ME 461-P4C2: AIR CONDITIONING & VENTILATION SYSTEM

A.) Using the psychrometric chart below, determine the relative humidity, %; specific humidity, gm/kg;
specific enthalpy, kJ/kg; specific volume, m3/kg, and the degree of saturation, %, of a moist air with
the following conditions: 32C dry-bulb temperature, 18C dew-point temperature, and at a pressure
of 101.325 kPaa. Plot and label values on the chart.

kgm
w=0.0 31
kga

kj
h=65.02271
kg

Φ = 43.4%

Tdp = 18 C
kgm
w=0.0129
kg

Tdb = 32 C
m3
v=0.8819
kg

10/29/2021 3:25 PM 1
NAME: LABAJO, KENT M. ME 461-P4C2: AIR CONDITIONING & VENTILATION SYSTEM

B.) Find the properties of the moist air mentioned above using the psychrometric equations and get the
percentage error for each property.

10/29/2021 3:25 PM 2