Address Unit

Salwico AE-2K/I
Part no: 46259

System: Fire Alarm System CS3000, CS3004 and CS4000

Description Data
The AE-2K/I is an address unit for use with the Salwico CS3000, Nominal voltage 28 VDC
CS3004 and CS4000 fire alarm systems. It has been designed for use Working voltage 18 – 39 VDC
in damp spaces. Working current 0.2 mA
The AE-2K/I address unit can be mounted on base plates with either Ambient temperature -10°C to +70°C
Ingress protection IP55
two or three pipes.
Cable diameter 9 – 15 mm
The AE-2K allows the connection of the flame detector UVFD-2. It Material Aluminium
may also be used together with intrinsically safe interface ES-2K. Colour Off-white
The system address of the AE-2K is set by a DIP-switch. The type of Weight 200 g
device connected is set by an additional DIP-switch and is shown on
the display in case of fire or fault. AE-2K/I without base Part no 46259

The AE-2K/I is delivered without base


plate. For information about suitable base
plates, see separate document “Base matrix
Salwico units”.

Dimensions (mm)
112
76

MOUNTING HOLES
2x∅5 43
53

Connection

+ +1 +1
LOOP
– -2 -2

+3 +3 +
LOOP
-4 -4 –
END-OF-LINE CIRCUIT
+5 +5
SLZ-2
-6 -6
FOR EXAMPLE:
CONVENTIONAL UNITS
ON A SUB-LOOP
Specifications may be subject to change for improvement without prior notice Data sheet no: 46259.08.1.E