415)
AXMP12 12 350
(2415)
AXMP14 14 350
(2415)
AXMP16 16 350
(2415)
AXTP3 Tapped Plug 3 350
(2415)
AXTP4 4 350
(2415)
AXTP6 6 350
(2415)
AXTP8 8 350
(2415)
AXTP10 10 350
(2415)
AXTP12 12 350
(2415)
AXTP14 14 350
(2415)
AXTP16 16 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-449
ADPB490 4 350
(2415)
ADPB690 6 350
(2415)
ADPB890 8 350
(2415)
ADPB1090 10 350
(2415)
ADPB345 45° Elbow 3 350
(2415)
ADPB445 4 350
(2415)
ADPB645 6 350
(2415)
ADPB845 8 350
(2415)
ADPB1045 10 350
(2415)
ADPB322 221⁄2° Elbow 3 350
(2415)
ADPB422 4 350
(2415)
ADPB622 6 350
(2415)
ADPB822 8 350
(2415)
ADPB1022 10 350
(2415)
ADPB311 111⁄4° Elbow 3 350
(2415)
ADPB411 4 350
(2415)
ADPB611 6 350
(2415)
ADPB811 8 350
(2415)
ADPB1011 10 350
(2415)
ADPF44 Tee (Push-On×Flange) 4×4 350
(2415)
ADPF64 6×4 350
(2415)
ADPF66 6×6 350
(2415)
ADPF86 8×6 350
(2415)
ADPF88 8×8 350
(2415)
ADPF103 10×3 350
(2415)
ADPF106 10×6 350
(2415)
ADPF108 10×8 350
(2415)
ADPF126 12×6 350
(2415)
ADPF128 12×8 350
(2415)
ADPY 44 45° Wye 4 350
(2415)
ADPY 63 6×3 350
(2415)
ADPY 64 6×4 350
(2415)
ADPY 66 6×6 350
(2415)
APFA6 Flange Adapter (Push-On × Flange) 6 350
(2415)
APFA8 8 350
(2415)
APFA10 10 350
(2415)
APFA12 12 350
(2415)
APR84 Reducer (Push-On × Push-On) 8×4 350
(2415)
FM Approvals
September 2007 — Approval Guide
1-450 Automatic Sprinkler Systems
AXPB490 4 350
(2415)
AXPB690 6 350
(2415)
AXPB890 8 350
(2415)
AXPB1090 10 350
(2415)
AXPB1290 12 350
(2415)
AXPB345 45° Elbow 3 350
(2415)
AXPB445 4 350
(2415)
AXPB645 6 350
(2415)
AXPB845 8 350
(2415)
AXPB1045 10 350
(2415)
AXPB1245 12 350
(2415)
AXPB322 221⁄2° Elbow 3 350
(2415)
AXPB422 4 350
(2415)
AXPB622 6 350
(2415)
AXPB822 8 350
(2415)
AXPB1022 10 350
(2415)
AXPB1222 12 350
(2415)
AXPB311 111⁄4° Elbow 3 350
(2415)
AXPB411 4 350
(2415)
AXPB611 6 350
(2415)
AXPB811 8 350
(2415)
AXPB1011 10 350
(2415)
AXPB1211 12 350
(2415)
AXPT44 Tee 4 350
(2415)
AXPT63 6×3 350
(2415)
AXPT64 6×4 350
(2415)
AXPT66 6 350
(2415)
AXPT83 8×3 350
(2415)
AXPT84 8×4 350
(2415)
AXPT86 8×6 350
(2415)
AXPT88 8 350
(2415)
AXPT103 10×3 350
(2415)
AXPT104 10×4 350
(2415)
AXPT106 10×6 350
(2415)
AXPT108 10×8 350
(2415)
AXPT1010 10 350
(2415)
AXPT123 12×3 350
(2415)
AXPT124 12×4 350
(2415)
AXPT126 12×6 350
(2415)
AXPT128 12×8 350
(2415)
AXPT1210 12×10 350
(2415)
AXPT1212 12 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-451
FM Approvals
September 2007 — Approval Guide
1-452 Automatic Sprinkler Systems
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Ductile Iron Grooved Fittings
Product Fitting Nominal Pipe
Designation Description Size, in.
Rated Working Pressure 250 psi (1725 kPa) for 3 thru 12 in. sizes
175 psi (1205 kPa) for 14 and 16 in. sizes
BLS Pipe 80 25
(normal locks or restraining rings) (360)
100 25
(360)
125 25
(360)
150 25
(360)
200 16
(232)
250 16
(232)
300 16
(232)
400 10
(145)
Griffin Pipe Products Co, 10 Adams St, Upper Basin, Lynchburg VA 24505
Pressure rating 350 psi (2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-453
Rated Working
Product Nominal Pipe
Pressure, psi Notes:
Designation Size, in.
(kPa)
Notes:
a. FM Approved with normal lock ring and gripper ring (for field cut joints).
Romac Industries Inc, 21919 20th Ave SE, Suite 100, Bothell WA 98021-4446
Ductile iron restraint gland for ductile iron pipe. Used to secure spigot ends of ductile iron pipe into standardized mechanical joint-ended
pipe fitting or other components.
Rated Working
Product Nominal Pipe Pressure, psi
Description Size, in. (kPa)
Ductile Iron Adapter Flanges used to secure plain-ended DI pipe to flange ended devices in underground mains or at the base of a sprinkler riser.
FlexiJoints are flexible expansion joints. Available with two articulated ball ends to accommodate pipeline deflection, settlement, and
expansion. Available with Flanged or Mechanical Joint end connections, or a combination.
Also available with a single articulated ball end to accommodate pipeline deflection and expansion. Available with Flanged or Mechanical
Joint end connections, or a combination.
Rated Working
Nominal Pipe Pressure, psi
Size, in. (kPa)
3, 4, 6 350
(2415)
8, 10 300
(2070)
12 250
(1725)
Pipe
Standard Pipe
FM Approvals
September 2007 — Approval Guide
1-454 Automatic Sprinkler Systems
Express Pipe
Fittings
Double Socket 90° Elbow 100 through 300 25 (363) (a), (b)
Double Socket 45° Elbow 100 through 300 25 (363) (a), (b)
Double Socket 221⁄2° Elbow 100 through 300 25 (363) (a), (b)
Double Socket 111⁄4° Elbow 100 through 300 25 (363) (a), (b)
All Socket Tee 300×300×300 20 (290) (a), (b)
300×300×250 20 (290) (a), (b)
300×300×200 20 (290) (a), (b)
300×300×150 20 (290) (a), (b)
300×300×100 20 (290) (a), (b)
250×250×250 20 (290) (a), (b)
250×250×200 20 (290) (a), (b)
250×250×150 20 (290) (a), (b)
250×250×100 20 (290) (a), (b)
200×200×200 25 (363) (a), (b)
200×200×150 25 (363) (a), (b)
200×200×125 25 (363) (a), (b)
200×200×100 25 (363) (a), (b)
150×150×150 25 (363) (a), (b)
150×150×125 25 (363) (a), (b)
150×150×100 25 (363) (a), (b)
125×125×125 25 (363) (a), (b)
125×125×100 25 (363) (a), (b)
100×100×100 25 (363) (a), (b)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-455
FM Approvals
September 2007 — Approval Guide
1-456 Automatic Sprinkler Systems
Sigma Corp, Rte 537 Goldman Dr, Box 300, Cream Ridge NJ 08514
Ductile iron restraint gland for ductile iron pipe. Used to secure spigot ends of ductile iron pipe into standardized mechanical joint-ended
pipe, fittings or other components.
Rated Working
Product Nominal Pipe Pressure, psi
Description Size, in. (kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-457
DME890 8
DME1090 10
DME1290 12
FM Approvals
September 2007 — Approval Guide
1-458 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-459
DTP6 6 350
(2415)
DTP8 8 350
(2415)
DTP10 10 350
(2415)
DTP12 12 300
(2070)
DTP14 14 350
(2415)
DTP16 16 250
(1725)
DMS3 Short Sleeve (M.J.) 3 350
(2415)
DMS4 4 350
(2415)
DMS6 6 350
(2415)
DMS8 8 350
(2415)
DMS10 10 350
(2415)
DMS12 12 300
(2070)
DMS14 14 350
(2415)
DMS16 16 250
(1725)
DML2 Long Sleeve (M.J.) 2 350
(2415)
DML3 3 350
(2415)
DML4 4 350
(2415)
DML6 6 350
(2415)
DML8 8 350
(2415)
DML10 10 350
(2415)
DML12 12 300
(2070)
DML14 14 350
(2415)
DML16 16 250
(1725)
DG2 M.J. Gland 2 350
(2415)
DG3 3 350
(2415)
DG4 4 350
(2415)
DG6 6 350
(2415)
DG8 8 350
(2415)
DG10 10 350
(2415)
DG12 12 300
(2070)
DG16 16 250
(1725)
DMC33 Cross (M.J.) 3×3 350
(2415)
DMC43 4×3 350
(2415)
DMC44 4×4 350
(2415)
DMC64 6×4 350
(2415)
DMC66 6×6 350
(2415)
DMC84 8×4 350
(2415)
DMC86 8×6 350
(2415)
DMC88 8×8 350
(2415)
DMC104 10×4 350
(2415)
DMC106 10×6 350
(2415)
DMC108 10×8 350
(2415)
FM Approvals
September 2007 — Approval Guide
1-460 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-461
FM Approvals
September 2007 — Approval Guide
1-462 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-463
FM Approvals
September 2007 — Approval Guide
1-464 Automatic Sprinkler Systems
DTT12 12 300
(2070)
DTT16 16 250
(1725)
DTC4 Tapped Cross 4 350
(2415)
DTC6 6 350
(2415)
DTC8 8 350
(2415)
DTC10 10 350
(2415)
DTC12 12 300
(2070)
DTC16 16 250
(1725)
SG6 Swivel Gland 6 350
(2415)
SG8 8 350
(2415)
SSA613 Solid Swivel Adapter 6 350
(2415)
SSA813 Solid Swivel Adapter 8 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-465
DFL1090 10
DFL1290 12
DFD3 90° Base Radius Elbow (Flanged) 3 250
DFD490 4 (1750)
DFD590 5
DFD690 6
DFD890 8
DFD1090 10
DFD1290 12
DFD108 90° Base Radius Reducing 10×8 250
Elbow (Flanged) (1750)
DFT33 Equal Tee (Flanged) 3 250
DFT44 4 (1750)
DFT55 5
DFT66 6
DFT88 8
DFT1010 10
DFT1212 12
DFT32 Reducing Tee (Flanged) 3×2 250
DFT42 4×2 (1750)
DFT425 4×21⁄2
DFT43 4×3
DFT62 6×2
DFT63 6×3
DFT64 6×4
DFT83 8×3
DFT84 8×4
DFT86 8×6
DFT103 10×3
DFT104 10×4
DFT106 10×6
DFT108 10×8
DFT123 12×3
DFT124 12×4
DFT126 12×6
DFT128 12×8
DFT1210 12×10
DRT433 Reducing Tee (Flanged) 4×3×3 250
DRT533 5×3×3 (1750)
DRT544 5×4×4
DRT633 6×4×4
DRT644 6×4×4
DRT646 6×4×6
DRT864 8×6×4
DRT866 8×6×6
DRT868 8×6×8
DFC33 Equal Cross (Flanged) 3 250
DFC44 4 (1750)
DFC55 5
DFC66 6
DFC88 8
DFC1010 10
DFC1212 12
DFC32 Reducing Cross (Flanged) 3×2 250
DFC42 4×2 (1750)
DFC425 4×21⁄2
DFC43 4×3
DFC62 6×2
DFC63 6×3
DFC64 6×4
DFC84 8×4
DFC86 8×6
DFC104 10×4
DFC106 10×6
DFC108 10×8
DFC124 12×4
DFC126 12×6
DFC128 12×8
DFC1210 12×10
DFY44 Lateral Wye (Flanged) 4 250
DFY55 5 (1750)
DFY66 6
DFY88 8
DFY1010 10
DFY1212 12
FM Approvals
September 2007 — Approval Guide
1-466 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-467
DFW1212 12×12
All above products used to join plain-end or mechanical joint or flanged ductile iron pipe to mechanical joint or flanged or plain end devices
as noted or to identical adapters in underground mains.
FM Approvals
September 2007 — Approval Guide
1-468 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-469
FM Approvals
September 2007 — Approval Guide
1-470 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-471
FM Approvals
September 2007 — Approval Guide
1-472 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-473
FM Approvals
September 2007 — Approval Guide
1-474 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-475
Tyler Pipe Co, Div of McWane Inc, Box 2027, Tyler Texas 75710-2027
Ductile iron restraint gland for ductile iron pipe. Used to secure spigot ends of ductile iron pipe into standardized mechanical joint-ended
pipe, fittings or other components.
Rated Working
Nominal Pipe Pressure psi
Description Size, in. (kPa)
FM Approvals
September 2007 — Approval Guide
1-476 Automatic Sprinkler Systems
TDMB1490 14 300
(2070)
TDMB1690 16 300
(2070)
TDMB345 3 350
(2415)
TDMB445 4 350
(2415)
TDMB645 6 350
(2415)
TDMB845 8 350
(2415)
TDMB1045 10 350
(2415)
TDMB1245 12 300
(2070)
TDMB1445 14 300
(2070)
TDMB1645 16 300
(2070)
TDMB322 221⁄2° Elbow (M.J.) 3 350
(2415)
TDMB422 4 350
(2415)
TDMB622 6 350
(2415)
TDMB822 8 350
(2415)
TDMB1022 10 350
(2415)
TDMB1222 12 300
(2070)
TDMB1422 14 300
(2070)
TDMB1622 16 300
(2070)
TDMB311 111⁄4° Elbow 3 350
(2415)
TDMB411 4 350
(2415)
TDMB611 6 350
(2415)
TDMB811 8 350
(2415)
TDMB1011 10 350
(2415)
TDMB1211 12 300
(2070)
TDMB1411 14 300
(2070)
TDMB1611 16 300
(2070)
TDMR43 Reducer 4×3 350
(2415)
TDMR63 6×3 350
(2415)
TDMR64 6×4 350
(2415)
TDMR84 8×4 350
(2415)
TDMR86 8×6 350
(2415)
TDMR104 10×4 350
(2415)
TDMR106 10×6 350
(2415)
TDMR108 10×8 350
(2415)
TDMR124 12×4 300
(2070)
TDMR126 12×6 300
(2070)
TDMR128 12×8 300
(2070)
TDMR1210 12×10 300
(2070)
TDMR1410 14×10 350
(2415)
TDMR166 16×6 250
(1725)
TDMR168 16×8 250
(1725)
TDMR1610 16×10 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-477
FM Approvals
September 2007 — Approval Guide
1-478 Automatic Sprinkler Systems
TDML6 6 350
(2415)
TDML8 Long Sleeve (M.J.) 8 350
(2415)
TDML10 10 350
(2415)
TDML12 12 300
(2070)
TDML16 16 250
(1725)
TDG3 M.J. Gland 3 350
(2415)
TDG4 4 350
(2415)
TDG6 6 350
(2415)
TDG8 8 350
(2415)
TDG10 10 350
(2415)
TDG12 12 300
(2070)
TDG16 16 250
(1725)
TDMC43 Cross (M.J.) 4×3 350
(2415)
TDMC44 4×4 350
(2415)
TDMC64 6×4 350
(2415)
TDMC66 6×6 350
(2415)
TDMC84 8×4 350
(2415)
TDMC86 8×6 350
(2415)
TDMC88 8×8 350
(2415)
TDMC104 10×4 350
(2415)
TDMC106 10×6 350
(2415)
TDMC108 10×8 350
(2415)
TDMC1010 10×10 350
(2415)
TDMC124 12×4 300
(2070)
TDMC126 12×6 300
(2070)
TDMC128 12×8 300
(2070)
TDMC1210 12×10 300
(2070)
TDMC1212 12×12 300
(2070)
TDMO612 Offset 6×12 300
(2070)
TDMO126 12×6 300
(2070)
TDMH66 Hydrant Tee 6×6 350
(M.J. × M.J. × Swivel End) (2415)
TDMH86 8×6 350
(2415)
TDMH88 8x8 350
(2415)
TDMH106 10×6 350
(2415)
TDMH108 10x8 350
(2415)
TDMH126 12×6 300
(2070)
TDMH128 12×8 350
(2415)
TDMH146 14×6 300
(2070)
TDMH166 16×6 250
(1725)
TDMF44 Hydrant Tee 4×4 350
(M.J. × M.J. × Flanged End) (2415)
TDMF64 6x4 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-479
FM Approvals
September 2007 — Approval Guide
1-480 Automatic Sprinkler Systems
TRMG6 6 300
(2070)
TRMG8 8 250
(1725)
TRMG10 10 175
(1205)
TRMG12 12 175
(1205)
TRLG6 Retainer Gland 6 300
Standard (M.J.) (2070)
TRLG8 8 175
(1205)
TDMY33 45° Wye 3 350
(2415)
TDMY43 4×3 350
(2415)
TDMY44 4 350
(2415)
TDMY63 6×3 350
(2415)
TDMY64 6×4 350
(2415)
TDMY66 6 350
(2415)
TDMY83 8×3 350
(2415)
TDMY84 8×4 350
(2415)
TDMY86 8×6 350
(2415)
TDMY88 8×8 350
(2415)
TDMY103 10×3 350
(2415)
TDMY104 10×4 350
(2415)
TDMY106 10×6 350
(2415)
TDMY108 10×8 350
(2415)
TDMY1010 10×10 350
(2415)
TLPR43 Reducer 4×3 350
(M.J. × P.E.) (2415)
TLPR63 6x3 350
(2415)
TLPR64 6×4 350
(2415)
TLPR84 8×4 350
(2415)
TLPR86 8×6 350
(2415)
TLPR104 10×4 350
(2415)
TLPR106 10×6 350
(2415)
TLPR108 10×8 350
(2415)
TLPR124 12×4 300
(2070)
TLPR126 12×6 300
(2070)
TLPR128 12×8 300
(2070)
TLPR1210 12×10 300
(2070)
TLPR166 16×6 250
(1725)
TLPR168 16×8 250
(1725)
TLPR1612 16×12 250
(1725)
TSPR43 Reducer 4×3 350
(P.E. × M.J.) (2415)
TSPR63 6x3 350
(2415)
TSPR64 6×4 350
(2415)
TSPR84 8×4 350
(2415)
TSPR86 8×6 350
(2415)
TSPR104 10×4 350
(2415)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-481
FM Approvals
September 2007 — Approval Guide
1-482 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-483
FM Approvals
September 2007 — Approval Guide
1-484 Automatic Sprinkler Systems
TDTF10 10
TDTF12 12
TBDF3 Blind Flange (solid) 3 250
TBDF4 4 (1750)
TBDF6 6
TBDF8 8
TBDF10 10
TBDF12 12 250
(1750)
Tll above products used to join plain-end or mechanical joint or flanged ductile iron pipe to mechanical joint or flanged or plain end devices
as noted or to identical adapters in underground mains.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-485
TXME845 8 350
(2415)
TXME1045 10 350
(2415)
TXME1245 12 350
(2415)
TXME322 (M.J.) × Plain End 221⁄2° Elbow 3 350
(2415)
TXME422 4 350
(2415)
TXME622 6 350
(2415)
TXME822 8 350
(2415)
TXME1022 10 350
(2415)
TXME1222 12 350
(2415)
TXME311 (M.J.) × Plain End 111⁄4° Elbow 3 350
(2415)
TXME411 4 350
(2415)
TXME611 6 350
(2415)
TXME811 8 350
(2415)
TXME1011 10 350
(2415)
TXME1211 12 350
(2415)
TXMT43 Tee 4×3 350
(2415)
TXMT44 4 350
(2415)
TXMT63 6×3 350
(2415)
TXMT64 6×4 350
(2415)
TXMT66 6 350
(2415)
TXMT83 8×3 350
(2415)
TXMT84 8×4 350
(2415)
TXMT86 8×6 350
(2415)
TXMT88 8 350
(2415)
TXMT103 10×3 350
(2415)
TXMT104 10×4 350
(2415)
TXMT106 10×6 350
(2415)
TXMT108 10×8 350
(2415)
TXMT1010 10 350
(2415)
TXMT123 12×3 350
(2415)
TXMT124 12×4 350
(2415)
TXMT126 12×6 350
(2415)
TXMT128 12×8 350
(2415)
TXMT1210 12×10 350
(2415)
TXMT1212 12 350
(2415)
TXMT143 14×3 350
(2415)
TXMT144 14×4 350
(2415)
TXMT146 14×6 350
(2415)
TXMT148 14×8 350
(2415)
TXMT1410 14×10 350
(2415)
TXMT1412 14×12 350
(2415)
TXMT1414 14 350
(2415)
FM Approvals
September 2007 — Approval Guide
1-486 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-487
FM Approvals
September 2007 — Approval Guide
1-488 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-489
TXTK16 16 350
(2415)
TXMP3 Plug 3 350
(2415)
TXMP4 4 350
(2415)
TXMP6 6 350
(2415)
TXMP8 8 350
(2415)
TXMP10 10 350
(2415)
TXMP12 12 350
(2415)
TXMP14 14 350
(2415)
TXMP16 16 350
(2415)
TXTP3 Tapped Plug 3 350
(2415)
TXTP4 4 350
(2415)
TXTP6 6 350
(2415)
TXTP8 8 350
(2415)
TXTP10 10 350
(2415)
TXTP12 12 350
(2415)
TXTP14 14 350
(2415)
TXTP16 16 350
(2415)
FM Approvals
September 2007 — Approval Guide
1-490 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-491
TXPB1011 10 350
(2415)
TXPB1211 12 350
(2415)
TXPT44 Tee 4 350
(2415)
TXPT63 6×3 350
(2415)
TXPT64 6×4 350
(2415)
TXPT66 6 350
(2415)
TXPT83 8×3 350
(2415)
TXPT84 8×4 350
(2415)
TXPT86 8×6 350
(2415)
TXPT88 8 350
(2415)
TXPT103 10×3 350
(2415)
TXPT104 10×4 350
(2415)
TXPT106 10×6 350
(2415)
TXPT108 10×8 350
(2415)
TXPT1010 10 350
(2415)
TXPT123 12×3 350
(2415)
TXPT124 12×4 350
(2415)
TXPT126 12×6 350
(2415)
TXPT128 12×8 350
(2415)
TXPT1210 12×10 350
(2415)
TXPT1212 12 350
(2415)
TXPF44 Tee (Push-On × Flange) 4x4 350
(2415)
TXPF63 6x3 350
(2415)
TXPF64 6x4 350
(2415)
TXPF66 6x6 350
(2415)
TXPF83 8x3 350
(2415)
TXPF84 8x4 350
(2415)
TXPF86 8x6 350
(2415)
TXPF88 8x8 350
(2415)
TXPF103 10x3 350
(2415)
TXPF104 10x4 350
(2415)
TXPF106 10x6 350
(2415)
TXPF108 10x8 350
(2415)
TXPF1010 10x10 350
(2415)
TXPF123 12x3 350
(2415)
TXPF124 12x4 350
(2415)
TXPF126 12x6 350
(2415)
TXPF128 12x8 350
(2415)
TXPF1210 12x10 350
(2415)
TXPF1212 12x12 350
(2415)
TXPFA4 Flange Adapter( Push-On × Flange) 4 350
(2415)
TXPFA6 6 350
(2415)
FM Approvals
September 2007 — Approval Guide
1-492 Automatic Sprinkler Systems
TXPFA8 8 350
(2415)
TXPFA10 10 350
(2415)
TXPFA12 12 350
(2415)
TXPK3 Cap 3 350
(2415)
TXPK4 4 350
(2415)
TXPK6 6 350
(2415)
TXPK8 8 350
(2415)
TXPTK3 Tapped Cap 3 350
(2415)
TXPTK4 4 350
(2415)
TXPTK6 6 350
(2415)
TXPTK8 8 350
(2415)
TXPP3 Plug 3 350
(2415)
TXPP4 4 350
(2415)
TXPP6 6 350
(2415)
TXPP8 8 350
(2415)
TXPTP3 Tapped Plug 3 350
(2415)
TXPTP4 4 350
(2415)
TXPTP6 6 350
(2415)
TXPTP8 8 350
(2415)
Uni-Flange, Sub Ford Meter Box Co Inc, Box 443, Wabash IN 46992
Ductile iron flange adapters used to join plain-end ductile iron pipe to flanged devices in underground mains or at the first aboveground
connection at the base of the sprinkler riser, only*.
Mechanical Joint Retainer Gland. Series 1400. 4, 6, 8, 10 and 12 in. For use with ductile iron pipe.
Union Foundry Co, 1501 W 17th St, Box 309, Anniston AL 36208
Product Fitting Nominal Pipe
Description Description Size, in.
Flange Adapters used to join plain-end ductile iron pipe to flanged devices in underground mains or at the first aboveground connection
at the base of a sprinkler riser, only. Nominal 90 lb·ft (120 n·m) torque set screws supplied with flange adapter.
United States Pipe & Foundry Co, 3300 First Ave N, Birmingham AL 35222
Tyton Joint Pipe and Fittings. Pressure rating 350 psi (2415 kPa). When used with Field-Lok gasket as a joint restraint the pressure rating
is 200 psi (1380 kPa). When used with the Field Lok 350 gasket and joint restraint, the pressure rating is 250 psi (1725 kPa), except for the
18, 20 and 24 in. NPS, which is rated at 200 psi (1379 kPa).
Product Nominal Pipe
Description Size, in. Remarks
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-493
6×6×6
8×8×4
8×8×6
8×8×8
10×10×4
10×10×6
10×10×8
10×10×10
12×12×4
12×12×6
12×12×8
12×12×10
12×12×12
Cross 4×4×4×4 BBBB
6×6×4×4
6×6×6×6
8×8×4×4
8×8×6×6
8×8×8×8
10×10×4×4
10×10×6×6
10×10×8×8
10×10×10×10
12×12×4×4
12×12×6×6
12×12×8×8
12×12×10×10
12×12×12×12
Concentric Reducer 6×4 Small end B
8×4
8×6
10×4
10×6
10×8
12×4
12×6
12×8
12×10
Plug 4 through 12
Hydrant Tee 6×6×6 BBS
8×8×6
10×10×6
12×12×6
16×16×6
*Min thickness in 4 in. size is Class 51.
Trim Tyton Fittings. Pressure rating 350 psi (2415 kPa). When used with Field-Lok gasket as a joint restraint the pressure rating is 200
psi (1380 kPa).
FM Approvals
September 2007 — Approval Guide
1-494 Automatic Sprinkler Systems
12×8
12×10
Hydrant Tee 6×6×6 BBS
8×8×6
10×10×6
12×12×6
TR-FLEX Restrained Joint, Pipe and Fittings. Pressure rating 250 psi (1725 kPa). When used with Gripper Ring as a joint restraint the
pressure rating is 200 psi (1380 kPa).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-495
10×10×4×4
10×10×6×6
10×10×8×8
10×10×10×10
12×12×4×4
12×12×6×6
12×12×8×8
12×12×10×10
12×12×12×12
Concentric Reducer 6×4 BB
8×4
8×6
10×4
10×6
10×8
12×4
12×6
12×8
12×10
Connecting Piece 4 through 12 TRF×TRF
Connecting Piece 4 through 12 TRF×TJ
Connecting Piece 4 through 12 TRF×Flg
Plug 4 through 12
Cap 4 through 12
Mechanical Joint Pipe and Fittings. Pressure rating 350 psi (2415 kPa).
FM Approvals
September 2007 — Approval Guide
1-496 Automatic Sprinkler Systems
10×6
10×8
12×4
12×6
12×8
12×10
Reducer 6×4 Small End MJ×Large End
8×4 PE
8×6
10×4
10×6
10×8
12×4
12×6
6×4
12×8
12×10
Reducer 6×4 Small End PE×Large End
8×4 MJ
8×6
10×4
10×6
10×8
12×4
12×6
12×8
12×10
Offset 4×6 Offset×27 Long BS
4×12 Offset×30 Long
6×6 Offset×28 Long
6×12 Offset×34 Long
6×18 Offset×41 Long
8×6 Offset×29 Long
8×12 Offset×36 Long
8×18 Offset×43 Long
10×6 Offset×30 Long
10×12 Offset×38 Long
10×18 Offset×46 Long
12×6 Offset×34 Long
12×12 Offset×45 Long
12×18 Offset×56 Long
Solid Sleeve 4 through 12×71⁄2 Long BB
4 through 12×12 Long
4 through 12×10 Long Min
Connecting Piece 4 through 12 MJ×MJ
Connecting Piece 4 through 12 MJ×B
Connecting Piece 4 through 12 MJ×Flg
Connecting Piece 4 through 12 MJ×PE
Cap 4 through 12
Plug 4 through 12
Dual Purpose Solid Sleeve 4 through 12 BB
Wye Branch 4×4×4 BBB
6×6×4
6×6×6
8×8×4
8×8×6
8×8×8
10×10×4
10×10×6
10×10×8
10×10×10
12×12×4
12×12×6
12×12×8
12×12×10
12×12×12
Tee, Valve and 6×6×6 BBS
Hydrant 8×8×6
10×10×6
12×12×6
16×16×6
8×8×8
10×10×8
12×12×8
Connecting Piece, 6×13 Long SS
Valve and Hydrant 6×24 Long
6×36 Long
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-497
6×48 Long
6×60 Long
8×13 Long
FLANGED Pipe and Fittings. Pressure rating 250 psi (2415 kPa).
FM Approvals
September 2007 — Approval Guide
1-498 Automatic Sprinkler Systems
12×12×12
True Wye 4 through 12 Flg, Flg, Flg
Side Outlet 90° Elbow 4 through 12 Flg, Flg, Flg
Side Outlet Tee 4 through 12 Flg, Flg, Flg, Flg
Straight 4 through 12 Flg and Flare
90° Elbow 4 through 12 Flg and Flare
90° Long Radius Elbow 4 through 12 Flg and Flare
Return Bend 4 through 12 Flg, Flg
B-Bell End, S-Spigot End, TJ-Tyton Joint, MJ-Mechanical Joint, TRF-TR-Flex Joint, Flg-Flanged End, PE-Plain End.
MJ Field Lok Retainer Gland for ductile iron pipe. Used to secure spigot ends of ductile iron pipe into standardized mechanical joint-ended
fitting or other components.
Rated Working
Product Nominal Pipe Pressure, psi
Description Size, in. (kPa)
Style 341 Vic-Flange. For use with cut groove-ended cast iron or ductile iron pipe in underground installations. With Grade H or
M gasket material.
Style 342 Vic-Flange. For use with cut groove-ended ductile iron pipe in underground installations. With Grade H or M gasket material.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-499
a. With gasket M.
b. Joins Cast Iron or Ductile Iron Pipe and fittings in underground main installations.
c. Joins Ductile Iron Pipe and fittings in underground main installations.
d. Joins rolled or cut grooved steel pipe to Ductile Iron pipe.
Style 341 Vic-Flange. For use with cut groove-ended cast iron or ductile iron pipe in underground installations. With Grade H or M gasket material.
Style 342 Vic-Flange. For use with cut groove-ended ductile iron pipe in underground installations. With Grade H or M gasket material.
4×3;
6×3, 4;
CI Reducing Elbow
8×4, 6;
10×6, 8
CI Tee 4, 6, 8, 10, 12
4×3;
6×4;
CI Reducing Tee
8×4, 6;
10×4, 6, 8;
12×4, 6, 8, 10
CI Lateral 4, 6, 8, 10, 12
CI Cross 4, 6, 8, 10, 12
4×3;
6×4;
CI Reducer 8×4, 6;
10×4, 6, 8;
12×4, 6, 8, 10
CI Cap 4, 6, 8, 10, 12
FM Approvals
September 2007 — Approval Guide
1-500 Automatic Sprinkler Systems
Cast iron fittings for use together with ductile iron pipe, valves, and other pipe fittings. They shall be installed and
anchored in accordance with the manufacturer’s instructions and FM Global Property Loss Prevention Data Sheets.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-501
Pipe manufactured from this thermoplastic material is acceptable when FM Approved. Typical coupling is by
push-on, bell and spigot joint with single elastomeric gasket. Fittings may be cast iron or other FM Approved
materials.
PVC pipe should be installed and anchored according to the pipe manufacturer’s instructions and FM Global
Property Loss Prevention Data Sheets. For underground use only.
FM Approvals
September 2007 — Approval Guide
1-502 Automatic Sprinkler Systems
W193-050 12×8
W193-051 12×10
W193-032 Flange×Gasket 4
W193-033 Adapter 6
W193-034 8
W193-035 10
W193-036 12
Clow Canada, Div Canada Pipe Co Ltd, 245 Industrial Dr, Grandview Industrial Park, Saint John New Brunswick
E2R 1A4 Canada
Ductile iron restrainers for AWWA C-900 PVC pipe. Used to secure spigot ends of PVC pipe into standardized mechanical joint ended pipe
fitting or other components.
Product Nominal Pipe Pressure
Designation Size, in. Rating, psi (kPa) Remarks
a. For use with Class 150 or Class 200 cast iron pipe equivalent sized PVC pipe.
b. For use with Class 150 cast iron pipe equivalent sized PVC pipe.
a. Pipe lengths are joined by single-gasketed bell and spigot joints and are joined to cast iron fittings.
b. Forsheda and S&B Technical Products gaskets available.
Series 2000 PV
2004 4 200 a
(1380)
2006 6 200 a
(1380)
2008 8 200 a
(1380)
2010 10 200 a
(1380)
2012 12 150 b
(1035)
Series 2100
2104 4 200 a
(1380)
2106 6 200 a
(1380)
2108 8 200 a
(1380)
2110 10 200 a
(1380)
2112 12 200 a
(1380)
a. For use with AWWA C900 PC200 pipe.
b. For use with AWWA C900 PC150 pipe.
Freedom Plastics Inc, 215 South Arch St, Box 1488, Janesville WI 54548
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-503
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron pipe fittings having standardized mechanical joint
connections.
b. Pipes are FM Approved when supplied with the ‘‘Rieber’’ style gaskets.
Industrias Vassallo Inc, Box 473, Coto Laurel, Puerto Rico 00644
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron fittings having standardized mechanical joint connections.
b. Pipes are Approved when supplied with either ‘‘Vassallo’’ or ‘‘Rieber’’ style gaskets.
c. Pipes are considered Approved when supplied in either light blue or white in color.
IPEX Inc, 3 Place du Commerce, Suite 101, Ile-des-Soeurs Verdun, Quebec H3E 1H7, Canada
Big Brute/Centurion
AWWA C905 Pipe
DR18 PR 235 14, 16, 18, 20 235 a
(1620)
AWWA C905 Pipe
DR14 PR 310 16 310 a
(2135)
FM Approvals
September 2007 — Approval Guide
1-504 Automatic Sprinkler Systems
6 × 1 AWWA 150 c, d
(1035)
6 × 2 NPT 150 c, d
(1035)
6 × 2 AWWA 150 c, d
(1035)
8 × 3⁄4 AWWA 150 c, d
(1035)
8 × 1 AWWA 150 c, d
(1035)
8 × 2 AWWA 150 c, d
(1035)
8 × 2 NPT 150 c, d
(1035)
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron fittings having bell or standardized mechanical
joint connections.
b. For use with Class 150 and 200 pipe.
c. For use with Class 150 pipe.
d. For use with cast iron pipe equivalent sized PVC pipe.
e. For use with steel pipe equivalent sized PVC pipe.
a. For anchoring AWWA C900 DR18 PVC pipe to cast iron valves and fittings having standardized mechanical joints.
b. For anchoring AWWA C900 DR18 PVC bell and spigot pipe joints.
c. For anchoring AWWA C905 DR18 PVC pipe to cast iron valves and fittings having standardized mechanical joints.
d. For anchoring AWWA C905 DR18 PVC bell and spigot pipe joints.
a. Pipe lengths are joined by single-gasketed bell and spigot joints and are to valves or fittings having bell or standardized mechanical joint
connections.
North American Pipe Corp, 2801 Post Oak Blvd, Suite 300, Houston TX 77056
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron valves or fittings having bell or standardized me-
chanical joint connections.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-505
Northern Pipe Products Inc, 1302 39th Street NW, Fargo ND 58102-2808
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron valves and fittings having bell or standardized mechanical
joint connections.
Remarks
a. Pipe lengths are joined by single gasketed bell and spigot ends and can be joined to cast iron fittings having standardized mechanical joint connection.
b. Pipe lengths are joined by single gasketed bell and spigot ends. Pipes are manufactured with cast iron outside diameters.
Aqualoc
AWWA C900 Pipe 4, 6, 8, 10, 12 150 a
DR18 PC 150 (1035)
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron fittings having bell or standardized mechanical
joint connections.
Pipelife Jet Stream Inc, 1700 S Lincoln Street, Siloam Springs AR 72761
a. Pipe lengths are joined by single-gasketed bell and spigot joints and are joined to valves or fittings having bell or standardized mechanical joint
connections.
FM Approvals
September 2007 — Approval Guide
1-506 Automatic Sprinkler Systems
Ductile Iron Adapter Flanges for AWWA C-900 PVC pipe. Used to secure plain-ended PVC pipe to flange ended devices in
underground mains.
Royal Pipe Systems, 131 Regalcrest Court Woodbridge, Ontario L4L 8P3, Canada
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron fittings having standardized bell or mechanical
joint connections.
b. When supplied with grooved ends, this pipe is Approved for use with Royal Pipe Systems Cobra-Lock spline couplings.
Sigma Corp, Rte 537 Goldman Dr, Box 300, Cream Ridge NJ 08514
PV-LOK ductile iron Restraints for AWWA C900 PVC pipe. Restraints used to secure spigot ends of AWWA C900 PVC pipe into
standardized mechanical joint-ended pipe fitting or other component.
PVM 4, 6, 8, 10 150 a, b
(1035)
Restraints used to secure bell and spigot joints in AWWA C900 PVC pipe.
PVP 4, 6, 8 150 a, b
(1035)
Restraints used to secure spigot ends of AWWA C900 PVC pipe in AWWA C905/907 gasketed PVC fittings. The Series PVPF is used
in conjunction with a Series PVM restrainer.
PVPF 4, 6, 8 150 a, b
(1035)
Ductile iron restraints for AWWA C900 PVC pipe. Used to secure spigot ends of AWWA C900 PVC pipe into standardized mechanical
joint-ended pipe fitting or other components.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-507
a. Used to join plain ended AWWA C900 PVC pipe to mechanical joint ended devices in underground fire service mains.
b. Pressure rating for use with AWWA C900 DR18 PVC pipe.
c. Pressure rating for use with AWWA C900 DR14 PVC pipe.
d. Restrainer Joints to maintain bell and spigot joint integrity in underground mains or at the base only of a sprinkler riser or with a mechanical joint fitting.
e. Used to join plain ended AWWA C900 PVC pipe to flanged devices in underground fire service mains.
Uni-Flange, Sub Ford Meter Box Co Inc, Box 443, Wabash IN 46992
Ductile iron restrainers for AWWA C900 PVC pipe. Used to secure spigot ends of AWWA C900 PVC pipe into standardized mechanical
joint-ended pipe, fitting or other components.
Ductile iron restrainers for bell and spigot AWWA C900 PVC pipe joints.
White Knight
AWWA C900 Pipe
DR18 PC 150 4, 6, 8, 10, 12 150 a, b
(1035)
AWWA C900 Pipe
DR14 PC 200 4, 6, 8, 10, 12 200 a, b
(1380)
a. Pipe lengths are joined by single-gasketed bell and spigot joints and can be joined to cast iron fittings having bell or standardized mechanical joint
connections.
b. Gulf Rubber or S&B Technical Products Gaskets available.
b. Pipe lengths are joined by single-gasketed bell and spigot joints and are joined to valves or fittings having bell or standardized mechanical joint connections.
FM Approvals
September 2007 — Approval Guide
1-508 Automatic Sprinkler Systems
Vulcan Plastics Corp, 207 Durham Dr, Breeding Industrial Park, Athens AL 35611
Polyethylene pipe should be installed and anchored according to the pipe manufacturer’s instructions and
FM Global Property Loss Prevention Data Sheets. For underground use only.
Nominal pipe size is the approximate outside diameter of the pipe. Refer to manufacturer’s catalog for pipe inside
diameter.
Remarks:
a. Dimensions refer to the pipe outside diameter. Pipe and fittings are directly connected by the butt fusion process, or the socket electro-fusion welding process.
b. The manufacturer fusion welding instructions must be strictly adhered to for a proper joint.
c. The color of the pipe is Black or Blue.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-509
Pressure
Product O.D., Pipe Rating Bar
Designation Size, mm (psi) Remarks
a. Dimensions refer to the pipe outside diameter. Pipe and fittings are directly connected by the butt fusion process.
b. The manufacturer’s fusion welding instructions must be strictly adhered to for a proper joint. The fittings may also be joined to other FM Approved flanged fittings
with the above flange adapters.
c. The fittings are manufactured of injection molded PE100.
d. The fittings are Approved when used with an EPDM Gasket supplied by AGRU Kunststofftechnik.
Pressure
Product O.D., Pipe Rating Bar
Designation Size, mm (psi) Remarks
a. Dimensions refer to the pipe outside diameter. The pipe fits into a socket in the fitting, and when electrical current is applied to the terminal, which is integral with
the fitting, the joint is completed.
b. The manufacturer’s electro-fusion welding instructions must be strictly adhered to for a proper joint.
c. The fittings are manufactured of injection molded PE100.
FM Approvals
September 2007 — Approval Guide
1-510 Automatic Sprinkler Systems
a. Pipe and fittings may be directly connected together by the butt fusion process. Manufacturer fusion instructions must be strictly followed for a proper fusion joint.
The fittings may also be joined to other FM Approved flanged pipe and fittings by using the listed flange adapters.
b. Provides transition between polyethylene pipe or fittings, using the butt fusion process, to threaded steel pipe or steel pipe provided with a weld-end or flanged.
c. The electrofusion couplings are designed to join two adjacent lengths of high density polyethylene pipe. The electrofusion branch saddles mount directly on the
outside diameter of lengths of high density polyethylene pipe. The Central Electrofusion System is used to fuse couplings and branch saddles to the pipe.
Manufacturer’s installation and assembly recommendations must be strictly followed for a proper joint.
Extrumex S.A., de C.V. Lerdo de Tejada, No. 899 Col. El Lechugal, Santa Catarina N.L., C.P. 66350, Mexico
Product Nominal Pipe Pressure
Designation Size, in. Rating, psi Remarks
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-511
ISCO Industries LLC, 926 Baxter Ave, Box 4545, Louisville KY 40204
Product Nominal Pipe Pressure
Designation Size, in. Rating, psi Remarks
(kPa)
FM Approvals
September 2007 — Approval Guide
1-512 Automatic Sprinkler Systems
Independent Pipe Products Inc, 4949 Joseph Hardin Drive, Dallas TX 75236
Pressure
Product Nominal Pipe Rating, psi
Designation Size, in. (kPa) Remarks
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-513
Pressure
Product Nominal Pipe Rating, psi
Designation Size, in. (kPa) Remarks
Class 150 Branch 3×2, 4×2, 4×3, 6×2, 6×3, 6×4, 8×2, 150 a
Saddle Reducing Tee 8×3, 8×4, 8×6, 10×2, 10×3, 10×4, (1035)
10×6, 10×8, 12×2, 12×3, 12×4, 12×6,
12×8, 12×10, 14×2, 14×3, 14×4,
14×6, 14×8, 14×10, 16×2, 16×3,
16×4, 16×6, 16×8, 16×10, 16×12,
18×2, 18×3, 18×4, 18×6, 18×8,
18×10, 18×12
Class 200 Branch 3×2, 4×2, 4×3, 6×2, 6×3, 6×4, 8×2, 200 a
Saddle Reducing Tee 8×3, 8×4, 8×6, 10×2, 10×3, 10×4, (1380)
10×6, 10×8, 12×2, 12×3, 12×4, 12×6,
12×8, 12×10, 14×2, 14×3, 14×4,
14×6, 14×8, 14×10, 16×2, 16×3,
16×4, 16×6, 16×8, 16×10, 16×12,
18×2, 18×3, 18×4, 18×6, 18×8,
18×10, 18×12
Class 150 Fabricated 90° Elbow 8, 10, 12, 14, 16, 18 150 a
(5 segments) (1035)
Class 200 Fabricated 90° Elbow 8, 10, 12, 14, 16, 18 200 a
(5 segments) (1380)
Class 150 Fabricated 45° Elbow 8, 10, 12, 14, 16, 18 150 a
(5 segments) (1035)
Class 200 Fabricated 45° Elbow 8, 10, 12, 14, 16, 18 200 a
(3 segments) (1380)
Class 150 Fabricated 90° Elbow 8, 10, 12, 14, 16, 18 150 a
(3 segments) (1035)
Class 200 Fabricated 90° Elbow 8, 10, 12, 14, 16, 18 200 a
(3 segments) (1380)
Class 150 Fabricated 45° Elbow 8, 10, 12, 14, 16, 18 150 a
(2 segments) (1035)
Class 200 Fabricated 45° Elbow 8, 10, 12, 14, 16, 18 200 a
(2 segments) (1380)
Class 150 Mechanical Joint Adapter 2, 3, 4, 6, 8, 10, 12, 14, 16, 18 150 b
(1035)
FM Approvals
September 2007 — Approval Guide
1-514 Automatic Sprinkler Systems
Pressure
Product Nominal Pipe Rating, psi
Designation Size, in. (kPa) Remarks
Class 200 Mechanical Joint Adapter 2, 3, 4, 6, 8, 10, 12, 14, 16, 18 200 b
(1380)
a. Pipe and fittings may be directly connected together by the butt fusion process. Manufacturer fusion instructions must be strictly followed for a proper fusion joint.
The pipe and fittings may also be joined to other FM Approved steel flanged pipe and fittings by using the listed flange adapters.
b. Pipe and adapter, with ductile iron gland ring attached, are directly connected by the butt fusion process. Manufacturer fusion instructions must be strictly followed
for a proper fusion joint. The polyethylene fitting, gland ring, gasket, and T-Head bolts are provided in a kit for field installation, which allows attachment to a
compatible flange with ductile iron pipe.
Pressure
Product Nominal Pipe
Rating, psi Remarks
Designation Size, in.
(kPa)
Molded Fittings
150
Elbow, 90° 2, 3, 4, 6, 8 a, b
(1035)
200
Elbow, 90° 2, 3, 4, 6, 8 a, b
(1380)
150
Elbow, 45° 2, 3, 4, 6, 8 a, b
(1035)
200
Elbow, 45° 2, 3, 4, 6, 8 a, b
(1380)
150
Equal Tee 2, 3, 4, 6, 8 a, b
(1035)
200
Equal Tee 2, 3, 4, 6, 8 a, b
(1380)
150
End Cap 2, 3, 4, 6, 8 a, b
(1035)
200
End Cap 2, 3, 4, 6, 8 a, b
(1380)
3 × 2, 4 × 2, 4 × 3, 150
Concentric Reducer a, b
6 × 4, 8 × 6 (1035)
3 × 2, 4 × 2, 4 × 3, 200
Concentric Reducer a, b
6 × 4, 8 × 6 (1380)
2, 3, 4, 6, 8, 10, 150
Flange Adapter a, b
12, 14, 16, 18 (1035)
200
Flange Adapter 2, 3, 4, 6, 8, 10, 12 a, b
(1380)
2, 3, 4, 6, 8, 10, 150
Stub End a, b
12, 14, 16, 18 (1035)
200
Stub End 2, 3, 4, 6, 8, 10, 12 a, b
(1380)
Fabricated Fittings
150
Elbows ≤ 90° 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Elbows ≤ 90° 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1380)
150
Equal Tee 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Equal Tee 10, 12 , 14, 16, 18, 20, 22, 24 a, b
(1380)
2 × 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24
3 × 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24
4 × 6, 8, 10, 12, 14, 16, 18, 20, 22, 24
150
Saddle Reducing Tee 6 × 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1035)
8 × 10, 12, 14, 16, 18, 20, 22, 24
10 × 14, 16, 18, 20, 22, 24,
12 × 16, 18, 20, 22, 24
2 × 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24
3 × 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24
4 × 6, 8, 10, 12, 14, 16, 18, 20, 22, 24
200
Saddle Reducing Tee 6 × 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1380)
8 × 10, 12, 14, 16, 18, 20, 22, 24
10 × 14, 16, 18, 20, 22, 24
12 × 16, 18, 20, 22, 24
150
End Caps 10, 12 a, b
(1035)
200
End Caps 10, 12 a, b
(1380)
10 × 8, 12 × 8, 12 × 10, 14 × 12, 150
Concentric Reducers a, b
16 × 12, 16 × 14, 18 × 14, 18 × 16 (1035)
200
Concentric Reducers 10 × 8, 12 × 8, 12 × 10 a, b
(1380)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-515
Pressure
Product Nominal Pipe
Rating, psi Remarks
Designation Size, in.
(kPa)
10 × 8, 12 × 8, 12 × 10, 14 × 10, 14 × 12,
150
Swage Reducer 16 × 12, 16 × 14, 18 × 14, 18 × 16, 20 × 16, 20 × 18, a, b
(1035)
22 × 18, 22 × 20, 24 × 20, 24 × 22
10 × 8, 12 × 8, 12 × 10, 14 × 10, 14 × 12, 16 × 12,
200
Swage Reducer 16 × 14, 18 × 14, 18 × 16, 20 × 16, 20 × 18, 22 × 18, a, b
(1380)
22 × 20, 24 × 20, 24 × 22
150
Flange Adapters 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Flange Adapters 14, 16, 18, 20, 22, 24 a, b
(1380)
150
Stub Ends 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Stub Ends 14, 16, 18, 20, 22, 24 a, b
(1380)
150
Beveled Flange Adapter 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Beveled Flange Adapter 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1380)
150
Mechanical Joint Adapter 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Mechanical Joint Adapter 3, 4, 6, 8, 10, 12, 14, 16, 18 a, b
(1380)
150
Wall Anchor 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 a, b
(1035)
200
Wall Anchor 2, 3, 4, 6, 8, 10, 12, 14, 16, 18 a, b
(1380)
Back-Up Rings 150
2, 3, 4, 6, 8, 10, 12, 14, 16, 18 , 20, 22, 24 –
DI Convoluted (1035)
Back-Up Rings 200
2, 3, 4, 6, 8, 10, 12, 14, 16, 18 , 20, 22, 24 –
DI Convoluted (1380)
Back-Up Rings 150
2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 –
SS Convoluted (1035)
Back-Up Rings 200
2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 –
SS Convoluted (1380)
Back-Up Rings 150
2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 –
Forged Carbon Steel (1035)
Back-Up Rings 200
2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 –
Forged Carbon Steel (1380)
Blind Flanges 150
2, 3, 4, 6, 8, 10, 12, 14, 16, 18 , 20, 22, 24 –
Forged Carbon Steel (1035)
Blind Flanges 200
2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 –
Forged Carbon Steel (1380)
150
Transition, HDPE × Steel Pipe, SS 2, 3, 4 a, b
(1035)
200
Transition, HDPE × Steel Pipe, SS 2, 3, 4 a, b
(1380)
150
Transition, HDPE × Steel Pipe, Brass 2, 3, 4 a, b
(1035)
200
Transition, HDPE × Steel Pipe, Brass 2, 3, 4 a, b
(1380)
Remarks
a. Fittings may be directly connected together by the butt fusion process. Manufacturer fusion instructions must be strictly followed for a proper fusion joint. The
fittings may also be joined to other FM Approved flanged pipe and fittings by using the listed flange adapters and back-up rings.
b. FM Approved with a diameter basis of IPS sizes.
KWH Pipe (Canada) Ltd, 6507 Mississauga Rd, Mississauga, Ontario L5N 1A6, Canada
FM Approvals
September 2007 — Approval Guide
1-516 Automatic Sprinkler Systems
a. Pipe and fittings may be directly connected together by the Butt Fusion process. Manufacturer fusion instructions must be strictly followed for a proper fusion joint.
The Pipe and Fittings may also be joined to other FM Approved steel flanged pipe and fittings by using the above listed flange adapters.
b. The diameter basis is IPS sizes.
Performance Pipe, A Division of Chevron Phillips Chemical Company LP, 5085 West Park Blvd, Suite 500,
Plano TX 75093
Product Nominal Pipe Pressure
Designation Size, in. Rating, psi Remarks
(kPa)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-517
DRISCOPLEX 1500
Molded Fittings,
IPS Class 150
Elbows ≤90° 2, 3, 4, 6, 8 150 a, b, c
(1035)
DRISCOPLEX 1500
Molded Fittings,
IPS Class 200
Elbows ≤90° 2, 3, 4, 6, 8 200 a, b, c
(1380)
Back-Up Rings (IPS) 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 150
(1035)
(IPS) 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 200
(1380)
(DIPS) 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 24 150
(1035)
(DIPS) 2, 3, 4, 6, 8, 10, 12, 14, 16, 18, 20, 24 200
(1380)
Back-Up Rings, Carbon Steel
a. Pipe and fittings may be directly connected together by the butt fusion process. Manufacturer fusion instructions must be strictly followed for a proper fusion joint.
b. The pipe and fittings may also be provided with flange adapters and back-up rings and bolted together. Back-up rings must be pressure rated at or above the
pressure rating of the pipe on which they are installed.
g. Pipe may be supplied as black, or with red stripe, or with blue stripe.
i = Pipe may be marked with the FM Approval Mark and NSF or the FM Approval Mark and AWWA.
FM Approvals
September 2007 — Approval Guide
1-518 Automatic Sprinkler Systems
For use with FM Approved polyethylene pipe in Class 150 and Class 200 wall thicknesses. Style 06 and 60 end caps may be used with
Style 997 couplings to close a line.
For use with FM Approved polyethylene pipe in Class 150 and Class 200 wall thicknesses. Style 06 and 60 end caps may be used with
Style 997 couplings to close a line.
Pipe and fittings made in various configurations of fiber reinforced composites are acceptable when FM Approved.
Installation of pipe and fittings should be according to pipe manufacturer’s instructions and FM Approvals
standards. For underground use only.
Abu Dhabi Pipe Factory, Box 4526, Mafraq-Tarrif Road, Abu Dhabi, United Arab Emirates
Product Nominal Pipe Pressure
Designation Size, mm Rating Remarks
(in.) bar (psi)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-519
Pipe, Bell and Spigot with Lock Strip 100 through 600 16 f, g, i
Joint, glass reinforced vinylester (4 through 24) (232)
(GRV) P/000/02A
Pipe, Bell and Spigot with Lock Strip 100 through 600 16 e, g, i
Joint, glass reinforced epoxy (GRE) (4 through 24) (232)
P/000/02B
Ameron Fiberglass-Composite Pipe Group/Europe, Box 6, 4190 CA Geldermalsen, The Netherlands (NE)
Product Nominal Pipe Pressure
Designation Size, in. Rating Remarks
bar (psi)
S37691 8 12 b
(175)
S37692 10 12 b
(175)
S37693 12 12 b
(175)
S37694 14 12 b
(175)
S37695 16 12 b
(175)
S229N33D5 2 20 a
(290)
S339N33D5 3 20 a
(290)
S449N33D5 4 20 a
(290)
S669N33D5 6 20 a
(290)
S229N33G9 2 20 e, i
(290)
S339N33G9 3 20 e, i
(290)
S449N33G9 4 20 e, i
(290)
S669N33G9 6 20 e, i
(290)
FM Approvals
September 2007 — Approval Guide
1-520 Automatic Sprinkler Systems
S229N07J8 2 20 e, j
(290)
S339N07J8 3 20 e, j
(290)
S449N07J8 4 20 e, j
(290)
S669N07J8 6 20 e, j
(290)
S338L33A2 3 14 a
(200)
S448L33A2 4 14 a
(205)
S668L33A2 6 14 a
(205)
S888L33A2 8 14 a
(205)
SAA8L33A2 10 14 a
(205)
SBB8L33A2 12 14 a
(205)
SCC8L33B5 14 14 a
(205)
SDD8L33B5 16 14 a
(205)
SEE8L30A2 18 14 a
(200)
SFF8L33B5 20 14 a
(200)
S888L35A2 8 14 a
(200)
SAA8L35A2 10 14 a
(200)
SBB8L35A2 12 14 a
(200)
SCC8L35B5 14 14 a
(200)
SDD8L35B5 16 14 a
(200)
SEE8L35B5 18 14 a
(200)
SFF8L35B5 20 14 a
(200)
S228L33G9 2 14 i, k
(200)
S338L33G9 3 14 i, k
(200)
S448L33G9 4 14 i, k
(200)
S668L33G9 6 14 i, k
(200)
S888L33G9 8 14 i, k
(200)
SAA8L33G9 10 14 i, k
(200)a
SBB8L33G9 12 14 i, k
(200)
SCC8L33G9 14 14 i, k
(200)
SDD8L33G9 16 14 i, k
(200)
SEE8L30G9 18 14 i, k
(200)
SFF8L30G9 20 14 a
(200)
SHH8L30G9 24 14 i, k
(200)
S888L35G9 8 14 i, k
(200)
SAA8L35G9 10 14 i, k
(200)a
SBB8L35G9 12 14 i, k
(200)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-521
SCC8L35G9 14 14 i, k
(200)
SDD8L35G9 16 14 i, k
(200)
SEE8L35G9 18 14 i, k
(200)
SFF8L35G9 20 14 a
(200)
SHH8L35G9 24 14 i, k
(200)
S648M83D4 6×6×4 14 b
(205)
S848M83D4 8×8×4 14 b
(205)
S868M83D4 8×8×6 14 b
(205)
SA48M83D4 10×10×4 14 b
(205)
SA68M83D4 10×10×6 14 b
(205)
SB48M83D4 12×12×4 14 b
(205)
SB68M83D4 12×12×6 14 b
(205)
SC48M83D3 14×14×4 14 b
(205)
SC68M83D3 14×14×6 14 b
(205)
SD48M83D3 16×16×4 14 b
(205)
SD68M83D3 16×16×6 14 b
(205)
S228L07D4 2 14 b
(200)
S338L07D4 3 14 b
(200)
S448L07D4 4 14 b
(205)
S668L07D4 6 14 b
(205)
S888L07D4 8 14 b
(205)
SAA8L07D4 10 14 b
(205)
SBB8L07D4 12 14 b
(205)
SCC8L07D4 14 14 b
(205)
SDD8L07D4 16 14 b
(205)
SEE8L07E5 18 14 b
(200)
SFF8L07E5 20 14 b
(200)
S228L28A1 2 14 l
(200)
S338L28A1 3 14 l
(200)
S448L28A1 4 14 l
(200)
S668L28A1 6 14 l
(200)
S888L28A1 8 14 l
(200)
SAA8L28A1 10 14 l
(200)a
SBB8L28A1 12 14 l
(200)
SCC8L28A1 14 14 l
(200)
SDD8L28B4 16 14 l
(200)
SEE8L28B4 18 14 l
(200)
FM Approvals
September 2007 — Approval Guide
1-522 Automatic Sprinkler Systems
SFF8L28B4 20 14 l
(200)
Bondstrand Series 3414 Taper × Taper Coupling
S228L07J8 2 14 f, j
(200)
S338L07J8 3 14 f, j
(200)
S448L07J8 4 14 f, j
(205)
S668L07J8 6 14 f, j
(205)
S888NL07J8 8 14 f, j
(205)
SAA8L07J8 10 14 f, j
(205)
SBB8L07J8 12 14 f, j
(205)
SCC8L07J8 14 14 f, j
(205)
SDD8L07J8 16 14 f, j
(205)
SEE8L07J8 18 14 f, j
(200)
SFF8L07J8 20 14 f, j
(200)
SHH8L07J8 24 14 f, j
(200)
S5288100 4 14 d, e
(205)
S5188200 6 14 d, e
(205)
S5188300 8 14 d, e
(205)
S5188400 10 14 d, e
(205)
S5388500 12 14 d, e
(205)
S5188650 14 14 d, e
(205)
S5188750 16 14 d, e
(205)
S5505000 6×4 14 c
(205)
S5505100 8×4 14 c
(205)
S5505200 8×6 14 c
(205)
S5505300 10×6 14 c
(205)
S5505400 10×8 14 c
(205)
S5505600 12×10 14 c
(205)
S5605700 14×10 14 c
(205)
S5605800 14×12 14 c
(205)
S5606000 16×14 14 c
(205)
S338M33A2 3 16 a
(230)
S448M33A2 4 16 a
(230)
S668M33A2 6 16 a
(230)
S888M33A2 8 16 a
(230)
SAA8M33A2 10 16 a
(230)
SBB8M33A2 12 16 a
(230)
SCC8M33B5 14 16 a
(230)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-523
SD8M33B5 16 16 a
(230)
SFF8M33B5 20 16 a
(230)
S888M35A2 8 16 a
(230)
SAA8M35A2 10 16 a
(230)
SBB8M35A2 12 16 a
(230)
SCC8M35B5 14 16 a
(230)
SDD8M35B5 16 16 a
(230)
SEE8M35B5 18 16 a
(200)
SFF8M35B5 20 16 a-
(200)
S228M33G9 2 16 i
(230)
S338M33G9 3 16 i
(230)
S448M33G9 4 16 i
(230)
S668M33G9 6 16 i
(230)
S888M33G9 8 16 i
(230)
SAA8M33G9 10 16 i
(230)
SBB8M33G9 12 16 i
(230)
SCC8M33G9 14 16 i
(230)
SDD8M33G9 16 16 i
(230)
SEE8M30G9 18 16 i
(230)
SFF8M30G9 20 16 i
(230)
SHH8M30G9 24 16 i
(230)
S888M35G9 8 16 i
(230)
SAA8M35G9 10 16 i
(230)
SBB8M35G9 12 16 i
(230)
SCC8M35G9 14 16 i
(230)
SDD8M35G9 16 16 i
(230)
SEE8M35G9 18 16 i
(230)
SFF8M35G9 20 16 i
(230)
SHH8M35G9 24 16 i
(230)
S5264030 6×6×4 16 b
(230)
S5264130 8×8×4 16 b
(230)
S5264140 8×8×6 16 b
(230)
S5264230 10×10×4 16 b
(230)
S5264240 10×10×6 16 b
(230)
S5264330 12×12×4 16 b
(230)
S5264340 12×12×6 16 b
(230)
FM Approvals
September 2007 — Approval Guide
1-524 Automatic Sprinkler Systems
S5664430 14×14×4 16 b
(230)
S5664440 14×14×6 16 b
(230)
S5664530 16×16×4 16 b
(230)
S5664540 16×16×6 16 b
(230)
S5288100 4 16 d, e
(230)
S5188200 6 16 d, e
(230)
S5280300 8 16 d, e
(230)
S5388400 10 16 d, e
(230)
S5388500 12 16 d, e
(230)
S5188650 14 16 d, e
(230)
S5388700 16 16 d, e
(230)
S228M07D4 2 16 b
(230)
S338M07D4 3 16 b
(230)
S448M07D4 4 16 b
(230)
S668M07D4 6 16 b
(230)
S888M07D4 8 16 b
(230)
SAAM07D4 10 16 b
(230)
SBB8M07D4 12 16 b
(230)
SCC8M07E5 14 16 b
(230)
SDD8M07E5 16 16 b
(230)
SEE8M07E5 18 16 b
(230)
SFF8M07E5 20 16 b
(230)
S228M28A1 2 16 l
(230)
S338M28A1 3 16 l
(230)
S448M28A1 4 16 l
(230)
S668M28A1 6 16 l
(230)
S888M28A1 8 16 l
(230)
SAA8M28A1 10 16 l
(230)
SBB8M28A1 12 16 l
(230)
SCC8M28A1 14 16 l
(230)
SDD8M28B4 16 16 l
(230)
SEE8M28B4 18 16 l
(230)
SFF8M28B4 20 16 l
(230)
S228M07J8 2 16 f, j
(230)
S338M07J8 3 16 f, j
(230)
S448M07J8 4 16 f, j
(230)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-525
S668M07J8 6 16 f, j
(230)
S888M07J8 8 16 f, j
(230)
SAA8M07J8 10 16 f, j
(230)
SBB8M07J8 12 16 f, j
(230)
SCC8M07J8 14 16 f, j
(230)
SDD8M07J8 16 16 f, j
(230)
SEE8M07J8 18 16 f, j
(230)
SFF8M07J8 20 16 f, j
(230)
SHH8M07J8 24 16 f, j
(230)
S5505000 6×4 16 c
(230)
S5505100 8×4 16 c
(230)
S5505200 8×6 16 c
(230)
S5505300 10×6 16 c
(230)
S5505400 10×8 16 c
(230)
S5505600 12×10 16 c
(230)
S5605700 14×10 16 c
(230)
S5605800 14×12 16 c
(230)
S5606000 16×14 16 c
(230)
S338N33A2 3 20 a
(290)
S448N33A2 4 20 a
(290)
S668N33A2 6 20 a
(290)
S888N35B5 8 20 a
(290)
SAA8N31B5 10 20 a
(290)
SBB8N30B5 12 20 a
(290)
SCC8N33B5 14 20 a
(290)
SDD8N33B5 16 20 a
(290)
SEE8N30A2 18 20 a
(290)
SFF8N33B5 20 20 a
(290)
S888N35B5 8 20 a
(290)
SAA8N35B5 10 20 a
(290)
SBB8N35B5 12 20 a
(290)
SCC8N35B5 14 20 a
(290)
SDD8N35B5 16 20 a
(290)
SEE8N35A2 18 20 a
(290)
SFF8N35B5 20 20 a
(290)
S228N33G9 2 20 e, i
(290)
FM Approvals
September 2007 — Approval Guide
1-526 Automatic Sprinkler Systems
S338N33G9 3 20 e, i
(290)
S448N33G9 4 20 e, i
(290)
S668N33G9 6 20 e, i
(290)
S888N33G9 8 20 e, i
(290)
SAA8N33G9 10 20 e, i
(290)
SBB8N33G9 12 20 e, i
(290)
SCC8N33G9 14 20 e, i
(290)
SDD8N33G9 16 20 e, i
(290)
SEE8N30G9 18 20 e, i
(290)
SFF8N30G9 20 20 e, i
(290)
SHH8N30G9 24 20 e, i
(290)
S888N35G9 8 20 e, i
(290)
SAA8N35G9 10 20 e, i
(290)
SBB8N35G9 12 20 e, i
(290)
SCC8N35G9 14 20 e, i
(290)
SDD8N35G9 16 20 e, i
(290)
SEE8N35G9 18 20 e, i
(290)
SFF8N35G9 20 20 e, i
(290)
SHH8N35G9 24 20 e, i
(290)
S228N07D4 2 20 b
(290)
S338N07D4 3 20 b
(290)
S448N07E5 4 20 b
(290)
S668N07E5 6 20 b
(290)
S888N07E5 8 20 b
(290)
SAA8N07E5 10 20 b
(290)
SBB8N07E5 12 20 b
(290)
SCC8N07E5 14 20 b
(290)
SDD8N07E5 16 20 b
(290)
SEE8N07E5 18 20 b
(290)
SFF8N07E5 20 20 b
(290)
S228N28A1 2 20 l
(290)
S338N28A1 3 20 e, i
(290)
S448N28B4 4 20 e, i
(290)
S668N28B4 6 20 e, i
(290)
S888N28B4 8 20 e, i
(290)
SAA8N28B4 10 20 e, i
(290)
SBB8N28B4 12 20 e, i
(290)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-527
SCC8N28B4 14 20 e, i
(290)
SDD8N28B4 16 20 e, i
(290)
SEE8N28B4 18 20 e, i
(290)
SFF8N28B4 20 20 e, i
(290)
S228N07J8 2 20 e, j
(290)
S338N07J8 3 20 e, j
(290)
S448N07J8 4 20 e, j
(290)
S668N07J8 6 20 e, j
(290)
S888N07J8 8 20 e, j
(290)
SAA8N07J8 10 20 e, j
(290)
SBB8N07J8 12 20 e, j
(290)
SCC8N07J8 14 20 e, j
(290)
SDD8N07J8 16 20 e, j
(290)
SEE8N07J8 18 20 e, j
(290)
SFF8N07J8 20 20 e, j
(290)
SHH8N07J8 24 20 f, j
(290)
S228630A2 2 40 a
(580)
S338730B5 3 40 a
(580)
Bondstrand Series 3440 Taper × Taper Pipe
S228730G9 2 40 i, f
(580)
S338731G9 3 40 i, f
(580)
S228W33G9 2 50 i, k
(725)
S44613463 4 12 f, h, i
(175)
S66613463 6 12 f, h, i
(175)
S88613363 8 12 f, h, i
(175)
SAA613363 10 12 f, h, i
(175)
SBB613363 12 12 f, h, i
(175)
SDD613263 16 12 f, h, i
(175)
a. Pipe with one integral key-lock female end and one integral key-lock male end.
b. Fittings with key-lock female ends.
c. Fittings with one key-lock female end and one key-lock male end.
d. Fittings with tapered spigot end and key-lock male end.
e. Bonded joints made with RP-48 adhesive.
f. Bonded joints made with RP-34 adhesive.
g. Fittings with Quick-lock bell ends.
h. Spigot end of pipe must be prepared with Ameron equipment. See manufacturer’s instructions.
i. Pipes equipped with one bell and one spigot end. Pipe lengths joined by bell and spigot joints.
j. Coupling equipped with two tapered female ends.
k. Bonded joints made with RP-44 adhesive.
l. Nipples supplied with two male key-lock ends.
FM Approvals
September 2007 — Approval Guide
1-528 Automatic Sprinkler Systems
Ameron International, Fiberglass Composite Pipe Division – The Americas, 1004 Ameron Rd, Burkburnett TX 76354
Bondstrand Series 3200/1, 3200 Pipe and Fittings.
Product Nominal Pipe Pressure
Designation Size, in. Rating Remarks
bar (psi)
Pipe Bell×Spigot
20344615 2 14 b, d, g, u, v
(200)
30344615 3 14 b, d, g, u, v
(200)
40344615 4 14 b, d, g, u, v
(200)
60344615 6 14 b, d, g, u, v
(200)
80344615 8 14 a, b, e, g, s, t
(200)
A0344615 10 14 a, b, e, g, s, t
(200)
B0344615 12 14 a, b, e, g, s, t
(200)
C0344615 14 12 a, b, e, g, s, t
(175)
D0344615 16 12 a, b, e, g, s, t
(175)
Couplings Bell×Bell
20340707 2 14 g, h, u, v
(200)
30340707 3 14 g, h, u, v
(200)
40340707 4 14 g, h, u, v
(200)
60340707 6 14 g, h, u, v
(200)
80340707 8 14 a, e, g, h, s, t
(200)
A0340707 10 14 a, e, g, h, s, t
(200)
B0340707 12 14 a, e, g, h, s, t
(200)
C0340707 14 12 a, e, g, h, s, t
(175)
D0340707 16 12 a, e, g, h, s, t
(175)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-529
80342008 8 14 a, c, g, h, s, t
(200)
A0342008 10 14 a, c, g, h, s, t
(200)
B0342008 12 14 a, c, g, h, s, t
(200)
C0342008 14 12 a, c, g, h, s, t
(175)
D0342008 16 12 a, c, g, h, s, t
(175)
FM Approvals
September 2007 — Approval Guide
1-530 Automatic Sprinkler Systems
D0348055 16 12 c, i, k, m
(175)
Blind Flange
20342504 2 14 f
(200)
30342504 3 14 f
(200)
40342504 4 14 f
(200)
60342504 6 14 f
(200)
80342504 8 14 n
(200)
A0342504 10 14 n
(200)
B0342504 12 14 n
(200)
C0342504 14 12 n
(175)
D0342504 16 12 n
(175)
Flange Ring
20342509 2 14 f
(200)
30342509 3 14 f
(200)
40342509 4 14 f
(200)
60342509 6 14 f
(200)
80342509 8 14 h
(200)
A0342509 10 14 h
(200)
B0342509 12 14 h
(200)
C0342509 14 12 h
(175)
D0342509 16 12 h
(175)
Stub End
20342510 2 14 f, u, v
(200)
30342510 3 14 f, u, v
(200)
40342510 4 14 f, u, v
(200)
60342510 6 14 a, f
(200)
80342510 8 14 a, o
(200)
A0342510 10 14 a, o
(200)
B0342510 12 14 a, o
(200)
C0342510 14 12 a, o
(175)
D0342510 16 12 a, o
(175)
End Cap
2 14 f, u, v
(200)
3 14 f, u, v
(200)
4 14 f, u, v
(200)
6 14 f, u, v
(200)
Reducers Bell×Bell
32347608 3×2 16 a, g, h, s, t
(232)
43347608 4×3 16 a, g, h, s, t
(232)
64347608 6×4 14 a, g, h, s, t
(200)
N/A 8×2 14 a, c, e, g, i, s, t
(200)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-531
N/A 8×3 14 a, c, e, g, i, s, t
(200)
N/A 8×4 14 a, c, e, g, i, s, t
(200)
N/A 8×6 14 a, c, e, g, i, s, t
(200)
N/A 10×2 14 a, c, e, g, i, s, t
(200)
N/A 10×3 14 a, c, e, g, i, s, t
(200)
N/A 10×4 14 a, c, e, g, i, s, t
(200)
N/A 10×6 14 a, c, e, g, i, s, t
(200)
N/A 10×8 14 a, c, e, g, i, s, t
(200)
N/A 12×2 14 a, c, e, g, i, s, t
(200)
N/A 12×3 14 a, c, e, g, i, s, t
(200)
N/A 12×4 14 a, c, e, g, i, s, t
(200)
N/A 12×6 14 a, c, e, g, i, s, t
(200)
N/A 12×8 14 a, c, e, g, i, s, t
(200)
N/A 12×10 14 a, c, e, g, i, s, t
(200)
N/A 14×2 12 a, c, e, g, i, s, t
(175)
N/A 14×3 12 a, c, e, g, i, s, t
(175)
N/A 14×4 12 a, c, e, g, i, s, t
(175)
N/A 14×6 12 a, c, e, g, i, s, t
(175)
N/A 14×8 12 a, c, e, g, i, s, t
(175)
N/A 14×10 12 a, c, e, g, i, s, t
(175)
N/A 14×12 12 a, c, e, g, i, s, t
(175)
N/A 16×2 12 a, c, e, g, i, s, t
(175)
N/A 16×3 12 a, c, e, g, i, s, t
(175)
N/A 16×4 12 a, c, e, g, i, s, t
(175)
N/A 16×6 12 a, c, e, g, i, s, t
(175)
N/A 16×8 12 a, c, e, g, i, s, t
(175)
N/A 16×10 12 a, c, e, g, i, s, t
(175)
N/A 16×12 12 a, c, e, g, i, s, t
(175)
N/A 16×14 12 a, c, e, g, i, s, t
(175)
N/A 8×2 14 c, i, k, m, s, t
(200)
N/A 8×3 14 c, i, k, m, s, t
(200)
N/A 8×4 14 c, i, k, m, s, t
(200)
N/A 8×6 14 c, i, k, m, s, t
(200)
N/A 10×2 14 c, i, k, m, s
(200)
N/A 10×3 14 c, i, k, m, s
(200)
N/A 10×4 14 c, i, k, m, s
(200)
N/A 10×6 14 c, i, k, m, s
(200)
N/A 10×8 14 c, i, k, m, s
(200)
N/A 12×2 14 c, i, k, m, s
(200)
N/A 12×3 14 c, i, k, m, s
(200)
N/A 12×4 14 c, i, k, m, s
(200)
N/A 12×6 14 c, i, k, m, s
(200)
FM Approvals
September 2007 — Approval Guide
1-532 Automatic Sprinkler Systems
N/A 12×8 14 c, i, k, m, s
(200)
N/A 12×10 14 c, i, k, m, s
(200)
N/A 14×2 12 c, i, k, m
(175)
N/A 14×3 12 c, i, k, m
(175)
N/A 14×4 12 c, i, k, m
(175)
N/A 14×6 12 c, i, k, m
(175)
N/A 14×8 12 c, i, k, m
(175)
N/A 14×10 12 c, i, k, m
(175)
N/A 14×12 12 c, i, k, m
(175)
N/A 16×2 12 c, i, k, m
(175)
N/A 16×3 12 c, i, k, m
(175)
N/A 16×4 12 c, i, k, m
(175)
N/A 16×6 12 c, i, k, m
(175)
N/A 16×8 12 c, i, k, m
(175)
N/A 16×10 12 c, i, k, m
(175)
N/A 16×12 12 c, i, k, m
(175)
N/A 16×14 12 c, i, k, m
(175)
C.I.P.E. Adapter
N/A 3 16 a, h
(232)
N/A 4 16 a, h
(232)
N/A 6 14 a, h
(200)
N/A 8 14 a, h, e
(200)
N/A 10 14 a, h, e
(200)
N/A 12 14 a, h, e
(200)
N/A 14 12 a, h, e
(175)
N/A 16 12 a, h, e
(175)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-533
20340756 2 14 l, o, u, v
(200)
30340756 3 14 l, o, u, v
(200)
40340756 4 14 l, o, u, v
(200)
60340756 6 12 l, o, u, v
(175)
FM Approvals
September 2007 — Approval Guide
1-534 Automatic Sprinkler Systems
3682500FM 8 12 a
(175)
3682600FM 10 12 a
(175)
3682700FM 12 12 a
(175)
3682800FM 14 12 a
(175)
3682900FM 16 12 a
(175)
Elbow-90° 6000
22602060 2 12 k
(175)
33602060 3 12 k
(175)
3683300FM 4 12 a
(175)
3683400FM 6 12 a
(175)
3683500FM 8 12 a
(175)
3683600FM 10 12 a
(175)
3683700FM 12 12 a
(175)
3683800FM 14 12 a
(175)
5141700FM 16 12 a
(175)
Elbow-45° 6000
22601460 2 12 k
(175)
33601460 3 12 k
(175)
3684300FM 4 12 a
(175)
3684400FM 6 12 a
(175)
3684500FM 8 12 a
(175)
3684600FM 10 12 a
(175)
3684700FM 12 12 a
(175)
3684800FM 14 12 a
(175)
5128900FM 16 12 a
(175)
Coupling 6000
22600760 2 12 k
(175)
33600760 3 12 k
(175)
3681300FM 4 12 a
(175)
3681400FM 6 12 a
(175)
3681500FM 8 12 a
(175)
3681600FM 10 12 a
(175)
3681700FM 12 12 a
(175)
3681800FM 14 12 a
(175)
3681900FM 16 12 a
(175)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-535
3685400FM 6 12 a
(175)
3685500FM 8 12 a
(175)
3685600FM 10 12 a
(175)
3685700FM 12 12 a
(175)
3685800FM 14 12 a
(175)
3685900FM 16 12 a
(175)
Reducer (6000)
3686800FM 12 × 8 12 a
(175)
3686900FM 12 × 10 12 a
(175)
Flange 6000
3406400FM 4 12 a, c, f
(175)
3406500FM 6 12 a, c, f
(175)
4002400FM 8 12 a, c, f
(175)
5488500FM 10 12 a, c, f
(175)
5472400FM 12 12 a, c, f
(175)
5472000FM 14 12 a, c, f
(175)
5471900FM 16 12 a, c, f
(175)
FM Approvals
September 2007 — Approval Guide
1-536 Automatic Sprinkler Systems
9039867 24 14 k
(65-70°) (200)
HH9L18J89 24 14 k
(70-75°) (200)
HH9L19J89 24 14 k
(75-80°) (200)
9039868 24 14 k
(80-85°) (200)
9039913 24 14 k
(85-90°) (200)
Elbow-90° (K16FM)
449M20D4 4 16 c, d
(230)
669M20D4 6 16 c, d
(230)
889M20D4 8 16 c, d
(230)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-537
AA9M20D4 10 16 c, d
(230)
BB9M20D4 12 16 c, d
(230)
CC9M20E5 14 16 c, d
(230)
DD9M20E5 16 16 c, d
(230)
FF9M20E5 20 16 d
(230)
TAA9M17J8 10 16
(230)
TCC9M17J8 14 16
(230)
FM Approvals
September 2007 — Approval Guide
1-538 Automatic Sprinkler Systems
TCC9M13J8 14 16
(230)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-539
C89M83D3 14 × 14 × 8 16 c, d
(230)
CA9M83D3 14 × 14 × 10 16 c, d
(230)
CB9M83D3 14 × 14 × 12 16 c, d
(230)
D69M83D3 16 × 16 × 6 16 c, d
(230)
D89M83D3 16 × 16 × 8 16 c, d
(230)
DA9M83D3 16 × 16 × 10 16 c, d
(230)
DB9M83D3 16 × 16 × 12 16 c, d
(230)
DC9M83E5 16 × 16 × 14 16 c, d
(230)
F69M83EJ8 20 × 20 × 6 16 d
(230)
F89M83E5 20 × 20 × 8 16 d
(230)
F69M83EJ8 20 × 20 × 10 16 d
(230)
FB9M83E5 20 × 20 × 12 16 d
(230)
FC9M83E5 20 × 20 × 14 16 d
(230)
FD9M83E5 20 × 20 × 16 16 d
(230)
FM Approvals
September 2007 — Approval Guide
1-540 Automatic Sprinkler Systems
HC9M83J8 24 × 24 × 14 16 k
(230)
HD9M83J8 24 × 24 × 16 16 k
(230)
HE9M83J8 24 × 24 × 18 16 k
(230)
HF9M83J8 24 × 24 × 20 16 k
(230)
HG9M83J8 24 × 24 × 22 16 k
(230)
Reducer T16FM
649M76J8 6×4 16 a, h
(230)
849M76J8 8×4 16 a, h
(230)
869M76J8 8×6 16 h
(230)
A69M76J8 10 × 6 16 h
(230)
A89M76J8 10 × 8 16 h
(230)
B89M76J8 12 × 8 16 h
(230)
BA9M76J8 12 × 10 16 h
(230)
CA9M76J8 14 × 10 16 h
(230)
CB9M76J8 14 × 12 16 h
(230)
DB9M76J8 16 × 12 16 h
(230)
DC9M76J8 16 × 14 16 h
(230)
Coupling T16FM
449M07J8 4 16 h
(230)
669M07J8 6 16 h
(230)
889M07J8 8 16 h
(230)
AA9M07J8 10 16 h
(230)
BB9M07J8 12 16 h
(230)
CC9M07J8 14 16 h
(230)
DD9M07J8 16 16 h
(230)
FF9M07E5 20 16 d
(230)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-541
669M03A6 6 16 e, h
(230)
889M03A6 8 16 e, h
(230)
AA9M03A6 10 16 e, h
(230)
BB9M03A6 12 16 e, h
(230)
CC9M03A6 14 16 e, h
(230)
DD9M03B9 16 16 e, h
(230)
FF9M03B8 20 16 k
(230)
FM Approvals
September 2007 — Approval Guide
1-542 Automatic Sprinkler Systems
DD9N20E5 16 20 c, d
(290)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-543
649N83D4 6×4 20 c, d
(290)
849N83D4 8×4 20 c, d
(290)
869N83D4 8×6 20 c, d
(290)
A49N83D3 10 × 4 20 c, d
(290)
A69N83D3 10 × 6 20 c, d
(290)
A89N83D3 10 × 8 20 c, d
(290)
B49N83D3 12 × 4 20 c, d
(290)
B69N83D3 12 × 6 20 c, d
(290)
B89N83D3 12 × 8 20 c, d
(290)
BAN83E5 12 × 10 20 c, d
(290)
C69N83D3 14 × 6 20 c, d
(290)
C89N83D3 14 × 8 20 c, d
(290)
CA9N83E5 14 × 10 20 c, d
(290)
CB9N83E5 14 × 12 20 c, d
(290)
D69N83D3 16 × 6 20 c, d
(290)
D89N83D3 16 × 8 20 c, d
(290)
DA9N83E5 16 × 10 20 c, d
(290)
DB9N83E5 16 × 12 20 c, d
(290)
DC9N83E5 16 × 14 20 c, d
(290)
Reducer T20FM
329N76J8 3×2 20 h
(290)
429N76J8 4×2 20 h
(290)
439N76J8 4×3 20 h
(290)
639N76J8 6×3 20 h
(290)
649N76J8 6×4 20 h
(290)
FM Approvals
September 2007 — Approval Guide
1-544 Automatic Sprinkler Systems
849N76J8 8×4 20 h
(290)
869N76J8 8×6 20 h
(290)
A69N76J8 10 × 6 20 h
(290)
A89N76J8 10 × 8 20 h
(290)
B89N76J8 12 × 8 20 h
(290)
BA9N76J8 12 × 10 20 h
(290)
CA9N76J8 14 × 10 20 h
(290)
CB9N76J8 14 × 12 20 h
(290)
DB9N76J8 16 × 12 20 h
(290)
DC9N76J8 16 × 14 20 h
(290)
Coupling T20FM
229N07J8 2 20 h
(290)
339N07J8 3 20 h
(290)
449N07J8 4 20 h
(290)
669N07J8 6 20 h
(290)
889N07J8 8 20 h
(290)
AA9N07J8 10 20 h
(290)
BB9N07J8 12 20 h
(290)
CC9N07J8 14 20 h
(290)
DD9N07J8 16 20 h
(290)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-545
Amiantit Epoxy Pipe Production Plant (Amipox), Box 589, First Industrial City, Dammam 31421,
Kingdom of Saudi Arabia
Identification Size Pressure Rating Remarks
mm (in.) bar (psi)
FM Approvals
September 2007 — Approval Guide
1-546 Automatic Sprinkler Systems
100 12 a, c, d
(4) (175)
150 12 a, c, d
(6) (175)
200 12 a, c, d
(8) (175)
250 12 a, c, d
(10) (175)
300 12 a, c, d
(12) (175)
350 12 a, c, d
(14) (175)
400 12 a, c, d
(16) (175)
Flange with Socket End, Bolting Flange, ANSI B16.5, Class 150
100 12 c
(4) (175)
150 12 c
(6) (175)
200 12 c
(8) (175)
250 12 c
(10) (175)
300 12 c
(12) (175)
350 12 c
(14) (175)
400 12 c
(16) (175)
a. Bonded joints made with RP-48 or Araldite AV4738 adhesive.
b. Joints made with O-Ring seal and locking key.
c. Standard Taper Flange.
d. Taper × taper adhesive joint.
Amiantit Fiberglass Industries Ltd, Box 589, Dammam 31421 Kingdom of Saudi Arabi
Product Nominal Pipe Pressure Rating,
Designation Size, mm bar
(psi)
Pipe
AF/FM/2200-1 750 12
(175)
AF/FM/2200-2 700 12
(175)
AF/FM/2200-3 600 12
(175)
AF/FM/2200-4 500 12
(175)
AF/FM-2200-5 450 12
(175)
AF/FM/2200-6 400 12
(175)
AF/FM/2200-7 350 12
(175)
AF/FM/2200-8 300 12
(175)
AF/FM/2200-9 700 15
(220)
AF/FM/2200-10 600 15
(220)
AF/FM/2200-11 500 15
(220)
AF/FM/2200-12 450 15
(220)
AF/FM/2200-13 400 15
(220)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-547
AF/FM/2200-14 350 15
(220)
AF/FM/2200-15 300 15
(220)
Butt Strap Joint
AF/FM/2304-1 750 12
(175)
AF/FM/2304-2 700 12
(175)
AF/FM/2304-3 700 15
(220)
AF/FM/2304-4 600 12
(175)
AF/FM/2304-5 600 15
(220)
AF/FM/2304-6 500 12
(175)
AF/FM/2304-7 500 15
(220)
AF/FM/2304-8 450 12
(175)
AF/FM/2304-9 450 15
(220)
AF/FM/2304-10 400 12
(175)
AF/FM/2304-11 400 15
(220)
AF/FM/2304-12 350 12
(175)
AF/FM/2304-13 350 15
(220)
AF/FM/2304-14 300 12
(175)
AF/FM/2304-15 300 15
(220)
Coupling
AF/FM/2600-01 750 12
(175)
AF/FM/2600-02 700 12
(175)
AF/FM/2600-03 600 12
(175)
AF/FM/2600-04 500 12
(175)
AF/FM/2600-05 450 12
(175)
AF/FM/2600-06 400 12
(175)
AF/FM/2600-07 350 12
(175)
AF/FM/2600-08 300 12
(175)
AF/FM/2600-09 700 15
(220)
AF/FM/2600-10 600 15
(220)
AF/FM/2600-11 500 15
(220)
AF/FM/2600-12 450 15
(220)
AF/FM/2600-13 400 15
(220)
AF/FM/2600-14 350 15
(220)
AF/FM/2600-15 300 15
(220)
30° Elbow
AF/FM/2301-1 750 12
(175)
AF/FM/2301-2 700 12
(175)
AF/FM/2301-3 600 12
(175)
AF/FM/2301-4 500 12
(175)
AF/FM/2301-5 450 12
(175)
AF/FM/2301-6 400 12
(175)
AF/FM/2301-7 350 12
(175)
AF/FM/2301-8 300 12
(175)
45° Elbow
FM Approvals
September 2007 — Approval Guide
1-548 Automatic Sprinkler Systems
AF/FM/2301-9 750 12
(175)
AF/FM/2301-10 700 12
(175)
AF/FM/2301-11 600 12
(175)
AF/FM/2301-12 500 12
(175)
AF/FM/2301-13 450 12
(175)
AF/FM/2301-14 400 12
(175)
AF/FM/2301-15 350 12
(175)
AF/FM/2301-16 300 12
(175)
90° Elbow
AF/FM/2301-17 750 12
(175)
AF/FM/2301-18 700 12
(175)
AF/FM/2301-19 600 12
(175)
AF/FM/2301-20 500 12
(175)
AF/FM/2301-21 450 12
(175)
AF/FM/2301-22 400 12
(175)
AF/FM/2301-23 350 12
(175)
AF/FM/2301-24 300 12
(175)
Blind Flange
AF/FM/2309-1 750 12
(175)
AF/FM/2309-2 600 12
(175)
AF/FM/2309-3 500 12
(175)
AF/FM/2309-4 450 12
(175)
AF/FM/2309-5 400 12
(175)
AF/FM/2309-6 350 12
(175)
AF/FM/2309-7 300 12
(175)
Eccentric Reducer
AF/FM/2306-1 750 × 700 12
(175)
AF/FM/2306-2 750 × 600 12
(175)
AF/FM/2306-3 750 × 500 12
(175)
AF/FM/2306-4 750 × 450 12
(175)
AF/FM/2306-5 750 × 400 12
(175)
AF/FM/2306-6 750 × 350 12
(175)
AF/FM/2306-7 750 × 300 12
(175)
AF/FM/2306-8 750 × 200 12
(175)
AF/FM/2306-9 750 × 150 12
(175)
AF/FM/2306-10 750 × 50 12
(175)
AF/FM/2306-11 700 × 600 12
(175)
AF/FM/2306-12 700 × 500 12
(175)
AF/FM/2306-13 700 × 450 12
(175)
AF/FM/2306-14 700 × 400 12
(175)
AF/FM/2306-15 700 × 350 12
(175)
AF/FM/2306-16 700 × 300 12
(175)
AF/FM/2306-17 600 × 500 12
(175)
AF/FM/2306-18 600 × 450 12
(175)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-549
FM Approvals
September 2007 — Approval Guide
1-550 Automatic Sprinkler Systems
Flange
AF/FM/2307-1 750 12
(175)
AF/FM/2307-2 600 12
(175)
AF/FM/2307-3 500 12
(175)
AF/FM/2307-4 450 12
(175)
AF/FM/2307-5 400 12
(175)
AF/FM/2307-6 356 12
(175)
AF/FM/2307-7 300 12
(175)
AF/FM/2307-8 750 15
(220)
AF/FM/2307-9 600 15
(220)
AF/FM/2307-10 500 15
(220)
AF/FM/2307-11 450 15
(220)
AF/FM/2307-12 400 15
(220)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-551
AF/FM/2307-13 356 15
(220)
AF/FM/2307-14 300 15
(220)
D36793 4 * a, b, c
(100)
D36794 6 * a, b, c
(150)
D36795 8 * a, b, c
(200)
D36796 10 * a, b, c
(250)
D36798 12 * a, b, c
(300)
D36799 14 * a, b, c
(350)
D36800 16 * a, b, c
(400)
90° Elbow, 4 * a, b, d
45° Elbow, (100)
Equal Tees, 6
45°Lateral (150)
8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
Flange, 4 * a, b, i
Bolting Flange, (100)
ANSI B16.5, 6
Class 150 (150)
8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
Bondstrand Series 2212 Pipe.
D30563 8 * –
(200)
D30564 10 * –
(250)
D36982 12 * –
(300)
D36983 14 * –
(350)
D36977 16 * –
(400)
4 * e, f, g
(100)
6 * e, f, g
(150)
8 * e, f, g
(200)
10 * e, f, g
(250)
12 * e, f, g
(300)
FM Approvals
September 2007 — Approval Guide
1-552 Automatic Sprinkler Systems
14 * e, f, g
(350)
16 * e, f, g
(400)
18 * e, f, g
(450)
20 * e, f, g
(500)
24 * e, f, g
(600)
Key-Lock Ends
90° Elbow, 4 * h
45° Elbow, (100)
Equal Tees, 6
45°Lateral (150)
8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
18
(450)
20
(500)
24
(600)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-553
Coupling 4 * j
(100)
6
(150)
8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
18
(450)
20
(500)
24
(600)
Key-Lock Adapter 4 * l
(100)
6
(150)
8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
18
(450)
20
(500)
24
(600)
Concentric Reducer 2 x 4 in. through * h
14 x 16 in. (14 sizes)
90° Elbow, 4 * k
45° Elbow, (100)
Equal Tees, 6
45°Lateral (150)
Coupling 8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
18
(450)
20
(500)
24
(600)
FM Approvals
September 2007 — Approval Guide
1-554 Automatic Sprinkler Systems
Flange, 4 * b, k
Bolting Flange, (100)
ANSI B16.5, 6
Class 150 (150)
8
(200)
10
(250)
12
(300)
14
(350)
16
(400)
18
(450)
20
(500)
24
(600)
45° Elbow 8 14 b, g, k
90° Elbow (200) (203)
Equal Tee 10 14 b, g, k
(250) (203)
12 14 b, g, k
(300) (203)
14 14 b, g, k
(350) (203)
16 14 b, g, k
(400) (203)
45° Elbow 8 16 b, g, k
90° Elbow (200) (232)
Equal Tee 10 16 b, g, k
(250) (232)
12 16 b, g, k
(300) (232)
14 16 b, g, k
(350) (232)
16 16 b, g, k
(400) (232)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-555
45° Elbow 4 20 b, g, k
90° Elbow (100) (290)
Equal Tee
Composite Pipes Industry L.L.C., Post Box 30, Postal Code 327, Sohar Industrial Estate, Sohar, Sultanate of Oman
FM Approvals
September 2007 — Approval Guide
1-556 Automatic Sprinkler Systems
100 × 100 × 80 16 a
(232)
150 × 150 × 50 16 a
(232)
150 × 150 × 80 16 a
(232)
150 × 150 × 100 16 a
(232)
150 × 150 × 125 16 a
(232)
200 × 200 × 80 16 a
(232)
200 × 200 × 100 16 a
(232)
Fiberglass Pipe Co Ltd, Dammam, Second Industrial City, Box 589, Dammam, 31421, Kingdom of Saudi Arabia
Identification Size, Pressure Rating Remarks
mm (in.) bar (psi)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-557
450 12
(18) (175)
500 12
(20) (175)
FM Approvals
September 2007 — Approval Guide
1-558 Automatic Sprinkler Systems
Future Pipe Industries LLC, Mussafah Industrial Area, Box 29205, Mussafah, Abu Dhabi, United Arab Emirates
Product Nominal Pipe Pressure
Designation Size, in. Rating, psi Remarks
(kPa)
Pipe-Plain Ends
(for laminated joints) PL/PL
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-559
PIV-11 450 16 b
(232)
PIV-12 500 16 b
(232)
PIV-13 600 16 b
(232)
PIV-24 100 20 a
(290)
PIV-25 150 20 a
(290)
PIV-26 200 20 a
(290)
PIV-27 250 20 a
(290)
PIV-28 300 20 a
(290)
PIV-29 350 20 a
(290)
PIV-30 400 20 a
(290)
PIV-17 100 20 b
(290)
PIV-18 150 20 b
(290)
PIV-19 200 20 b
(290)
PIV-20 250 20 b
(290)
PIV-21 300 20 b
(290)
PIV-22 350 20 b
(290)
PIV-23 400 20 b
(290)
PIV-8 450 20 b
(290)
PIV-9 500 20 b
(290)
PIV-10 600 20 b
(290)
FM Approvals
September 2007 — Approval Guide
1-560 Automatic Sprinkler Systems
EL 17 450 12.5 a
(180)
EL 18 500 12.5 a
(180)
EL 19 600 12.5 a
(180)
EL90-24 450 16 b
(232)
EL90-25 500 16 b
(232)
EL90-26 600 16 b
(232)
EL90-30 100 20 b
(290)
EL90-31 150 20 b
(290)
EL90-32 200 20 b
(290)
EL90-33 250 20 b
(290)
EL90-34 300 20 b
(290)
EL90-35 350 20 b
(290)
EL90-36 400 20 b
(290)
EL90-21 450 20 b
(290)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-561
EL90-22 500 20 b
(290)
EL90-23 600 20 b
(290)
EL 14 450 12.5 a
(180)
EL 15 500 12.5 a
(180)
EL 16 600 12.5 a
(180)
EL45-24 450 16 b
(232)
EL45-25 500 16 b
(232)
EL45-26 600 16 b
(232)
EL45-30 100 20 b
(290)
EL45-31 150 20 b
(290)
EL45-32 200 20 b
(290)
EL45-33 250 20 b
(290)
EL45-34 300 20 b
(290)
EL45-35 350 20 b
(290)
EL45-36 400 20 b
(290)
FM Approvals
September 2007 — Approval Guide
1-562 Automatic Sprinkler Systems
EL45-21 450 20 b
(290)
EL45-22 500 20 b
(290)
EL45-23 600 20 b
(290)
ET 14 450 12.5 a
(180)
ET 15 500 12.5 a
(180)
ET 16 600 12.5 a
(180)
ET-24 450 16 b
(232)
ET-25 500 16 b
(232)
ET-26 600 16 b
(232)
ET-24-C 450 16 b
(232)
ET-25-C 500 16 b
(232)
ET-26-C 600 16 b
(232)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-563
ET-30 100 20 b
(290)
ET-31 150 20 b
(290)
ET-32 200 20 b
(290)
ET-33 250 20 b
(290)
ET-34 300 20 b
(290)
ET-35 350 20 b
(290)
ET-36 400 20 b
(290)
ET-21 450 20 b
(290)
ET-22 500 20 b
(290)
ET-23 600 20 b
(290)
ET-21-C 450 20 b
(290)
ET-22-C 500 20 b
(290)
ET-23-C 600 20 b
(290)
FM Approvals
September 2007 — Approval Guide
1-564 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-565
UT-21/K 500x450 16 b
(232)
UT-21/L 600x450 16 b
(232)
UT-21/M 600x500 16 b
(232)
UT-21/K-C 500x450 16 b
(232)
UT-21/L-C 600x450 16 b
(232)
UT-21/M-C 600x500 16 b
(232)
UT-22/H 150x100 20 b
(290)
UT-23/H 200x100 20 b
(290)
UT-23/I 200x150 20 b
(290)
UT-24/H 250x100 20 b
(290)
UT-24/I 250x150 20 b
(290)
UT-24/J 250x200 20 b
(290)
UT-25/H 300x100 20 b
(290)
UT-25/I 300x150 20 b
(290)
UT-25/J 300x200 20 b
(290)
UT-25/K 300x250 20 b
(290)
UT-26/H 350x100 20 b
(290)
UT-26/I 350x150 20 b
(290)
UT-26/J 350x200 20 b
(290)
UT-26/K 350x250 20 b
(290)
UT-26/L 350x300 20 b
(290)
UT-27/H 400x100 20 b
(290)
UT-27/I 400x150 20 b
(290)
UT-27/J 400x200 20 b
(290)
UT-27/K 400x250 20 b
(290)
UT-27/L 400x300 20 b
(290)
UT-27/M 400x350 20 b
(290)
UT-21/H 500x450 20 b
(290)
UT-21/I 600x450 20 b
(290)
UT-21/J 600x500 20 b
(290)
UT-21/H-C 500X450 20 b
(290)
UT-21/I-C 600x450 20 b
(290)
UT-21/J-C 600x500 20 b
(290)
FM Approvals
September 2007 — Approval Guide
1-566 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-567
CR-22/A-C 500x450 16 b
(232)
CR-25/A-C 600x450 16 b
(232)
CR-28/A-C 600x500 16 b
(232)
CR-30 150x100 20 b
(290)
CR-31 200x100 20 b
(290)
CR-32 200x150 20 b
(290)
CR-33 250x150 20 b
(290)
CR-34 250x200 20 b
(290)
CR-35 300x200 20 b
(290)
CR-36 300x250 20 b
(290)
CR-37 350x250 20 b
(290)
CR-38 350x300 20 b
(290)
CR-39 400x300 20 b
(290)
CR-40 400x350 20 b
(290)
CR-21/A-C 500x450 20 b
(290)
CR-24/A-C 600x450 20 b
(290)
CR-27/A-C 600x500 20 b
(290)
ER-1 150x100 20 b
(290)
ER-2 200x100 20 b
(290)
ER-3 200x150 20 b
(290)
ER-4 250x150 20 b
(290)
ER-5 250x200 20 b
(290)
ER-6 300x200 20 b
(290)
ER-7 300x250 20 b
(290)
ER-8 350x250 20 b
(290)
ER-9 350x300 20 b
(290)
ER-10 400x300 20 b
(290)
ER-11 400x350 20 b
(290)
Adaptor, TS/TS
FM Approvals
September 2007 — Approval Guide
1-568 Automatic Sprinkler Systems
Adaptor, TS/TS
Adaptor, TS/TS
Coupler, TB/TB
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-569
Coupler, TB/TB
Coupler, TB/TB
FL 1 450 12.5 a
(180)
FM Approvals
September 2007 — Approval Guide
1-570 Automatic Sprinkler Systems
FL 2 500 12.5 a
(180)
FL 3 600 12.5 a
(180)
F-23 450 16 b
(232)
F-24 500 16 b
(232)
F-25 600 16 b
(232)
F-23-C 450 16 b
(232)
F-24-C 500 16 b
(232)
F-25-C 600 16 b
(232)
F-29 100 20 b
(290)
F-30 150 20 b
(290)
F-31 200 20 b
(290)
F-32 250 20 b
(290)
F-33 300 20 b
(290)
F-34 350 20 b
(290)
F-35 400 20 b
(290)
F-20 450 20 b
(290)
F-21 500 20 b
(290)
F-22 600 20 b
(290)
F-20-C 450 20 b
(290)
F-21-C 500 20 b
(290)
F-22-C 600 20 b
(290)
Blind Flange, FL
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-571
BF 17 600 12.5
(180)
Blind Flange, FL
BF-1 100 16
(232)
BF-2 150 16
(232)
BF-3 200 16
(232)
BF-4 250 16
(232)
BF-5 300 16
(232)
BF-6 350 16
(232)
BF-7 400 16
(232)
BF-23 450 16
(232)
BF-24 500 16
(232)
BF-25 600 16
(232)
Blind Flange, FL
BF-29 100 20
(290)
BF-30 150 20
(290)
BF-31 200 20
(290)
BF-32 250 20
(290)
BF-33 300 20
(290)
BF-34 350 20
(290)
BF-35 400 20
(290)
BF-20 450 20
(290)
BF-21 500 20
(290)
BF-22 600 20
(290)
SdN-01 100 20 b, e
(290)
SdN-02 150 20 b, e
(290)
SdN-03 200 20 b, e
(290)
SdN-04 250 20 b, e
(290)
FM Approvals
September 2007 — Approval Guide
1-572 Automatic Sprinkler Systems
SdN-05 300 20 b, e
(290)
SdN-06 350 20 b, e
(290)
SdN-07 400 20 b, e
(290)
SLAM-01 100 20 a
(290)
SLAM-02 150 20 a
(290)
SLAM-03 200 20 a
(290)
SLAM-04 250 20 a
(290)
SLAM-05 300 20 a
(290)
SLAM-06 350 20 a
(290)
SLAM-07 400 20 a
(290)
a. Pipe lengths joined with Butt Wrap joint.
b. Joined by Easy Fit Wavistrong Adhesive.
c. Joints made with O-Ring seal and locking device.
d. Available with 1⁄4, 1⁄2, 3⁄4 and 1 in. nipple.
e. Available with 1⁄4, 1⁄2 and 3⁄4 nipple.
Future Pipe Industries (SAE), Industrial Zone 5, Box 96, Postal Zone 12573, 6th of October City, Egypt
Product Nominal Pipe Pressure
Designation Size, mm Rating* Remarks
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-573
FM Approvals
September 2007 — Approval Guide
1-574 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-575
FM Approvals
September 2007 — Approval Guide
1-576 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-577
FM Approvals
September 2007 — Approval Guide
1-578 Automatic Sprinkler Systems
a. Spigot end(s).
b. Socket end(s).
c. Spigot end(s) × Socket end(s).
e. Bolt holes according to ASA150.
f. 6 m (20 ft) length.
g. 10 m (33 ft) length.
h. 12 m (40 ft) length.
m. Plain end(s).
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-579
n. Saddle cemented.
o. Saddle laminated.
Future Pipe Industries BV, JC Kellerlaan 3, Box 255, 7770 AG Hardenberg, The Netherlands
LJ (Laminate) Jointed System.
Pipe
12.3.08.15 80 EST40/FM40 m, f
12.3.08.14 80 EST40/FM40 m, g
11.3.08.05 80 EST32/FM32 m, f
11.3.10.51 100 EST25/FM20 m, f
11.3.15.51 150 EST25/FM20 m, f
11.3.15.50 150 EST25/FM20 m, g
11.3.20.51 200 EST25/FM20 m, f
11.3.20.50 200 EST25/FM20 m, g
11.3.25.51 250 EST25/FM20 m, f
11.3.25.50 250 EST25/FM20 m, g
Fittings — Coupling
32.4.08.70 80 EST40/FM40 b, p
32.4.08.70 80 EST40/FM40 b, p
31.4.08.35 80 EST32/FM32 b
31.4.13.50 100 EST25/FM20 b
31.4.18.50 150 EST25/FM20 b
31.4.23.50 200 EST25/FM20 b
31.4.28.50 250 EST25/FM20 b
31.4.23.40 200 EST20/FM16 b
31.4.28.40 250 EST20/FM16 b
31.4.33.40 300 EST20/FM16 b
31.4.38.40 350 EST20/FM16 b
31.4.43.40 400 EST20/FM16 b
Fittings — Adapter
32.4.05.71 50 EST40/FM40 a, p
31.4.05.45 50 EST32/FM32 a
31.4.08.45 80 EST32/FM32 a
32.4.08.71 80 EST40/FM40 a, p
31.4.14.50 100 EST25/FM20 a
31.4.19.50 150 EST25/FM20 a
31.4.24.50 200 EST25/FM20 a
31.4.29.50 250 EST25/FM20 a
31.4.24.40 200 EST20/FM16 b
FM Approvals
September 2007 — Approval Guide
1-580 Automatic Sprinkler Systems
Fittings — Lateral
11.4.24.40 200 EST20/FM16 b
11.4.29.40 250 EST20/FM16 b
11.4.34.40 300 EST20/FM16 b
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-581
Fittings — Flange
25.4.05.70 50 EST40/FM40 b, e, p
21.4.05.35 50 EST32/FM32 b, e
21.4.08.35 80 EST32/FM32 b, e
25.4.08.70 80 EST40/FM40 b, e, p
21.4.13.50 100 EST25/FM20 b, e
21.4.18.50 150 EST25/FM20 b, e
21.4.23.50 200 EST25/FM20 b, e
21.4.28.50 250 EST25/FM20 b, e
21.4.23.40 200 EST20/FM16 b, e
21.4.28.40 250 EST20/FM16 b, e
21.4.33.40 300 EST20/FM16 b, e
21.4.23.42 200 EST20/FM16 b, l
21.4.28.42 250 EST20/FM16 b, l
21.4.33.42 300 EST20/FM16 b, l
21.4.24.40 200 EST20/FM16 b, e
21.4.29.40 250 EST20/FM16 b, e
21.4.34.40 300 EST20/FM16 b, e
21.4.24.42 200 EST20/FM16 b, l
21.4.29.42 250 EST20/FM16 b, l
21.4.34.42 300 EST20/FM16 b, l
Fittings — Adapter
31.4.21.40 200 EST20/FM16 b
31.4.26.40 250 EST20/FM16 b
31.4.31.40 300 EST20/FM16 b
31.4.36.40 350 EST20/FM16 b
FM Approvals
September 2007 — Approval Guide
1-582 Automatic Sprinkler Systems
Fittings — Lateral
11.4.22.40 200 EST20/FM16 c
11.4.27.40 250 EST20/FM16 c
11.4.32.40 300 EST20/FM16 c
Fittings — Flange
21.4.21.40 200 EST20/FM16 b, e
21.4.26.40 250 EST20/FM16 b, e
21.4.31.40 300 EST20/FM16 b, e
21.4.21.42 200 EST20/FM16 b, e
21.4.26.42 250 EST20/FM16 b, e
21.4.31.42 300 EST20/FM16 b, e
21.4.36.42 350 EST20/FM16 b, e
21.4.41.42 400 EST20/FM16 b, e
21.4.21.43 200 EST20/FM16 b, l
21.4.26.43 250 EST20/FM16 b, l
21.4.31.43 300 EST20/FM16 b, l
21.4.22.40 200 EST20/FM16 a, e
21.4.27.40 250 EST20/FM16 a, e
21.4.32.40 300 EST20/FM16 a, e
21.4.22.42 200 EST20/FM16 a, l
21.4.26.42 250 EST20/FM16 a, l
21.4.32.42 300 EST20/FM16 a, l
CE (cement) jointed system. Joints must be made with cement kit stock number 79.4.00.21.
Pipe
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-583
Fittings.
Coupling
31.4.13.50 100 EST 25 / FM 16 b
31.4.18.40 150 EST 20 / FM 16 b
31.4.23.30 200 EST 16 / FM 12.5 b
31.4.28.30 250 EST 16 / FM 12.5 b
31.4.33.30 300 EST 16 / FM 12.5 b
31.4.38.30 350 EST 16 / FM 12.5 b
31.4.43.30 400 EST 16 / FM 12.5 b
31.4.28.20 250 EST 12.5 / FM 10 b
31.4.33.20 300 EST 12.5 / FM 10 b
31.4.38.20 350 EST 12.5 / FM 10 b
31.4.43.20 400 EST 12.5 / FM 10 b
Adapter
31.4.14.50 100 EST 25 / FM 16 a
31.4.19.40 150 EST 20 / FM 16 a
31.4.24.30 200 EST 16 / FM 12.5 a
31.4.29.30 250 EST 16 / FM 12.5 a
31.4.34.30 300 EST 16 / FM 12.5 a
31.4.39.30 350 EST 16 / FM 12.5 a
31.4.44.30 400 EST 16 / FM 12.5 a
31.4.29.20 250 EST 12.5 / FM 10 a
31.4.34.20 300 EST 12.5 / FM 10 a
31.4.39.20 350 EST 12.5 / FM 10 a
31.4.44.20 400 EST 12.5 / FM 10 a
90° Elbow
01.4.13.50 100 EST 25 / FM 16 b
01.4.18.40 150 EST 20 / FM 16 b
01.4.38.40 350 EST 20 / FM 16 b
01.4.43.40 400 EST 20 / FM 16 b
01.4.23.30 200 EST 16 / FM 12.5 b
01.4.28.30 250 EST 16 / FM 12.5 b
01.4.33.30 300 EST 16 / FM 12.5 b
01.4.38.30 350 EST 16 / FM 12.5 b
01.4.43.30 400 EST 16 / FM 12.5 b
01.4.28.20 250 EST 12.5 / FM 10 b
01.4.33.20 300 EST 12.5 / FM 10 b
01.4.38.20 350 EST 12.5 / FM 10 b
01.4.48.20 400 EST 12.5 / FM 10 b
45° Elbow
01.4.14.50 100 EST 25 / FM 16 b
01.4.19.40 150 EST 20 / FM 16 b
01.4.39.40 350 EST 20 / FM 16 b
01.4.44.40 400 EST 20 / FM 16 b
01.4.24.30 200 EST 16 / FM 12.5 b
01.4.29.30 250 EST 16 / FM 12.5 b
01.4.34.30 300 EST 16 / FM 12.5 b
FM Approvals
September 2007 — Approval Guide
1-584 Automatic Sprinkler Systems
Tee
11.4.13.50 100 EST 25 / FM 16 b
11.4.18.40 150 EST 20 / FM 16 b
11.4.38.40 350 EST 20 / FM 16 b
11.4.43.40 400 EST 20 / FM 16 b
11.4.23.30 200 EST 16 / FM 12.5 b
11.4.28.30 250 EST 16 / FM 12.5 b
11.4.33.30 300 EST 16 / FM 12.5 b
11.4.38.30 350 EST 16 / FM 12.5 b
11.4.43.30 400 EST 16 / FM 12.5 b
11.4.28.20 250 EST 12.5 / FM 10 b
11.4.33.20 300 EST 12.5 / FM 10 b
11.4.38.20 350 EST 12.5 / FM 10 b
11.4.43.20 400 EST 12.5 / FM 10 b
Tee Reducing
11.4.28.23 250, 250, 100 EST 12.5 / FM 10 b
11.4.28.22 250, 250, 150 EST 12.5 / FM 10 b
11.4.28.21 250, 250, 200 EST 12.5 / FM 10 b
11.4.33.24 300, 300, 100 EST 12.5 / FM 10 b
11.4.33.23 300, 300, 150 EST 12.5 / FM 10 b
11.4.33.22 300, 300, 200 EST 12.5 / FM 10 b
11.4.33.21 300, 300, 250 EST 12.5 / FM 10 b
11.4.38.25 350, 350, 100 EST 12.5 / FM 10 b
11.4.38.24 350, 350, 150 EST 12.5 / FM 10 b
11.4.38.23 350, 350, 200 EST 12.5 / FM 10 b
11.4.38.22 350, 350, 250 EST 12.5 / FM 10 b
11.4.38.21 350, 350, 300 EST 12.5 / FM 10 b
11.4.43.26 400, 400, 100 EST 12.5 / FM 10 b
11.4.43.25 400, 400, 150 EST 12.5 / FM 10 b
11.4.43.24 400, 400, 200 EST 12.5 / FM 10 b
11.4.43.23 400, 400, 250 EST 12.5 / FM 10 b
11.4.43.22 400, 400, 300 EST 12.5 / FM 10 b
11.4.43.21 400, 400, 350 EST 12.5 / FM 10 b
11.4.23.32 200, 200, 100 EST 16 / FM 12.5 b
11.4.23.31 200, 200, 150 EST 16 / FM 12.5 b
11.4.28.33 250, 250, 100 EST 16 / FM 12.5 b
11.4.28.32 250, 250, 150 EST 16 / FM 12.5 b
11.4.28.31 250, 250, 200 EST 16 / FM 12.5 b
11.4.33.34 300, 300, 100 EST 16 / FM 12.5 b
11.4.33.33 300, 300, 100 EST 16 / FM 12.5 b
11.4.33.32 300, 300, 200 EST 16 / FM 12.5 b
11.4.33.31 300, 300, 250 EST 16 / FM 12.5 b
11.4.38.35 350, 350, 100 EST 16 / FM 12.5 b
11.4.38.34 350, 350, 150 EST 16 / FM 12.5 b
11.4.38.33 350, 350, 200 EST 16 / FM 12.5 b
11.4.38.32 350, 350, 250 EST 16 / FM 12.5 b
11.4.38.31 350, 350, 300 EST 16 / FM 12.5 b
11.4.43.36 400, 400, 100 EST 16 / FM 12.5 b
11.4.43.35 400, 400, 250 EST 16 / FM 12.5 b
11.4.43.34 400, 400, 200 EST 16 / FM 12.5 b
11.4.43.33 400, 400, 250 EST 16 / FM 12.5 b
11.4.43.32 400, 400, 300 EST 16 / FM 12.5 b
11.4.43.31 400, 400, 350 EST 16 / FM 12.5 b
11.4.18.41 150, 150, 100 EST 20 / FM 16 b
11.4.38.45 350, 350, 100 EST 20 / FM 16 b
11.4.38.44 350, 350, 150 EST 20 / FM 16 b
11.4.38.43 350, 350, 200 EST 20 / FM 16 b
11.4.38.42 350, 350, 250 EST 20 / FM 16 b
11.4.38.41 350, 350, 300 EST 20 / FM 16 b
11.4.43.46 400, 400, 100 EST 20 / FM 16 b
11.4.43.45 400, 400, 150 EST 20 / FM 16 b
11.4.43.44 400, 400, 200 EST 20 / FM 16 b
11.4.43.43 400, 400, 250 EST 20 / FM 16 b
11.4.43.42 400, 400, 300 EST 20 / FM 16 b
11.4.43.41 400, 400, 350 EST 20 / FM 16 b
Lateral
11.4.14.50 100 EST 25 / FM 16 b
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-585
Concentric Reducer
41.4.28.22 250, 150 EST 12.5 / FM 10 b
41.4.28.21 250, 200 EST 12.5 / FM 10 b
41.4.33.22 300, 200 EST 12.5 / FM 10 b
41.4.33.21 300, 250 EST 12.5 / FM 10 b
41.4.38.22 350, 250 EST 12.5 / FM 10 b
41.4.38.21 350, 300 EST 12.5 / FM 10 b
41.4.43.22 400, 300 EST 12.5 / FM 10 b
41.4.43.21 400, 350 EST 12.5 / FM 10 b
41.4.28.31 250, 200 EST 16 / FM 12.5 b
41.4.33.32 300, 200 EST 16 / FM 12.5 b
41.4.33.31 300, 250 EST 16 / FM 12.5 b
41.4.38.32 350, 250 EST 16 / FM 12.5 b
41.4.38.31 350, 300 EST 16 / FM 12.5 b
41.4.43.32 400, 300 EST 16 / FM 12.5 b
41.4.43.31 400, 350 EST 16 / FM 12.5 b
41.4.18.41 150, 100 EST 20 / FM 16 b
41.4.38.42 350, 250 EST 20 / FM 16 b
41.4.38.41 350, 300 EST 20 / FM 16 b
41.4.43.42 400, 300 EST 20 / FM 16 b
41.4.43.41 400, 350 EST 20 / FM 16 b
Eccentric Reducer
41.4.29.22 250, 150 EST 12.5 / FM 10 b
41.4.29.21 250, 200 EST 12.5 / FM 10 b
41.4.34.22 300, 200 EST 12.5 / FM 10 b
41.4.34.21 300, 250 EST 12.5 / FM 10 b
41.4.39.22 350, 250 EST 12.5 / FM 10 b
41.4.39.21 350, 300 EST 12.5 / FM 10 b
41.4.44.22 400, 300 EST 12.5 / FM 10 b
41.4.44.31 400, 350 EST 12.5 / FM 10 b
41.4.24.32 200, 100 EST 16 / FM 12.5 b
41.4.24.31 200, 150 EST 16 / FM 12.5 b
41.4.29.32 250, 150 EST 16 / FM 12.5 b
41.4.29.31 250, 200 EST 16 / FM 12.5 b
41.4.34.32 300, 200 EST 16 / FM 12.5 b
41.4.34.31 300, 250 EST 16 / FM 12.5 b
41.4.39.32 350, 250 EST 16 / FM 12.5 b
41.4.39.31 350, 300 EST 16 / FM 12.5 b
41.4.44.32 400, 300 EST 16 / FM 12.5 b
41.4.44.31 400, 350 EST 16 / FM 12.5 b
41.4.19.41 150, 100 EST 20 / FM 16 b
41.4.39.42 350, 250 EST 20 / FM 16 b
41.4.39.41 350, 300 EST 20 / FM 16 b
41.4.44.42 400, 300 EST 20 / FM 16 b
41.4.44.41 400, 350 EST 20 / FM 16 b
Short Reducer
41.4.28.23 250, 150 EST 12.5 / FM 10 c
41.4.28.24 250, 200 EST 12.5 / FM 10 c
41.4.33.23 300, 200 EST 12.5 / FM 10 c
41.4.33.24 300, 250 EST 12.5 / FM 10 c
41.4.38.23 350, 250 EST 12.5 / FM 10 c
41.4.38.24 350, 300 EST 12.5 / FM 10 c
41.4.43.23 400, 300 EST 12.5 / FM 10 c
41.4.43.24 400, 350 EST 12.5 / FM 10 c
41.4.23.33 200, 100 EST 16 / FM 12.5 c
41.4.23.34 200, 150 EST 16 / FM 12.5 c
41.4.28.33 250, 150 EST 16 / FM 12.5 c
41.4.28.34 250, 200 EST 16 / FM 12.5 c
41.4.33.33 300, 200 EST 16 / FM 12.5 c
41.4.33.34 300, 250 EST 16 / FM 12.5 c
41.4.38.33 350, 250 EST 16 / FM 12.5 c
41.4.38.34 350, 300 EST 16 / FM 12.5 c
41.4.43.33 400, 300 EST 16 / FM 12.5 c
41.4.43.34 400, 350 EST 16 / FM 12.5 c
41.4.18.44 150, 100 EST 20 / FM 16 c
Flange
FM Approvals
September 2007 — Approval Guide
1-586 Automatic Sprinkler Systems
Blind Flange
51.4.10.40 100 EST 25 / FM 16 e
51.4.15.40 150 EST 20 / FM 16 e
51.4.35.40 350 EST 20 / FM 16 e
51.4.40.40 400 EST 20 / FM 16 e
51.4.20.30 200 EST 16 / FM 12.5 e
51.4.25.30 250 EST 16 / FM 12.5 e
51.4.30.30 300 EST 16 / FM 12.5 e
51.4.35.30 350 EST 16 / FM 12.5 e
51.4.40.30 400 EST 16 / FM 12.5 e
51.4.35.20 350 EST 12.5 / FM 10 e
51.4.40.20 400 EST 12.5 / FM 10 e
51.4.10.52 100 EST 25 / FM 16 i
51.4.15.42 150 EST 20 / FM 16 i
51.4.35.42 350 EST 20 / FM 16 i
51.4.40.42 400 EST 20 / FM 16 i
51.4.20.32 200 EST 16 / FM 12.5 i
51.4.25.32 250 EST 16 / FM 12.5 i
51.4.30.32 300 EST 16 / FM 12.5 i
51.4.35.32 350 EST 16 / FM 12.5 i
51.4.40.32 400 EST 16 / FM 12.5 i
51.4.35.22 350 EST 12.5 / FM 10 i
51.4.40.22 400 EST 12.5 / FM 10 i
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-587
RSLJ (rubber seal, lock joint) socket and spigot system. Joints are made using a rubber ring and a pvc cotter strip. Provides integral restraint
against hydraulic forces.
Pipe
11.3.21.20 200 EST 12.5 / FM 10 c, g
11.3.26.21 250 EST 12.5 / FM 10 c, f
11.3.26.20 250 EST 12.5 / FM 10 c, g
11.3.31.20 300 EST 12.5 / FM 10 c, g
11.3.36.20 350 EST 12.5 / FM 10 c, g
11.3.41.20 400 EST 12.5 / FM 10 c, g
11.3.11.51 100 EST 25 / FM 16 c, f
11.3.16.41 150 EST 20 / FM 16 c, f
11.3.21.40 150 EST 20 / FM 16 c, g
11.3.26.31 250 EST 16 / FM 12.5 c, f
11.3.26.30 250 EST 16 / FM 12.5 c, g
11.3.31.30 300 EST 16 / FM 12.5 c, g
11.3.36.30 350 EST 16 / FM 12.5 c, g
11.3.41.30 400 EST 16 / FM 12.5 c, g
11.3.21.30 200 EST 16 / FM 12.5 c, g
11.3.21.31 200 EST 16 / FM 12.5 c, f
Adapter
31.4.26.20 250 EST 12.5 / FM 10 b
31.4.31.20 300 EST 12.5 / FM 10 b
31.4.36.20 350 EST 12.5 / FM 10 b
31.4.41.20 400 EST 12.5 / FM 10 b
31.4.21.30 200 EST 16 / FM 12.5 b
31.4.26.30 250 EST 16 / FM 12.5 b
31.4.31.30 300 EST 16 / FM 12.5 b
31.4.36.30 350 EST 16 / FM 12.5 b
31.4.41.30 400 EST 16 / FM 12.5 b
31.4.11.50 100 EST 25 / FM 16 b
31.4.16.40 150 EST 20 / FM 16 b
31.4.27.20 250 EST 12.5 / FM 10 a
31.4.32.20 300 EST 12.5 / FM 10 a
31.4.37.20 350 EST 12.5 / FM 10 a
31.4.42.20 400 EST 12.5 / FM 10 a
31.4.22.30 200 EST 16 / FM 12.5 a
31.4.27.30 250 EST 16 / FM 12.5 a
31.4.32.30 300 EST 16 / FM 12.5 a
31.4.37.30 350 EST 16 / FM 12.5 a
31.4.42.30 400 EST 16 / FM 12.5 a
31.4.12.50 100 EST 25 / FM 16 a
Spools
**67.4.xx.xx All sizes All pressure ratings
**68.4.xx.xx All sizes All pressure ratings
90° Elbow
01.4.26.20 250 EST 12.5 / FM 10 c
01.4.31.20 300 EST 12.5 / FM 10 c
01.4.36.20 350 EST 12.5 / FM 10 c
01.4.41.20 400 EST 12.5 / FM 10 c
01.4.21.30 200 EST 16 / FM 12.5 c
01.4.26.30 250 EST 16 / FM 12.5 c
01.4.31.30 300 EST 16 / FM 12.5 c
01.4.36.30 350 EST 16 / FM 12.5 c
01.4.41.30 400 EST 16 / FM 12.5 c
01.4.11.40 100 EST 25 / FM 16 c
01.4.16.40 150 EST 20 / FM 16 c
01.4.36.40 350 EST 20 / FM 16 c
01.4.42.40 400 EST 20 / FM 16 c
45° Elbow
01.4.27.20 250 EST 12.5 / FM 10 c
01.4.32.20 300 EST 12.5 / FM 10 c
01.4.37.20 350 EST 12.5 / FM 10 c
01.4.42.20 400 EST 12.5 / FM 10 c
01.4.22.30 200 EST 16 / FM 12.5 c
01.4.27.30 250 EST 16 / FM 12.5 c
01.4.32.30 300 EST 16 / FM 12.5 c
01.4.37.30 350 EST 16 / FM 12.5 c
01.4.42.30 400 EST 16 / FM 12.5 c
01.4.12.50 100 EST 25 / FM 16 c
01.4.17.40 150 EST 20 / FM 16 c
FM Approvals
September 2007 — Approval Guide
1-588 Automatic Sprinkler Systems
Tee
11.4.26.20 250 EST 12.5 / FM 10 c
11.4.31.20 300 EST 12.5 / FM 10 c
11.4.36.20 350 EST 12.5 / FM 10 c
11.4.41.20 400 EST 12.5 / FM 10 c
11.4.21.30 200 EST 16 / FM 12.5 c
11.4.26.30 250 EST 16 / FM 12.5 c
11.4.31.30 300 EST 16 / FM 12.5 c
11.4.36.30 350 EST 16 / FM 12.5 c
11.4.41.30 400 EST 16 / FM 12.5 c
11.4.11.50 100 EST 25 / FM 16 c
11.4.16.40 150 EST 20 / FM 16 c
11.4.36.40 350 EST 20 / FM 16 c
11.4.41.40 400 EST 20 / FM 16 c
Tee-Reducing
11.4.26.23 250, 250, 100 EST 12.5 / FM 10 c
11.4.26.22 250, 250, 150 EST 12.5 / FM 10 c
11.4.26.21 250, 250, 200 EST 12.5 / FM 10 c
11.4.31.24 300, 300, 100 EST 12.5 / FM 10 c
11.4.31.23 300, 300, 150 EST 12.5 / FM 10 c
11.4.31.22 300, 300, 200 EST 12.5 / FM 10 c
11.4.31.21 300, 300, 350 EST 12.5 / FM 10 c
11.4.36.25 350, 350, 100 EST 12.5 / FM 10 c
11.4.36.24 350, 350, 150 EST 12.5 / FM 10 c
11.4.36.23 350, 350, 200 EST 12.5 / FM 10 c
11.4.36.22 350, 350, 250 EST 12.5 / FM 10 c
11.4.36.21 350, 350, 300 EST 12.5 / FM 10 c
11.4.41.26 400, 400, 100 EST 12.5 / FM 10 c
11.4.41.25 400, 400, 150 EST 12.5 / FM 10 c
11.4.41.24 400, 400, 200 EST 12.5 / FM 10 c
11.4.41.23 400, 400, 250 EST 12.5 / FM 10 c
11.4.41.22 400, 400, 300 EST 12.5 / FM 10 c
11.4.41.21 400, 400, 350 EST 12.5 / FM 10 c
11.4.21.32 200, 200, 100 EST 16 / FM 12.5 c
11.4.21.31 200, 200, 150 EST 16 / FM 12.5 c
11.4.26.33 250, 250, 100 EST 16 / FM 12.5 c
11.4.26.32 250, 250, 150 EST 16 / FM 12.5 c
11.4.26.31 250, 250, 200 EST 16 / FM 12.5 c
11.4.31.34 300, 300, 100 EST 16 / FM 12.5 c
11.4.31.33 300, 300, 150 EST 16 / FM 12.5 c
11.4.31.32 300, 300, 200 EST 16 / FM 12.5 c
11.4.31.31 300, 300, 250 EST 16 / FM 12.5 c
11.4.36.35 350, 350, 100 EST 16 / FM 12.5 c
11.4.36.34 350, 350, 150 EST 16 / FM 12.5 c
11.4.36.33 350, 350, 200 EST 16 / FM 12.5 c
11.4.36.32 350, 350, 250 EST 16 / FM 12.5 c
11.4.41.31 350, 350, 300 EST 16 / FM 12.5 c
11.4.41.36 400, 400, 100 EST 16 / FM 12.5 c
11.4.41.35 400, 400, 150 EST 16 / FM 12.5 c
11.4.41.34 400, 400, 200 EST 16 / FM 12.5 c
11.4.41.33 400, 400, 250 EST 16 / FM 12.5 c
11.4.41.32 400, 400, 300 EST 16 / FM 12.5 c
11.4.41.31 400, 400, 350 EST 16 / FM 12.5 c
11.4.16.41 150, 150, 100 EST 20 / FM 16 c
11.4.36.45 350, 350, 100 EST 20 / FM 16 c
11.4.36.44 350, 350, 150 EST 20 / FM 16 c
11.4.36.43 350, 350, 200 EST 20 / FM 16 c
11.4.36.42 350, 350, 250 EST 20 / FM 16 c
11.4.36.41 350, 350, 300 EST 20 / FM 16 c
11.4.41.46 400, 400, 100 EST 20 / FM 16 c
11.4.41.45 400, 400, 150 EST 20 / FM 16 c
11.4.41.44 400, 400, 200 EST 20 / FM 16 c
11.4.41.43 400, 400, 250 EST 20 / FM 16 c
11.4.41.42 400, 400, 300 EST 20 / FM 16 c
11.4.41.41 400, 400, 350 EST 20 / FM 16 c
Lateral
11.4.27.20 250 EST 12.5 / FM 10 c
11.4.32.20 300 EST 12.5 / FM 10 c
11.4.22.30 200 EST 16 / FM 12.5 c
11.4.27.30 250 EST 16 / FM 12.5 c
11.4.32.30 300 EST 16 / FM 12.5 c
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-589
Concentric Reducer
41.4.26.22 250, 150 EST 12.5 / FM 10 c
41.4.26.21 250, 200 EST 12.5 / FM 10 c
41.4.31.22 300, 200 EST 12.5 / FM 10 c
41.4.31.21 300, 250 EST 12.5 / FM 10 c
41.4.36.22 350, 250 EST 12.5 / FM 10 c
41.4.36.21 350, 300 EST 12.5 / FM 10 c
41.4.41.22 400, 300 EST 12.5 / FM 10 c
41.4.41.21 400, 350 EST 12.5 / FM 10 c
41.4.21.32 200, 100 EST 16 / FM 12.5 c
41.4.21.31 200, 150 EST 16 / FM 12.5 c
41.4.26.32 250, 150 EST 16 / FM 12.5 c
41.4.26.31 250, 200 EST 16 / FM 12.5 c
41.4.31.32 300, 200 EST 16 / FM 12.5 c
41.4.31.31 300, 250 EST 16 / FM 12.5 c
41.4.36.32 350, 250 EST 16 / FM 12.5 c
41.4.36.31 350, 300 EST 16 / FM 12.5 c
41.4.41.32 400, 300 EST 16 / FM 12.5 c
41.4.41.31 400, 350 EST 16 / FM 12.5 c
41.4.16.41 150, 100 EST 20 / FM 16 c
41.4.36.42 350, 250 EST 20 / FM 16 c
41.4.36.41 350, 300 EST 20 / FM 16 c
41.4.41.42 400, 300 EST 20 / FM 16 c
41.4.41.41 400, 350 EST 20 / FM 16 c
Eccentric Reducer
41.4.27.22 250, 150 EST 12.5 / FM 10 c
41.4.27.21 250, 200 EST 12.5 / FM 10 c
41.4.32.22 300, 200 EST 12.5 / FM 10 c
41.4.32.21 300, 250 EST 12.5 / FM 10 c
41.4.37.22 350, 250 EST 12.5 / FM 10 c
41.4.37.21 350, 300 EST 12.5 / FM 10 c
41.4.42.22 400, 300 EST 12.5 / FM 10 c
41.4.42.21 400, 350 EST 12.5 / FM 10 c
41.4.22.32 200, 100 EST 16 / FM 12.5 c
41.4.22.31 200, 150 EST 16 / FM 12.5 c
41.4.27.32 250, 150 EST 16 / FM 12.5 c
41.4.27.31 250, 200 EST 16 / FM 12.5 c
41.4.32.32 300, 200 EST 16 / FM 12.5 c
41.4.32.31 300, 250 EST 16 / FM 12.5 c
41.4.37.32 350, 250 EST 16 / FM 12.5 c
41.4.37.31 350, 300 EST 16 / FM 12.5 c
41.4.42.32 400, 300 EST 16 / FM 12.5 c
41.4.42.32 400, 350 EST 16 / FM 12.5 c
41.4.17.41 150, 100 EST 20 / FM 16 c
41.4.37.42 350, 250 EST 20 / FM 16 c
41.4.37.41 350, 300 EST 20 / FM 16 c
41.4.42.42 400, 300 EST 20 / FM 16 c
41.4.42.41 400, 350 EST 20 / FM 16 c
Flange
21.4.11.50 100 EST 25 / FM 16 b, e
21.4.16.40 150 EST 20 / FM 16 b, e
21.4.36.40 350 EST 20 / FM 16 b, e
21.4.41.40 400 EST 20 / FM 16 b, e
21.4.21.30 200 EST 16 / FM 12.5 b, e
21.4.26.30 250 EST 16 / FM 12.5 b, e
21.4.31.30 300 EST 16 / FM 12.5 b, e
21.4.36.30 350 EST 16 / FM 12.5 b, e
21.4.41.30 400 EST 16 / FM 12.5 b, e
21.4.11.52 100 EST 25 / FM 16 b, e
21.4.16.42 150 EST 20 / FM 16 b, e
21.4.26.20 250 EST 12.5 / FM 10 b, e
21.4.31.20 300 EST 12.5 / FM 10 b, e
21.4.36.43 350 EST 20 / FM 16 b, l
21.4.41.43 400 EST 20 / FM 16 b, l
21.4.21.32 200 EST 16 / FM 12.5 b, l
21.4.26.32 250 EST 16 / FM 12.5 b, l
21.4.31.32 300 EST 16 / FM 12.5 b, l
21.4.36.32 350 EST 16 / FM 12.5 b, l
21.4.41.32 400 EST 16 / FM 12.5 b, l
21.4.26.22 250 EST 12.5 / FM 10 b, l
21.4.31.22 300 EST 12.5 / FM 10 b, l
FM Approvals
September 2007 — Approval Guide
1-590 Automatic Sprinkler Systems
Adapters 3, 4 365 k
(80, 100) (2515)
6 290 k
(150) (2000)
8, 10 180 k
(200, 250) (1240)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-591
12 175 k
(300) (1205)
Flanges 3, 4 365 k
(w/socket ends) (80, 100) (2515)
6 290 k
(150) (2000)
8, 10 180 k
(200, 250) (1240)
12 175 k
(300) (1205)
Coupler 3 365 k
(80) (2515)
4, 6 290 k
(100, 150) (2000)
8, 10, 12 180 k
(200, 250, 300) (1240)
*Pressure ratings are determined by the ‘‘FM’’ part of the number. The ‘‘EST’’ designation refers to the manufacturer’s commercial (non-fire protection) ratings for
these products. Specifically, FM 10 rated items are FM Approved for 10 bar (150 psi) service; FM 12.5 for 12.5 bar (180 psi); FM 16 for 16 bar (230 psi), etc.
**This product designation is assigned to various system assemblies fabricated from FM Approved products at the manufacturer’s facilities. Each design variation
will be identified by manufacturer, with four additional digits following the four listed above. The list of ‘‘Spools’’ will be available from the manufacturer.
Future Pipe Industries LLC-KSA, Box 8513, Dammam 31492, Kingdom of Saudi Arabia
Product Nominal Pipe Pressure Rating
Designation Size, mm bar (psi) Remarks
FM Approvals
September 2007 — Approval Guide
1-592 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-593
FM Approvals
September 2007 — Approval Guide
1-594 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-595
FM Approvals
September 2007 — Approval Guide
1-596 Automatic Sprinkler Systems
Blind Flange, FL
Reducing Saddle, CS
Epoxy Pipe
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-597
P-4 80 465 a
(3200)
P-5 100 365 a
(2500)
P-6 150 290 a
(2000)
Epoxy Fittings.
Elbows (90° and 45°)
EL 13, 12 300 230 e
(1600)
EL 7 250 180 e
(1240)
EL 6 200 180 e
(1240)
EL 5 150 180 e
(1240)
EL 4 100 365 e
(2515)
EL 3 80 365 e
(2515)
Concentric Reducers
CR 18 300×250 230 e
(1600)
CR 17 300×200 230 e
(1600)
CR 7 250×200 175 e
(1205)
CR 6 250×150 175 e
(1205)
CR 5 200×150 175 e
(1205)
CR 4 200×100 175 e
(1205)
CR 12 150×100 290 e
(2000)
CR 11 150×80 290 e
(2000)
CR 1 100×80 365 e
(2515)
Equal Tees
ET 13 300×300 230 e
(1600)
ET 7 250×250 180 e
(1240)
ET 6 200×200 180 e
(1240)
ET 5 150×150 180 e
(1240)
ET 4 100×100 290 e
(2000)
ET 3 80×80 365 e
(2515)
Unequal Tees
UT 38 300×250 230 e
(1600)
UT 37 300×200 230 e
(1600)
UT 36 300×150 230 e
(1600)
UT 35 300×100 230 e
(1600)
UT 34 300×80 230 e
(1600)
UT 19 250×200 180 e
(1240)
UT 18 250×150 180 e
(1240)
UT 17 250×100 180 e
(1240)
UT 16 250×80 180 e
(1240)
UT 14 200×150 180 e
(1240)
UT 13 200×100 180 e
(1240)
UT 12 200×80 180 e
(1240)
UT 11 150×100 180 e
(1240)
UT 10 150×80 180 e
(1240)
UT 9 100×80 290 e
(2000)
Flange (w/socket end)
FM Approvals
September 2007 — Approval Guide
1-598 Automatic Sprinkler Systems
FS 3 80 465 e
(3200)
FS 5 100 365 e
(2500)
FS 10 150 290 e
(2000)
FS 11 200 230 e
(1600)
FS 12 250 230 e
(1600)
FS 13 300 230 e
(1600)
Blind Flanges
BF 4 80 465 e, f
(3200)
BF 5 100 365 e, f
(2500)
BF 11 150 290 e, f
(2000)
BF 12 200 230 e, f
(1600)
BF 13 250 230 e, f
(1600)
BF 14 300 230 e, f
(1600)
GEI/FM/541001-1 350 150 e, f
(1050)
GEI/FM/541001-2 400 150 e, f
(1050)
GEI/FM/541001-3 450 150 e, f
(1050)
GEI/FM/541001-4 500 150 e, f
(1050)
GEI/FM/541001-5 600 150 e, f
(1050)
Full Vinylester Pipe
GE/FM/51001-1 80 365 b
(2500)
GE/FM/51001-2 100 290 b
(2000)
GE/FM/51001-3 150 230 b
(1600)
GE/FM/51001-4 200 230 b
(1600)
GE/FM/51001-5 250 180 b
(1250)
GE/FM/51001-6 300 180 b
(1250)
Vinylester/Polyester Pipe
GE/FM/51002-1 100 175 c
(1200)
GE/FM/51002-2 150 175 c
(1200)
GE/FM/51002-3 200 175 c
(1200)
GE/FM/51002-4 250 175 c
(1200)
GE/FM/51002-5 300 175 c
(1200)
GE/FM/51003-1 350 175 c
(1200)
GE/FM/51003-2 400 175 c
(1200)
GE/FM/51003-3 450 175 c
(1200)
GE/FM/51003-4 500 175 c
(1200)
GE/FM/51003-5 600 175 c
(1200)
Vinylester/Polyester Pipe
GE/FM/51-1 350 175 d
(1200)
GE/FM/51-2 400 175 d
(1200)
GE/FM/51-3 450 175 d
(1200)
GE/FM/51-4 500 175 d
(1200)
GE/FM/51-5 600 150 d
(1050)
Vinylester/Polyester Fittings.
Concentric Reducers
GE/FM/52400-1 600×500 150 e
(1050)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-599
Iniziative Industriali SPA, Via Rosignanina 14 56040, Santa Luce (PI) Localita, Macchiaverde Italy
Product Nominal Pipe Pressure
Designation Size, in. Rating, bar Remarks
(psi)
FM Approvals
September 2007 — Approval Guide
1-600 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-601
National Oilwell Varco, Smith Fibercast™ Products Div, 2700 W 65th St, Little Rock AR 72209
200
011040-073-3 4 a, b, c, d, f
(1380)
200
011060-120-3 6 a, b, c, d, f
(1380)
200
011080-126-3 8 a, b, c, d, f
(1380)
200
011100-156-3 10 a, b, c, d, f
(1380)
200
011120-185-3 12 a, b, c, d, f
(1380)
200
011140-220-3 14 a, b, c, d, f
(1380)
200
011160-250-3 16 a, b, c, d, f
(1380)
200
022160-310-3 16 d, e
(1380)
200
022040-360-3 4 d, e
(1380)
200
022060-360-3 6 d, e
(1380)
200
022080-360-3 8 d, e
(1380)
200
022100-360-3 10 d, e
(1380)
200
022120-360-3 12 d, e
(1380)
200
022140-360-3 14 d, e
(1380)
200
022160-360-3 16 d, e
(1380)
FM Approvals
September 2007 — Approval Guide
1-602 Automatic Sprinkler Systems
200
022040-410-3 4 d, e
(1380)
200
022060-410-3 6 d, e
(1380)
200
022080-410-3 8 d, e
(1380)
200
022100-410-3 10 d, e
(1380)
200
022120-410-3 12 d, e
(1380)
200
022140-410-3 14 d, e
(1380)
200
022160-410-3 16 d, e
(1380)
200
022060-236-3 6×4 d, e
(1380)
200
022080-237-3 8×6 d, e
(1380)
200
022080-235-3 10×8 d, e
(1380)
200
022100-237-3 12×10 d, e
(1380)
200
022100-235-3 8×4 d, e
(1380)
200
022120-237-3 10×6 d, e
(1380)
200
022120-235-3 12×8 d, e
(1380)
200
022140-237-3 14×10 d, e
(1380)
200
022140-235-3 14×12 d, e
(1380)
200
022160-237-3 16×12 d, e
(1380)
200
022160-235-3 16×14 d, e
(1380)
200
022040-172-3 4 d, e
(1380)
200
022060-172-3 6 d, e
(1380)
200
022080-172-3 8 d, e
(1380)
200
022100-172-3 10 d, e
(1380)
200
022120-172-3 12 d, e
(1380)
200
022140-172-3 14 d, e
(1380)
200
022160-172-3 16 d, e
(1380)
200
022080-460-3 8×6 d, e
(1380)
200
022100-460-3 10×6 d, e
(1380)
200
022100-480-3 10×8 d, e
(1380)
200
022120-460-3 12×6 d, e
(1380)
200
022120-480-3 12×8 d, e
(1380)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-603
200
022120-490-3 12×10 d, e
(1380)
200
022140-460-3 14×6 d, e
(1380)
200
022140-480-3 14×8 d, e
(1380)
200
022140-490-3 14×10 d, e
(1380)
200
022140-490-3 14×12 d, e
(1380)
200
022160-460-3 16×6 d, e
(1380)
200
022160-480-3 16×8 d, e
(1380)
200
022160-490-3 16×10 d, e
(1380)
200
022160-492-3 16×12 d, e
(1380)
200
022160-494-3 16×14 d, e
(1380)
Remarks
a. Pipe lengths available in two configurations: two spigot ends or one spigot and one bell end.
b. Pipes equipped with two spigot ends joined by sleeve couplings.
c. Pipes equipped with one bell and one spigot end joined by bell and spigot joints.
d. Joints must be made with adhesive kit No. 7014, 7069, 7024 or 7054.
e. Fittings with bell ends.
f. Joints must be made with adhesive kit No. 8014, 8024, 8069 or 8069-C.
N Sguassero Spa, Via Pasubio 36, 20037 Paderno Dugnano (MI), Italy
NP 16 G.R.P. Pipes And Fittings
Pipe a, b, c
4 (100) 16 (230)
6 (150) 16 (230)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 14 (205)
16 (400) 16 (230)
20 (500) 10.5 (150)
Butt and Strap Lamination a, b
4 (100) 16 (230)
6 (150) 16 (230)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 16 (230)
16 (400) 16 (230)
20 (500) 10.5 (150)
Elbows ≤90° a, b, c
4 (100) 20 (290)
6 (150) 16 (230)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 16 (230)
16 (400) 16 (230)
20 (500) 16 (230)
Fixed Flange a, b, c
4 (100) 20 (290)
6 (150) 20 (290)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 14 (205)
16 (400) 16 (230)
20 (500) 12 (175)
FM Approvals
September 2007 — Approval Guide
1-604 Automatic Sprinkler Systems
4 (100) 20 (290)
6 (150) 20 (290)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 14 (205)
16 (400) 16 (230)
20 (500) 12 (175)
Cap a, b, c
4 (100) 20 (290)
6 (150) 16 (230)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 16 (230)
16 (400) 16 (230)
20 (500) 16 (230)
Equal Tee a, b, c
4 20 (290)
6 20 (290)
8 16 (230)
10 12 (175)
12 12 (175)
16 12 (175)
20 12 (175)
Unequal Tee a, b, c
5×4, 6×4, 6×5 20 (290)
8×4, 8×5, 8×6 16 (230)
10×5, 10×6, 12 (175)
10×8, 12×6, 12 (175)
12×8, 12×10, 12 (175)
14×8, 14×10, 12 (175)
14×12, 16×10, 12 (175)
16×12, 16×14, 12 (175)
18×12, 18×14, 12 (175)
18×16, 20×14, 12 (175)
20×16, 20×18 12 (175)
Concentric Reducers a, b, c
Eccentric Reducers 5×4, 6×4, 6×5 16 (230)
8×4, 8×5, 8×6 16 (230)
10×5, 10×6, 10×8 16 (230)
12×6, 12×8, 12×10 16 (230)
14×8, 14×10, 14×12 16 (230)
16×10, 16×12, 16×14 16 (230)
18×12, 18×14, 18×16 16 (230)
20×14, 20×16 16 (230)
20×18 10.5 (150)
Glass Reinforced Polyester Resin Pipes and Fittings, with Glued Joints
Glued Joint b
4 20 (290)
6 16 (230)
8 16 (230)
10 16 (230)
12 14 (200)
16 16 (230)
Elbows ≤90° a, b, c
4 (100) 20 (290)
6 (150) 16 (230)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 16 (230)
16 (400) 16 (230)
20 (500) 16 (230)
Fixed Flange a, b, c
4 (100) 20 (290)
6 (150) 20 (290)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 14 (205)
16 (400) 16 (230)
20 (500) 12 (175)
Stub End Flange a, b, c
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-605
4 (100) 20 (290)
6 (150) 20 (290)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 14 (205)
16 (400) 16 (230)
20 (500) 12 (175)
Cap a, b, c
4 (100) 20 (290)
6 (150) 16 (230)
8 (200) 16 (230)
10 (250) 16 (230)
12 (300) 16 (230)
16 (400) 16 (230)
20 (500) 16 (230)
Equal Tee a, b, c
4 20 (290)
6 20 (290)
8 16 (230)
10 12 (175)
12 12 (175)
16 12 (175)
20 12 (175)
Unequal Tee a, b, c
5×4, 6×4, 6×5 20 (295)
8×4, 8×5, 8×6 16 (230)
10×5, 10×6, 12 (175)
10×8, 12×6, 12 (175)
12×8, 12×10, 12 (175)
14×8, 14×10, 12 (175)
14×12, 16×10, 12 (175)
16×12, 16×14, 12 (175)
18×12, 18×14, 12 (175)
18×16, 20×14, 12 (175)
20×16, 20×18 12 (175)
Concentric Reducers a, b, c
Eccentric Reducers
5×4, 6×4, 6×5 16 (230)
8×4, 8×5, 8×6 16 (230)
10×5, 10×6, 10×8 16 (230)
12×6, 12×8, 12×10 16 (230)
14×8, 14×10, 14×12 16 (230)
16×10, 16×12, 16×14 16 (230)
18×12, 18×14, 18×16 16 (230)
20×14, 20×16 16 (230)
20×18 10.5 (150)
a. Pipe and fittings available with double O-ring seal.
b. Pipe and fittings available with butt and strap lamination.
c. Pipe and fittings with re-useable nylon locking keys as joint restraints.
TPR Fiberdur GmbH + Co KG, Industriepark Emil Mayrisch, D-52457 Aldenhoven/Siersdorf, Germany
Pipe
Fiberdor VE16 50 175 a, b, c
(1205)
80 175 a, b, c
(1205)
100 175 a, b, c
(1205)
150 175 a, b, c
(1205)
90° Elbow 50 175 a, d
Type 555 (1205)
45° Elbow 80 175 a, d
Type 565 (1205)
100 175 a, d
(1205)
150 175 a, d
(1205)
Tee 50 175 a, d
Type 575 (1205)
80 175 a, d
(1205)
FM Approvals
September 2007 — Approval Guide
1-606 Automatic Sprinkler Systems
100 175 a, d
(1205)
150 175 a, d
(1205)
Coupling 50 175 a, d
Type 514 (1205)
Coupling 80 175 a, d
Type 514 (1205)
100 175 a, d
(1205)
150 175 a, d
(1205)
PIPE HANGERS
Pipe hangers are used to support a sprinkler piping system from the building structure. Two or more listed
components may be required to form a complete hanger. The specific components required depend upon the type
of building construction and the pipe size.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-607
A53 1⁄ 2 ’’ 5 through 8
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
69 3⁄ 8 ’’ 21⁄2, 3, 4
69 1⁄ 2 ’’ 5 through 8
69E 10 ’’ 3⁄4 through 4
12 ’’ 5 through 8
86 3⁄ 8 C-Clamp with C.P. Set Screw and Locknut 3⁄4 through 4
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
NC
(Rod Attachment)
110R 1⁄ 2 ’’ 5 through 8
134 1⁄ 2 I-Beam Clamp 5 through 8
134 5⁄ 8 ’’ 10, 12
136 3⁄ 8 Rod Coupling 3⁄4 through 4
136 1⁄ 2 ’’ 5 through 8
153 3⁄ 8 Pipe Hanger Flange 3⁄4 through 4
153 1⁄ 2 ’’ 5 through 8
157 3⁄ 8 Extension Piece 3⁄4 through 4
194 1⁄ 2 ’’ 5 through 8
202 3⁄ 8 Side Beam Bracket † 3⁄4 through 4
206 1⁄ 2 ’’ 5 through 8
207 3⁄ 8 Side Beam Bracket ‡ 3⁄4 through 4
Extension Piece
227 3⁄ 8 Top Beam Clamp 3⁄ 4through 4
260 3⁄ 8 Clevis Hanger 3⁄ 4through 2
260 1⁄ 2 ’’ 21⁄2 through 31⁄2
260 5⁄ 8 ’’ 4, 5
260 3⁄ 4 ’’ 6
260 7⁄ 8 ’’ 8
FM Approvals
September 2007 — Approval Guide
1-608 Automatic Sprinkler Systems
Bolivar Ltd, Devonshire Works West Lane, Keighley, West Yorkshire BD21 2LB, United Kingdom
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, mm
(in.) (in.)
CCTF Corp, #4-480 Audley Blvd, Delta, British Columbia V3M 5S4, Canada
For
Product Component Nominal Rod Nominal Pipe
Designation Description Size, in. Sizes, in.
Debro Engineering & Presswork, Stourvale Trading Estate, Banners Ln, Halesowen B63 2AX, United Kingdom
For
Product Hanger Rod Component Nominal Pipe
Designation Size, mm Description Sizes, in.
10 ’’ 1
10 ’’ 11⁄4
10 ’’ 11⁄2
10 ’’ 2
10 ’’ 21⁄2
10 ’’ 3
10 ’’ 4
12 ’’ 6
18 ’’ 8
FIL00272 M10 Filbow 3⁄4
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-609
For
Product Hanger Rod Component Nominal Pipe
Designation Size, mm Description Sizes, in.
†For European jurisdictions that prefer to use clearance holes for the threaded rod and hex jam nuts to secure the rods to the beam clamps.
FM Approvals
September 2007 — Approval Guide
1-610 Automatic Sprinkler Systems
For
Product Hanger Rod Component Nominal Pipe
Designation Size, mm Description Sizes, in.
36**†† 1⁄ 2 ’’ 5 through 8
37†† 3⁄ 8 Wide Throat 3⁄4 through 4
C-Clamp
37†† 1⁄ 2 ’’ 5 through 8
58 3⁄ 8 Steel Side Beam 4
Bracket
128BTS 3⁄ 8 Ceiling Plate 3⁄ 4through 2
547 3⁄ 8 Steel Clamp 4
548 1⁄ 2 ’’ 8
FCS 3⁄ 8 Loop Hanger 3⁄4 through 4
(10)
FCS 1⁄ 2 Loop Hanger 5, 6
(12)
FCS 5⁄ 8 Loop Hanger 8
(16)
**FM Approved for use in the top and inverted bottom beam positions.
†† These hanger components are also FM Approved when threaded for use with the nearest equivalent standard metric size hanger rod.
†Model 135 ‘‘Yook’’ Lo op Hanger using two MCO 43-16 wood screw fasteners in each arm is FM Approved to support 3⁄4 through 4 in. NPS sprinkler system piping.
‡ Model 135CT ‘‘Yook’’ Loop Hanger using two MCO 43-16 wood screw fastener in each arm is FM Approved to support 3⁄4 through 2 in. NPS sprinkler system copper
tubing.
*Model 137 ‘‘Yook’’ Loop Hanger using one MCO 43-16 wood screw fastener in each arm is FM Approved to support 3⁄4 through 2 in. NPS sprinkler system piping.
These hanger components are also FM Approved when threaded for use with the nearest equivalent standard metric size hanger rod. The
suffix -M appears after the model number.
Empire Industries Inc, 180 Olcott St, Box 1020, Manchester CT 06045-1020
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
NC
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-611
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
NC
BES 12 ’’ 5 through 8
BKS12 12 ’’ 4 through 8
KCK 12 12 ’’ 5 through 8
All pipe hangers are FM Approved for use with U.S. NC 3⁄8-16 and NC 1⁄2-13 threaded rod as an alternate to the metric rod. Markings so
designate appropriate rod.
Globe Pipe Hanger Products Inc, 14601 Industrial Pkwy, Cleveland OH 44135
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. (mm) Description Sizes, in.
NC
*These hanger components are also FM Approved when threaded for use with the nearest equivalent standard metric size hanger rod, M10 or M12, as shown. The
suffix -MM appears after the model number for hangers using Metric rods.
FM Approvals
September 2007 — Approval Guide
1-612 Automatic Sprinkler Systems
Hilti AG, Feldkircher Str 100, Postfach 333, FL-949 Schaan, Fuerstentum Liechtenstein
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Size, in.
NC
12 ’’ 133 mm through 6
16 ’’ 219 mm
MP-MS 10 Pipe Clamp Hanger 68/72 through 4
MP-MS2 12 ’’ 133 mm through 6
16 ’’ 219 mm
MF-SKD-M10 10 Toggle 3⁄4 through 11⁄2
LH 1 3⁄ 8 ’’ 1
LH 11⁄4 3⁄8 ’’ 11⁄4
LH 1-1⁄2 3⁄8 ’’ 11⁄2
LH 2 3⁄ 8 ’’ 2
LH 21⁄2 3⁄8 ’’ 21⁄2
LH 3 3⁄ 8 ’’ 3
LH 4 3⁄ 8 ’’ 4
LH 6 1⁄ 2 ’’ 6
LH 8 1⁄ 2 ’’ 8
BC-WM 3⁄8 3⁄8 Beam Clamp 3⁄4 through 4
Lindapter International, Lindsay House Brackenbeck Rd, Bradford, West Yorkshire BD7 2NF, United Kingdom
For
Product Hanger Rod Component Nominal Pipe
Designation Size, mm Description Sizes, in.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-613
Minimax GmbH & Co KG, Box 1260, Industriestrasse 10-12, D-23840 Bad Oldesloe, Germany
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
(mm)
(10)
SM 25/10 3⁄ 8 ’’ 3⁄ 4 through 1
(10)
SM 32/10 3⁄ 8 ’’ 1 through 11⁄4
(10)
SM 40/10 3⁄ 8 ’’ 11⁄4 through 11⁄2
(10)
SM 50/10 3⁄ 8 ’’ 11⁄2 through 2
(10)
SM 65/10 3⁄ 8 ’’ 2 through 21⁄2
(10)
SM 80/10 3⁄ 8 ’’ 21⁄2 through 3
(10)
SM 100/10 3⁄ 8 ’’ 3 through 4
(10)
SM 125/12 1⁄ 2 ’’ 4 through 5
(12)
SM 150/12 1⁄ 2 ’’ 5 through 6
(12)
SM 200/16 5⁄ 8 ’’ 8
(16)
*FM Approved for use in the top and inverted bottom beam positions.
Myland Industrial Co Ltd, Room 708, Metro Centre 32 Lam Hing St, Kowloon Bay Hong Kong
FM Approvals
September 2007 — Approval Guide
1-614 Automatic Sprinkler Systems
Diamond Clevis Hanger M10 Clevis Hanger 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4
Diamond Clevis Hanger M12 Clevis Hanger 5, 6, 8
Diamond Sprinkler Clamp M10 Band Hanger 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2, 3, 4
SMK Meister GmbH & Co KG, Lombacher Strasse 53, Postfach 27, 72293 Glatten, Germany
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
NC
Shanghai Vision Mechanical Joint Co Ltd, No. 221 Jinlan Road, Loutang Industrial Park, Jaiding District,
Shanghai 201807, Peoples Republic China
Product Nominal Rod Component For
Designation Size, in. Description Nominal Pipe
(mm) Sizes, in.
(DN20) (10)
702-1 in. 3⁄ 8 Loop Pipe Hanger 3⁄4, 1
(DN25) (10)
702-11⁄4 in. 3⁄ 8 Loop Pipe Hanger 1, 11⁄4
(DN32) (10)
702-11⁄2 in. 3⁄ 8 Loop Pipe Hanger 11⁄4, 11⁄2
(DN40) (10)
702-2 in. 3⁄ 8 Loop Pipe Hanger 11⁄2, 2
(DN50) (10)
702-21⁄2 in. 3⁄ 8 Loop Pipe Hanger 2, 21⁄2
(DN65) (10)
702-3 in. 3⁄ 8 Loop Pipe Hanger 21⁄2, 3
(DN80) (10)
702-4 in. 3⁄ 8 Loop Pipe Hanger 3, 4
(DN100) (10)
702-5 in. 1⁄ 2 Loop Pipe Hanger 4, 5
(DN125) (12)
702-6 in. 1⁄ 2 Loop Pipe Hanger 5, 6
(DN150) (12)
702-8 in. 1⁄ 2 Loop Pipe Hanger 8
(DN200) (12)
Shurjoint Piping Products Inc, 4601 E Cheyenne Ave, Suite 105, Las Vegas NV 89115
Product Hanger Rod Component For
Designation Size, in. Description Nominal Pipe
(mm) Sizes, in.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-615
For
Product Eye Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
(mm)
(10×20)
118842 3⁄8×11⁄2 ’’ 3⁄4
(10×40)
118851 3⁄8×11⁄2 ‘‘ 1
(10×40)
118860 3⁄8×11⁄2 ’’ 11⁄4
(10×40)
118879 3⁄8×11⁄2 ‘‘ 11⁄2
(10×40)
118888 3⁄8×11⁄2 ’’ 11⁄2
(10×40)
118897 3⁄8×11⁄2 ‘‘ 2
(10×40)
118903 3⁄8×11⁄2 ’’ 21⁄2
(10×40)
102612 3⁄8×11⁄2 ‘‘ 21⁄2
(10×40)
102621 3⁄8×11⁄2 ’’ 3
(10×40)
102630 3⁄8×11⁄2 ‘‘ 31⁄2
(10×40)
102649 3⁄8×11⁄2 ’’ 4
(10×40)
118912 3⁄8×11⁄2 ‘‘ 4
(10×40)
118921 3⁄8×11⁄2 ’’ 4
(10×40)
102658 1⁄2×3⁄4 ‘‘ 5
(12×20)
118930 1⁄2×11⁄2 ’’ 5
(12×40)
102667 1⁄2×11⁄2 ‘‘ 6
(12×40)
118949 1⁄2×11⁄2 ’’ 6
(12×40)
118958 1⁄2×11⁄2 ‘‘ 6
(12×40)
118967 1⁄2×11⁄2 ’’ 6
(12×40)
118976 1⁄2×11⁄2 ‘‘ 6
(12×40)
118985 1⁄2×11⁄2 ’’ 6
(12×40)
102676 5⁄8×1 ‘‘ 8
(16×25)
118994 5⁄8×1 ’’ 8
(16×25)
119001 5⁄8×1 ‘‘ 8
(16×25)
119010 5⁄8×1 ’’ 8
(16×25)
119791 5⁄8×1 ‘‘ 10
(16×25)
119807 5⁄8×1 ’’ 010
(16×25)
FM Approvals
September 2007 — Approval Guide
1-616 Automatic Sprinkler Systems
For
Product Hanger Rod Component Nominal Pipe
Designation Size in. Description Size, in.
(mm)
(10)
118295 3⁄ 8 ‘‘ 1
(10)
118301 3⁄ 8 ’’ 11⁄4
(10)
118310 3⁄ 8 ‘‘ 11⁄2
(10)
118329 3⁄ 8 ’’ 11⁄2
(10)
118338 3⁄ 8 ‘‘ 2
(10)
118620 5⁄ 8 ’’ 21⁄2
(16)
118639 5⁄ 8 ‘‘ 21⁄2
(16)
118648 5⁄ 8 ’’ 3
(16)
118657 5⁄ 8 ‘‘ 31⁄2
(16)
118666 5⁄ 8 ’’ 4
(16)
118675 5⁄ 8 ‘‘ 4
(16)
118684 5⁄ 8 ’’ 4
(16)
118693 5⁄ 8 ‘‘ 5
(16)
118709 5⁄ 8 ’’ 5
(16)
118718 5⁄ 8 ‘‘ 6
(16)
118727 5⁄ 8 ’’ 6
(16)
118736 5⁄ 8 ‘‘ 6
(16)
118745 5⁄ 8 ’’ 6
(16)
118754 5⁄ 8 ‘‘ 6
(16)
118763 5⁄ 8 ’’ 6
(16)
118772 5⁄ 8 ‘‘ 8
(16)
118781 5⁄ 8 ’’ 8
(16)
118790 5⁄ 8 ’’ 8
(16)
118806 5⁄ 8 ’’ 8
(16)
118198 5⁄ 8 ’’ 10
(16)
118204 5⁄ 8 Pipe Clamp/ 10
(16) Welded Nut
‘‘STABIL’’ D-3G,
GROUP 1240 M10 Pipe Clamp 1 through 2
’’ M10, M12 ’’ 21⁄2 through 4
’’ M12, M16 ’’ 5 and 6
a. For use with DIN 2440, 2448 and 2458 (ISO 4200) steel pipe.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-617
L E Taylor Associates Ltd, 555 Parkdale Ave N, Hamilton, Ontario L8H 5Y9, Canada
Hanger Rod For
Product Size, in., Component Nominal Pipe
Designation NC Description Sizes, in.
Bracket
1⁄ 2 ’’ 5 through 8
56 3⁄ 8 Angle Bracket 3⁄ 4
through 2
3⁄8×11⁄2 in.
(10×38 mm)
Lag Screw
56 3⁄ 8 Angle Bracket 21⁄2 through 4
1⁄2×2 in.
(13×51 mm)
Lag Screw
58†** 3⁄ 8 (10) Side Beam 3⁄ 4 through 4
Connector
130-1 3⁄ 8 Beam Clamp 3⁄ 4through 4
130-2 ’’ ’’ ’’
130-3 ’’ ’’ ’’
130-4 ’’ ’’ ’’
130-5 ’’ ’’ ’’
200 3⁄ 8 Loop Hanger 3⁄4 through 4
1⁄ 2 ’’ 5 through 8
*The Fig. 2 ring hangers using the polycarbon encased hex nut are FM Approved to support 21⁄2 through 4 in. NPS sprinkler system piping only.
†Uses 16×2 in. drive screw to support up to 2 in. piping and 1⁄2×3 in. lag screw to support up to 4 in. piping.
#Alternate material — stainless steel.
**These hanger components are also FM Approved when threaded for use with the nearest equivalent standard metric size hanger rod, M10 or M12, as shown. The
suffix M appears after the model number for hangers using metric rods.
Tyco Fire and Building Products (Netherlands), Box 198, 7500 AD Enschede, Holland
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
NC
FM Approvals
September 2007 — Approval Guide
1-618 Automatic Sprinkler Systems
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
NC
91 M12, 13 mm ’’ 5 through 8
TCB10& M10 Trapeze Ceiling Bracket 3⁄ 4through 2
TDM10% M10 Tipping Dowel 3⁄ 4through 2
UNI-SOLID 02 M10* UNI-Solid Pipe Clip 3⁄ 4
UNI-SOLID 03 M10* ’’ 1
UNI-SOLID 05 M10* ’’ 11⁄4
UNI-SOLID 06 M10* ’’ 11⁄2
UNI-SOLID 08 M10* ’’ 2
UNI-SOLID 10 M10 ’’ 21⁄2 (76.1 mm)
UNI-SOLID 12 M10 ’’ 3
UNI-SOLID 15 M10 ’’ 4
UNI-SOLID 19 M12 ’’ 5 (139.7 mm)
UNI-SOLID 22 M12 ’’ 6 (168.3 mm)
*For European jurisdictions that prefer to use clearance holes for the threaded rod and hex jam nuts to secure the rods to the beam clamp.
**Approved for use with the set screw on the load side.
J. Van Walraven, Holding B.V., Industrieweg 5, Box 15, 3640 AA Mijrecht, The Netherlands
Hanger Rod For
Product Size, in., Component Nominal Pipe
Designation NC Description Sizes, in.
Beam C-Clamp
12W* 1⁄ 2 ’’ 5 through 8
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-619
FASTENERS
Anchors, expansion shields, concrete inserts, explosive-driven fasteners and threaded head screws provide
anchorage to building structural members for supporting pipe hangers. See PIPE HANGER listing for other
components and minimum rod sizes. Unless specifically noted in the listing, the following fasteners are FM Approved
for vertical installation only.
Expansion Shields
Expansion shields provide anchorage to a concrete building member for supporting pipe hangers.
*These expansion shields are available in carbon steel or 316 stainless steel.
(prefix)-3572 3⁄8×3
(prefix)-3575 3⁄8×33⁄4
(prefix)-3583 3⁄8×5
(prefix)-3588 3⁄8×61⁄2
(prefix)-3640 1⁄2×41⁄4
(prefix)-3648 1⁄2×51⁄2
(prefix)-3665 1⁄2×7
(prefix)-3670 1⁄2×81⁄2
(prefix)-3672 1⁄2×10
(prefix)-3735 5⁄8×5
(prefix)-3739 5⁄8×6
(prefix)-3743 5⁄8×7
(prefix)-3745 5⁄8×81⁄2
(prefix)-3747 5⁄8×10
(prefix)-3778 3⁄4×51⁄2
(prefix)-3784 3⁄4×61⁄4
(prefix)-3787 3⁄4×7
(prefix)-3790 3⁄4×81⁄2
(prefix)-3793 3⁄4×10
(prefix)-3795 3⁄4×12
All anchors are available in zinc plated steel and stainless steel. A Prefix is added to the Part Number, used to designate finish and
packaging category.
The first 3 digits in the Prefix identified below are for product finish.
FM Approvals
September 2007 — Approval Guide
1-620 Automatic Sprinkler Systems
fischerwerke Artur Fischer GmbH and Co KG, Weinhalde 14-18, D-72178 Waldachtal, Germany
EA M12 12 8
EA M16 16 12
EA M20 20 12
EA 11 M12 12 8
EA 11 M16 16 12
EA 11 M20 20 12
FH 15** 10 4
FH 18/80** 12 8
FH 18/100**
FH 24** 16 12
*These anchors are also FM Approved when threaded for use with the nearest equivalent standard metric or UNC size rod.
**Model FH Approved with Bolt, Screw, Cap Nut or Countersink Screw Head.
All anchors are available in zinc plated steel and stainless steel.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-621
Kwik Bolt 3 3⁄ 8 4
Kwik Bolt 3 1⁄ 2 8
Kwik Bolt 3 5⁄ 8 12
Kwik Bolt 3 3⁄ 4 12
FM Approvals
September 2007 — Approval Guide
1-622 Automatic Sprinkler Systems
Redi-Drive Anchor
PD8-134 3⁄ 8 3⁄4 through 4
RM-12 1⁄ 2 5-8
RM-58 5⁄ 8 12
RM-34 3⁄ 4 12
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-623
1⁄2×23⁄4 5-8 –
1⁄2×33⁄4
1⁄2×41⁄4
1⁄2×51⁄2
1⁄2×7
1⁄2×81⁄2
1⁄2×10
3⁄4×41⁄4 10, 12 –
3⁄4×43⁄4
3⁄4×51⁄2
3⁄4×61⁄4
3⁄4×7
3⁄4×81⁄2
3⁄4×10
3⁄4×12
MKT-Metall-Kunststoff-Technik GmbH & Co KG, Auf dem Immel 2, D-67685 Weilerbach, Germany
Product Hanger Rod Component For Nominal
Designation Size, mm Description Pipe Sizes, in.
B-12* M12 ’’ 5, 6, 8
B-16* M16 ’’ 10, 12
*These expansion shields are available in carbon steel or 316 stainless steel.
†These anchors are also FM Approved when threaded for use with the nearest equivalent standard UNC size rod.
LOK-BOLT
Series 5000
5815 3⁄ 8 One piece 4
5825 1⁄ 2 sleeve anchor 8
5840 5⁄ 8 12
STEEL DROPIN
6206 3⁄ 8 4
6208 1⁄ 2 303 stainless 8
6210 5⁄ 8 Inserted in drilled 12
6212 3⁄ 4 concrete 12
STEEL DROPIN
6226 3⁄ 8 4
6228 1⁄ 2 316 stainless 8
6230 5⁄ 8 Inserted in drilled 12
6232 3⁄ 4 concrete 12
STEEL DROPIN
Series 6300
6306 3⁄ 8 4
6308 1⁄ 2 Carbon steel 8
6310 5⁄ 8 Inserted in drilled 12
6312 3⁄ 4 concrete 12
FM Approvals
September 2007 — Approval Guide
1-624 Automatic Sprinkler Systems
HS DROPIN
Series 9300
3⁄ 8 Heavy-duty 4
1⁄ 2 machine bolt 8
5⁄ 8 anchor 12
POWER-BOLT
Series 6900
6910 3⁄ 8 Heavy-duty 4
6911 3⁄ 8 sleeve anchor 4
6912 3⁄ 8 4
6913 3⁄ 8 4
6914 3⁄ 8 4
6916 3⁄ 8 4
6930 1⁄ 2 8
6931 1⁄ 2 8
6932 1⁄ 2 8
6933 1⁄ 2 8
6934 1⁄ 2 8
6935 1⁄ 2 8
6936 1⁄ 2 8
6940 5⁄ 8 12
6941 5⁄ 8 12
6942 5⁄ 8 12
6943 5⁄ 8 12
6944 5⁄ 8 12
6945 5⁄ 8 12
6946 5⁄ 8 12
6947 5⁄ 8 12
6950 3⁄ 4 12
6951 3⁄ 4 12
6952 3⁄ 4 12
6953 3⁄ 4 12
6954 3⁄ 4 12
6955 3⁄ 4 12
6956 3⁄ 4 12
6957 3⁄ 4 12
SET-BOLT
Series 7100
7123 3⁄ 8 Stud anchor 4
7126 3⁄ 8 4
7129 3⁄ 8 4
7134 3⁄ 8 4
7145 1⁄ 2 8
7151 1⁄ 2 8
7153 1⁄ 2 8
7168 5⁄ 8 12
7172 5⁄ 8 12
7176 5⁄ 8 12
7189 3⁄ 4 12
7194 3⁄ 4 12
7196 3⁄ 4 12
SET-BOLT (METRIC)
Series 61000
61050 10mm Stud anchor (metric) 4
61052 12mm 8
POWER-STUD
Series 7300
7310 3⁄ 8 Wedge anchor 4
7312 3⁄ 8 304 Stainless steel 4
7313 3⁄ 8 4
7314 3⁄ 8 4
7315 3⁄ 8 4
7316 3⁄ 8 4
7320 3⁄ 8 4
7322 3⁄ 8 4
7323 3⁄ 8 4
7324 3⁄ 8 4
7326 3⁄ 8 4
7330 1⁄ 2 8
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-625
7332 1⁄ 2 8
7333 1⁄ 2 8
7334 1⁄ 2 8
7336 1⁄ 2 8
7338 1⁄ 2 8
7342 5⁄ 8 12
7344 5⁄ 8 12
7346 5⁄ 8 12
7348 5⁄ 8 12
7349 5⁄ 8 12
POWER-STUD
Series 7400
7412 3⁄ 8 Wedge anchor 4
7413 3⁄ 8 Carbon steel 4
7414 3⁄ 8 4
7415 3⁄ 8 4
7416 3⁄ 8 4
7417 3⁄ 8 4
7420 1⁄ 2 8
7422 1⁄ 2 8
7423 1⁄ 2 8
7424 1⁄ 2 8
7426 1⁄ 2 8
7427 1⁄ 2 8
7430 5⁄ 8 12
7432 5⁄ 8 12
7433 5⁄ 8 12
7434 5⁄ 8 12
7436 5⁄ 8 12
7438 5⁄ 8 12
7439 5⁄ 8 12
7440 3⁄ 4 12
7441 3⁄ 4 12
7442 3⁄ 4 12
7444 3⁄ 4 12
7446 3⁄ 4 12
7448 3⁄ 4 12
7449 3⁄ 4 12
7451 3⁄ 4 12
7450 7⁄ 8 12
7452 7⁄ 8 12
7454 7⁄ 8 12
7461 1 12
7463 1 12
7465 1 12
POWER-STUD
Series 7600
7610 3⁄ 8 Wedge anchor 4
7612 3⁄ 8 316 stainless steel 4
7613 3⁄ 8 4
7614 3⁄ 8 4
7615 3⁄ 8 4
7616 3⁄ 8 4
7620 1⁄ 2 8
7622 1⁄ 2 8
7623 1⁄ 2 8
7624 1⁄ 2 8
7626 1⁄ 2 8
7630 5⁄ 8 12
7632 5⁄ 8 12
7633 5⁄ 8 12
7634 5⁄ 8 12
7636 5⁄ 8 12
7638 5⁄ 8 12
7642 3⁄ 4 12
7644 3⁄ 4 12
7646 3⁄ 4 12
7648 3⁄ 4 12
POWER-STUD
Series 7700
7720 1⁄ 2 Wedge anchor 8
7723 1⁄ 2 Mech. galvanized 8
7724 1⁄ 2 8
FM Approvals
September 2007 — Approval Guide
1-626 Automatic Sprinkler Systems
7726 1⁄ 2 8
7730 5⁄ 8 12
7734 5⁄ 8 12
7741 5⁄ 8 12
7742 3⁄ 4 12
7748 3⁄ 4 12
7750 7⁄ 8 12
7752 7⁄ 8 12
7763 1 12
7765 1 12
POWER-STUD
Series 7800
7806 3⁄ 8 Wedge anchor 4
7808 1⁄ 2 Rod hanger style 8
7810 5⁄ 8 12
7812 3⁄ 4 12
DRIVE ANCHOR
Series 3000
3633 3⁄ 8 Split drive anchor 4
3663 3⁄ 8 4
3693 3⁄ 8 4
3723 3⁄ 8 4
3813 1⁄ 2 8
3843 1⁄ 2 8
DIA50 1⁄ 2 8 ‘‘
DIA62 5⁄ 8 12 ’’
DIA75 3⁄ 4 12 ’’
1⁄ 2 1
DIA50C 8 Drop-In Anchor-Coil Thread
DIA75C 3⁄ 4 12 ’’
3⁄ 8 1
DIAL37 4 Drop-In Anchor, with Lip
DIAL50 1⁄ 2 8 ’’
DIAL62 5⁄ 8 12 ’’
DIAL75 3⁄ 4 12 ’’
3⁄ 8 2
DIA37S 4 Short Drop-In Anchor
SL50214C 1⁄ 2 8 ’’
SL62214C 5⁄ 8 12 ’’
SL37300H 3⁄ 8 4 ’’
SL37400H 3⁄ 8 4 ’’
SL50214H 1⁄ 2 8 ’’
SL50300H 1⁄ 2 8 ’’
SL50400H 1⁄ 2 8 ’’
SL50600H 1⁄ 2 8 ’’
SL62214H 5⁄ 8 12 ’’
SL62300H 5⁄ 8 12 ’’
SL62414H 5⁄ 8 12 ’’
SL62600H 5⁄ 8 12 ’’
SL75214H 3⁄ 4 12 ’’
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-627
SL75414H 3⁄ 4 12 ’’
SL75614H 3⁄ 4 12 ’’
SL37500PF 3⁄ 8 4 ’’
SL37600PF 3⁄ 8 4 ’’
SL37434R 3⁄ 8 4 ’’
3⁄ 8 3
WA37214 4 Wedge-All Wedge Anchor
WA37234 3⁄ 8 4 ’’
WA37300 3⁄ 8 4 ’’
WA37312 3⁄ 8 4 ’’
WA37334 3⁄ 8 4 ’’
WA37500 3⁄ 8 4 ’’
WA37700 3⁄ 8 8 ’’
WA50234 1⁄ 2 8 ’’
WA50334 1⁄ 2 8 ’’
WA50414 1⁄ 2 8 ’’
WA50512 1⁄ 2 8 ’’
WA50700 1⁄ 2 8 ’’
WA50812 1⁄ 2 8 ’’
WA50100 1⁄ 2 8 ’’
WA50120 1⁄ 2 8 ’’
WA62312 5⁄ 8 12 ’’
WA62412 5⁄ 8 12 ’’
WA62500 5⁄ 8 12 ’’
WA62600 5⁄ 8 12 ’’
WA62700 5⁄ 8 12 ’’
WA62812 5⁄ 8 12 ’’
WA62100 5⁄ 8 12 ’’
WA62120 5⁄ 8 12 ’’
WA75414 3⁄ 4 12 ’’
WA75434 3⁄ 4 12 ’’
WA75512 3⁄ 4 12 ‘‘
WA75614 3⁄ 4 12 ’’
WA75700 3⁄ 4 12 ‘‘
WA75812 3⁄ 4 12 ’’
WA75100 3⁄ 4 12 ‘‘
WA75120 3⁄ 4 12 ’’
WA87600 7⁄ 8 12 ‘‘
WA87800 7⁄ 8 12 ’’
WA87100 7⁄ 8 12 ‘‘
WA87120 7⁄ 8 12 ’’
WA16000 1 12 ‘‘
WA19000 1 12 ’’
WA11200 1 12 ‘‘
FM Approvals
September 2007 — Approval Guide
1-628 Automatic Sprinkler Systems
WA12590 11⁄4 12 ’’
WA12512 1 1⁄ 4 12 ‘‘
WA15012 1 1⁄ 2 12 ’’
1
Available in stainless steel and zinc plated carbon steel.
2
Available in zinc plated carbon steel.
3
Available in stainless steel and zinc plated or mechanically galvanized carbon steel anchors.
Störring and Bruckmann GmbH, Postfach 150425, 42523 Velbert Neviges, Germany
Product Hanger Rod Component For Nominal
Designation Size, mm Description Pipe Size, in.
(mm)
UCAN Fastening Products, 155 Champagne Drive, Unit 10 Toronto, Ontario M3J 2C6, Canada
Product Hanger Rod Max Nominal
Designation Size, mm Pipe Size, in. Remarks
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-629
Concrete Inserts
Concrete inserts provide anchorage to concrete building structures for supporting pipe hangers. Concrete inserts
must be installed when the building is constructed.
Anvil International Inc, 110 Corporate Drive, Suite 10, Portsmouth NH 03801
Fig. 152. 3⁄8, 1⁄2, 5⁄8, 3⁄4, 7⁄8
in. (10, 13, 16, 19, 22 mm) rods.
Fig. 281. 3⁄ 4through 8 in. NPS (19 through 203 mm).
Fig. 282. 3⁄4 through 8 in. NPS (19 through 203 mm).
Fig. 285. 3⁄4 through 5 in. NPS (19 through 127 mm).
Empire Industries Inc, 180 Olcott St, Box 1020, Manchester CT 06045-1020
Fig. 81. Concrete insert with Fig. 81-N nuts.
3⁄8 in. (10 mm) nut. 3⁄4 through 4 in. NPS (19 through 102 mm).
1⁄2 in. (13 mm) nut. 5, 6, 8 in. NPS (127, 152, 203 mm).
Globe Pipe Hanger Products Inc, 14601 Industrial Pkwy, Cleveland OH 44135
Type 726-106.
Concrete insert with Type 725 nuts
725-103 3⁄8’’ nut, 3⁄4 through 4 in. NPS
725-104 1⁄2’’ nut, 5 through 8 in. NPS
725-105 5⁄8’’ nut 10 through 12 in. NPS
725-106 3⁄4’’ nut 10 through 12 in. NPS
FM Approvals
September 2007 — Approval Guide
1-630 Automatic Sprinkler Systems
HCI-WF 3⁄8 3⁄8 Cast in Anchor – concrete with wood forms 3⁄ 4through 4
HCI-WF 1⁄2 1⁄2 Cast in Anchor – concrete with wood forms 3⁄ 4through 8
HCI-MD 3⁄8 3⁄8 Cast in Anchor – concrete over steel deck 3⁄4 through 4
BANG-IT
CONCRETE INSERT
Series 7500
7542 3⁄ 8 Concrete over steel deck 4
(Upper & Lower Flute)
7544 1⁄ 2 Concrete over steel deck 8
(Upper Flute)
7546 5⁄ 8 Concrete over steel deck 12
(Upper Flute)
WOOD-KNOCKER
CONCRETE INSERT
Series 7500
7552 3⁄ 8 Concrete with wood forms 4
(vertical only)
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-631
Störring and Bruckmann GmbH, Postfach 150425, 42523 Velbert Neviges, Germany
Subex Concrete Anchors
Unistrut Corp dba Unistrut Diversified Products, 35660 Clinton St, Wayne MI 48184
Cat. Nos. M24, M26.
Cat. Nos. P3249-70 inclusive.
Cat. Nos. P3349-70 inclusive.
All nuts are available with or without springs.
Explosive-Driven Fasteners
Explosive-driven fasteners provide anchorage to concrete or steel building members for supporting pipe hangers.
The powder-actuated tool used for driving these fasteners may represent an ignition source; therefore, it should not
be used in classified hazardous locations or near easily ignited materials. Fasteners should not be used for support
of pipe hangers to structural members in Earthquake Zones 500 or less as defined by FM Global Property Loss
Prevention Data Sheet 1-2.
A coupling and locknut are provided with each fastener for attaching a pipe hanger to the fastener.
FM Approvals
September 2007 — Approval Guide
1-632 Automatic Sprinkler Systems
These fasteners are also FM Approved for horizontal installation. Max pipe size 31⁄2 in. (89 mm).
Screws
Threaded head screws provide anchorage to concrete, steel or wood building structural members for supporting
pipe hangers. Fasteners should not be used for support of pipe hangers to structural members in Earthquake Zones
500 or less as defined by FM Global Property Loss Prevention Data Sheet 1-2.
ITW Buildex Corp, 1349 West Bryn Mawr Ave, Itasca IL 60143
For
Product Hanger Rod Component Nominal Pipe
Designation Size, in. Description Sizes, in.
DST 516 3⁄ 8 Threaded Head Screw for use in steel I beams 3⁄ 4 through 4
TEK 50 3⁄ 8 Threaded Head Screw for use in steel I beams 3⁄ 4 through 4
DSTR-1 3⁄ 8 Threaded Head Screw for use in steel I beams and 12 gage purlins 3⁄ 4 through 4
DSTR-11⁄2 3⁄8 Threaded Head Screw for use in steel I beams and 12 gage purlins 3⁄ 4 through 4
DSTR 516 3⁄ 8 Threaded Head Screw for use in steel I beams and 12 gage purlins 3⁄ 4 through 4
SH DSTR1 3⁄ 8 Threaded Head Screw for use in steel I beams and 12 gage purlins 3⁄ 4 through 4
XP 20 3⁄ 8 Threaded Head Screw for use in 12 gage purlins 3⁄ 4 through 4
XP 35 3⁄ 8 Threaded Head Screw for use in 12 gage purlins 3⁄ 4 through 4
SWDR1 3⁄ 8 Threaded Head Screw for use in 16 gage purlin 3⁄ 4 through 4
SWDR 516 3⁄ 8 Threaded Head Screw for use in 16 gage purlin 3⁄ 4 through 4
SWDR 11⁄2 3⁄8 Threaded Head Screw for use in 16 gage purlin 3⁄ 4 through 4
SH GST20 3⁄ 8 Threaded Head Screw for use in Wood 3⁄ 4 through 4
SH GST30 3⁄ 8 Threaded Head Screw for use in Wood 3⁄ 4 through 4
GST 20 3⁄ 8 Threaded Head Screw for use in Wood 3⁄ 4 through 4
GST 30 3⁄ 8 Threaded Head Screw for use in Wood 3⁄ 4 through 4
CST 20 3⁄ 8 Threaded Head Screw for use in Concrete 3⁄ 4 through 4
SWC20 3⁄ 8 Threaded Head Screw for use in Concrete 3⁄ 4 through 4
For
Product Hanger Rod Component Nominal Pipe
Designation Size, mm Description Sizes, in.
DST 516 M10 10 Threaded Head Screw for use in steel I beams 20 through 100
TEK 50 M10 10 Threaded Head Screw for use in steel I beams 20 through 100
DSTR-1 M10 10 Threaded Head Screw for use in steel I beams and 12 gage purlins 20 through 100
DSTR-11⁄2 M10 10 Threaded Head Screw for use in steel I beams and 12 gage purlins 20 through 100
DSTR 516 M10 10 Threaded Head Screw for use in steel I beams and 12 gage purlins 20 through 100
SH DSTR1 M10 10 Threaded Head Screw for use in steel I beams and 12 gage purlins 20 through 100
XP 20 M10 10 Threaded Head Screw for use in 12 gage purlins 20 through 100
XP 35 M10 10 Threaded Head Screw for use in 12 gage purlins 20 through 100
SWDR 1 M10 10 Threaded Head Screw for use in 16 gage purlin 20 through 100
SWDR 516 M10 10 Threaded Head Screw for use in 16 gage purlin 20 through 100
SWDR 11⁄2 M10 10 Threaded Head Screw for use in 16 gage purlin 20 through 100
SH GST20 M10 10 Threaded Head Screw for use in Wood 20 through 100
SH GST30 M10 10 Threaded Head Screw for use in Wood 20 through 100
GST 20 M10 10 Threaded Head Screw for use in Wood 20 through 100
GST 30 M10 10 Threaded Head Screw for use in Wood 20 through 100
CST 20 M10 10 Threaded Head Screw for use in Concrete 20 through 100
SWC20 M10 10 Threaded Head Screw for use in Concrete 20 through 100
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-633
Elco Fastening Systems LLC, Falcon Road Operation, 5110 Falcon Road, Rockford IL 61109
Hanger Rod For
Product Size, in., Component Nominal Pipe
Designation NC Description Sizes, in.
ZG471 with backing nut 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
and purlins 16 gage and thicker
ZG491 with backing nut 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
and purlins 16 gage and thicker
ZG511 with backing nut 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
and purlins 16 gage and thicker
ZG470 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
and purlins 12 gage and thicker
ZG471 with backing nut 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
and purlins 16 gage and thicker
ZG490 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
and purlins 12 gage and thicker
ZG550 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
ZG510 3⁄8 Threaded Head Screw for uses in steel beams 3⁄ 4 through 4
ZG730 3⁄8 Threaded Head Screw for uses in concrete 3⁄ 4 through 4
ZG650 3⁄8 Threaded Head Screw for uses in wood beams 3⁄ 4 through 4
ZG660 3⁄8 Threaded Head Screw for uses in wood beams 3⁄ 4 through 4
ZG670 3⁄8 Threaded Head Screw for uses in wood beams 3⁄ 4 through 4
For
Product Hanger Rod Component Nominal Pipe
Designation Size, mm Description Sizes, mm
ZG640 10 Threaded Head Screw for uses in steel beams 20 through 100
ZG705 10 Threaded Head Screw for uses in wood beams 20 through 100
ZG780 10 Threaded Head Screw for uses in concrete 20 through 100
VERTIGO
Series 7100
7173 3⁄ 8 Concrete drilled insert 4
(vertical only)
7175 1⁄ 2 Concrete drilled insert 8
(vertical only)
7162 3⁄ 8 Wood Beams 4
(vertical only)
7161 1⁄ 2 Steel Beams 8
(1⁄4’’ thick)
7158 3⁄ 8 Steel Purlins (12 gage minimum) 4
and Steel Beams (vertical mount)
7154 3⁄ 8 Steel Purlins (12 gage minimum) and 4
Steel Beams (vertical mount)
7160 3⁄ 8 Steel Purlins (12 gage minimum) and 4
Steel Beams (vertical mount)
7184 3⁄ 8 Steel Purlins (12 gage minimum) 4
(horizontal mount)
7186 3⁄ 8 Steel Purlins (12 gage minimum) 4
(horizontal mount)
7201 3⁄ 8 Steel Purlins (12 gage minimum) 4
(horizontal mount)
7188 3⁄ 8 Steel Purlins (12 gage minimum) 4
(horizontal mount)
VERTIGO (METRIC)
Series 28000
28084 10mm Concrete drilled insert 4
(vertical only)
28038 12mm Steel Beams 8
(6.3mm thick minimum)
28008 10mm Steel Purlins (2.7mm minimum) 4
and Steel Beams (vertical mount)
28010 10mm Steel Purlins (2.7mm minimum) 4
and Steel Beams (vertical mount)
28100 10mm Steel Purlins (2.7mm minimum) 4
(horizontal mount)
28102 10mm Steel Purlins (2.7mm minimum) 4
(horizontal mount)
FM Approvals
September 2007 — Approval Guide
1-634 Automatic Sprinkler Systems
THD50400H 1⁄ 2 8 ’’
THD50500H 1⁄ 2 8 ’’
THD50600H 1⁄ 2 8 ’’
THD50612H 1⁄ 2 8 ’’
THD50800H 1⁄ 2 8 ’’
THD501100H 1⁄ 2 8 ’’
THD501200H 1⁄ 2 8 ’’
THD501300H 1⁄ 2 8 ’’
THD501400H 1⁄ 2 8 ’’
THD501500H 1⁄ 2 8 ’’
THD62500H 5⁄ 8 12 ’’
THD62600H 5⁄ 8 12 ’’
THD62612H 5⁄ 8 12 ’’
THD62800H 5⁄ 8 12 ’’
THD75500H 3⁄ 4 12 ’’
THD75600H 3⁄ 4 12 ’’
THD75700H 3⁄ 4 12 ’’
THD37500HMG 3⁄ 8 4 Titen HD Screw Anchor-Hex Head,
and Mechanically Galvanized
THD37600HMG 3⁄ 8 4 ’’
THD50612HMG 1⁄ 2 8 ’’
THD50800HMG 1⁄ 2 8 ’’
THD62600HMG 5⁄ 8 12 ’’
THD62612HMG 5⁄ 8 12 ’’
THD62800HMG 5⁄ 8 12 ’’
POWDER-ACTUATED TOOLS
Powder-actuated tools utilize expanding gases from a power load to drive a fastener into masonry, concrete or
steel. Use of these tools shall be in strict conformance with the manufacturer’s recommended procedures. These
tools are divided into two types: direct-acting, in which the expanding gas of the power load acts directly on the
fastener to be driven and indirect-acting, in which the expanding gas of the power load acts on a captive piston which
in turn drives the fastener. These tools have three velocity classifications: low, medium and high. Powder-actuated
tools are tested by FM Approvals, FM Approved and listed in strict conformance with the American National Standard
Safety Requirements for Powder-Actuated Fastening Systems: ANSI A10-1970, ANSI A10-1972 and ANSI
A10-1977, and also the Federal Register, Occupational Safety and Health Administration (OSHA), Volume 37, No.
202 and Title 29, Part 1910.
Model UNIDEK. .25 caliber, multi-shot, low velocity, indirect acting, piston type. For use with Model BX 14 fasteners in steel or concrete
building structural members.
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-635
FM Approvals
September 2007 — Approval Guide
1-636 Automatic Sprinkler Systems
FM Approvals
September 2007 — Approval Guide
Automatic Sprinkler Systems 1-637
FM Approvals
September 2007 — Approval Guide
1-638 Automatic Sprinkler Systems
Steel Pipe
Lightwall Pipe — Non-threadable Non-schedule — Normal connections welded, rolled groove or plain end
Schedule 10 — Normal connections are welded, rolled groove, or plain end
Schedule 40 — Normal connections are threaded, welded, rolled or cut groove, or
plain end
Schedule 5 — Non-threadable Lightwall Pipe — Normal connections welded, ‘‘Press-Fit’’, limited Approval of rolled groove
Thinwall Pipe — Non-schedule — Normal connections are threaded, welded, rolled groove or plain end
Schedule 80 — Normal connections are threaded, welded, rolled or cut groove, or plain end
Suction Pressure Regulating Valves for Booster Pumps
Surge and Waterhammer Arresters
Telescoping Sprinkler Assemblies for Use in Anechoic Chambers
Testers for Vane Type Waterflow Detectors
Water Motor Gongs
Waterflow Alarm Valves
Waterflow Detector Check Valves
Waterflow Detectors, Vane Type
Trim Water Pressure Relief Valves (Adjustable)
Trim Water Pressure Relief Valves (Fixed)
FM Approvals