External Alarm Validation and Rectification

Acceptance Date
Project Name Battle 1 Q1 AOP 2021
Site ID 11TGR0189
Site Name BATUSARI2_HS
System Key 22NDXXXNW606411

This page will explain how this validation external alarm implementation in the field
accepted by both party

Review Status
Alarm External alarm (shall be Eltek or Delta
6150 Cabinet/Port
Position # confirmed with NOC to monitor Cabinet /Port NOT Remarks
Number OK
the result of alarm test) Number OK

1 Main Power Failure OK/2 OK/1 V When 2 or all 3 phase fails in 3 phase scenario
2 Rectifier Module Failure OK/4 OK/2 V When rectifier module fails due to module internal
failure but NOT due to main power
3 High Temperature Alarm OK/3 OK/3 V High temperature inside the cabinet
4 NPLVD Disconnect (RRUs off) OK/4 V When RRUs (i.e. Non-Priority Loads) are disconnected
due to lack of battery backup after 4 hours, typically
NPLVD/LVD2 is set to 46V. Then NPLVD/LVD2
Reconnect level is set 49.5V or hysteresis is set to 3.5V.
Rectifier Type:
1. IFORTE/ELTEK/ (NPLVD value: 46 Volt)
2. Westindo/ELTEK (NPLVD value: 46 Volt)
3. Hariff/DELTA (NPLVD value: 46 Volt)
4. TBG/Energy Manager (NPLVD value: 45 Volt)
5. IBS/DELTA (NPLVD value: 45 Volt)
6. BALI TOWER/ZTE (NPLVD value: 46 Volt –Lithium
Battery)
7. BALI TOWER/ZTE (NPLVD value: 43.2 Volt –Non-
Lithium Battery)
8. STP/Emerson (NPLVD value: 46 Volt)
9. STP/Exicom/Eltek (NPLVD value: TBD)

5 Surge Arrester Failure OK/2 OK/5 V When any of the 3 Surge arresters fail
6 Load Breaker Trip OK/6 V When any DC load breaker trips (i.e. telecom equipment
power off) or battery breaker trips
7 Door Open OK/1 OK/7 V When door is opened
8 Aviation Light Failure When Aviation light fails
9 Fire Smoke Heat Alarm Only for Indoor Shelter
10 Gensets Working If Applicable
11 Gensets Fails If Applicable
12 ATS Fail If Applicable
13 Low Fuel If Applicable
14
Site ID 11TGR0189
Site Name BATUSARI2_HS
Enclosure Type Enclosure 6150 / Non Enclosure 6150

Acceptance of Device Alarm Image


External Photo (Alarm Active) Photo (Alarm Cleared) Alarm Status
Alarm
Alarm Active

Alarm Cleared

Main
Power
Failure

Alarm Active

Rectifier
Module
Failure Alarm Cleared
Alarm Active

High
Tempera
ture
Alarm Cleared
Alarm

Alarm Active
NPLVD
Disconne
Alarm Cleared 3
ct (RRUs
off)

Alarm Active

Surge
Arrester
Failure
Alarm Cleared

Alarm Active
Load
Breaker
Trip
Alarm Cleared
Alarm Active

Door
Open
Alarm Cleared

Submit Approver
VENDOR MS NE ACCEPTANCE INDOSAT

Name : FERI DIAN KOSWARA Name : Name :


Date : 20 Maret 2021 Date : Date :

Aktual alarm

- DOOR OPEN ✅

-Main fails ❌

-Arrester failure ✅

- Low Voltage disconnet ❌

-Rectifier main failure ✅

-Battery failure ❌
-high temperature ✅

Note : Aktual di site tidak ada baterai 🙏