Professional Documents
Culture Documents
Overview
Hardware – I/O’s
KG-1500
10 digital inputs
11 digital outputs (relays)
7 analog inputs
2 analog output (+/- 10V or +/- 20mA or PWM)
Service port (ToolKit / KRM)
2 CAN interface (load share and J1939)
D+ connection
1 RS-485 interface with Modbus
1 MPU input
2 |
Application
Single Unit Mains Parallel
Engine start / stop
Generator protection 3ph
AMF (auto mains failure) 1ph
Generator control:
− Frequency / active power o/c
3 |
Application
Multiple Unit Isolated Parallel
Engine start / stop
Generator control / protection
Frequency / load sharing
Voltage / reactive load sharing
Sequencing (Load Dependent Start /Stop: LDSS)
Maximum 16 units in parallel
Inbuilt Neutral Interlocking logic
Run-Up Sync
4 |
Voltage and Current sensing Generator and Mains
3Ph4W (3phase, 4wire) 3Ph3W (3phase, 3wire)
1-, 2- and 3-phase CT arrangement possible & configurable for each phase
5 |
AC Generator sensing
True RMS Voltage Sensing True RMS Current Sensing
4-phase (L1, L2, L3, Neutral) 3-phase
100 and 400 V input Class 1 accuracy
Frequency measurement
Field rotation detection
Class 1 accuracy
7 |
PAGE 7
Alarm Classes
Classes are free configurable for most monitoring functions
Class Action Result
Display Warning
Display and Horn Unload Gen. and open GCB Cool down Shut down
Display and Horn Immediately Open GCB Cool down Shut down
Display and Horn Unload Gen. and open GCB Immediate Stop Shut down
Display and Horn Immediately Open GCB Immediate Stop Shut down
8 |
Generator Protection
# of Trip Levels ANSI Code
Over-/undervoltage 2/2 [59/27]
Voltage asymmetry 1 [47]
Over-/underfrequency 2/2 [81O/U]
Overload (IOP/MOP) 2 [32]
Reverse/reduced power 2 [32R/F]
Unbalanced load 2 [46]
Definite time-overcurrent 3 [50/51]
Inverse time-overcurrent 1 [IEC 255]
Overspeed (MPU) 2 [12]
Measured ground current 2 [50G]
Calculated ground current 2
9 |
Generator Protection
# of Trip Levels ANSI Code
Power factor (PF) lagging 2
PF leading – loss of excitation 2
Phase rotation field CW/CCW 1
Unload mismatch (time out monitoring) 1 Controller*
Operating range failed 1 Controller*
10 |
Engine Protection
Maintenance days/hours exceeded
Over-/Under speed (MPU)
Unintended Stop
Engine Stop malfunction
Speed/frequency mismatch
Start failure
Charge alternator low voltage
Red stop and Amber warning lamp (J1939)
Battery over-/under voltage
11 |
Mains Protection
# of Trip Levels ANSI Code
Over-/undervoltage 2/2 [59/27 ]
Over-/underfrequency 2/2 [81O/U]
Import/Export power 2 [32]
Power factor leading 2
Power factor lagging 2
Phase shift 1ph/3ph [78 ]
df/dt 1 [81R]
Field rotation
12 |
Miscellaneous Monitoring
Phase rotation mismatch generator / busbar / mains
Mains decoupling
CAN bus communications monitoring (J1939, CANopen)
Parameter alignment (multiple units)
Missing members (multiple units)
Wire break analog inputs
Discrete inputs
Free Alarms (1-8)
FlexLimitsTM for analog values
Breaker Monitoring
Breaker fail to open / close (GCB / MCB)
Breaker Failure – 50BF (GCB / MCB)
Sync time out (GCB / MCB)
Neutral Contactor
13 |
Neutral Interlocking
The Neutral Interlocking function controls in multiple-gen applications the Neutral
Contactor (NC) of each generator. The contactor bridges the Neutral with the PE. The
rule is that only one neutral of the running generators in the same segment are
bridged to earth.
The Logic ensures that with changing of generators or a lacking neutral breaker the
neutral link is passed over to another active running generator. This requires
information exchange between the genset controls. The load share protocol in the
easYgen provides the according information.
14 |
Neutral Interlocking
Application
Wiring neutral Interlocking: GCB 3-pole Wiring neutral Interlocking: GCB 4-pole
15 |
Neutral Interlocking
Start and operating
The genset control closes principally after each successful start (firing speed reached) the NC. The genset control proceeds
with closing the GCB, if the NC has been closed successfully. If the NC closure was not successful the easYgen issues an
alarm. The NC and GCB closure procedure is blocked from now on, until the alarm is acknowledged.
When the GCB is closed the genset control begins to figure out, whether the own NC can remain closed or must be opened.
This monitoring is done continuously. As long the GCB is closed, the NC remains closed or is closed, if:
No connection to mains is active
AND
one of the following is TRUE
– the own NC is the only closed NC in the same segment
OR
– there is minimum one other NC in the same segment closed but the own generator has a higher neutral interlocking priority
OR
– there is minimum one other NC in the same segment closed which has the same neutral interlocking priority but the
own genset control has a lower device number
16 |
Neutral Interlocking
Parameters in KG-1500
As long the engine/generator is running and the GCB is open the NC will be closed or remains closed until the engine
/ generator is stopped.
17 |
Neutral Interlocking
Parameters in KG-1500
The discrete input 10 (DI 10) is used as feedback of the Neutral contactor and cannot be configured
onto another discrete input. If the input is energized, the neutral contactor is recognized as closed..
Monitoring of NC feedback
The priority for closing GCB is configurable. This priority is independent from the LDSS priority. The
customer can freely decide which generator shall get which priority.
18 |
Run-UP Sync
Close GCB before excitation
Transformer magnetizing: generator and transformer build up voltage gradually through the
start without large inrush
Used to get several synchronous generators onto load in a very short time
In some cases the in-rush current of a transformer may be more than one generator can supply
when closing the live generator to the dead transformer
19 |
Run-UP Sync
General notes
RPM speed source required (MPU or J1939)
20 |
Run-UP Sync
Application
21 |
Run-UP Sync
Single generator with power transformer.
Precondition
GCB open
GCB MCB MCB open
Engines stopped
Run-up synchronization released (LM)
Load
22 |
Run-UP Sync
Single generator with power transformer.
Application Flow
Start Command
GCB MCB Engine Started
Load
23 |
Run-UP Sync
Single generator with power transformer.
Application Flow
Start Command
GCB MCB Engine Started
GCB closed, when minimum
speed for close GCB is reached
(350 rpm)
Load
24 |
Run-UP Sync
Single generator with power transformer.
Application Flow
Excitation ON at 700 rpm (speed
GCB MCB for excitation to start)
Load
25 |
Run-UP Sync
Multiple generators with load on common busbar
GCB
Precondition
GCB open
Engines stopped
Run-up synchronization released (LM)
GCB Load
GCB
26 |
Run-UP Sync
Multiple generators with load on common busbar
GCB
Application Flow
Start Command
Engines Started
GCB Load
GCB
27 |
Run-UP Sync
Multiple generators with load on common busbar
GCB
Application Flow
Start Command
Engines Started
GCB close, when minimum speed for
GCB Load
close GCB is reached (350 rpm)
GCB
28 |
Run-UP Sync
Multiple generators with load on common busbar
GCB
Application Flow
Excitation ON at 700 rpm (speed for
excitation to start)
GCB Load
GCB
29 |
Run-UP Sync
Multiple generators with large transformer on common busbar
GCB
Precondition
GCB open
Engines stopped
Run-up synchronization released (LM)
GCB Load
GCB
30 |
Run-UP Sync
Multiple generators with large transformer on common busbar
GCB
Application Flow
Start Command
Engines Started
GCB Load
GCB
31 |
Run-UP Sync
Multiple generators with large transformer on common busbar
GCB
Application Flow
Start Command
Engines Started
GCB close, when minimum speed for
GCB Load
close GCB is reached (350 rpm)
GCB
32 |
Run-UP Sync
Multiple generators with large transformer on common busbar
GCB
Application Flow
Excitation ON at 700 rpm (speed for
excitation to start)
GCB Load
GCB
33 |
Configuration via ToolKit
RS-232 or CAN
34 |
Load setting file via KG1500 Setup s/w
RS-232
35 |
Any Questions ?