Dear Chandresh,
 
As discussed, please collect the required data as per procedure and share the same with us:­
 
1.     FIM­4 Embedded logs.
2.     Alarm and Event summery.
3.     DCT from Primary Experion Server.
 

         HOW TO COLLECT C300, FIM4/8 OR PGM EMBEDDED LOG FILES.
 
‐          On the primary Experion PKS server, open CTools.
o   For Experion PKS releases R400 and newer, navigate to “C:\Program Files
(x86)\Honeywell\Experion PKS\Engineering Tools\system\Firmware\CTools”.
o   For Experion PKS releases prior to R400, navigate to “C:\Program
Files\Honeywell\Experion PKS\Engineering Tools\system\Firmware\CTools”.
‐          Double click on the CTools.exe file.
‐          Select the checkbox next to the module that you need the embedded logs from.
‐          Select the Diagnostic button.
o   Select Upload and then Save Data in the Diagnostic Capture window.
o   Once CTools has captured the logs, a dialog box to save the CAP file will appear.
o   In the Save As dialog window, navigate to the desired file storage location and
type the desired name in the File name field and select Save.
o   Repeat this procedure for the redundant controller if redundant configuration.
 
‐                   

http://mail.gnfc.in/webmail/ 1/5
07/07/2015 Inbox [1/1108] ­ GNFC Webmail Client ­ P N VADALIA <pnvadalia@gnfc.in>

         CONFIGURE AN ALARM AND EVENT REPORT
‐          On the primary Experion PKS server, open Station and select Configure / Reports /
Reports.
o   Select Server wide report configuration.
o   Set all Field Width values to Max setting
  Time: 30
  Source: 40
  Description: 132
  Value:  24
  Operator: 50
  Condition: 30

o   Select Configure reports.
  On the Reports page, select a blank Report line.
  Select a Report type of Alarm and Event.
  Enter a Name for the report and press Enter key.

http://mail.gnfc.in/webmail/ 2/5
07/07/2015 Inbox [1/1108] ­ GNFC Webmail Client ­ P N VADALIA <pnvadalia@gnfc.in>

  Check the box for Enable reporting on request.
  Leave the Destination as Station Default Printer.

 
o   Select the Content tab.
  Select the Occurring as Between.
  If you did not received specific instructions for start and end times, please
use the following as a default.
         Start time should be at least one hour before the incident.
         End time should be at least one hour after the incident.
  Click on Request.

o   The output file is of text format and have a RPT### type filename format.
  For Experion PKS releases R400 and newer, the report will be located in
“C:\ProgramData\Honeywell\Experion PKS\Server\Data\Report”.
 

         EXPERION PKS DCT PROCEDURE

http://mail.gnfc.in/webmail/ 3/5
07/07/2015 Inbox [1/1108] ­ GNFC Webmail Client ­ P N VADALIA <pnvadalia@gnfc.in>

‐          Select Start  All Programs  Honeywell Experion PKS  Server  Diagnostic Tools
 Diagnostic Capture Tool.
‐          Select Yes to allow changes window.
‐          When DCT opens, select the ‘Save Diagnostic Package’ button and click YES to
proceed.
‐          Select the location to save the DCT and use the default filename which contains the
Server name and the date/time the DCT was generated. Select SAVE.
‐          DCT will take several minutes to gather information from the.
‐          Click OK When done.

 