Adjustment of SW1
5. When using a DSExx20 synchronising module, ensure the inputs configured for ‘Mains Load Inhibit’ and ‘Generator
Load Inhibit’ are active.
6. Start the generator and ensure that the breaker is left open.
7. Check the direction of drive by increasing and decreasing SW1. If the frequency or voltage increases whilst SW1 is
being decreased, tick the option ‘Output Reversed’. If moving SW1 does not change the frequency or voltage, check
wiring.
8. Adjust the SW1setting for both the Governor and AVR until the generator runs at Nominal Voltage (230V for
example) and Frequency (50Hz or 60Hz)
9. Stop the generator. SW1 is now complete and needs to be left alone.