OLYMPIC CABLE COMPANY SDN. BHD.

1KV 4CORES, XLPE INSULATED, PE INNER SHEATHED, COPPER TAPE SCREENED, PE OVERSHEATHED NON-ARMOURED CABLE

TECHNICAL DATA
2
REF DESCRIPTION UNIT 25 mm x 4C
1 Reference standard IEC 60502-1:2004
2 Voltage (Uo / U) kV 0.6 / 1.0
3 Number of cores 4
4 Conductor
- Material Aluminium
- Cross sectional area mm2 25
- Number of strands Nos. Min. 6
- Conductor shape Sectoral stranded
- Conductor's outermost direction Right-handed (Z)
5 Insulation
- Material Cross-linked Polyethylene
- Nominal thickness mm 0.9
- Method of application Extrusion
7 Inner sheatlh
- Material Black PE
- Minimum thickness at any point mm 0.8
- Overall diameter over inner shealth mm 19.86
8 Metallic Screen
- Material Copper Tape
- Nominal Thickness mm 0.08
9 Outer Sheath
- Material Black PE
- Nominal thickness mm 1.8
- Overall diameter over outer shealth (approx) mm 23.92
10 Condition Upon Which Current Carrying
Capacities are Based
- Soil thermal resistivity K-m/w 1.2
o
- Ground temperature C 25
o
- Ambient air temperature C 40
- Burial depth mm 600
- Load factor % 100
- Number of circuit 1
11 Minimum Radius of Bend
- Laid direct in ground mm 191
- Laid in duct mm 191
- Laid in air mm 191
12 Minimum interal diameter of duct mm 38
13 Maximum DC Resistance of Conductor at 250 C ohm/km 1.224
14 Maximum Conductor Temperature
o
- Laid direct in ground C 90
o
- Drawn into duct C 90
o
- Laid in air C 90

Page 1 of 2
OLYMPIC CABLE COMPANY SDN. BHD.

1KV 4CORES, XLPE INSULATED, PE INNER SHEATHED, COPPER TAPE SCREENED, PE OVERSHEATHED NON-ARMOURED CABLE

TECHNICAL DATA
2
REF DESCRIPTION UNIT 25 mm x 4C
15 Maximum Current Carrying Capacity Based
on condition Specified (See Ref : 14)
- Laid in ground Amp 100
- Drawn into duct Amp 86
- Laid in air Amp 89
16 Copper Tape Earth Fault Current Rating
o
- Initial temperature C 80
o
- Maximum conductor fault teperature C 200
- Short circuit current rating:-
- For 1 second kA 0.48
- For 3 second kA 0.28
17 Maximum Volt Drop at Maximum Conductor
Temperature
- For 1 - phase circuits mV/A.m 3.08
- For 3 - phase circuits mV/A.m 2.67

Page 2 of 2