‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT: 01910 th CABLE CALCULATIONS AagsullieS TTECNICAS REUNIDAS DOCUMENT # —500-85C-0006 PAGE 1 of 36 ‘SAUDI KAYAN CLIENTS DOCUMENT; Client's 1D Code (f required) See 2 MAIN DOCUMENT REV. DATE DESCRIPTION COMMENTS: 1 11-10-07 Issue for Design 2 41-12-07 Issue for Construction 3 09-04-08 Issue for Construction ATTACHMENTS, ATTACHMENT # DESCRIPTION ot Cable Data Base 09/04/08, ETAP Report (Ampacity Calculation, Duct Bank i 3x8, Depth = 30°) iu eee ETAP Report (Ampacity Calculation, Duct Bank _ 3x5, Depth = 102") i ett 04 SS 50, Cable Trench Layout (N°501-65P-0700) 1 24109107 ETAP Report (Temperature Calculation, Duct _ < Bank; EDB-132, Depth = 30") 1 eee ETAP Report (Temperature Calculation, Duct bd Bank; EDB-132, Depth = 75") ; pean ETAP Report (Temperature Calculation, Duct id Bank; EDB-132, Depth = 75" and DF = 0.22) : eee Coordination Curves of MV Motors (Fuse vs 08 dwar Gabia) 1 09/04/08, PREPAREDBY | REVIEWED BY APPROVED BY Name Name Name. cect ¢| | Bales THN ae “This document Is property of TR Group. Reproduction thereo is forbidden, ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 th CABLE CALCULATIONS seagulls TECNICAS REUNIDAS DOCUMENT #: 500-650-0008 PAGE 2 0f 35, 4. OBJETIVE 3 2. GENERAL DESCRIPTION OF THE ELECTRICAL POWER SYSTEM OF SAUDI KAYAN PETROCHEMICAL COMPLEX 3 3. APPLICABLE REFERENCE DOCUMENTS AND STANDARDS 3 3.1 Sabic Engineering Standards 3 3.2 Engineering Project Specifications 4 3.3. Industry Codes and Standards 4 3.4 Technical Papers Consulted (IEEE) 4 4, METHODOLOGY AND CALCULATION PREMISES 5 441 Maximum Voltage Drops Calculations 6 4.2 Technical Considerations on Ampacity Calculations 8 4.3. Underground Raceway Module of ETAP 9 4.4 General Example of Ampacity Calculation (Std IEEE 399 vs ETAP) 10 4.5 Ampacity Calculation on Saudi Kayan Project 18 4.8 Short Circuit Fault Checking 22 5. EXAMPLES OF CABLE CALCULATIONS 23 51 Cable Calculation (MV): 23 5.2 Cable Calculation (Lv): 25 6 CONCLUSIONS 28 7. ATTACHMENTS 29 7.1 Attachment N° 1: Cable Data Base 29 72 la N° 2: ETAP Report (Ampacity Calculation, Duct Bank 3x5, Depth = 7 73 rein N° 3: ETAP Report (Ampacity Calculation, Duct Bank 3x5, Depth = i 7.4 Attachment N° 4: SS 50, Cable Trench Layout (N° 501-65P-0700) 32 7.8 Attachment N° 5: ETAP Report (Temperature Calculation, Duct Bank; EDB- 132, Depth = 30") 33 7.6 Attachment N° 6: ETAP Report (Temperature Calculation, Duct Bank; EDB- 132, Depth = 75°) 34 7.7 Attachment N° 7: ETAP Report (Temperature Calculation, Duct Bank; EDB- 132, Depth = 75" and DF = 0.22) 35 7.8 Coordination Curves of MV Motors (Fuse vs Power Cable). 36 TABLE OF CONTENTS ‘This documents property of TR Group, Reproduction thereof is forbidden, ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 ti CABLE CALCULATIONS QagaulS TECHICAS REUNIDAS ae DOCUMENT #: — 500-65¢-0008 PAGE 9 of 95, 4, OBJETIVE 3 This purpose of this study is to establish the criteria for properly sizing all medium and low voltage cables to be installed in the Saudi Kayan Petrochemical Complex. 2, GENERAL DESCRIPTION OF THE ELECTRICAL POWER SYSTEM OF SAUDI KAYAN PETROCHEMICAL COMPLEX Saudi KAYAN will construct a new PETROCHEMICAL COMPLEX in Al-Jubail, Kingdom of Saudi Arabia as described previously, which will include the new electrical substation (SS 50). Electrical substation #50 will supply power to units Phenol, Cumene & Future Acetone, BPA (North and South) and Phenolics Tankage will be electrically fed from existing Substation 75A, through Switchgears SG-76A-102 (34.5 kV) and ESG-75A- 301 (4.16 kV). This new substation will have a nominal capacity of 48 MVA installed, with two (2) 2 winding transformers of 20 MVA, 34.5/4:16-KV [TX-50-301A and B], two of 3 MVA, 4.1610.48 kV [ETX-50-410A and B], one (1) of 2 MVA, 4.16/0.48 KV [TX-50-406], one (1) and exclusive of 10 MVA, 34.5/13.8 kV [TX-50-201] feeding the Turbo Compressor K-52200 (6200 kW) of Phenol Unit, and six (6), 3 winding transformers of 6/3/3 MVA 34,5/0.48/0.48 KV [TX-50-401A and B, TX-50-402A and B, TX-50-403A and BI, feeding the low voltage loads of the units Phenol, Cumene & Acetone, BPA (North and South) and Phenolics Tankage. The Electrical Power Distribution System has a secondary selective configuration, constituted by seven (7) MCC's (480V), [EMC-50-410, MC-50-401, 402, 403, 404, 405, 406] and one Switchgear [SG50-301], (4.16kV). APPLICABLE REFERENCE DOCUMENTS AND STANDARDS 3.1. Sabic Engineering Standards + SES-£02-E01: Power System and Equipment Design Calculations * SES-E22-S01: Cables, Low Voltage (NEC and IEC). + SES-E22-S02: Cables, 5 to 35 KV (NEC and IEC), ‘This document is propeny of TR Group. Reproduction thereot is forbiiden, ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 th CABLE CALCULATIONS Sage DOCUMENT # —500-65¢-0006, PAGE 4 0f 36 TTECNICAS REUNIDAS 3.2 Engineering Project Specifications * 000-658-0001: Criteria for Electrical System Design. 3.3. Industry Codes and Standards «IEEE Std 399; Recommended Practice for Industrial and Commercial : Power System Analysis. «IEEE Std 141: Recommended Practice for Electric Power Distribution for Industrial Plants. + IEEE Std 242; Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. * NFPA7O: National Electrical Code. 3.4. Technical Papers Consulted (IEEE) * Major factors affecting cable ampacity de Leon, F. Power Engineering Society General Meeting, 2006, IEEE Volume , Issue , 18-22 June 2006 Page(s): 6 pp. - Digital Object Identifier 10.1109/PES.2006.1708875 ‘Summary: This paper presents a parametric study of the major factors affecting cable ampacity calculations. The current carrying capacity (or ampacity) of a cable depends on many of the installation properties and conditions. In this paper the effects on* ampacity of conductor size, ambient temperature, bonding arrangement, duct size, soil thermal resistivity, resistivity and size of backfill (or duct bank) and depth of installation for underground installations are presented. For cables air the effects on ampacity of the intensity of solar radiation, the spacing from the wall and the grouping of cables are analyzed. For riser pole installations the effect of the solar radiation, wind speed, ventilation and diameter of the duct are shown. + Cable crossings-derating considerations. lI. Example of derivation of derating curves Anders, G. Brakelmann, H. Ontario Hydro, Toronto, Ont, Publication Date: Jul 1999 Volume: 14, Issue: 3 Digital Object Identifier: 10.1109/61.772305, ‘This documents property of TR Group. Reproduction thereof is forbidden | SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 thy CABLE CALCULATIONS Hagel TECNICAS REUNIDAS DOCUMENT: 500-650-0005 PAGE 5 of 38, Summary: Cables crossing other heat sources either perpendicularly or at oblique angles will experience a rise in conductor temperature which should result in ampacity derating. In the first part of the paper a mathematical model for calculation of derating factors was presented. In this paper, a practical numerical example is considered with a 138 kV pipe-type cable crossing a 10 kV distribution circuit. The numerical analysis presented confirms experimental findings reported in the literature that the cable crossing may elevate conductor temperature by as much as 20°C METHODOLOGY AND CALCULATION PREMISES According to standards SES-E22-S01 and SES-E22-S02, voltage levels shall be 35 kV (for 34500 Volts feeders), 12/20 KV (for 13800 Volts feeders), 6/10 KV (for 4160 Volts feeders) and 0.6/1 kV (for 480 Volts feeders). The smallest core SES-E22-S02. selected shall be in accordance to SES-E22-S01 and In order to properly size medium and low voltage cables, three aspects shall be checked: ‘+ Maximum Voltage drop: steady state and during motor starting. * Cable Ampacity calculations. © Short circuit fault levels. The largest cable size resulting from the above calculations shall be the selected for all applications. Cable data specifications are to be taken from available manufacturer's information. Once the final manufacturer's data is available (i.e. project's cables manufacturer data), a complete revision of the calculations shall be carried out ‘This cacurents propesty of TR Group. Reproduction thereat is forbidden ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #01910 th CABLE CALCULATIONS Bagels TTECHICAS REUNIDAS DOCUMENT # —500.65¢-0006 PAGE 6 of 96 4.1 Maximum Voltage Drops Calculations ‘Steady state voltage drops for low voltage systems shall be considered as, follows: | + Summation of voltage drops in the main and feeders supplying a motor control center or switch rack: Maximum of 3%, providing the maximum total voltage drop for the main, feeder, and branch circuit does not exceed 5%. ‘© Motor branch circuit: Maximum of 5%, providing the maximum total voltage drop. * Summation of voltage drops in feeders from main to distribution center, panel board, or transformer that supply lighting, instrumentation, or other low voltage requirements: Maximum 2%. '* Branch circuit supplying lighting, instrumentation, or other low-voltage requirements: Maximum 3%, to the most distant outlet. Steady state voltage: drops for medium voltage systems shall be considered as follows: + Summation of voltage drops in main and feeders supplying equipment remote from the main switchgear: Maximum of 3%, providing the total voltage drop for main, feeders, and branch circuit does not exceed 5%. * Motor branch circuit originating at starter remote from main switchgear: Maximum of 5%. To calculate the Steady State Voltage Drop, the following formula may be used: < ldesign> (Rx Cosd-+ X x Sing) K%) AV =[ 3x1 nave ‘This documents property of TR Group. Reproduction thereo is forbidden. SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 th CABLE CALCULATIONS Aaqaulliys TECNICAS REUNIDAS eee DOCUMENT#: sooéscatoe PAGE Tt 96 ‘Where: AV: Steady state voltage drop (%). L: Total cable length between motor and switchgear (km) R: Resistance of the conductor (Ohm/km). X: — Reactance of the conductor (Ohm/km).. # — Power factor angle. Vn: Nominal system voltage (V). Transient Voltage Depression shall be considered as follows: + Voltage dips at utilization devices at any location within the electrical system, other than motors, caused by motor ‘starting shall not exceed the limits established in the specification 000-65S-0001. ‘+ Minimum voltage at motor terminals of motors during starting shall be greater than 80% of the rated motor voltage during motor starting. To calculate voltage drops during motor starting, the next formula may be used: Istart x(Rx Cos$ +X x Sing) (%) AV =[ \BxLx 10xVn Where: AV: Steady state voltage drop (%) Total cable length between motor and switchgear (km). Istart: Motor starting current (Amps) R: Resistance of the conductor (Ohm/km). X: _ Reactance of the conductor (Ohm/km). This documents property of TR Group. Reproduction thereois forbidden. ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 th CABLE CALCULATIONS. TECNICAS REUNIDAS DOCUMENT #: —500.85C-0008 PAGE 80f 6 @ — Power factor angle. Vn: Nominal system voltage (V) 4.2. Technical Considerations on Ampacity Calculations ‘Ampacity calculations and cable sizing shall be based on the National Electrical Code (NEC), and using the principles defined in the IEEE standards 399 and 141 On the other hand, the Cable De-rating Module of the Electrical Transient Analyzer Program (ETAP) shall be used to determine and verify the de-rating factor to be applied in determining the cable size for any given application. For motor feeders, the National Electrical Codes states in its article 430.22 that "branch circuit conductors that supply a single motor used in @ continuous duty application shall have an ampacity of not less than 125% of the motor’s full load current (FLC) rating’. For the basis of sizing a feeder which supplies distribution equipment, the maximum operating load shall be equal to the minimum of: * The continuous current rating of the distribution equipment main bus. + The site rating of the upstream transformer. * Load Factor shall be 100%. | Ambient temperatures and thermal resistivity to be considered in the calculations shall be as following: + 60°C for cables to be installed outdoors, exposed to Sun (for exposed cables, cables in conduit, and cables in uncovered cable trays) ‘+ 50°C for cables to be installed outdoors, shaded (for exposed cables, cables in conduit, cables in covered trays exposed to the sun, and cables in cable trays in the shade). * 50°C for cables to be installed indoors, at non-air-conditioned environments. + 36°C for cables to be installed indoors, at air-conditioned controlled environments. ‘This document i property of TR Group. Reproduction thereo Is forbidden. ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #. 01910 th CABLE CALCULATIONS agai TECNICAS REUNIDAS eee] DOCUMENT'#: 500.650.0006 PAGE 90135 + 35°C for soil temperature. ‘+ The vaiue of soil thermal resistivity used in cable current rating calculation is 120 °C-omW. Cable sizing calculations shall include an overall de-rating factor due ambient site conditions, temperature, grouping, and others defined in the standards listed before. 4.3. Underground Raceway Module of ETAP ETAP software has available an Underground Raceway Module based on Std IEC 60287 or the NEC and Recommended Practice IEEE Std 399 accepted Neher- McGrath method for these calculations. It determinates steady-stated and transient conductor temperature for the specified cable loading: and raceway system configuration, considering the effect of heat generated by neighboring cables and ‘external heat sources. ‘This module is integrated with the cables in. one-line diagram of the project and hence with the load flow results (to perform the cable temperature calculations the load flow was calculated considering the absorbed power of each motor & static load). Additionally ETAP Underground Raceway Module has two equivalent options for cable ampacity calculation known as Uniform-Ampacity Calculation and Uniform- Temperature Calculation. Uniform-Ampacity Calculation: The cable ampacity is calculated by loading of all cables until the temperature of the hottest cable reaches the maximum allowable limit (ETAP uses the Neher-McGrath method for this application) easing the Uniform-Temperature Calculation: This calculation adjusts individual cable loading to maintain uniform temperature throughout the raceway system. The cable ampacity is obtained when the cable temperature reaches the maximum allowable limit (ETAP uses the Neher-McGrath method for this application). “This document is property of TR Group. Reproduction thereof is forbden. SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 a | th CABLE CALCULATIONS aeoqeull he TECNICAS REUNIDAS ‘i DOCUMENT #: — 500.65¢-0008 PAGE 10026 Note: All the Ampacity Calculations were carryout based on the method: “Uniform- Ampacity Calculation” on this project. 4.4 General Example of Ampacity Calculation (Std IEEE 399 vs ETAP) ‘The objective of this example is to illustrate the limitations for some applications of the manual method presented on the Standard IEEE 399, Section 13.1 to determinate the Overall De-rating factor based on the Ampacity Adjustment Factors calculated by computer program (USAmp) for different installations conditions of underground power cable systems. The method presented on Std JEEE 399 is based on the concept of an adjustment (de-rating) factor applied against a base ampacity to provide the allowable cable ampacity. V=Fet Where FF: Itis the allowable ampacity under the actual installation conditions. F: Itis the overall cable ampacity adjustment factor. [It is the base ampacity, i.e., the ampacity specified by the manufacturers or other authorities sources, such as the ICEA. Note: A Cable Data Base was generated for this project by using manufacturer | information for LV and MV cables (see Attachment 1). | The overall cable adjustment factor is a correction factor that takes into account the differences in the cable's actual installation and operating conditions from the base conditions. This factor establishes the maximum load capability that in an actual cable life equal to or greater than that expected when operated at the base ampacity under the specified conditions ‘This document is property of TR Group. Reproduction thereof is forbidden. | ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 aa th CABLE CALCULATIONS Saqauls TECNICAS REUNIDAS DOCUMENT #: —500.65C-0006 PAGE 11 of 6 The overall ampacity adjustment factor is composed of several components as indicated in the next equation: F = (Ft) x (Fth) x (Fg) Where Ft Itis the adjustment factor to account for the differences in the ambient and conductor temperatures from the base case. This adjustment factor is used to determine the cable ampacity when the operating ambient temperature and/or the maximum allowable conductor temperature differ from the original temperatures at which the cable base ampacity is specified. The expression for calculating the effect of changes in the conductor temperature and ambient temperatures on the base ampacity is given by the nex equation Ft=[(Po-Ta)l(To-Ta)x(234.5+Te)(234.5+T'c)]" (Cooper conductor) Where Te: It is the conductor rated temperature in °C at which the base ampacity is specified. Tc: It is the maximum allowable conductor operating temperature in °C. Ta: It is the ambient temperature in °C at which tha base ampacity is specified. a: Itis the actual (maximum) soil ambient temperature in °C. Fh: It is the adjustment factor to account for the differences in the soil thermal resistivity, from the RHO of 90 °C-cm/W at which the base ampacities are specified. Fg: Itis the adjustment factor to account for cable grouping. Note: For cable separations other than those considered in the Tables 13-8 and 13-9 of the Std IEEE 399 (No spare ducts, non-metallic conduits of 5” with center-to-center spacing of 7.5”), one can use one’s own judgment for estimating the value of Fg or use a computer program directly without on initial approximation for the grouping effect. In general, increasing the horizontal and vertical spacing between the cables would decrease the temperature interference between them and, therefore, increase the value of Fg (Source: Std IEEE 399, Section 13.4.3 Grouping Adjustment Factors). ‘Ths documents property of TR Group, Reproduction there is forbidcen, ti ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 CABLE CALCULATIONS DOCUMENT# 500-650-0006 PAGE 12.038 TECNICAS REUNIDAS To obtain the values of the adjustment factors Fth and Fg, a computer program was develop based on the Neher-McGrath method and was used to calculate the conductor temperatures for various arrangements. The ampacity adjustment tables presented on the Std IEEE 399 are based on the following simplifying assumptions: a) Cables for some voltage ratings and sizes are combined for the Fth table. For some applications where RHO is considerably high (more than 180°C-cm/W) and a mixed group of cables are installed, the interdependencies of the adjustment factors for different cable sizes may not be negligible and up to a 4% error in the overall conductor temperatures may be expected. b) The effect of the temperature rise due to the insulation dielectric losses is | neglected for the temperature adjustment factor Ft. Note: Hoverer this effect can be included in Ft by adding the temperature rise due to the dielectric losses to the ambient temperatures Ta and T’a. ©) The often negligible effects of any applicable sheath, shield, and metallic conduit losses are ignored. Note: In the final design case where accuracy and precision are required, the previously mentioned assumptions cannot be disregarded, and the ampacities obtained from the manual method can be used as an initial approximation for computer simulation of the actual design condition (Source: Std IEEE 399, Section 13.4 Ampacity Adjustment Factors). Additionally large variations in the duct bank depth, or larger soil thermal resistivity, may significantly affect ampacities (Source: Std IEEE 399, Section 13.5 Example) = EXAMPLE To illustrate the limitations for some applications of the manual method presented on the Standard JEEE 399, Section 13.1, a 3 x 5 duct bank system (3 rows, 5 columns, depth = 30" = 76.2 cm) is considered. The duct bank contains MV Power Cable of 185 ‘This documents property of TR Group. Reproduction tnereofis forbidden. ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 as ty CABLE CALCULATIONS agoullihS | TECNICAS REUNIDAS : DOCUMENT # —500.650-0006 PAGE 18 of 95 mm? (12-20kV, Material: Cooper), and duct are a diameter of 5 inches of PVC, separated by 7.5 inches, the soil thermal resistivity is 120 °C-cmiW and the temperature of the sand is 35°C as shown in the Figure 4 Figure 4: 3 x 5 Duct Bank Arrangement (Source: Std IEEE 399, Section 13.5 Example). In order to compare the results of the calculation! Based on manual method and the calculations carryout by a program computer (ETAP), on the first step an exactly configuration was generated by using the Underground Raceway Module of ETAP. Then according to the final ampacity of the cables, a load (Current) is assigned to each cable with the aim of calculate the operation temperature and finally the depth of the duct bank is changed on the digital model setting it to Max Depth = 102.36” = 260 ‘om, according to the maximum depth presented in Saudi Kayan Project, and cheeking the new temperatures. Note: This Maximum Depth correspond to the duct bank EDB-187 (length = 60 meters long) located at the interconnection area between the Electrical Substation N50 and the units Phenol and Cumene. + Manual Method: Cable Ampacity = 351 A (Based of maximum conductor temperature = 90°C and thermal resistivity of 120 °C-cm/W and soil temperature 35°C), “This document is property of TR Group. Reproduction thereot is forbidden. TECNICAS REUNIDAS SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FAGILITIES PROJECT # 01910 3 ti CABLE CALCULATIONS Bag ous DOCUMENT #: — 500-65¢-0008, PAGE 14 0f 35 Note: The cable technical data was given by a cable manufacturer. Real condition of the installation: RHO(Soll) = 120 °C-cmW Soil Temperature = 35 °C ‘The required ampacity adjustment factors for ambient temperature, thermal resistivity and grouping are as follow: Due to the conductor and ambient temperature are the same of the installation condition. Fth = 1 Due to the thermal resistivity which the ampacity specified by the manufacturer is the same of the installation condition. Fg = 0.451 for grouping adjustment factor of (6/10KV) cable installed in a 3 x 5 duct bank (see Table 13-9 of Std IEEE 399-1997) The overall cable adjustment factor is: F=1x1x0.451 = 0.451 Therefore the maximum allowable ampacity of each cable size is the multiplication product of the cable base ampacity by the overall adjustment factor. This ampacity adjustment would limit the temperature of the hottest conductor to 90°C when all of the cables in the duct bank are loaded at 100% of their derated ampacities. I= (351A)x(0.451) = 158,3 A + Am Underground Raceway Module of ETAP By using the digital model, the Ampacity Calculated was equal to 157.88 A (See jure 2, Attachment 2 and the summary report indicated below). ‘This documents property of TR Group. Reproduction thereat is forbid, ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 ti CABLE CALCULATIONS Sagal TECNICAS REUNIDAS DOCUMENT #: —500.65¢-0006 PAGE 15 0f 33 Figure 2: 3 x 5 Duct Bank Arrangement (Source: Underground Raceway Module of ETAP) suai Roaln.cuva, Cnn Tuell te Crate ye cai Contaretonio Coie peGate_ nite” ow vey We we tee coer nee According to these ampacities a load was assigned to each cable and set to 134 Amp (85% of the ampacity calculated), and then the steady state temperature was performed, as indicated on the next report. ‘This document is property of TR Group, Reproduction thereat is forbidden ‘SAUDI KAVAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 th CABLE CALCULATIONS spss bs TECIICAS REUNIDAS DOCUMENT # 500-650-0008, PAGE 18 0f 36 Antec wor Enid Rak Die contr $= sae o19C wane Gnome ase ora ca i ete The maximum temperature (72.8°C) was reached by the cable N°8 (conduit N°08), located at the middle of the grouping, so the ampacity calculated by ETAP and by the Manual Method are virtually the same:and can be used to define to load associated to each cable size, keeping the temperature below the limit specified = Ampacity calculations by Underground Raceway Module of ETAP (by changing the Depth of the Duct Bank): ‘The depth of the duct bank is changed to Max Depth = 102.36” = 260 om, according to the maximum depth presented in Saudi Kayan Project, and the ampacity is calculated again (see Attachment 3 and next summary report). ‘This documents property of TR Group, Reproduction theres forbidden | ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 ti CABLE CALCULATIONS spall | TECNICAS REUNIDAS Zt DOCUMENT #: 500-650-0008 PAGE 17 of 6 as Ren 2 Conc Frat Ble @ Die Conic Se cate condetacint> Ge pea teen Wore Yet ae The new Ampacity Calculated is 129.6 A, it means that the new De-rating factor for this depth would be DF = [Ampacity Calculated / Base Ampacity of the Cable]. DF(new) = 129.6 A/ 361 A = 0.369 Therefore there is a deviation of the Overall De-rating factor calculated initially by Std IEEE 399 method, calculated as: [DF(newy/DF(According to Std IEEE 399)}= 0.369/0.451 = 0.81 This result confirms the warnings presented on the Std IEEE 399, about large variations on the duct bank's depth, which produce significant deviations (about 20%, on this particular example) from the ampacities calculated by the manual method. Then, keeping the same load associated to each cable (134 Amp), the steady state temperature was performed with the new depth of the duct bank, getting a new temperature profile (see the report below). ‘This documents property of TR Group. Reproduction thereo is forbidden | emg SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01810 i CABLE CALCULATIONS Aageullie | ‘TECNICA REUNIDAS DOCUMENT # —500.65¢-0008 PAGE 18 0f 36 Coadnir Emrgrd Re Diteie wane | pr Condor Fit Tewp. Lanes Vos Ota Tea cue Gin perce | ata veo me ae On this case the maximum temperature: (94.53°C) was reached by the cable N°8 (conduit N°08), located at the middle of the grouping, exceeding the limit of 90°C. According with these results the ampacity of the cable calculated by the Manual Method cannot apply if the Teal depth of the duct bank presents a large variation from the depth considered for the adjustment factors calculated originally (Depth = 30in = 76.2 cm). To take account this deviation of the DF, the Ampacity of each cable size with the real depth of each configuration studied, shall be carryout for MV and LV cables. 45 Ampacity Calculation on Saudi Kayan Project According to the analysis presented on the previous section, the adjustment factors defined on the Recommended Practice Std IEEE 399, can be applied perfectly to predict the final ampacity of the power cables without any significant error, if the installation conditions (meanly duct bank's depth and arrangement) do not present any large variation from de original calculation premises presented on this mentioned “This documents property of TR Group. Reproduction thereof is forbidden. ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 Gi CABLE CALCULATIONS Sogou TECNICAS REUNIDAS DOCUMENT# 500-650-0008 PAGE 19 of 36 engineering practice and the real conditions presented on this project, however for critical cases (duct banks associated to the interconnection are between the ES N°50 ‘and Phenol & Cumene units) were these assumptions cannot be applied, the next procedure shall be followed as indicated on the next example: I Note: The design of the duct banks associated to the interconnection area was studied and discussed by TR and U8O due to interferences presented with the Pipe Rack Foundations and Electricity Duct Banks, and therefore the coordinates of the top of each duct bank were fitted. + Asa first step a similar procedure of the general example is presented, in order to verify the deviation of the Overall Derating Factor (F = Ft x Fth x Fg) predicted by using the Manual Method for duct banks configurations: with a high variation of standard depth (30° = 76.2 cm). + A study case was established considering one of the duct bank defined on the interconnection area mentioned previously. The duct bank selected was DB-132 (Arrangement: 2 x 19, overall diameter of the ducts = 6 inches, Real Depth = 74.8 inches = 190 cm), as indicated on drawing N° 501-65P-0700, included in the Attachment 4. + Each power cable was sized considering the manual method (adjustment factors). Note: According to the Tables 13,18-13-19 of Std IEEE 399, they have 15 columns ‘as a maximum configuration for grouping factors. + The initial calculation of the cable steady state temperature was performed by using ‘the standard depth equal to 30 inches, see Attachment 5. * According to the results on this case, any power cable exceeds the maximum temperature of 90°C. ‘This document is propery of TR Group. Reproduction thereo is forbidden. ay] ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 CABLE CALCULATIONS geal aS TECNICAS REUNIDAS DOCUMENT #: — 500-85¢-0008 PAGE 20 0 36, + As a second step the cable steady state temperature was performed by using the real depth equal to = 74.8 inches = 190 cm, see Attachment 6. ‘+ The results shown that every single cable exceeds the temperature limit (80°C) when the depth of the duct bank is set to Depth = 74.8 inches (190 cm), + To take account the deviation of the DF, the Ampacity of each cable size with the real depth and arrangement (2 x 19) of the duct bank was carryout for MV and LV cables by using ETAP Software, see Tables 2, 3, 4, 5 and 6. + Finally, the cables were re-sized considering the new DF's calculated, and as a last step the steady state temperature was performed considering the real depth of 74.8, inches (190 cm), see Attachment 7. + The two main models of the Duct Banks located at the interconnection are was studied, these two main model of duct bank were named as indicated on the Table 1. ‘Model | Arrangement | Real Depth | A 4x12 102.96" = 260em | B 2x19 74.8" = 1900m Table 4 + Asummary of the deviations and news DF were defined, see Tables 2, 3, 4, 5 and 6 for the re-sized cable calculations. ‘This documents property of TR Group. Reproduction thereof is forbidden. ‘ samy SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #01910 i CABLE CALCULATIONS ageless TECNICAS REUNIDAS iit | DOCUMENT #: —500.65¢-0008 PAGE 21 of 36 uct Bank Model A (4X 12/4) Deserplonof the Cates: 06-1 kV) /Cu/XLPE! PVC! SWATPUC @ 80° ee Eas ‘accruing Su Eee eet [Bes fry TPS | oe i aa oa ie oar a0 ; oe 7 Baie tse tee 1 oat for roma [Cae + 368 a (Gotumns: 12 “3 we t 3 ar [se ¢ att 1as—[ tr + ae zo] ae + aes uct Bank Mod: 8 42/407) ‘seer o the Cables: (6-10 KY} CU! XLPEIPYGISWA/PYC @ 50°C ee | ec) errenon Premicrnins | meesuah Tor Tape a a asst arf oa} — oe a wae tat | So ttf eee] oe Tas oats na a Sst fess | os ae oa? oor eo Tez re oe po — [tf oe | oer ne er ae pagar “| oa? —— reemenst —na Table 3 Buct Bank Model: A (4X 12/4¥) Description of the Cables: (12-20 k¥) I Cu/ XLPE/ PVC /SWA/ PVC @ 90°C ile) ene =F ee ig 16 SISIEER 399. _ DF Galculated byETAP |. DF Deviation EEA eran avenee For S 301 + [4 | 2s 0282 Baz 0.260 082 DEER 28. DER 0200 Table 4 “This document is property of TR Group. Reproduction thereof is forbcden, | ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #01910 _ Gi CABLE CALCULATIONS TECNICAS REUNIDAS DOCUMENT #: — 500.8650-0008 PAGE 226 36, Buct Rak Mode: B(2 19/40) ‘Desenpton ofthe Cables: (08-1 KV) /Cu /LPE PVC /SWAI PVE 80°C Zs a ae a = = Ome) OPES bec em eg [esmricrnxray Ter osege a er | cama bj tae a see See Bee eee ea rit ae (Note: Group Fatre were taken om St IEEE 960 (Those aden cos were clad consider 16 Columns Miu, Table 5 ‘uct ak Mowe: 8 (2x 19/1) Desert of the Celes (610k) {Cus XLPE/ PVC /SWA/ PVC @ 90°C epee EET) eo “hrc nar eo) ‘dlGateuaieo De ase fe lcokamns: 18} 20 re 72) a s60_| a4 286 08 sas [ 351 ra at 210 a O6. a 364 (Mots: Gong Factors were token om Si EEE 239 (These jsment alors wc considering 15 Columns Maxi, Table 6 According to the results shown on the tables above, it is clear that low voltage cables Present a maximum deviation, the average DF deviation goes from 0,37 to 0,231 (gotten on Model A: 4 x 12/LV @ Table 2) and a minimum deviation for medium voltage cables (6-10kV) from 0.32 to 0.312 (gotten on Model A: 4.x 12/MV @ Table 3) 4.6 Short Circuit Fault Checking * For low voltage cables, fault duration time was assumed as 1.1 cycles or 0.0183 seconds for feeders with a Model Case Circuit Breaker associated, (for Frame Sizes up to 100A) and 1.5 cycles or 0.025 seconds (for Frame Sizes between 225 up to 1200A) according to Table 41 ‘Estimated Clearing Times of Protective This document is property of TR Group. Reproduction thereo is forbidden. ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #01910 ti CABLE CALCULATIONS Hagens TECHICAS REUNIDAS DOCUMENT s —500-65C-0006 PAGE 23 of 28 Devices" of ANSIIEEE Std 242-1986, Fault location shall be assumed to be at the load end of the cable. + For medium voltage cables, fault duration time was assumed as 1 cycle or 0.0166 seconds for feeders with a Medium Voltage Fuse associated (for power rated motors below 1.865 kW) and 10 cycles or 0.166 seconds for feeders with a Relayed Circuit Breaker associated (for power rated motors above 1.865 kW) according to Table 41 “Estimated Clearing Times of Protective Devices” of ANSIIEEE Std 242-1986. Fault location shall be assumed to be at the load end of the cable. 5, EXAMPLES OF CABLE CALCULATIONS 8.4 Cable Calculation (MV): System Data: Parameters Nominal Voltage 16 kV, 3 Ph, 3W. ‘System Frequency oe 60 Hz Short Circuit (Available) on PM-52223 A/B 9.47 kA (1/2 cycle) Motor Data: “Oxidizer Circulation Pump” PM-52223 AJB. Power 224 kW Full Load Amps ~ 38.63 Amps Efficiency te 0.93 Power Factor a9 i Nominal Voltage 4KV | Circuit Length: 425m * Cable Ampacity Calculations: I pesian= 1.25 x Inom(Motor) <= [Overall De-rating Factor x Cable Base Ampacity] .25 x 38.63 A = 48.26 A Voesien De-rating Factors shall be (See Table 3): | This documents property of TR Group, Reproduction thereois forbidden ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 ti CABLE CALCULATIONS Bagot TECHICAS REUNIDAS DOCUMENTS: 500-85¢-0008 PAGE 24 of 36 Ft = 1 (Adjustment factor to account for the differences in the ambient and conductor temperatures from the base case). Fth = 1 (Adjustment factor to account for the differences in the soil thermal resistivity, at which the base ampacities are specified). Fg = 0.348 (Adjustment factor account for cable grouping of (35mm’, 6/10kV) cable installed in a 4.x 12 duct bank EDB-187 see Table 13-9 of Std IEEE 399-1997and Dwg N° 501-65P-0700). P= Ftx Fthx Fg F=(1)x (1) x (0.348) = 0.348 Therefore the maximum allowable ampacity of'a power cable 1-3C-35mm’, 6/OKV, with an ampacity base of 147 A, specified for Tc = 90°C, Ta = 35°C and RHO = 120°C- mY, shall be: I derated = F x Ibase I derated = (0.348) x (147 A) = 51.15A ‘To meet the requirement indicated above, 3Cx35 mm2, 6/10 kV, XLPE insulated, AWA cable shall be necessary. ‘+ Maximum Voltage Drop Calculation (Steady State): ‘The steady state voltage drop for the cable selected above is: 48.28 x (0.669 0.90 +0.13% 0.435) _ AV = JB x 425 OE OO ET = 0.562% 10x (4160) + Maximum Voltage Drop Calculation (During Motor Starting): 231.78 x (0.669 x 0.45 + 0.13x0.893) AV = 4/3 x425x 10x (4160) =1L.71% Note: Assuming PF=0.45 and Istart =6 x (FLC) This documents property of TR Group. Reprocuction there is forbidden sjq__-SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 | ti CABLE CALCULATIONS Aageatoe | TECNICAS REUNIDAS 3 DOCUMENT#: —500.650-0006 PAGE 25 of 6 Both voltage drops are within the acceptable margins indicated in Section 4. ‘+ Short circuit Consideration: The short-circuit level at PM-52223 AIB is 9.47 kA (1/2 cycle), and considering that the main protection is provided by a MV fuse with a total clearing time of 1 cycle or 0.0166 seconds , then the cable selected shall have a minimum short circuit thermal capability of Px t = (9.47 kA)?x(0.0166secons) = 1.498 kA*xsec . According to the manufacturer data of the power cable, 3Cx35 mm2, 6/10 kV, XLPE insulated, AWA, its short circuit capability is 5 kA during 1 second, or K = Px t = (5 kA)*x(1secons) = 25 kA?xsec Therefore one cable 3Cx35 mm2, 6/10 KV, XLPE insulated, AWA meets all requirements. 5.2 Cable Calculation (LV): System Data: Parameters Nominal Voltage 0.48 kV, 3 Ph, 3W. ‘System Frequency 60 Hz ‘Short Circuit (Available) on PM-52271 A/B 9.47 kA (1/2 cycle) Motor Data: “Secondary Striper Bottoms Pumps” PM-52223 A/B Power 55 kW Full Load Amps 97.25 Amps | Efficiency ost Power Factor 0.78 Nominal Voltage 0.48 kV ircuit Length: 422m ‘This documents propery of TR Group. Reproduction there is forbidden SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 th CABLE CALCULATIONS Sogou TECNICAS REUNIDAS 4 DOCUMENT #: —500-65C-0008 PAGE 26 of 36, * Cable Ampacity Calculations: 1.25 x Inom(Motor) <= [Overall De-rating Factor x Cable Base Ampacity] 25 x 97.25 A= 121.56A De-rating Factors shall be (See Table 2): Ft = 1 (Adjustment factor to account for the differences in the ambient and conductor temperatures from the base case). Fth = 1 (Adjustment factor to account for the differences in the soil thermal resistivity, at | which the base ampacities are specified). | Fg = 0.33 (Adjustment factor account for cable grouping of (185mm*, 0.6-1kV) cable installed in a 4 x 12 duct bank EDB-187 see Table 13-9 of Std IEEE 399-1997and Dwg N° 501-65P-0700). F=Ftx Fthx Fg F= (1)x (1) x (0.33) = 0.33 Therefore the maximum allowable ampacity of a power cable 1-3C-185mm”, 0.6-1kV, with an ampacity base of 387 A, specified for Tc = 90°C, Ta = 35°C and RHO = 120 °C- ‘om, shall be: I derated = F x Ibase I derated = (0.33) x (387 A) =127.7A And according to the new De-rating Factors due to the depth of the Duct Bank EDB-187 (102, 36°=260cm) be (See Table 2): ‘The real Overall De-rating Factor for a power cable 1-3C-120mm?, 0.6-1kV shall be: F=0.22 And taken two cable per phase, the de-rated ampacity would be: I derated = (0.22) x 2x (310 A) = 136.44 ‘This documents property of TR Group. Reproduction thereois forbidden ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 th CABLE CALCULATIONS aoe TECNICAS REUNIDAS DOCUMENT ®: 500-650-0006 PAGE 27 0f 35 To meet the requirement indicated above and considering the deviation on the original DF, 2x(1-3Cx120 mm2)}, 6/10 kV, XLPE insulated, SWA cable shall be necessary. ‘+ Maximum Voltage Drop Calculation (Steady State): ‘The steady state voltage drop for the cable selected above is: 60.78 (0.197 x 0.78 + 0.0904 x 0.625) AV = 4/3 x422x 10% 480 94% * Maximum Voltage Drop Calculation (During Motor Starting): 291.75x (0.197 0.45 +.0.0904 x 0.893) AV = 5/3 x422x 10x (480) = 752% Note: Assuming PF=0.45 and Istart= 6 x (FLC) Both voltage drops are within the acceptable margins indicated in Section 4. © Short circuit Consideration: The short-circuit level at PM-52271 AIB is 6.79 KA (1/2 cycle), and considering that the main protection is provided by a Model Case Circuit Breaker with a total clearing time of 1.1 cycles or 0.0183 seconds, then the cable selected shall have a minimum short circuit thermal capability of P’x t = (6.79 kA/2)°x(0.0183secons) = 0.21 kA’xsec . According to the manufacturer data, one power cable, 3Cx120 mm2, 0.6-1 KV, XLPE insulated, SWA, has a short circuit capability of 17.16 kA during 1 second, or K = Fx t= (17.16 KA)’x(1secons) = 294.5 kA*xsec Therefore two cables 3Cx120 mm2, 0.6-1 kV, XLPE insulated, SWA meets all requirements, ‘This docurnont is property of TR Group. Reproduction thereof is forbidden, SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #01910 os ti CABLE CALCULATIONS Sagal TECNICAS REUNIDAS ° DOCUMENT #: 500-650-0008 PAGE 28 of 35 6. CONCLUSIONS The largest cable SIZE resulting from the calculations described in Section 4, was the selected one for all applications. For critical cases where the depth of the duct bank | exceeds the standard value, a deviation on the De-rating Factors shall be accounted and for rest of the cases, the Manual Method described on the Std IEEE 399 shall I applied. For cable sizes refer to project cable lists: | a).- 601-651-0002 (Substation Cable List) b).-510-65L-0002 (Cumene Unit Cable List). ¢).-520-65L-0002 (Phenol Unit Cable List). d).-560-65-0002 (BPA Unit Cable List), d).-590-65L-0002 (Tankage Unit Cable List). ‘This document is property of TR Group. Reproduction thereof is frbiddon, ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #. 01910 ti CABLE CALCULATIONS Sagan TECNICAS REUNIDAS DOCUMENT 500-850-0006 PAGE 29 0f 95 7. ATTACHMENTS 7.1 Attachment N° 1: Cable Data Base ‘This document is property of TR Group. Reproduction thereof is forbden. eee eee eee sopnpuooginyl 241 3142D ‘OA / WMS / Od /3d1K 9 / (AY-8'0) MoNdDEIq aIGeD 9)q89 [pnes saumaeyNUEY 9142 A7J0 Bed Jeo1UYysa, Swann svoinoa, mm soronpuoonny :9d 21925 ‘Ad WMV / DA / BK NO J (4401/0) UONdLDSaG aqeD ‘91420 iPneg ‘sasM2e]NUEH SeIdBD AI JO BEG TesIUyDa], Sane bcte wag Fpe ager SANymebcr— ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 th CABLE CALCULATIONS Sogou TECHICAS REUNIDAS DOCUMENT # —00-85¢-0008, PAGE 300f36, 7.2 Attachment N° 2: ETAP Report (Ampacity Calculation, Duct Bank 3x5, Depth = 30”) “This documents property of TR Group. Reproduction theroo is forbidden. ETar Prise Kaven Prose ree oesion: Maid pt ao Das 200-2008 conn: 1910 Si TROWCASIY gece Cristen Cube T ees Revise: Die FllnameKAVANP PLUS Sey nie Apa het 2 ‘Underground Cable Raceway Systems Ampacity Optimization Analysis ~ Unifora Asupacity IG Sytem ember of Sait Tye cena < ‘Sinty Dey a0 so Makin Ess 0) Asian ME: Coad Indvil Grmeh Facer, Not Conia aa Gon Facto 10% Method: Nebor Meith Fak Hae Sooees ‘Temmperntre Lis ‘Aone Waring c %e oo mao ut Fie piecing nd Management ac aucdETAP FILES We Cable Cleaiond TAP FILES 02 Balance A BEampeol.co1 evar ois Kaan Pros rae? ostbon: — Madad pai ie ax 2003-2008 const 01910 8 TECMCASMN eyieer Crs Galo aaa Reviion: Bam Flnae KAVANPPLUS Sty: Unit Anpacty indergronnd Cale Racenay Systems (RW2 act Bask Raceway Datar eferenseDitnce ___ Dimension ra att amber Number Average Distance Viorica) Vericad gt Wilh cr oe Com Cener b> = mar am Type___eetin Conder Caer o ne Tee te we Teams = Ps veo Referene Diane ircntal Verde Sue Thekaes OD RHO Thermal ut im = 2 yee ee ee ceeatiin "Ome tas sss nas oe Bam mon ome cots sm 9% oe naw ames + Waring ndsy reeves recommen swing irae 0281032. Ala Caja may aca tara ewecn 278 a2 Cable Data: on Contvewe ena Ratt Curest Fiewr Face rer ‘Tickoos Thermal p sig_WV tm te Na Type Phase _ Cominco aye cone evar. Propet Kayan ret Pgs 3S Lectin Maid Epa sss Das: 20082008 Conse: 1010 sm TRENICASIN Engineer CrinianJCunloT eat tae Fisme: KAVANPRLUS Sty: Unies Ags / Cable Data: Ratet Current “Plcr Face Per ‘Tics Thermal » We her ot Ne Type Phase _ Contraction Te tee esis a ee yore 3s ue Sistine het ele Oude at Tikeknes Shear “Tames @2C— Uaewter ty Sue type commen en “Te ye sits Sie oro Ome tr Rameanagaw We ve cotean oe Ope Or eamannagisw NE 0 mas eteas ve tape ne 21 eAmoanagise we er) cateot ve Coe One O1 stamanoansw We 30 moss cots ve eo om 81 Seamanoais# NC 0 mea stn ves Cope ma a1 ScAmoavaans# WE 0 eas cover ve tne one o) Skamenoansw We so mms eater ye Coe Ona o) samanoayiee ne. Mo es cater ve Coe nm or seamaavaysw Ne 0 mash tee cae On 01 SeAmanbayisw me ae mas eats ve cae pn 61 seamenbaynsw We a caters Ya Cove One 01 Sehmaaoagisw We ee) comets ve Coe pm 01 sehmonnaynse Ne 30 nas comets YC ne o1 Seamanvasw we 0 mas cates Ye Cone one 0) SeAmanoaensw WE a0 as TAP Project Kaye Prec Peet Lacon Madd ta saa Pee 2008 coneet: 01910 STEGUCASH egscer Costa Jano pcan Revons Bue leone: KAYANP PLUS Say: Unie Apasiy Anas Rests @BW2) Conductor Enerind Re @Disectrie Contactor No cote Conduittecason™ Cable _perCabin_ phan” Wile Ye Vy Matin ape tmete ADC rte oe ne anole ot Neha mae TAP Prost Key Paeet nie Pec 5 Lecain — Madid pada Dee mame sgocer Crit Calo ae Reve Base Picuume: KAYANPFLUS Smt: Uae Ampacty soma ice a Seated | | ve care mt sm mite | va eis cmt me wee ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 =a th CABLE CALCULATIONS Sageulie TECNICAS REUNIDAS DOCUMENT: —500-65C-0008 PAGE 31 of 35 7.3 Attachment N° 3: ETAP Report (Ampacity Calculation, Duct Bank 3x5, Depth = 102”) “This document i property of TR Group. Reproduction thereof is forodden evar. Projets Kayan Peja Poet ocnion: Mid Ep area Deon 208 peer Crisan Cato T ninpaeert Rover Bae Filuase KAYAXPFLUS Seay: Usiem Ampacty letra! Transient Anshzee Program Underground Cable Raceway Spuems Ampacity Optimization Analysis - Uniform Ampacty Mes: Neer MeGrah he Sytem Member of amber of » ‘Cab Racorays Ext Heat Sourees seit “Temperature Limits RHO AnbieTemperainre ‘erm Waring re cna c “ “ ‘Seay Dw 0 so ou = Mains sts SD Intvidn Geom Fao Net Conia leat Gow Pac wo vp Fle, C\Deamt Setingone OOacsino\ETAP Fae deETAP PILES CADLE BASTESxple-01CD1 evar, Prsect Kagan Pret Page 2 Z ssse oealon Mi Epa De: ast 2008 comme 0810 Se TeENIEASTE se Cran Caio Reve Bae Fag ‘su Cate Femme KAYANP PLUS. Sip: Use Amps _Uadespround Cabs Raceway Swstms (RW2), ‘uct Bank Raceway Ds ree eee sd ember -Nomber Average ise THorionel Vere!” Wait Wide wo at wi ConerteCemtr » = type anor Conate Cal es awe awe aw SSD Una i 1% ae Conduit Data: Reference Bite orem Vert See Thickness OD RHO Therma at » = = Tye ere came cary es Oke tame Talo eooe ayn conan sos oe ome Mim gee + Waning Io reese command ning ti of 281932 4 Alums Cals jnning may ear hon amram ween 272 CableData, Iida eo Gronth Lond Cooder Rated Corrent “Factor Face Per “Wicknew Thorwal » se tap ete Ne Tye Phase Comtrcton pe moon Gear ‘Some wee a ker ze rr? ETAP Poet Kayan Pjet Pee 3 Teen: Mab ps bial ‘ae 9.42808 Contact m910 Ss THCMICASIN ner Cris Calo aes Rendon aue Flenne: KAYANPPLS Say; Union Apc Cable Pata, aed Cunt ‘Pee Pace Per “Thicws Toma > sine "WW Shoe oth No. Type Pome _Comtmason Type Oe sens Jae Ric Obie Tad Thltnes | SheutArmor Tice @2C Diawter » state Comecion ne "tye yen soln se cy ‘ om ot amano wiw eve aa oa a ean ve om 01 Stkmanowiw Ave ve mma eas ve o 01 sixmaneieisw Fv as catoas ve om 01 samamowinn wv seas coeas ve om aL seameupagrw rv se mn as cateos x“ om a Sexmapeietsw ve sma catear ve om 01 sexmeneapisw ve ae mas caooe ve oe on suamunodpisw ve remo a cates “ om 0 Sezmmnodetse ve ee taro ve Oo 01 Sexmanvastow ve re mea ean ve Ome 0 suamaneasisw Fv ye mwa catet2 ve om en 0 oma caters ™ om on seamunnagiow eve emma cate ve ome Ou Sermuneaeisw VE emma caters ve oo 08 sammnnannsw YE vo mmo YAP, Peet Raven ree Location: Madd Pram ae ate: a804-2006 joer: Cine CaioT Revisor: Bae ae sus cute iene: KAVANP PLUS Stuy: Unie Ami ‘Amalysis Resi RW2, Conductor Tnergned Ride @_Diketre Condi No comet Cvadnacation D___Cale _perCabie_ gOmim” Wom Ye Ys ate ame 5 catows condos 3 , vas ote ecw 6am seo sas “Yo= meet sf ACIDE rene i Acs ca iy ‘Noun s(ASHC eur rte reac a wrap Pret Kayan Proget Pes oewion: Mati Eta a Das 02008 Coane 1910 sx TECNICASMY ogoece — CraianJCunttoT Beaute Revel Bae FlenmneKAYANPPLUS Sys Unit Ampaiy | ‘Smaars W2, Pn ne lees aso eee lems enemas ceaon | Sus ceumpeaure sda | 2 US Stones melt ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 ty CABLE CALCULATIONS Saget TECNICAS REUNIDAS DOCUMENT # 500-650-0006 PAGE 82.036 7.4 Attachment N° 4: SS 50, Cable Trench Layout (N° 501-65P-0700) This documents property of TR Group, Reproduction thereo is forbidden. SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT #: 01910 | ti CABLE CALCULATIONS Segal TECNICAS REUNIDAS DOCUMENT #: 500-650-0006 PAGE 33 of 38, 7.8 Attachment N° : ETAP Report (Temperature Calculation, Duct Bank; EDB-132, Depth = 30”) ‘This document is property of TR Group. Reproduction thereof is forbidden Kapa Pj Na pase rim J Curl evar sss sty Cue: cD sx Sot (Bhesticl Transient Analyzer Program Underground Cable Raceway Sytems Cable Temperature Analysis Method Neher MeCath wi sytem Name of » Cable Racoraye eoe.is2 T Soil RHO Anbie Tampeatire Tye SCenvan “ ‘Swab i200 so Making crs) Arplitice ME: Conied udvdal awth Facer Not Conder a Grom ace 100% ‘erm Waraing a “c ono 78 cota Sty Ste Tapers ‘rtp FileC\Danet ai Seine OT ExsirTAP ie Capia de ETAP FILES CABLE BASEIEDE-167.CD4 evar Prec Kagan er 2 Loewen: Maid Ep oe Dae tpot2008 comer 110 sw TECNICASEN Engineer Cetin Carlo Revlon; ae | Smty Coe CD Flame KAYANPRLUS. Saye Stedy tte Tepe Indergrownd Cable Raceway Sretems (RWS | Reference Ditanes __ Dimension pat eter Worsonal Verda Height With WHO at Totter o = eet Type Coan Candas Cable om ws ja Ie wea o or oe ‘Conduit Data: Reference tame Twieaal Verdet See Teles OD RO Thermal w es = yee a ee ee ean ae Ho ‘oe eae leew HO cmt enw oe eae tom a0 i TAP Proiet Kaya Pet Pee 8 ssse scion: Madd Epo Dae ano.2008 Cmtmct 1910 SX TeeNICaSI fngneer Chis 3 Caro T ates ion: Be Plemame: KAYANPLUS Stay: Stn Site Teapete Conduit ata: Referer Dance Weraontl Vert Seo Thidkoms OD RHO Pema rab w = = ae Sm ee oni Ore “= Waris recess esarmend avg jamin 281052 1 Aloo: Calming oy ocr hn eas in baenn? Hand 8 Cable Dats eet eel Conte lesan Rated Curent Facbr Fact Pe ‘ices Thera w see te ae no type thee Contraction Ie chm meses ako ramet at sue 7 om | | wrap Prose Kagan Poss ; Poet osnion: Maid pt ead Dee 9.02008 conanct 1910, SX TRONICASIN x Céinin Cito Revkion Bae Bagneer —Criin ee Flemane AVANP PLUS Sys Sten Sate Tempo Cable Data, w suet Snape oe Na Type Fete _Comsrostion aye evar, Pract Kaa Post mee ecw Maid pat aad Poe op-oz costact 110 sx TRENICASTS Engine: Cita J Caro fee Reviion Que Flame: KAVANP PLUS Seah Steady Ste epee | cates, | aie Eee oe ant caret Wager Ba me Tuoos Tage » ati ert eoteteear er cesses eeseesae ee gee eects Sting Jute ee aaae | tanto Aree Tues gic Dane | eee camara nee omen mane SR eseeee ee aac reece roe a | pest erased sev Tug cena eFunds 11 | ae RCP ees eee faa 11 re CH ome ES : mss = oom ae akmemaey emma Lest Yes coepes Oven OF Stamm dg/5W ve 20 100, ot | resaian ve Cope onm OL Siamenowiw eve pe qeieet paaee Py | psn =o ammewey oemtinea | ress ve om om at Bkmamatty eae | mes RU PPS Pe oo eat facantsaee | Pe ont tenet a | pes east eevee cee Uae tae 1a | mami Rr Eee at tuft eine 0 | sive wo ae met ee mea | PMSETIB EL Ye. ‘Copecs Open 01 StAmmen i dg/5W ve, ae 800 an I MSTA Yer cusp Open 1 StAmmenrt6dassW re ie ss060 au | smn oe waa meso foe om kmaomasiy emma | sabe come oe mena ea resin eet eee 0 aa amma et ae EE | msn Presa setae? usc el UE an laa mesma Racers fet set ET umonasne et UE ast 1 mesin0 a re | resem eee Parte ag amioemsm eee acim Eee | meson Recetas tee tees gumignneteereCttisttt2eee resunn ye owe am keane reat reset Yo Core Oe 04 StArmov¥6 a5 ve ise nao au | eso ecg Fedde TUTE Paaeeboas ae ce UE an fea | pes Ra rea fet er UU naPpmogeel A000 | psi Rare fet set 0 ua aumoatet Ut af | peso a eeeeeae desc dHtEEH catia eee Pet aes tt et | resin oom mat PMSESHIASPL ves cones ‘onn OF StAmonedeI SW eve 20 sao o20 | reseon Preece tee tee fap amino teem isto 2th esDesBeT Yes Corse Ope 1 Samu dg) SW we 0 waco a ] Proj Kayan rj prar Poe Locator: Maid pin sae Dees onoe208 const 1910 sw TeeMICASIN Bryieor Crisin Caio T sme Cue CD Revit Bae Fename KAYANPPLUS Sty Stn Sie epee Sodding seeket te Ouite | Eel Thcines | SheatiArmor Thickness @2°C Diameter | D> Somme Type Commecion ‘Dee eee Besaar Yo Core om 0) Shomtodgnsy me rr eT) suse Ya cop om a1 Seamanodensy We tm aw con ve Coe om 8 Seamemadsisy 1 yma | vsonins) ve Come om 1 SiAmeapodens We te tep@ a meno on ome a) seamasougnse ave 1 ema eso Yo care orm a1 sAmanoughsw We He nema rs) vs cane one 1 Samenodgnsw we ae mao ese Yo crv One a1 Seteeodgtsw we rome a exes: Ve Come Ome ar Samenowen We te asia ase va cer mm Or Sekmeoasw NC tw soma meson ve Cone on 01 Samesodensy We te moma pasate Ye Com Ore at samnowe ne town an mesmaet Yo Cone om or stmaown Ne to tem att sone vs coe ome Ot Samenowin We Me ewe an meseneny vaca On 8 seamennodgnsy we ae ae meson: Yo Come One er Seecougsw ne vo wnat ncsmca ve Coe om Or Stmenowe We a0 sam messaaasi va cape ome Or Samenoasw we towne meses ve Cone om 4) SAmmaoaensw we 10 ama meson ve Coe ome 4) Samonoqsw we mm am pesos Ye Cone orm or samuaoansw We no tons esemat ys Conte on a) Skmasoayis# We wo nae ne ve came om ar Samenoaynsw we we nee ae on Ore 4) mimeo we 20 amas ve Coe om er sAmanoanse We 1 mw am ve ee om er Samanoaunsw We wo mm aw ve Cone Ome 4) Sameaoasiw We wo ome ve Cone om er samenoanse We tome a meson Ye Coe om er samaognse ne io nme a rises ye Co om at sameaeanse ve te wom ae pesana ve coe ore er Shmanbaynsw we 0 moat i TAP Poet Kan Prost Pee 7 ‘oetion: Maddy aad ne 0.04208 i coxmact 010 Se TRCMICASHY agecer CrstenJCuniteT Heeeaniees Revisor: Bae PlemeKAYANPRLDS Stay Stuy Sate Tampon | Aas 9 Celnior toed te Diet ace | mw ncaa Had reason eared fee ee 9 mse cont 29 3 o an cv onto oem om T5 40, t ve nesaoant cto : 3 aims eso came ome ao a2 | 1s nascar nt > 3 it 000) 008 amo 28 eh | te MSIL ood . 4 a a ee | ; caseemee ae Reeeeeeee geese fat aerated | ister a COSCON tase ge aa das | 2 REsETMARLA ceed 27 a ms a0 = oom = a000 kom ass TH | 2 est aa Ieeeeee sees oat peat cite ceeee ett i | ETAP, telat Rare bet Location: Maki pain pee Date 0042008 ome won se owen eco Cte Cnet iuinagu tow fe teecar Seat Tp Annie Cater Sonate @ hee Conte | xa cate, ConduiotoesiontD Cae _percae_ "whan Woe Ye Ye Wry ke | neon om SPREE HEE cero gat ge oan aa cc St psi cons 214 3 : 6 opm ono T3 | 0 PMSA conde + 1 em pao omen keane I ae a He tee ae een ee eae decade | Beaeeeee: con eereeeierenieer eur = pasraeer ener P REED | oeaeae ae sega Hae eae eee aos ft aac | peers con pseeeeeapeenieesr? out outsrt™ pest =yeter=opneiPPanTEES) Hassieinns a ee aa | saree et one Kegs Pijest Mali ae comer prar suay Coe oma o> Page: Revi: sty Bue Stel Ste Teoperata rar ns yas rie Poe Maki pt 5580 Dae aBe42008 Revise ate Sealy Coe cD KAvAND ms Soy Seine Temperate se cave, Goednittecntonty meeps Fla esta leo eine lange nr nec aeion tetas aeenpeaiesesny t hea ae pare ceg ei t ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 th CABLE CALCULATIONS ayagaulihS ‘TECHICAS REUNIDAS DOCUMENT # — 500-65¢-0006 PAGE 34 of 36 7.6 Attachment N° 6: ETAP Report (Temperature Calculation, Duct Bank; EDB-132, Depth = 75" “This document is property of TR Group. Reproduction thereot is forben evar, Pract Kayan rot i ovale: Ma Ep : opocame Conti 91910 % TEENteASEN Spicer Cutan Carlo oe evion: Bare Fmans:KAYANPFLUS Simp Seay Se open ‘Seca Transient Amalver Program, ‘Underground Cable Raceway Systems CCable Temperature Analysis Mati: Neber McGrath We Sytem, ember sf Nomberof Coke Raconays at Heat Suaret oa 7 ° soit “Temperatare Limits RHO Aries Temperatre ‘sere Wenig yee cana “e “ “ Sey to 30 ey 750 Malibing Fast Aroliaion ME Conte Invite Gm Faeon———Net Coder (lta Cron te too Cute: Caos Seige ened AP File Cpia de EAP FILES CABLE BASBIEDE-IB.CDL rap Port Kayan Pots Pec 2 | Loci: Moda cid Dac op0-2008 combat 8 St _TRENICASIN egos: Cian J CataT eee Revs: ine Fenane — KAYANP PLAS Sate Stendy State Temper ade sw | eeeiact__Dinenin Nomter Ney Avge Dee Tena! Veal Hig Wa mo GO Satie » er tree ere arid ne cate Se = aaa aN am Teikwe Oe oo Conduit Data: | Tim Veal Sie ‘Tikdows 0D RHO Tham > reer aeest efter tetra fom cnt aE added oa EEE Haas Pa eens ae cnt2 aso 6590 eae: 1s nme tom coe twee | cntoo ae aed eee eae aaa cee cao that | TAP Keyes Pie Peed Mati paa aad De o.0t 2005 i910 se TRowcASNY iin Colo eae won KAYANPOLUS Stay: Stay Ste Peper Sareannaaat | Relerene ince vinta Veréeat Sie Thickness 0D RHO w = = ae neem Cowie * Ween nity seperti examen wong je at of 2810 2 1 Aluon= Cableuming ny ocr when jm a in erween 27d 28 Cable Dat: roar ewan ‘Gromth Cond Cendocte Rated Comment Factor Factor Per “Thctnes Teermal », sie MW nme NN type Phase Consretion ye ome pasar ee mre or om | ETAP Prot Peet toca: cid Dae LIE cont se TECMICASIN rgcor Cian Cato T ie Revison: Sue lenane: KAYANP PLUS Sua: Sten State epee | Cable Dat, | Coadactoe roan » — Na Tyne Phase _Conatrvein Ime = thon eran te imme ase Ut vue oom i axes et ee ee ee sre or 08s ware atm mesos 10 tmp aa tae Laat | ese fo two amp ame et aN va oom | eset 1 tm gore eet sare ows asm two 67m tT sare or cum mesures ee nore 7 ow» | rusts See eee 7 eee | rusooe ttm awe weet NT mn oar TAP Print Rap net Location: — Madrid Epa asia Date: os-04-2008 cme wt se Teams tect Cin Cano? mt Cue evi: ae Pinme eAYANO RS SSeS Tn | cates: | sited Conte an / ft Coretta be Taco Tak | » ic Peel rattle fate eee gE teeter stan, eat eat tat Tika ihrer Ties ate Meme » fare tne contin MT eee See Sonor ir eT mesoran cme eh mhmamain Ummm esate ye om mt imamate tata ner vom me hmong me tte tan mem naman eat menue cee mama eam esas a a vce Om Rhee oe om prin er oe msm ena illasstiss-Sheeetteer gap OO?" Per ge essere eet SESE esa yo cme ma Shaina RC at esse pe em em Rennteam res pat treeee Cet peat -H apace reece mac esa yo cme hmamagtty eth tama ‘soe we cee mane ein enn Sseeetep ieee ceeaee emeeeeee eer =monPO steerer este peeeer penal te ome heme Etat moon Yo ce OH Ramana ew OH none ve cer mt mametngmy tao pasonant emt om Smet ema neon pa Pheeee Cees tetas psn oom mamma etna ws ve owe hmmm eam a eons woot om hme eum a sa we ome mH Shumate tow pial vo ome Om hmm eto moon ve oem ame ee aa nena ve ome oma nama etm meme om ma Rammmatey ma ene tom Rhone mee a esa RUPP eo aa fanuamae 1 re eae rseenn yom tamumane ama ane woe mama ama Preet Kayan rj Lecaien Madd Epa Conimct 010 egecor—Chiston Calo T Flenne! KAVANPPLUS Era. ssse Sindy Cae: cD Pee 6 Dae mot 2008 SN TeawIcasme Stal: Sindy Sate Tempe Shang shetet a Ted Thon ShexhiArmor Ties @ISC w Stas Type___Connecion ‘Tyre ye enn ear Ye Cope nm oh WAmesouiow eve te ise) scious Ye Ge oe a1 stamennodsisy VC tee neseinr ye Gas open 0 StammeDodgisw FE rem a mesarpel ve cae ome o) seamasougisw ve tm nem ah mnnnet ve Cree Oe 5 stamamoignsy Ve te eee meomn Yo Oe oe 0 Seamentodgisw ve tinea noma ce ove D1 Selemanigsw IE 2 amas meses od ome 0 Sehmesndgtsy IE am mma wows Ye Ome oe 0 Sthmeesveatsw IE vm asm asxon Yo Coe we DL StAmesbéesw AE tema mesic ye Come opm Ok seamanoegtsw we tw wee a reson ye me om ek samaandgnsw ve tem ah mesma ve Game om 0 sehomanlatsy WE tna osm yo me Oe 01 Sedona dansw PIE teen a meson ve coe om 0) Selrmnanigsw we er) reneian ve Conor om 01 selmaanegtsw IE i mem a sarah Ye oe or StAmanesisw We momma asses Ye Gone om 2) scAmmabeeisw Pe 1 me Pass Ye cas oe 21 Stamonbayisw we teen mason ye Gage oom 01 seamuaeepisw We tem musmaar ye Gave om 01 sAmaabasisw WC 20 eas sama to Gane ope Ot Sumenbistsy NE tm item ae Paso ve cone om 01 SAmmtbagtsw Ie tm nem te esamas es ve Come om o1 samemoagtsw WC a0 eas asin! ve Gone om 01 Samaabavisw We 1 mm am cso. Ye Gone om OL Samanbesisw mC 0 mam an acsmner ye cone coe ot Samanbéetsw We tte ae renee ve Coe oom eo) samanoggisw ne te ema reesemints ye Come om o1 seamacnagsw WE tana remnen Yo Coe om a} Samenbaetsw WE ter arma acs ve coe oom OL Smeabigisw we mmm ah | ETAP: oiee Kani Pet Pe 7 oct: Madrid pata ssse Due ¢B02008 come 01810 st: TEENICASIN Enger ChisanJ Cardio T tobe ep Revisions Base Fiknime KAVANP PLUS Stay: Stn Se epee Anatuts Revots RWS) Conduct Encpeed Ree @ _Didestre Condector or Candice FinalFemp. Canes Tastee Current Temp. Na cable ContatLaionD Cable porate -vonnin” Wats Ye Ye Wate mp so mesma et conta? : > zoe ecm a008 0mm LI) ans mw I a memman 3 3 atom ome tem sas i 22 mesma cont : ee ee ee ee Ce | 3 mason cend23 . ° a ee ee | . . ee | TAP Projet Kam Past Pee 8 ssse Loetion: — Madipei Pee: op. ne2008 | ote 01910 se THOMTCASIY gieer—Crtien Cato T iat Revlon: Bae Fagnane: —KAYANPRLUS Siwy; Sted Ste Tempe Anas Resals (RWS, | Conducar Peers Re @)_Diterie xe Cohen Conduitecatonty Cate erable ""nohmm” Wonks Ye Ye tamim Ame | mesa cmini6 3 3 ee ee ee ee ee) | a maaan clzi6 2 ° oe | & nesaier cite 3 re ec) | | 2 mesmin cont 210 3 3 we 4000 cmos ae | ‘E" Mam s ACD ese rf cy elk si ha nd amor | rap Price Keyan Pot Page Lest Madi pan sae Pe Cone: sx Feiner Chis Carlo? Beg evo: Fignime: KAYANPPLUS say ‘sam See Curent Temp, Ne Contain ee ee i resma cots ® sat Base Sty Site Temperate Sao Keyan Pest Made pats cine ie J Cio KAYANPPUS cone erAP sey Cues cD Poe sx Indesign fa termes no ensign Sse i bates tmp oon tr aga Sed Sate Tempers ‘SAUDI KAYAN PETROCHEMICAL COMPLEX - PHENOLICS FACILITIES PROJECT # 01910 ti CABLE CALCULATIONS Sagan TECNICAS REUNIDAS DOCUMENT #: —500.85¢-0006 PACE 36 of 36, 7.7 Attachment N° 7: ETAP Report (Temperature Calculation, Duct Bank; EDB-132, Depth = 75” and DF = 0.22) This document is property of TR Group. Reproduction thereotisforoicden. rar Projet aon sssc Enger Crs Carle T tue Ee Pest SK TRENICASIN Revi Base Sis: Steady Sate Temper lesrial Tramsent Aualzor Presram “Underground Cable Raceway Syren Cable Temperature Analysis Method: Neher MaCrath UC Sytem, » Cable Racenays soit RHO Ambien Temperature tyme Scania < ‘Siety Dey a0 wo Mating Faces openion contend Inde Goweh Fase Not Cone ote Grom Fae 100% Nemberat Yat Heat Sores “Tempernture Lins, ‘te Waray ‘uit ik: Dace Seng ems Eat SETAP FitiC op de EAP FILES CABLE BASBIEDE-187. CDI ETAP Project Kayan Project meal Poe 2 ovale: Maid pt De one. Connce 1910 SX Tews Enpseer — Ceten JCal T ee Revion: Bee Fiemme KAYANPPLIS Sule Steady Ste Tempers ‘Underground Cable Racca Seems 205) ‘Dust Bank Raceway Data eee ane eneeee a Nomber Number Average Distance erent Verteal Heit Wie RHO at oe Contetn eter w = eae em Type “conn Condite Cables = ws mw sam a aoe SO 7 # ars CondiData: Relereee Diane Herma Vertet See Thickens OD RHO Thermal ms oo ome 1 emote ent cont mo aot Oe a contns som a3 oe 1s emma ats | TAP Pinot Ker Pet Pee 8 ‘con: Mai Epa ses Dee apo-2008 nace Crit 5 Caro ates Revoon: Bae ‘kus KAYANP PLUS Siwy: Sted St Temper Conducta: Worn) Verkcal Sce Thidnesy 0D RHO Thermal Fl + Waning Int egrets reommend sing. tio of 81032, 1 atsm= Cab ming my acar when jm a in teen 27d 28 Cable Data: pau Condor a ated Coreent Factor Face Per ‘Thickness Thermal w Se ON Am te Na Type Plate Comiracon ye cm rap ‘ ist de ae toon Man oe euit amt O10 se Teowensr ter tnt sncue em vm Oat rome eArANP Sy Seer comeane at Come ‘at ae m ace Tage » eT SST Te le comemtn tear” "a — pre neater core Ee pene sow oe a com oo ne een tee ear Gaara | eau Geiser ta amram stam atts cacao | messiAr a a Cont xu a cause | maw, ie thet amt toad aft cocoa tte Te | we 1 caumed NT aoe ar aus | resem tom oem me at cata mma | amen faifconel alld ef ctee Ae tt tomar tam Saft feat elas eta ema Ct m1 a ce | moma a erAP Pre Kayan rot Pee 8 osnion: Mae Epa bell Dae 9.042008 Cont 010 Se TacMCASDY apecer Chat J Caro ata Revi: Bae Faename KAYANP PLUS Stay Sted State Tempera Cae Dat Tait Cendactor ns asd Cort Pear Peer er Taktncr Towmale w sue SENT Ne Taye Phe Comorcton Tee stk ‘Scag sche eee Tad Tiida | ShebvArmer Tiiees @2FC Diameter » Sint __Type___Conmenan "Tee type ohne neem ve Cee oe OY Samesndgisw ve ee ae resonant Ye Oe oom D1 SeAmeansgisw FE re reson Ya Oe om b) scamcsodptsw WE re ee resus Yo Coe oe 01 dmanedetsw PvE usa pesos ve Gap Om 01 Stdmeondensw ve tm tne reser ve Ge oe 1 seamaodensw WE verso as resco Ye Ore oe 01 Sthmasodgisw WE rao ns museaie ve Cae om OL Sedma gts eve uo ses resmme ye Cape oom 01 Sebmnandensw VE 19 sme esr Ye Coe Om 01 sthmacndgtsw VE 1 wma russe Yo Ome ome a) stamucaneytaw ve 1» mm ae usm Ye coe om 01 sthmennagtsw wv a ome ae nese ve coe on 1 Amaabagnsw Wve mma rename ve Coe Ome 0) Stleman aes AVE a essa Ye Gore om en seamacnagtse PVC sms essoma va Come om 01 SAmasnagisw Pv te mae resume ye Cape Com 01 Sthmabeetsw VE vse a sume Ya Coe oe 01 stammmabsetsw PVC le soa sour ye Gee om 01 samavegtsw rv imu 28 essen Ye Ge oe a1 seaemesnestsw Pv as ems resus ve ee on 0) Seamenbagtsw Ave rue S08 pesomer ve Ge om 01 tdrmmansgtst ve was reson Ye Ce ome ol summapagisw ve ose resoanat Ye Go om 01 samavagtsw WC toe asoainos oe om ot Smembaeisw rv 1am ae muscu ve Cape oom 4) Smonbaense PvE msm ase reser Ye Come oo OL Stameravegiow rv anisms essen xe Ge om OL Samomvegiw Ave ttm an rasieiar Ye me oe ol samaapaiw ve te tg an esos Yo me om OL samabaw Rv am se aw rsasian oe jee OL Stamombagow Pv a0 oo massa va Go om 01 smmabagnsw AVE a 20 rusia Ye Gore om OL samartagw PvE 19 20. era. Prost Kaan rot ree Lectin: Mei aa ay Ds «04 2008 cone: 01910 SM: TeeNIcasne Bryiese — Crsin Geno sy Ce: CD Revere Base icsame: KAYANP PLUS Sto: Sted Sut Teerne sai Jace SerasetSaevt Tad Thicknas | ShenttArmor Thideos @ISCDimeter D Same tyre Cammneon ‘tyre aye ae) mene Ye ene ope Gr Bamenvaaw NE Te howe nesecor Ye Cone One O1 kamonoasw We ne nme mesonanrt ve cane a Or stAmanoagiw We no 20m as Ye Cae Ona or Amanoayise We ni amas ve Cae oom 01 ScAmonoansw we ve 7m ae ve Cone One 01 Sthmemoaytse NE som ae Yo Coe na 21 stamonnayisw we a0 ta ast Ye Cone One or stamannansw 2st 808 ve Coe ne o) StAmenoagisw NE ee Yo Coe One 2) samanoayte ee es vo come Op 21 Amenoayisw Wwe wo mea mason ve cae nn 01 Amonoagisy we to mmm ae mes Ye Cone On 01 Sthmmonoagisy we tm a mesmans ve Con opm 01 StAmaodgisy me ty sen a esis Ye Cone Op 01 Shmenoansy NE asm ae messin ve Cone On 01 stamaogyisw RE v9 im an esionns we Game one 01 Stammnoayisw We. ttn aa mesos Ye core one 2) stamanognay ne Ho tem oe rmasenaen Yo Cone opm 01 stacmaioupisw We ae ime ast mesma. ve cnn one 0 Stsmmaaghsy We ese ae mesa Ye coe One 1 StAmansnggnsy me a suse Ye carve one 0 stameoghsy we ain nam as russ.) Ye core onm 0 Sawenadensy WE 2 im 5 must Yo cine om 0 Seamecnoansy KE ne muse ve cope or 1 Sthmonodensw We ne tans sesmnaet ve oe om 1 Stammnodensw we no imme meson Ye Coe om 1 Sehmanodgnsy ve pe sms susanaer vom Ome 1 scAmonaugrsw We 0 toss rusanast ve coe om ni SeAmenodgnsy we 20 mss muse ve Ce One A Seawmnadgnsr We tam at reenact Ye come Om 81 seawmnodensw We = ma

You might also like