INFLOOR DESIGN GUIDE 1
DISTRIBUTION
AND FEEDER RUNS
DISTRIBUTION RUNS:
Every infloor system consists of two
parts – distribution runs and feeder runs.
n Education
n Government
n Museums
n Retail
FEEDER RUNS:
n Walkercell n Walkercell
n Walkerduct n Walkerduct
LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 3
Walkerduct
FEEDER SYSTEM
COMPATIBILITY:
TRENCHDUCT JUNCTION BOXES
Trenchduct allows easy access to cabling Walkerduct junction boxes are available in several
The Walkerduct system includes after installation via removable cover plates. configurations to accommodate 1, 2, 3 and 4 duct systems.
two sizes of underfloor ducts – It features extremely large cable capacity Standard cover plates are ¼" thick and can be customized
and is available in many different widths and with round or square access openings to complement space
No. 2 and No. 4 – for maximum depths to accommodate all jobs. Trenchduct design. Junction boxes can also be used in terrazzo applications
flexibility. This allows you to is installed above the Walkerduct system, by adding an optional terrazzo holder. Consult factory for
match cable capacity to project flush with the finished floor. additional custom options including heavy load applications.
31/8" 7¼" [184mm] 113/8" [289mm] 6½" [165mm] 14" [356mm] 10 5/8" [270mm]
[79mm]
1 No. 2 2 No. 2 3 No. 2 1 No. 4 2 No. 4 1 No. 2 and 1 No. 4
525™ Series 1200™ Series Source 1 Series
181/8" [460mm] 181/8" [460mm] 13¾" [349mm] Available in brushed aluminum and Compatible with Walkerduct IPS presets Offer single and dual-service power
accommodate interchangeable faceplates and available in aluminum or brass. and communications connections in a
in a pedestal style. flush style.
2 No. 4 and 1 No. 2 1 No. 2 and 2 No. 4 2 No. 2 and 1 No. 4
Spacing between ducts will always be 1" LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 5
WALKERDUCT
WITH JUNCTION BOXES
SERVICE FITTING
COMPATIBILITY:
n 1200 SERIES
n 525 SERIES
n MULTIPLEX SERIES
n PRO SERIES
n PSRC9 SERIES
n SOURCE 1 SERIES
Riser
SYSTEM FEATURES:
n an be installed in medium-sized
C
concrete slabs (3½ – 6")
Support Coupling
#2 Duct
#4 Duct
Conduit Adapter
LEGRAND.US/INFLOOR
Duct End Plug INFLOOR DESIGN GUIDE 7
WALKERDUCT
WITH TRENCHDUCT
SERVICE FITTING
COMPATIBILITY:
n 1200 SERIES
n 525 SERIES
n MULTIPLEX SERIES
Riser n PRO SERIES
n PSRC9 SERIES
n SOURCE 1 SERIES
SYSTEM FEATURES:
Trenchduct n ust be installed in concrete
M
T-Unit slabs at least 4" deep
n ombines flexibility of
C
Walkerduct with high capacity
of Trenchduct
COMMON LAYOUTS:
Pro Series Preset n aceway 5' or 6' on center, presets
R
24" on center
LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 9
The Walkercell system is
a three-in-one raceway
that offers extremely
FEEDER SYSTEM
high capacity and installs
quickly and easily.
COMPATIBILITY:
Ideal for:
n Call centers
n Data centers
n Education
Walkercell
WCR2 11 115 89 285 155 33 146 96 77
WCR3 18.8 197 153 488 265 56 252 162 130
Shielded Twisted Pair Fiber
Cell/Duct
Raceway Type TYPE 1 TYPE 2 TYPE 3 2 Strand 4 Strand 6 Strand Fiber ZipCord
Capacity
Sq. In. 0.119 0.17 0.047 0.025 0.028 0.035 0.01
WCR11/2 8.2 27 19 69 130 116 93 326
WCR2 11 37 26 93 173 155 127 463
WCR3 18.8 63 44 159 296 264 216 791
KEY SYSTEM FEATURES: *Consult factory for Cat6a wire fill information.
n Ample bend radius throughout the system maintains the integrity of fiber optic cable connections
n riple service presets deliver up to three services to the workstation at one location. These
T
WALKERCELL POWER WIRE FILL CAPACITY
larger presets span all three cells and enable connection of FloorPort™ Service Fittings Raceway Type Cell/Duct Capacity 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG
n FloorPort Service Fittings are UL scrub water listed Sq. In. 0.0097 0.0133 0.0211 0.0366 0.0507 0.0824
SERVICE FITTINGS
WALKERCELL SYSTEM OPTIONS FloorPort Series Consult factory for
Available in flush or recessed style, compatibility with other
Preset adds height of 13/8" (PK150) – 33/8" (PK350) FloorPort fittings include blank or service fittings.
furniture feed covers in aluminum,
1½" [38mm] 2" [51mm] 3" [76mm] black, brass, bronze, gray and
nickel finishes.
8.2 in 2
4.2 in
2
8.2 in
2
11.0 in
2
4.3 in
2
11.0 in2
18.8 in2
8.5 in2
18.8 in
2
17¾" [448mm] WCR1½ Total capacity: 26.3 in2 217/8" [552mm] WCR2 Total capacity: 26.3 in2 217/8" [552mm] WCR3 Total capacity: 46.1 in2 LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 11
WALKERCELL
WITH JUNCTION BOXES SERVICE FITTING
COMPATIBILITY:
n FLOORPORT SERIES
Walkercell
SYSTEM FEATURES:
n an be installed in medium-sized
C
concrete slabs (3½ – 6")
LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 13
WALKERCELL
WITH JUNCTION BOX HEADER SERVICE FITTING
COMPATIBILITY:
n FLOORPORT SERIES
Walkercell
SYSTEM FEATURES:
n an be installed in medium-sized
C
concrete slabs (3½ – 6”) due to
side feeds
COMMON LAYOUTS:
End Closure
n aceway 5' or 6' on center, presets
R
PK Preset
24" on center
Conduit Adapter aceway 10' on center, presets 24" on
R
Raceway Support n
center
Conduit n Raceway 5' or 6' on center, no presets
LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 15
WALKERCELL
WITH TRENCHDUCT SERVICE FITTING
COMPATIBILITY:
n FLOORPORT SERIES
n TRENCH ACCESS HOOD
Walkercell
SYSTEM FEATURES:
n ust be installed in concrete
M
slabs at least 4” deep
Vertical Riser
n Highest capacity infloor system
Trenchduct T-Unit
COMMON LAYOUTS:
LEGRAND.US/INFLOOR
INFLOOR DESIGN GUIDE 17
Flushduct
Trenchduct
Only from Legrand. The Flushduct system is available in 1, 2 or 3 duct combinations and Trenchduct allows easy access to cabling
installs flush with the finished floor. The system’s slim design enables installation in projects after installation via removable cover plates. It
features extremely large cable capacity and is
with shallow concrete pours and also allows Flushduct to be used in retrofit applications. available in many different widths and depths to
Ideal for: n Retail accommodate all jobs. Trenchduct is installed
KEY SYSTEM FEATURES: FLUSHDUCT SYSTEM OPTIONS above the Walkercell or Walkerduct system, flush
with the finished floor.
n Flush installation simplifies locating and accessing the system Single 3.31 in2
after installation Flushduct [21.3cm2] 1¼"[32mm]
n Minimum system depth for systems with junction boxes is 2½" 6¼" [166mm]
SERVICE FITTINGS
525 Series Multiplex Series
These durable, pedestal-style fittings Multiplex is available in brushed
are available in brushed aluminum aluminum and accommodates power
and accommodate interchangeable and communications connections in a
faceplates to support power and pedestal style.
communications connections. LEGRAND.US/INFLOOR 19
INFLOOR DESIGN GUIDE
FLUSHDUCT
WITH JUNCTION BOXES SERVICE FITTING INTERESTED IN LEARNING MORE?
COMPATIBILITY: Visit us online at www.legrand.us/infloor to explore our interactive tools and videos,
research technical product details and request assistance on your next project. We’d be happy
n 525 SERIES to send you more information or schedule an in-person visit when it’s convenient for you.
n MULTIPLEX SERIES
Flushduct
SYSTEM FEATURES:
n an be installed in concrete slabs
C
as thin as 2” using conduit feeds
Couplings/Supports
Leveling Foot
Plugs
Conduit Adapter
Conduit