You are on page 1of 2

053-090

TYPICAL WIRING DIAGRAM DEEP SEA ELECTRONICS ISSUE 1


A larger diagram is available in the operators manual.
Part No 057-202 D S EE 8 0 0 I NST AL L AT I O N I NST R UCT I O NS

ACCESSING THE FRONT PANEL CONFIGURATION EDITOR


• Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset
button.

• Press and hold the the (stop) button and (tick) button together.
• If a module security PIN has been set, the PIN number request is then shown .

• Press (tick), the first ‘#’ changes to ‘0’. Press (up) or (down) to adjust it to the correct
value.
• Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.

• The other digits of the PIN number. You can press (left) if you need to move back to adjust
one of the previous digits.

• When (tick) is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, you must re-enter the PIN.
• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed.

• To edit the parameter, press (tick) to enter edit mode. The parameter begins to flash to indicate
that you are editing the value.
• Press the up or down buttons to change the parameter to the required value.
• Press (tick) to save the value. The parameter ceases flashing to indicate that it has been saved.

• To exit the editor at any time, press and hold the (stop) to eixit without saving changes or
(tick) button to save changes and exit.

EDITING A PARAMETER

• Enter the editor as described above.

• Press the (up) (down) and (right) to cycle to the section you wish to view/change.
Then press (up) or (down) to cycle to the parameter within the section you have chosen.

• To edit the parameter, press (tick) to enter edit mode. The parameter begins to flash to indicate
that you are editing the value.
• Press the up or down buttons to change the parameter to the required value.

• Press (tick) to save the value. The parameter ceases flashing to indicate that it has been saved.

• To exit the editor at any time, press and hold the (stop) or (tick) button.

NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to
ensure security.
NOTE: More comprehensive module configuration is possible using the PC configuration software. Please
contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module configuration.
ADJUSTABLE PARAMETERS - Front Panel Configuration Editor. ACCESSING THE “MAINTENANCE” EDITOR
Section Parameter As Shown On Display Values

Display Contrast 0 % Description Action Activation


Language English, others. Press (up) or (down) buttons together.
Current Date and Time Date hh:mm USB Stick Removal Request
Engine Oil Pressure Low shutdown 0 bar Override Starting Alarms Request Press
Oil Pressure Low Pre-Alarm 0 bar Clear AMF Alarm Clear
Coolant Temp High Pre-Alarm 0 ºC
Press ,(up) or (down) (right) to cycle to Manual Fuel Pump Inactive
Coolant Temp High Shutdown 0 ºC the Parameter you wish to action. Min / Max Session Reset Request Button
Start Delay Off load 0 s Cancel Telemetry Request
Start Delay on load 0 s
Start Delay Telemetry 0 s
Pre Heat Timer 0 s
Crank Duration 0 s To exit the editor at any time, press and hold the (tick) button.
Crank rest Time 0 s
Safety On Delay 0 s
Smoke Limiting 0 s
Smoke limiting off 0 s
Warm Up Time 0 s
Cool Down Time 0 s
Under Speed Shutdown Inactive ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
Under Speed Warning Inactive
Over Speed Shutdown Inactive
Over Speed Warning Inactive
Over Speed Shutdown 0 RPM
Speed Overshoot 0% • The ‘running’or editor can be entered while the engine is running. All protections remain active if the engine is
Fail To Stop Delay 0 s running while the running editor is entered.
Battery Under Volts Warning Active
Battery Under Volts Warning Delay 0 m
Battery Under Volts Warning 0 v • Press and hold the (tick) button to enter the running editor.
Battery Over Volts Warning Active
Battery Over Volts Warning Delay 0 m
Battery Over Volts Warning 0 v
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning 0 V ADJUSTABLE PARAMETERS - Running Configuration Editor
Charge Alternator Warning Delay 0 s
Charge Alternator Failure Shutdown Inactive
Priming Delay 0 s • Enter the editor as described above.
Clutch Engage Speed 8
Clutch Disengage Speed 0
Idle Speed 0.00
Warming Speed 0.00
• Press the (up) or (down) buttons to cycle to the section you wish to view / change.
Cooldown Speed 0.00
Starting 0.00
Min Speed 0.00
On Load Speed 0.00 • To Edit the parameter press the (tick) button to enter edit mode. The parameter begins to flash to indicate that
Max Speed 0.00
you are editing the value.
Auto Adjustable Speed Inactive
Cool Down at Idle 0 s
LCD Page Timer 5m
Timers
Scroll Delay 2s
Engine Pre Heat Timer 0s
• Press the (up) or (down) buttons to change the parameter to the required value.
Engine Crank Duration 10s
Engine Crank Rest Time 10s
Engine Safety On Delay 10s • Press the (tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
Engine Smoke Limiting 0s
Engine Smoke Limiting Off 0s
Engine Warm Up Time 0s
Engine Cool Down Time 1m • Press and hold (tick) button to exit the “Running Configuration Editor”.
Engine Speed Overshoot Delay 0s
Engine Failed To Stop Delay 30s
Battery Under Voltage Warning Delay 1m
Battery Over Voltage Warning Delay 1m
Return Delay 30s Section Parameter Values
Under Voltage Pre-Alarm 196v Display Contrast 0%
Nominal Voltage 230v Language English (United Kingdon), Other
Schedule Schedule Inactive
Schedule On Load Active , Inactive (Only Available When Scheduler Is Active) b SectiT
Schedule Period Weekly, Monthly (Only Available When Scheduler Is Active) o

Schedule Time & Date Selection (1-16) Press to begin editing then or when
selecting the different parameters in the scheduler.

Deep Sea Electronics Plc. Deep Sea Electronics Inc.


Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706 DIMENSIONS AND MOUNTING
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 For flat surface mounting in a Type 1 enclosure to meet UL requirements
Email: support@deepseaplc.com TOLL FREE (USA) : Tel: 1 866 636 9703
Web: www.deepseaplc.com Email: dsesales@deepseausa.com DIMENSIONS PANEL CUTOUT:
240.0 mm x 181.1 mm x 41.7 mm (9.4” x 7.1” x 1.6”) 220 mm x 160 mm (8.7” x 6.3”)
Web: www.deepseausa.com

You might also like