SIL CERTIFIED

ADDRESSABLE
FIRE AND GAS
DETECTION
HS-81
The Safety Bus system allows the fire detection and the firefighting control through dedicated
SIL Certified bus assuring a high safety level of communication. The system is composed by
one or two control cards, that are integrated in the panel HS-81, and up to 64 addressable
remote modules installed in the field. The communication between the control cards and the
addressable modules is based on CAN protocol (Controller Area Network) with ring architecture
to guarantee the best functionality in fault condition and high communication speed.

V24 Power Supply


Safety Bus on Copper Wire
Safety Bus on Optic Fiber

SIL2/SIL3 S81-HS
Fire and Gas
Control Panel

Max 250m
Copper
Up to 4 km
Fiber Optic

2
SAFETY BUS VALUE

• Addressable system with remote I/O – saves installation costs in cables and conduits.
Isolated I/ Os, power supply and communication bus allow for installation of local independent
power supplies without the need to home run power cables.

• Safety Integrity Level – designed to meet the most imperative industrial safety standards,
certified up-to SIL3 level ensures the highest reliability in execution of critical Fire & Gas detection
and Extinguishing functions.

• Safety Functions – Fire and Gas detection, automatic fire extinguishing/release, actuation of
Notification Appliances, integration with other safety systems (such as ESD, DCCS,
emergency EVAC) and HVAC systems.

• Fault tolerant – the safety addressable bus uses a closed ring tolerant to a single fault in the loop
(Short/Open Circuit).

• I/O density – with 8 I/O per remote module, up to 64 modules per control card and up to
130 control cards per panel, matches the size of virtually any installation site.

• Modular Design and scalability – can be configured to match what is needed now and then easily
expanded later.

• No constraint on device brands or type – compatible with standard 4-20mA input, high current
range for conventional input and output. Any type of Flame/Gas detector, conventional detector
or actuating device can be connected. Avoids lock-in with one single vendor for field devices.

• Easy configuration – configuration of modules and field devices is as easy and flexible as with
any other I/O within the same HS-81 panel. Menu driven pull-down programming speeds
configuration and commissioning work.

3
SYSTEM
ARCHITECTURE

The system is composed by one or two control cards F7011 installed in a HS-81 panel
and a number of I/O addressable modules connected in a closed fault tolerant looped ring.
Control cards carry out complete monitoring of devices to detect possible fault conditions of
modules or ring. The I/O modules communicates with the control cards on a safety bus giving
all information on channels I/O status and diagnostics.

Messages from/to the modules are properly prioritized to guarantee immediate signalling
of alarm conditions. Both control cards and modules are equipped with two independent
communication links: link 1 connected to the succeeding module, link 2 connected to the
preceding module. Both links are galvanic isolated to the power supply voltage.

System architecture with mono configuration

Node-1 Node-64
SB-SIM SB-SIM
+V +V
+V RUN +V
-V -V
-V RUN DISABLED -V RUN
FAULT
-LK1 -LK1
+LK1 LK1-Fault
L. ON FAULT +LK1 LK1-Fault
SLK1 SLK1
-LK2 DEVICE FAULT -LK2
+LK2 LK2-Fault RING FAULT +LK2 LK2-Fault

Link-1 Link-2 Link-1 Link-2 Link-1 Link-2


SLK2 SLK2
LK-1 FAULT
+L1 LK-2 FAULT +L1
-L1 -L1
+L2 +L2
-L2 -L2
+L3 L1 +L3 L1
-L3 -L3
L2 L2
+L4 +L4
L3 L3
-L4 -L4
L4 L4
+L5 L5 +L5 L5
-L5 L6 -L5 L6
+L6 L7 +L6 L7
-L6 -L6
+L7
-L7
L8
F7011-1 +L7
-L7
L8

+L8 +L8
-L8 -L8

Node-2 Node-3 Node-xx


SB-SIM SB-SIM SB-SIM
+V +V +V
+V +V +V
-V -V -V
-V RUN -V RUN -V RUN

-LK1 -LK1 -LK1


+LK1 LK1-Fault +LK1 LK1-Fault +LK1 LK1-Fault
SLK1 SLK1 SLK1
-LK2 -LK2 -LK2
+LK2 LK2-Fault +LK2 LK2-Fault +LK2 LK2-Fault

Link-1 Link-2 Link-1 Link-2 Link-2 Link-1


SLK2 SLK2 SLK2

+L1 +L1 +L1


-L1 -L1 -L1
+L2 +L2 +L2
-L2 -L2 -L2
+L3 L1 +L3 L1 +L3 L1
-L3 -L3 -L3
L2 L2 L2
+L4 +L4 +L4
L3 L3 L3
-L4 -L4 -L4
L4 L4 L4
+L5 L5 +L5 L5 +L5 L5
-L5 L6 -L5 L6 -L5 L6
+L6 L7 +L6 L7 +L6 L7
-L6 L8 -L6 L8 -L6 L8
+L7 +L7 +L7
-L7 -L7 -L7
+L8 +L8 +L8
-L8 -L8 -L8

System architecture with duplex configuration

Node-1 Node-64
SB-SIM SB-SIM
+V +V
+V RUN RUN +V
-V -V
-V RUN DISABLED DISABLED -V RUN
FAULT FAULT
-LK1 -LK1
+LK1 LK1-Fault
L. ON FAULT L. ON FAULT +LK1 LK1-Fault
SLK1 SLK1
-LK2 DEVICE FAULT DEVICE FAULT -LK2
+LK2 LK2-Fault RING FAULT RING FAULT +LK2 LK2-Fault

Link-1 Link-2 Link-1 Link-2 Link-1 Link-2 Link-1 Link-2


SLK2 SLK2
LK-1 FAULT LK-1 FAULT
+L1 LK-2 FAULT LK-2 FAULT +L1
-L1 -L1
+L2 +L2
-L2 -L2
+L3 L1 +L3 L1
-L3 -L3
L2 L2
+L4 +L4
L3 L3
-L4 -L4
L4 L4
+L5 L5 +L5 L5
-L5 L6 -L5 L6
+L6 L7 +L6 L7
-L6 -L6
+L7
-L7
L8
F7011-1 F7011-1 +L7
-L7
L8

+L8 +L8
-L8 -L8

Node-2 Node-3 Node-xx


SB-SIM SB-SIM SB-SIM
+V +V +V
+V +V +V
-V -V -V
-V RUN -V RUN -V RUN

-LK1 -LK1 -LK1


+LK1 LK1-Fault +LK1 LK1-Fault +LK1 LK1-Fault
SLK1 SLK1 SLK1
-LK2 -LK2 -LK2
+LK2 LK2-Fault +LK2 LK2-Fault +LK2 LK2-Fault

Link-1 Link-2 Link-1 Link-2 Link-2 Link-1


SLK2 SLK2 SLK2

+L1 +L1 +L1


-L1 -L1 -L1
+L2 +L2 +L2
-L2 -L2 -L2
+L3 L1 +L3 L1 +L3 L1
-L3 -L3 -L3
L2 L2 L2
+L4 +L4 +L4
L3 L3 L3
-L4 -L4 -L4
L4 L4 L4
+L5 L5 +L5 L5 +L5 L5
-L5 L6 -L5 L6 -L5 L6
+L6 L7 +L6 L7 +L6 L7
-L6 L8 -L6 L8 -L6 L8
+L7 +L7 +L7
-L7 -L7 -L7
+L8 +L8 +L8
-L8 -L8 -L8

4
FEATURES
AND BENEFITS

• Fire optic newtork for wide area coverage


• Modular system for easy additions of inputs / outputs in existing systems
• Reliable and safe with SIL3 certifications
• High availability with redundant network and hardware
• ATEX options for classified area installations
• SIL3 certified extinguishing to increase the reliability and safety

5
MODEL COMPACT PANEL WALL MOUNT 1 RACK WALL MOUNT 2 RACK FREE STANDING

Floor standing single door


(800 x 800 x 2100h mm) or
Compact wall mount Wall mount Wall mount Floor standing double door
MOUNT
(500 x 250 x 700h mm) (600 x 400 x 700h mm) (1100 x 400 x 700h mm) (1600 x 800 x 2100h mm)
Front only or
Front and Rear access

RACKS 1 compact rack 1 rack Up to 2 racks Up to 10 racks


CARDS Up to 8 cards Up to 13 cards Up to 26 cards Up to 130 cards
Integrated marshalling
OTHER
cabinet

SAFETY BUS SAFETY BUS SAFETY BUS


ENCLOSURE ENCLOSURE ENCLOSURE
SB-ENCLT5/B5 SB-ENCLT7/B7 SB-ENCLT5-EXD

• IP66 transparent • IP66 transparent • Explosion proof enclosure


or blank door or blank door • Up to 5 SB modules
• Up to 5 SB modules • Up to 7 SB modules • Cable trays
• Cable trays • Redundant power supplies • Field terminals
• Field terminals and battery charger
• Earth bar
• Earth bar • Cable trays

• Stainless steel option • Field terminals

• UL listed option • Earth bar


• Stainless steel option
6
SAFETY BUS CONTROL SB-SIM MODULE
CARD F7011 SB-SIM
+V
+V
-V
-V RUN

RUN -LK1
DISABLED +LK1 LK1-Fault

FAULT
L. ON FAULT
Control cards are integrated in SLK1
-LK2 Controls 8 supervised inputs for
+LK2 LK2-Fault

the HS-81 panel. Controls the conventional devices with safety


SLK2
DEVICE FAULT
RING FAULT +L1
-L1
LK-1 FAULT
LK-2 FAULT SIL3 Safety Communication +L2
-L2
related feature. Two individually
+L3 L1
Protocol, detects possible -L3
+L4
L2
L3
programmable thresholds for
-L4

fault conditions of modules each channel to connect any


L4
+L5 L5
-L5 L6

or in the ring. Can be installed device type: fire and gas.


+L6 L7
-L6 L8
+L7
F7011-1 -L7
in redundant configuration. +L8
-L8

SB-AIM MODULE SB-SCM MODULE


SB-AIM SB-SCM
+V +V
+V +V
-V -V
-V RUN -V RUN

-LK1 -LK1
+LK1 LK1-Fault +LK1 LK1-Fault
SLK1
-LK2 Controls 8 analog inputs SLK1
-LK2 Controls 8 outputs with
+LK2 LK2-Fault +LK2 LK2-Fault

4-20mA, with safety related 500mA each to drive releasing


SLK2 SLK2
+V1
-V1 +L1
+L1 -L1
+V2
-V2
+L2
feature. Alarm on three +L2
-L2
solenoids or other safety
+V3
L1 +L3 L1
individually programmable related actuators. All channels
-V3
+L3 -L3
+V4 L2 L2
+L4
-V4 L3 L3
+L4 -L4

thresholds. Combustible, are individually supervised to


L4 L4
+V5
-V5 L5 +L5 L5
+L5 L6 -L5 L6
+V6

toxic, and oxygen gas detect short/open circuits.


-V6 L7 +L6 L7
+L6
L8 -L6 L8
+V7
-V7
+L7
+L7 -L7
+V8
-V8
+L8
detection. Temperature +L8
-L8

and flame fire detection.

SB-NCM MODULE SB-ECM MODULE


SB-NCM SB-ECM
+V +V RUN
+V +V LK1-Fault
LK2-Fault
-V -V L1
-V RUN -V L2
L3
L4
-LK1 -LK1 L5
L6
+LK1 LK1-Fault +LK1 L7

Controls 8 outputs with 250mA Manages automatic fire


SLK1 SLK1 L8
L9
-LK2 -LK2 L10
+LK2 LK2-Fault +LK2 L11
L12

to drive notification appliances. extinguishing release system.


SLK2 SLK2 L13
L14
Aut. Disch.
+L1 +L1 Activated
-L1 -L1
+L2
-L2
Channels are supervised with +L2
-L2
L9
L9
Controls 8 supervised safety
+L3 L1 +L3 L10
-L3
+L4
L2
L3
polarity reversal monitoring -L3
+L4
L10
L11
related inputs and 6 supervised
-L4 -L4 L11

to detect short/open circuits. safety related outputs. Works


L4
L12
+L5 L5 +L5 L12
-L5 L6 -L5 L13

as part of the system or as a


+L6 L7 +L6 L13
-L6 L8 -L6 L14
+L7 +L7 L14
-L7 -L7
+L8
-L8
+L8
-L8
485
485
stand-alone release controller.

7
TYPICAL
APPLICATIONS

• Oil & gas tanks / wellheads ​


• Pipelines​
• Platforms​
• Tunnels​
• Remote areas
• Hazardous areas

Honeywell Industrial Fire


Via Lombardia 5
20004 Arluno (Milan) Italy
Tel: +39 02 36017829
E-mail: industrialfire@honeywell.com
HIF_SIL3_Brochure | Rev 14 | 10/19
industrialfire.honeywell.com © 2019 Honeywell International Inc.