You are on page 1of 83

Chapter 5

Applied
Psych rometrics
5-l INTRODUCTION bular heating coil where a medium, such as
steam or hot water, circulates within the coil
The psychrometric chart, introduced in
tubes, or an electrically heated coil, or the
Chapter 4, is one of the most useful tools of
heat-transfer surfaces of a warm-air furnace .
the practicing air-conditioning engineer and
Figure 5-1 shows a typical heat-transfer coil
technologist. The chart assists in the solution
for heating air by the use of steam. Figure 5-2
of simple as well as complex · processes in-
is a schematic drawing showing the heat-trans-
volved in the conditioning of moist air. Most
fer coil and the skeleton psychrometric chart
of the complex problems consist of various
illustrating the sensible-heating process. As in-
combinations of simple processes, such as sen-
dicated in Fig. 5-2, during a sensible-heating
sible heating, sensible cooling, humidification,
process the dry- and the wet-bulb temperatures
or dehumidification. The chart provides a
means for showing these various processes
graphically. In this chapter we will progress
through the various types of basic processes
and into the analysis of the more complex pro-
cesses.
Although the psychrometric chart is most
helpful, jt must be understood that graphic~
solution of problems must be done with great
care if satisfactory results are to be obtained.
Therefore, we should stress careful and neat
work on the chart to obtain as much accuracy
as possible.

5-2 SENSIBLE HEATING OF MOIST


AIR
If heat is added to moist air with no addition
of moisture, the process is called sensible heat-
ing. Such a process may occur when moist air
passes through or over a heat-transfer surface Figure 5-1
which causes a rise in the air dry-bulb temper- Single row heating coli (Courtesy of
ature. The heat-transfer surface may be a tu- The Trane Company.)

169
170 APPLIED PSYCHAOMETAICS

.--
W = humidity ratio (lb water vapor!lb
v dry air)
to be det
of the ai
tw 1
v h = enthalpy of moist air (Btu/lb dry air) rate , m.,,
air at the
1
Therefore, for sensible heating of moist air, flow rate
......_ and using Eq. (5-1) and (5-2), we have

Since the humidity ratio is constant during the where ma


process, it is closely true that the moist-air en- 60 min/h
thalpy is air at the
~ For un
h = 0.240t + W(1060 + 0.45t) (4-7) try air-hru

...,._..,__..,.
Repeated the basis '
2 w1 = w2 fined as d
If t 1 and -t2 are substituted into Eq. (4-7) to ometric I
obtain h 1 and h2 and if the results are substi- 0.075 Ibn
tuted in Eq . (5-4), we would have in Eq. (5-

ma =
Figure 5-2
where t 1 and t2 are the initial and final dry-bulb If this val
Schematic: Sensible heating process
temperatures, respectively, for the sensible- we have
heating process. Equation (5-5) assumes a con-
increase, but the dew-point temperature and stant specific heat of superheated steam of
humidity ratio are constant. 0.45. It is often convenient to combine the two
The steady-flow .and material-balance equa- specific heat values for an average value of hu- And , if WI
tions which apply to this process are midity ratio, say 0.01 lb vapor!lb da (70 (5-6), we
grains!lb da) . This gives a single specific heat
of moist air of 0.244, and Eq. (5-5) becomes
(5-2)
(5-6) or
(5-3)
Air-handling components in systems, such
where as fans, ducts, and so forth, are selected on the
Caution: 'J
basis of volume flow rather than mass flow of
equations j
ma = pounds of air flowing per unit of time air. This introduces a little difficulty in prob-
the only 01
(usually lblhr) lem solutions because the volume flow varies
maining eq
with temperature and pressure (or, the specific
called appr
Iq
. s2 sensible heat added from condition 1 volume), whereas the mass flow rate is con-
we made .c
stant. Therefore, if the air volume flow rate is
to condition 2 per unit of time their develt
to be determined, it is necessary to specify the
(usually in Btulhr) 5) through
point in the system where flow volume rate is
tual work I
~-

APPLIED PSYCHROMETRICS 171

to be determined and find the specific volume dry-bulb temperatures are easy to read from a
of the air at that point. With the mass flow psychrometric chart. Another reason for using
rate, rna , known and the specific volume of the these equations instead of Eq. (5-4) is because
air at the point, we may calculate the volume of difficulty in reading accurate enthalpy val-
flow rate in cubic feet per minute from ues from the psychrometric chart, which is
lir.
quite necessary in some problems . For exam-
cfm = (rna)(v) ple, assume that a system requires an air flow
60 (5-7) rate of 50,000 lb/hr of air and an enthalpy
54)
change (h 2 - h 1) equal to 15.5 Btu/lb da. The
where rna is the mass flow rate of air in lb/hr, resulting 1qs2 would be 775,000 Btu/hr. How-
the
60 minlhr, and, v the specific volume of the ever, if the enthalpy difference read from the
en-
air at the point in question in fe/lb da. psychrometric chart had been 15 .7 Btu/lb da,
For uniformity in the manufacturing indus- the resulting 1qs2 would be 785,000 Btulhr,
try air-handling equipment is normally rated on with an error of about 1.3 percent. This is well
(4-7)
~aJed the basis of "standard air" which has been de- within the accuracy of Eqs. (5-5) through (5-
fined as dry air at 70°F and 29.92 in. Hg bar- 9).
') to ometric pressure, which gives a density of
bsti- 0.075 lbrnlft3 . Using this density, equal to llv, 5-3 SENSIBLE COOLING OF MOIST
in Eq . (5-7) we have AIR

(5-5) rna = (60 X 0.075)(cfm) = 4.5 cfm If heat is removed from moist air with no
change in moisture content, the process is
·bulb If this value of rna is substituted in Eq. (5-4), called sensible cooling. Such a process occurs
;ible- we have when warm air from a warm-air heating sys-
con- tem enters a space and replaces the heaf lost
m of 1iJs = (4.5 cfm)(h2 - h 1) (5-8) from the space. This is true if there are no
2
~two
sources within the space giving off moisture.
>f hu- And, if we substitute the value of rna into Eq. This assumption is normally made when de-
(70 (5-6), we have signing winter heating systems. Sensible cool-
heat ing also occurs if moist air passes through a
>mes 1iJs = 0.244(4.5 cfm)(t2 - tt) tubular cooling coil where a medium such as
2
chilled water circulates through the coil tubes.
or The chilled water must be above the moist-air
(5-6)
dew-point temperature because no condensa-
1iJs
2
= (1.10 cfm)(t2 - t 1) (5-9) tion from the air is a requirement for sensible
such cooling.
on the Caution: You should recall that of the series of Figure 5-3 shows a typical cooling coil for
OW of
equations just developed for 1qs2 , Eq. (5-4) is chilled water, and Fig. 5-4 shows the sche-
prob- the only one that may be called exact. There- matic drawing representing the sensible-cool-
varies mainin~ equations, <?-5) through (5-9), can be ing process. Equations (5-1) through (5-9) ap-
ecific called approximate because, as you have seen, . ply to sensible-cooling processes, however, the
(On- we made _fertain assumptions about the air in subscripts should be reversed if a positive
ate is their development. Regardless of this, Eqs. (5- value is wanted for 1qs2 • Remember that heat
y the 5) through (5-9) are used quite generally in ac- is being removed from the air in the sensible-
ate tual work because of their simplicity, and the cooling process.
172 APPLIED PSYCHROMETRICS

lllustrative Problem 5-l

How much heat is required to heat 3000


cfm of moist air at 45°F DB and 35°F WB to
a final temperature of 90°F DB without change
in humidity ratio?

Solution:
(Refer to Fig . 5-5). Since the problem
states no change in humidity ratio, the process
is a sensible-heating process.
Figure 5-3
· Step 1: On the psychrometric chart locate
Dralnable water cooling coli
(Courtesy of The Trane Company.) point I at the intersection of 45°F
DB and 35°F WB. At this point
read W1 = 14 grains/lb da, h 1 =
13.0 Btu/lb da and v1 = 12.76
fellb da. = 0.244
r-- Step 2: On the psychrometric chart locate
t,
I~ point 2 by drawing a horizontal
t2 line (constant humidity ratio)
By Eq. (5-9)
tw 1 through point 1 and extend to
I~ tw 2 point 2 at 90°F DB. At this point 1iJs2 = {1.10 I
find w2 = 14 grains/lb da, h2 =
w, w2 l.IO C
23.9 Btu/1b da, and v2 = 13.90
tdp1 - tdp2 ft 3/lb da.
Step 3: Determine the mass of air heated .
From Eq . (5-7)

rna cfm X (60)/v 1 = 3000 (60)/ 12.76


rna = 14,100 lb/hr

Step · 4: Determine sensible heat added .


By Eq. (5-4)

tiJs2 =
rna(h2 - ht) = 14, 100(23 .9 13.0)
1qs 2 = 153,700 Btu/hr (ans)

Figure 5-4
By Eq. (5-6)

Schematic: Sensible cooling process


APPLIED PSYCHROMETRICS 173
Illustrative Problem 5-1

How much heat is required to heat 3000


cfm of moist air at 45°F DB and 35°F WB to
a final temperature of 90°F DB without change
in humidity ratio?
w
Solution:
(Refer to Fig. 5-5) . Since the problem
states no change in humidity ratio, the process
t ...

is a sensible-heating process. I I ,,.... I I w, '!'2


==:_

Step I : On the psychrometric chart locate 90 = 14


point I at the intersection of 45°F
Figure 5-5
DB and 35°F WB. At this point
read W1 = 14 grains/lb da, h 1 = Solution for Example 5-1
13.0 Btu/lb da and v 1 = 12.76
fe/lb da. = 0.244 (14)00)(90 - 45) Illustrative Problem 5-2
Step 2: On the psychrometric chart locate
1iJs2 = 156,800 Btu/hr (ans)
(Refer to Fig. 5-6.) Hpw much heated air
point 2 by drawing a horizontal
line (constant humidity ratio) must be supplied to a space within a building
By Eq. (5-9)
through point I and extend to to offset a heat loss of 38,200 Btu/hr? The
point 2 at 90°F DB. At this point 1iJs2 = (1.10 cfm)(t2 - t 1) space aii condition is to be maintained at 70°F
find w2 = 14 grains/lb da, h2 = DB and 50 percent RH, and the air supplied is
23 .9 Btu/lb da, and v2 = 13 .90 I. I 0 (3000)(90 - 45) at a temperature of 105°F DB . Assume no
fe/Jb da . moisture addition within the space.
1iJs7- = 148,500 Btl,lfhr (ans)
Step 3: Determine the mass of air heated .
From Eq . (5-7)

rna = · cfm X (60)/vl = 3000 (60)/ 12.76 w


rna = 14,100 lb/hr

Step · 4: Determine sensible heat added . r


By Eq. (5-4)

1iJs • = rna<h2 - h1) = 14, 100(23 .9 13 .0) W1 = W2


2
1iJs = 153,700 Btu/hr =55
(ans)
2 dB-.
70 105 '
By Eq. (5-6)
Figure 5--6
1iJs 2 = 0 .244rna(t 2 - 11) Solution for Example 5-2
m., mix
Solution : 4442 X 14.4 1
cfm = - ---- t,
h,
cal
Since there is no moisture addition in the 60 5-3
space, the supply air will have the same hu- cfm = 1067 at supply air conditions (ans) I
w3 t3 h3
midity ratio as the space air, and we have a do
.m
sensible-cooling process. The supply air An approximate solution could be obtained by "3 0 .5
cools to the space condition as it gives up its use of Eq. (5-9): sub
sensible heat to overcome the space heat
loss. 1q52 = (1.10 cfm)(t 1 - 12) t2
m.2
Step 1: On the psychrometric chart at 38 ,200 = (1.10 cfm)(l05 - 70)
70°F DB and 50 percent RH, lo- cfm = 992 (ans)
Als•
cate space air condition, point 2.
oft
At this point read W2 = 55 5-4 ADIABATIC MIXING OF TWO oft:
grains/lb da, h2 = 25 .3 Btu/lb STREAMS OF AIR Thi:
da, and v2 = 13.51 fetlb da. w2
A frequently encountered process in air flov
Step 2: On the psychrometric chart locate conditioning is the mixing of two or more w3
rna~

the supply air condition by con- streams of air having different psychrometric
structing a horizontal line through properties . Figure 5-7 represents the schematic
point 2 and extend to the supply drawing of the two flow streams mixing and IIlli
w,
air temperature , 105°F, point 1. the psychrometric chart for the process. The
At this point find W1 = 55 grains/ fundamental equations which apply to this t, t3 t2 10<
lb da, h 1 = 33 .9 Btu/lb da, and mixing process are
v, = 14.41 fetlb da. at l
Figure 5-7
the
Step 3: Determine the mass of heated air math! + ma2h2 = ma3h3 (5-10) Schematic: Mixing process ent
supplied. By Eq. (5-4),
mal + ma2 = ma3 (5-11)
tiis2 = ma(h, - h2) Making use of Eqs . (5-10) through (5 -13),
ma,Wt + ma2W2 = ma3W3 (5-12) the following three equations become useful in
Note that subscripts on h have been reversed the evaluation of the mixed air properties:
to give a positive value of 1q52 .
If ma3 is eliminated from Eqs. (5-10) , (5-11 ),
and (5-12) we would have
mal X1t + ma2 X 12
38,200 = ma{33 .9 - 25 .3) t3 = mal + ma2
(5-14)

rna = 4442 lb/hr (ans) m al h2 - h3 W2 w,


- = (5-13) mal X Wt + ma2 X W2
ma2 h3 - h, w3 w, w3 =
mal + ma2
(5-15)
30<
Step 4: Determine volume of supply air.
By Eq. (5-7) , • I
This defines a straight line on the psychrome-
mal X h1 + ma2 X h2 Sp<
tric chart between points 1 and 2. Point 3 lies h3 = mal + ma2
(5-16)
1
(rna x v) on the line between points 1 and 2, and the Hu
cfm
60 line segments produced are proportional to the 1
masses of air mixed , the temperature differ- The solution of a mixed-air problem in psy-
En
The specific volume of the supply air ences, humidity ratio differences, and the en- chrometrics normally makes use of one of Eqs. }
(5-14) through (5-16), and then the remaining
Vt = 14.41 fe /lb da . thalpy differences.
APPLIED PSYCHROMETRICS 175

me 1 mixed-air properties are determined by graphi-


4442 X 14.41 t, cal means. This will be illustrated by Problem
cfm = ---
60
-- h,
5-3 to follow .
w, If the specific volumes of the two airstreams
cfm = 1067 at supply air conditions (on1) w3 t3 h3
do not vary appreciably from each other (about
. m.J
An approximate solution could be obtained by 0.5 fe/lb da) then Eq . (5-14) could be used,
use of Eq. (5-9): substituting cfm in place of rnaas follows :

lqs = (1.10 cfm)(t 1 - t2) • cfm 1 x t 1 + cfm 2 x t2


2 t3 = (5-17)
cfm 1 + cfm 2
38 ,200 = (1.10 cfm)(105 - 70)
cfm = 992 (onl)
Also , in some problems involving the mixing
of two airstreams, data is given on the percent
5-4 ADIABATIC MIXING OF TWO of the total flow entering at the two conditions.
STREAMS OF AIR ~w2
This is handled by substituting the percentage
flow , expressed as a decimal , in place of the
A frequently encountered process in air
I I I WJ mass flow quantities.
conditioning is the mixing of two or mor~
streams of air having different psychrometric
properties . Figure 5-7 represents the schematic
drawing of the two flow streams mixing and .... I I I w, Illustrative Problem 5-3
the psychrometric chart for the process . Tho Three hundred cfm of air at 35°F DB and
fundamental equations which apply to this t, t3 t2 100 percent RH are mixed with 600 cfm of air
mixing process are at 85°F DB and 50 percent RH . What will be
Figure 5-7
the dry-bulb temperature, humidity ratio, and
ma!hl + ma2h2 = ma3h3 (5-10) Schematic: Mixing process enthalpy of the mixture?

mal + ma2 = ma3 (5-11) Solution:


Making use of Eqs. (5-10) through (5-13),
the following three equations become useful in (See Figure 5-8 .)
ma1W1 + ma2W 2 = ma3W3 (5-12)
the evaluation of the mixed air properties: Step 1: Determine the psychrometric
properties of the two airstreams
If ma 3 is eliminated from Eqs . (5-10), (5 - 11) , mal X t1 + ma2 X t2
(5-14) from psychrometric chart.
and (5-12) we would have t3
mal + ma2

mal W2- W1 Condition 1 Condition 2


-=
h2 - h3 (5-I.l) w - mal X WI + ma2 X w 2
ma2 h 3 - hi w3- w! 3 -
mal + ma2
(5-15)
300 cfm at 35°F DB , 600 cfm at 85°F DB ,
100 percent RH 50 percent RH
This defines a straight line on the psychrome h - IDa ! X hi + ma2 X h2 Specific volume
3 - (5-16)
tric chart between points 1 and 2. Point 3 lieN mal + ma2 v, = 12.ss fe!lb da V2 = 14.02
on the line between points 1 and 2, and th Humidity ratio
line segments produced are proportional to th W, = 30 grains/lb da W2 = 90
The solution of a mixed-air problem in psy-
masses of air mixed , the temperature differ Enthalpy
chrometrics normally makes use of one of Eqs. h 1 = 13.1 Btu/lb da h2 = 34.5 Btu/lb da
ences , humidity ratio differences , and tho en (5-14) through (5-16) , and then the remaining
thalpy differences.
176 APPLIED PSYCHROMETRICS

5-5 HUMIDIFICATION OF AIRt Illus1

w As stated previously, the purpose of en- A:


vironmental control is to make people more perce

50% t
w3 = 68
comfortable and the labor of people and
equipment ll'lore efficient. Temperature, hu-
midity, cleanliness, air movement, and ther-
insid1
- woul·
the i1
~,..£1 I mal radiation interrelate to create conditions
Sc
= 60.5 in which people are more comfortable or
less comfortable. In a home, business, or L<
industry, comfort or production efficiency is diti01
greatly affected by changes in these environ- perce
d8----.35 67 85 mental variables . . tio oJ
Least evident of these variables to human additi
Figure 5-8 perception is humidity. All of us will recog- have
Solution for Example 5-3 nize and react more quickly to temperature A1
changes, odors, or heavy dust in the air, 72°F,
. drafts, or radiant heat from sunlight or a radia- less t
Step 2: Determine mass of the two air- 23.9 X 35 + 42.8 X 85 tor, th.ep we will to a change in relative humid- SiJ
streams using Eq. (5-8) to deter- 23.9 + 42.8 ity, However, as relative humidity interrelates cure·
mine lb per min, we have 67.08°F (say 67°F) (ans) with temperature and others of these variables, tratio:
t3
it becomes a vital ingredient in total environ- make
Where t3 = 67°F intersects the mixture line mental control. thew
. _ cfm 1 _ 300 ~"" y'i\\f
mal - VJ - 12.55 between points 1 and 2 determines the mixed- Frequently, in air-conditioning work it is this <
air condition, point 3. From the chart at point necessary to humidify the air by introducing warm
. _ cfm 2 _ 600 3 find tw3 = 60SF, W3 = 68 grains/lb da, moisture into the air. The moisture added healtt
ma 2 - v2 - 14.02 h3 = 26.6 Btu/lb da, dew point tdp = 56.4°F, may be already in the vapor state or it may some
partial pressure, Pv = 0.455 in. Hg. be liquid. (It may also be solid, although In<
mal = 23.9 lb/min infrequently.) Humidification is frequently did iii
Step 4: Determine the dry-bulb tempera-
ture of the mixture by using ap- required during cold weather conditions be- oretic
ma2 = 42.8 lb/min cause the cold outside air infiltrating into a dition
proximate Eq. (5-17).

Step 3: Determine psychrometric proper-


€11
300 X
t3Y ~+ QIV Tv
600 X 85
heated building, or being brought in by a
mechanical ventilation system, is normally
ing. I
hygro
ties of the mixed air. t3 very dry (low humidity ratio, even though oretic
300 + 600
its relative humidity may be high). If the
On the psychrometric chart,
draw a straight line joining point t3 68.3°F 6-J ~ (ans)
infiltration or ventilation air is not humidi-
heate<
source
1 and point 2. Calculate the dry- fied, a low dew-point temperature, relative moist
This varies 1.3°F from the previous value of humidi~, and humidity ratio could exist within buildi
bulb temperature of the mixture
t 3 = 67°F. The significance of the difference the heated .building. skin
by using Eq. (5-14).
must be evaluated by the engineer as to the
accuracy with which he should be working.
X t1 + ma2 X t2 The exact Eq. (5-14) should be used when
t3 = mal possible.
tExtracted from The Armstrong Humidification Handbook, A
mal + ma2 igan p. 2-3, with permission .
APPLIED PSYCHROMETRICS 177

5-5 HUMIDIFICATION OF AIRt . Illustrative Problem 5-4


~ I
Assume that outside air at 30°F DB and 40
As stated previously, the purpose of en-
w vironmental control is to make people more percent RH infiltrates into a building where the

50% I
w3 = 68
• comfortable and the labor of people and
equipment more efficient. Temperature, hu-
midity, cleanliness, air movement, and ther-
mal radiation interrelate to create conditions
inside is being maintained at 72° F DB. What
would · be the theoretical relative humidity of
the infiltrated air at 72°F?
Solution:
in which people are more comfortable or
tw = 60 . 5
. 3 less comfortable. In a home, business, or Locate on the psychrometric chart the con-
industry, comfort or production efficiency is dition of the outside air at 30°F DB and 40
greatly affected by changes in these environ- percent RH. At that point find the humidity ra-
mental variables. tio of 9.5 grains/lb da. If there is no moisture
85 Least evident of these variables to human addition in the building, the infiltration ~ir will
5-8 perception is humidity. All of us will recog- have the same humidity ratio at 72°F.
nize and react more quickly to temperature At a humidity ratio of 9.5 grains/lb da and
xample 5-3
changes, odors, or heavy dust in the air, 72°F, find the relative humidity to be slightly
drafts, or radiant heat from sunlight or a radia- less than 9.0 percent_ (ans.)
23.9 X 35 + 42.8 X 85 tor, ~we will to a change in relative humid- Since one to three complete air changes oc-
23.9 + 42.8 ity: However, as relative humidity interrelates cur every hour in most buildings through infil-
with temperature and others of these variables, tration (and many m9re times with forced
t
3
= 67 .08°F (say 67°F) (ans)
it becomes a vital ingredient in total environ- makeup or exhaust), cold outdoor air replaces
Where t 3 = 67°F intersects the mixture line mental control. the warm indoor air. The heating system heats
between points 1 and 2 determines the mixed- Frequently, in air-conditioning work it is this cold, moist outdoor air and it becomes
air condition, point 3. From the chart at point necessary to humidify the air by introducing warm, dry indoor air. This condition is un-
3 find tw = 60SF, W3 = 68 grains/lb da, moisture into the air. The moisture added healthy for people and may be troublesome for
3
h3 = 26.6 Btu/lb da, dew point tdp = 56.4°F, may be already in the vapor state or it may some industrial processes.
partial pressure, Pv = 0.455 in. Hg. be liquid. (It may also be solid, although Indoor relative humidity calculated as we
infrequently.) Humidification is frequently did in Problem 5-4 should be called the "the-
Step 4: Determine the dry-bulb tempera-
required during cold weather conditions be- oretical" indoor relative humidity. This con-
ture of the mixture by using ap-
cause the cold outside air infiltrating into a dition very seldom actually exists in a build-
proximate Eq. (5-17).
heated building, or being brought in by a ing. Relative humidity values observed on a
&, ~ , GIV 1-v mechanical ventilation system, is normally hygrometer will almost always exceed this the-
300 X 3~ + 600 X 85 very dry (low humidity ratio, even though oretical value. The reason is that this dry,
t3 -
- 300+600 its relative humidity may be high). If the heated air will absoib moisture from any
t3 = 68 .3°F 6--i .}--~ (ans) infiltration or ventilation air is not humidi- source it can within the building. It will absorb
fied, a low dew-point temperature, relative moisture from any hygroscopic material in the
This varies 1.3°F from the previous value of humidity, and humidity ratio could exist within building, as well as from nasal passages and
t = 67°F. The significance of the difference the heated building. skin of human beings. This is not "free" hu-
3
must be evaluated by the engineer as to the
accuracy with which he should be working.
The exact Eq. (5-14) should be used when tExtracted from The Armstrong Humidification Handbook, Armstrong Machine Works, Three Rivers, Mich-
possible. igan p. 2-3, with permission.
178 APPLIED PSYCHROMETRICS

midification; it is the most expensive when at 35 percent relative humidity (because people
translated into terms of human health and com- can be more comfortable at a lower tempera-
fort, material deterioration, and production dif- ture with higher humidity levels), the enthalpy
ficulties . Moreover, it requires the same is only 21.8 Btu/lb da, which is a very slight
amount of energy whether the moisture is ab- increase 21.8 - 21.7 = 0.1 Btu/lb da in en-
sorbed from people and materials or added to ergy. In many cases there will be a decrease in
the air by an efficient humidification system. the required energy.
The introduction of water into the air for
Dlustrative Problem 5-5 purposes of humidification is relatively easy

Let us examine the theoretical system of


and can be accomplished with rather simplified
equipment. However, before we introduce this
-
Problem 5-4 using enthalpy as the base and equipment, we will discuss briefly the princi-
determine the energy exchanges taking place. ple of vaporization of a liquid. (a)
From the psychrometric chart at 30°F DB Vaporizationt of a liquid, such as water,
and 40 percent RH, find hoa = 8.8 Btu/lb da. may take place in two different ways: (1) by Figure 5-9
If this air is heated to 72°F without moisture evaporation and (2) by boiling. Evaporation of Evaporation of
addition, the enthalpy is hra = 18.7 Btu/lb da, a liquid can occur only at the free surface of
ture in the air in the sealed container. Vapor
and the resulting relative humidity of 9.0 per- the liquid and may take place at any liquid
pressure difference is the controlling factor in dri
cent. temperature between its saturation temperature
evaporation and also condensation of water; or fro
If the actual inside relative humidity were and the dew-point temperature of the surround-
we may say that the dew-point temperature lon
25 percent by actual measurement by a hy- ing air. (Free surface means the interface be-
of the air above the liquid is the controlling uall
grometer, the enthalpy at 72°F and 25 percent tween the liquid surface and the surrounding
factor. rate
relative humidity would be, hra = 21.7 Btu/lb air.) Boiling takes place both at the liquid free
Consider an open pan of water, such as Fig.
da, 'with the additional moisture coming from surface and within the body of the liquid and
5-9a, setting in a room where the air tempera- is p
hygroscopic materials and people in the area. can occur only at the saturation temperature
The additional energy 21. 7 - 18. 7 = 3.0 ture is 74°F and the relative humidity is 40 per- 9b),
corresponding to the absolute pressure on the
cent; the corresponding dew-point temperature air
Btu/lb da, which is 16 percent, must come liquid.
from the heating system. is the saturation temperature of the moisture due
Water left standing in a pan open to the at-
vapor at its vapor pressure, Pv = <I> X Pvs = Eve
If a humidification system is used and mois- mosphere (Fig . 5-9a) will eventually evaporate
ture added to achieve a comfortable 35 percent completely, even though the actual water tem- 0.40 x 0.8462 = 0.3385 in. Hg. The dew- esta
point temperature at 0.3385 in. Hg (Table 4- and
relative humidity, the enthlllpy at 72°F and 35 perature is below its saturation temperature.
percent relative humidity is 23 .6 Btu/lb da, However, if the open pan is placed inside of a 1) is 48 .2°F. Although the water temperature orati
in the pan could fall to the wet-bulb tempera- the
which is only (23.6 - 21.7)/21.7 = 8.0 per- closed container, as shown in Fig. 5-9b, only
cent increase over the "inevitable" energy a portion of the water will evaporate; the bal- ture (tw = 58 .8°F) of the surrounding air, it cont
will in a case such as this probably assume a the
load of 21.7 Btu/lb da. This is substantially ance will remain in the pan for an indefinite
temperature that is closer to the air dry-bulb the a
less than (23 .6 - 18.7)/ 18.7 = 26 percent, length of time if the closed container remains
temperature (t = 74°F). Assume, for purposes F:
which is the theoretical increase from 9.0 per- sealed. The reason for this difference in behav-
of discu~ion, that the water assumes a temper- ature
cent relative humidity and 35 percent relative . ior is found in the difference between the va-
ature df 65°F. The vapor pressure correspond- point
humidity . por pressure of the water in the pan and the
ing to the air dew point was 0.3385 in. Hg. At air d
If the inside air temperature were only 68°F pressure exerted by the vapor pressure of mois-
the same time the vapor pressure of the water evap
at 65°F is 0.6222 in. Hg. Since the vapor pres- T
sure of the surrounding air is less than that of laten
t infonnation extracted from Trane Air Conditioning Manual, The Trane Company , LaCrosse, Wisconsin,
the water, evaporation of the water into the air result
1965, with pennission .
will occur. wate
APPLIED PSYCHROMETRIC$ 179
at 35 percent relative humidity (because people
can be more comfortable at a lower tempera-
ture with higher humidity levels), the enthalpy
is only 21.8 Btu/lb da , which is a very slight
increase21.8- 21.7 = 0. 1 Btu/lbdaine•
ergy. In many cases there will be a decreas~ in
the required energy.
The introduction of water into the air for
purposes of humidification is relatively easy
and can be accomplished with rather simplified
equipment. However, before we introduce this
---
equipment, we will discuss briefly the princi-
ple of vaporization of a liquid. (a) (b)
Vaporizationt of a liquid, such as water, Figure 5-9
may take place in two different ways: (1) by
Evaporation of water
evaporation and (2) by boiling. Evaporation of
a liquid can occur only at the free surface of ture in the air in the sealed container. Vapor This difference in vapor pressure is the
the liquid and may take place at any liquid pressure difference is the controlling factor in driving force that causes the vapor to diffuse
temperature between its saturation temperature evaporation and also condensation of water; or from the liquid surface into the air above. As
and the dew-point temperature of the surround- we may say that the dew-point temperature long as the air currents above the liquid contin-
ing air. (Free surface means the interface be- of the air above the liquid is the controlling ually carry away the moisture being evapo-
tween the liquid surface and the surrounding factor . rated , evaporation will continue.
air.) Boiling takes place both at the liquid free Consider an open pan of water, such as Fig . On the other hand, when the pan of water
surface and within the body of the liquid and 5-9a, setting in a room where the air tempera- is placed inside the closed container (Fig. 5-
can occur only at the saturation temperature ture is 74°F and the relative humidity is 40 per- 9b), the pressure of the vapor mixed with the
corresponding to the absolute pressure on the cent; the corresponding dew-point temperature air in the container is continually increasing
liquid. is the saturation temperature of the moisture due to the water evaporating from the pan.
Water left standing in a pan open to the at- vapor at its vapor pressure, Pv = <I> X Pvs = Eventually , vapor pressure equilibrium will be
mosphere (Fig . 5-9a) will ev~ntually evaporate 0.40 X 0.8462 = 0.3385 in. Hg. The dew- established when the vapor pressure in the air
completely, even though the actual water tem- point temperature at 0.3385 in. Hg (Table 4- and of the water are equal and no further evap-
perature is below its saturation temperature. 1) is 48.2°F. Although the water temperature oration takes place. When evaporation ceases,
However, if the open pan is placed inside of a in the pan could fall to the wet-bulb tempera- the dew-point temperature of the air inside the
closed container, as shown in Fig. 5-9b, only ture <tw = 58.8°F) of the surrounding air, it container will be equal to the temperature of
a portion of the water will evaporate; the bal- will in a case such as this probably assume a the water in the pan. Under these conditions
ance will remain in the pan for an indefinite temperature that is closer to the air dry-bulb the air is said to be satu¥tted.
length of time if the closed container remains temperature (t = 74°F) . Assume, for purposes From this, it is apparent that if the temper-
sealed. The reason for this difference in behav- of discussion, that the water assumes a temper- ature of the water is greater than the air dew
ior is found in the difference between the va- ature of 65°F. The vapor pressure correspond- point, evaporation takes place; and when the
por pressure of the water in the pan and th ing to the air dew point was 0.3385 in. Hg. At air dew point is equal to the water temperature,
pressure exerted by the vapor pressure of mois- the same time the vapor pressure of the water evaporation ceases.
at 65°F is 0.6222 in. Hg. Since the vapor pres- The evaporation of a liquid requires that the
sure of the surrounding air is less than that of latent heat of vaporization be supplied. As a
Manual , The Trane Company, LaCrosse, Wi scon~i n , the water, evaporation of the water into the air result of the water evaporation into the air, the
will occur. water remaining tends to cool as it surrenders
180 APPLIED PSYCHROMETRICS
nozzles
application. A fourth medium, wetted element posits a
the necessary latent heat from vaporization. In where the water is continually recirculated
humidifiers, applies primarily to private resi- capac it)
the preceding discussion of the pan of water, it being neither heated nor cooled externally, the
dences or similar small buildings where very ersare
has been assumed that heat would flow from temperature of the spray water does not change
low humidifying capacities are required (see the hea
the surrounding air into the water, as no insu- because there is no addition or removal of heat
lation was indicated. As a result, even tho!Jgh from the system. The latent heat required for Figs. 5-10, 5·11). additivt
Steam is ready-made water vapor that needs
the water tends to cool slightly, its temperature evaporation of water comes from the sensible the wa
only to be mixed with the air. With evapora-
remains nearly constant because of heat flow heat in the air, which causes a reduction in air by as -r
tive pan humidification, air flows across the
into it from the surrounding air. dry-bulb temperature.
surface of heated water in a pan and absorbs Respor
In order to humidify air with water sprays,
the temperature of the spray water must always
the water vapor. Both steam and evaporative ~
S-6 HEAT EXCHANGE BETWEEN
pan humidification are essentially isothermal with tl
AIR AND WATERt be higher than the required final dew point of
processes . where little change in air tempera- tern. I
the air. Such an amount of water must be used
When air is brought in contact with water at ture occurs. with 1
that, as the water cools down from its initial
a temperature different from the air wet-bulb Water spray humidification is an adiabatic where
temperature, its final temperature will still be
temperature, an exchange of heat, as well as process if evaporation of the water is caused humid
above the required final air dew point. It is
moisture, will take place between the air and by the water absorbing sensible heat from the
also necessary to remember that, besides the Contr
water. air reducing the air dry-bulb temperature. The
relationship between the final air dew-point types
latent heat of evaporation reduces the sensible
1. If the water temperature is higher than temperature and the water temperature, the ex- contr•
heat of the air by about 1000 Btu for each
the air wet-bulb temperature, the water change of heat and moisture between air and space
temperature will drop and the air wet- water depends upon the air dry-bulb and wet- pound of water evaporated.
Let us examine the basic requirements for air d1
bulb temperature will rise because the bulb temperatures. pan
effective humidification and see how each of
water surrenders heat to the air. spon:
the humidifying media satisfies these require-
S-7 METHODS OF midi·
2. If the water temperature is lower than ments.
HUMIDIFICATIONt spra~
the air wet-bulb temperature, the water
Capacity. Small-capacity requirements can be face
temperature will rise and the air wet- If you are humidifying a hospital operating
economically with evaporative pan mete
bulb temperature will drop. room, obviously your design criteria are differ-
or self-contained steam-generating unit humid- coot
ent than those for hurhidifying a textile mill,
3. In any exchange of heat between water ifiers, installed either in the air-handling sys- · ' troll
an office building, a laboratory, or a home.
and air, the water temperature can never tem or individually within the area(s) to be any'
Different types of operations have substantially
fall, or rise, to the initial air wet-bulb humidified . Larger-capacity needs , depending mid
different requirements for the achievement of
temperature. on the application, can best be met by either syst
proper relative humidity. These requirements
water spray or steam humidification systems,
4. Whenever an exchange of heat occurs determine what means of humidification you
which may be installed either in nonducted in- San
between air and water, the temperature should use.
dustrial applications or in air-handling sys- ste~
of both must change. Three basic humidifying media are avail-
tems . As a rule, steam humidification can pro- me•
able: steam, evaporative pan, and water spray.
vide ~arger capacities than water spray units. sati
There is one important exception to item 4 Each has particular advantages and limitations
tiOJ
ubove. ln air washers, to be discussed later, which determine its suitability for a particular Maitftenance . Steam humidification systems
ba<
are largely maintenance free. Maintenance re·
ste
quirements for both water spray and evapora- ifi(
tive pan humidification depend on fi1ineral con·
tlnformation extracted from Trane Air Conditioning Manual, The Trane Company , LaCrosse, Wisconsin , ef
tent of the water. With water spray equipment
1965, pp. 69- 76, with permission . mi
minerals dispersed in the water mist settle out
tExtructcd from The Armstrong Humidification Handbook, Armstrong Machine Works , Three Rivers, Mich- W
as dust when the droplets evaporate . Spray
i2an , pp . 12 15, with permission .
~~
~ APPLIED PSYCHROMETRICS 181

application. A fourth medium, wetted element nozzles can become clogged with mineral de-
humidifiers, applies primarily to private resi- posits and require regular cleaning to maintain
dences or similar small buildings where very capacity. Similarly, evaporative pan humidifi-
low humidifying capacities are required (see ers are subject to "liming up," particularly on
• ' Figs. 5-10, 5-11).
Steam is ready-made water vapor that needs
the heating coils in the pan, although chemical
additives automatically or manually added to
only to be mixed with the air. With evapora- the water in the pan can reduce this problem
tive pan humidification, air flows across the by as .much as 50 percent.
surface of heated water in a pan and absorbs
the water vapor. Both steam and evaporative Response to control. Since steam is ready-
pan humidification are essentially isothermal made water vapor, it needs only to be mixed
processes . where little change in air tempera- with the air to satisfy the demands of the sys-
ture occurs. tem. Response to control is much faster than
Water spray humidification is an adiabatic with either water spray or evaporative pan
process if evaporation of the water is caused where evaporation must take place before
' humidified air can be circulated.
by the water absorbing sensible heat from the
air reducing the air dry-bulb temperature. The Control of output. Operation of the three basic
latent heat of evaporation reduces the sensible types of systems is regulated by a humidity
heat of the air by about 1000 Btu for each controller (hygrostat) located either in the
pound of water evaporated. space humidified or in the return air duct of an
Let us examine the basic requirements for air duct system. Water spray and evaporative
effective humidification and see how each of pan equipment operate intermittently in re-
the humidifying media satisfies these require- sponse to control. Output for these types of hu-
ments. midifiers is determined by size and number of
t Capacity. Small-capacity requirements can be spray nozzles or by water temperature and sur-
met most economically with evaporative pan face area, respectively. Steam humidifiers can
or self-contained steam-generating unit humid- meter the output by means of a modulating
ifiers, installed either in the air-handling sys- control valve in response to the humidity con-
tem or individually within the area(s) to be troller, by positioning the humidifier operator
humidified. Larger-capacity needs, depending anywhere from closed to fully open. Steam hu-
on the application, can best be met by either ~idifiers can thus respond more precisely to
water spray or steam humidification systems, system demand than can the other two types.
which may be installed either in nonducted in-
Sanitation. The high temperatures inherent in
dustrial applications or in air-handling sys-
steam humidification make it virtually a sterile
tems. As a rule, steam humidification can pro-
medium. Assuming boiler makeup water is of
vide larger capacities than water spray units.
satisfactory quality, and there is no condensa-
Maintenance. Steam humidification systems tion, dripping or spitting in the air ducts, no
are largely maintenance free. Maintenance re- bacteria or odors will be disseminated with
quirements for both water spray and evapora- steam humidification. Evaporative phn humid~
tive pan humidification depend on 111ineral con- ifiers can sustain bacteria colonies in the res-
tent of the water. With water spray equipment ervoir and distribute them throughout the hu-
minerals dispersed in the water mist settle out midified space. High water temperatures,
as dust when the droplets evaporate. Spray water treatment, and regular cleaning and
Constant steam supply'-,.

~ n-:;:;~~.

l•o 0 0 0 0 0 : 4® valve

'\Steam jacketed Condensate


dispersion manifold separator

Cross-section of manifold

FIG. A-13-STEAM METHOD

Water vapor
Steam, hot water
or electricity in

......... Auto valve

Water pan/

FIG. B-13- EVAPORATIVE PAN METHOD

Heat taken from air


to evaporate moisture ~

pressure

FIG. C-13- WATER SPRAY METHOD

Figure 5-10

Humidification methods: (a) using


dry steam (b) Using evaporated
watar lc\ Ualnn flnrav wat&r
APPLIED PSYCHROMETRICS 183
where the water is continually ·recirculated
being neither heated nor cooled externally, the flushing of the humidifier help to minimize the ter, steam, electricity, and so forth, close to
temperature of the spray water does not chang problem, however. Water spray systems can the humidifiers can vary greatly between jobs.
because there is no addition or removal of heat distribute large amounts of bacteria and can Operating costs are similar between the three
from the system. The latent heat required for present odor problems in air-handling systems. types, although they are insignificant compared
evaporation of water comes from the sensib,c Drip· from spray nozzles and unevaporated wa- to heating and cooling system costs .
heat in the air, which causes a reduction in ~ir ter discharge can collect in ducts , around Maintenance costs vary widely with water
dry-bulb temperature. drains and drip pans, and on eliminator plates, spray and to a lesser degree with evaporative
In order to humidify air with water sprays, encouraging the growth of algae and bacteria. pan equipment, requiring substantially more
the temperature of the spray water must always maintenance than steam humidification. Table
Corrosion. Whenever -liquid moisture is pres-
be higher than the required final dew point of 5-1 summarizes the capabilities of each type.
ent in a humidification system, corrosion can
the air. Such an amount of water must be used be a problem. Since steam and evaporative pan
that, as the water cools down from its initial RECOMMENDED APPLICATIONS:
humidifiers are designed to discharge only wa-
temperature , its final temperature will still be ter vapor, corrosion in ductwork is not a prob- Steam. Recommended for virtually all com-
above the required final air dew point. It is lem. Evaporative pan units are subject to corro- mercial, institutional, and industrial applica-
also necessary to remember that, besides the sion and deterioration, the severity of which tions . Where steam is not available, small-ca-
relationship between the final air dew-point depends on materials of construction and fre- pacity needs up to 50 to 75 lb/hr can be met
temperature and the water temperature, the ex- quency of cleaning. Steam units are largely self- best using self-contained steam-generating
change of heat and moisture between air and cleaning; scale or sediment, whether formed in units; above this capacity range, central system
water depends upon the air dry-bulb and wet- the unit or entrained in the supply steam, are steam humidifiers are most effective and eco-
bulb temperatures.
drained from the humidifier through the drain nomical. Steam should be specified with cau-
trap. Water spray humidifiers and all duct- tion where humidification is being used in
5-7 METHODS OF
work, eliminator plates, and so forth in prox- small, confined areas to add large amounts of
HUMIDIFICA TIONt
imity to them are highly susceptible to corro- moisture to hygroscopic materials.
If you are humidifying a hospital operating sion.
room , obviously your design criteria are differ- Evaporative pan . Recommended only as an
Costs. Evaluation of costs in selecting a hu- alternative to self-contained steam-generating
ent than those for humidifying a textile mill , midification system should include installation,
an office building, a laboratory, or a home. unit humidifiers for small commercial or insti-
operating and maintenance costs, as well as tutional applications . Generally not recom-
Different types of operations have substantially first cost. However, total humidification costs
different requirements for the achievement of mended where load requirements exceed 50 to
should run far less than heating or cooling sys- 75 lb/hr.
proper relative humidity. These requirements
tem costs.
determine what means of humidification you First costs, of course, vary with the size of Water spray. Recommended for industrial ap-
should use .
the units. Priced on a capacity basis, larger- plications where evaporative cooling is re- '
Three basic humidifying media are avail- capacity units are the most economical, regard- quired; typical application is summer time hu-
able: steam, evaporative pan, and water spray . less of the types of humidifier; that is, one hu- midification of textile mills in southern United
Each has particular advantages and limitations midifier capable of delivering 1000 lb of hu- States.
which determine its suitability for a particular midification per hour costs less than two 500- A fourth medium, mentioned previously, is
lb/hr units of the same type . wetted element humidifiers. These units are
Of the three basic humidification media, recommended for private residences, or similar
steam humidifiers will provide the highest ca- small buildings where very low humidifying
:Manual, The Trane Company, LaCrosse, Wisconsin,
pacity per first-cost dollar; water spray is next, capacities are required. Figure 5-11 represents
lbook, Armstrong Machine Works, Three Rivers, Mich- and evaporative pan is the least economical, a humidifying device which exposes a large
assuming capacity needs are 75 lb/hr or more. wetted surface to an airstream. The unit shown
Installation costs for the three types cannot would be mounted in the warm airstream in a
be accurately formulated, as availability of wa- duct system. The unit consists of a series of
184 APPLIED PSYCHROMETRICS

Table 5-1
Comparison of Humidification Methods*
Evaporative
Steam Pan Water Spray

Effect on air Virtually no Small temperature Substantial temperature


temperature change rise drop (if no heating
of spray water)

Unit capacity per unit Small to very Small Small


size large

Maintenance frequency Annual Weekly to Weekly to bimonthly


monthly

Response to control Immediate Slow Slow

Control of output On-off or full On-off On-off


range
modulation Figure 5-11
Wetted element humldlfiel
Sanitation/Corrosion Sterile medium; Pan subject to Subject to severe
AIRE {Courtesy of Har
corrosion corrosion; corrosion and Humidity, Inc.)
free bacteria can be bacteria problems
present

Cost: Price (per unit of Low High Low to medium


capacity)
Installation Varies with availability of steam, water, electricity, etc.
Operating Low Low Low
Maintenance Low High Very high
~---
Breaker comb
*Reproduced from The Armstrong Humidification Handbook, Armstrong Machine Works, Three Rivers, Michigan , with
permission.

rotating, alloy metal, screened disks rotated at tion is quite simple. The motor section, sealed
slow speed (2 rpm) by a small electric motor against water, drives both disk and pump tube.
drive. The disks rotate in a bath of water in the Water is drawn from the reservoir through the
pan where water is picked up and held in the pump tube and is placed on top of the rotating
mesh of the screen by surface tension. The disk. The water is cast centrifugally against the
wetted disks rotate into the airstream, present- breaker comb, which in tum atomizes the wa-
ing a large surface area for water evaporation. ter. Primary air enters the disk and picks up •
The disks rotate only when humidification is the water particles and produces partial evapo-
Figure 5-12
called for by the humidity control system. ration. This partially vaporized water is then
Figure 5-12 represents a type of humidifier introduced either into the space or the duct The Walton Atomizer {
which breaks up a stream of water into a fine where the surrounding air completes the evap- Walton Laboratorlet
mist by throwing it against a breaker. Opera- oration process.
185
able 5-1
lumldlflcatlon Methods*
Evaporative
Pan Water Spray

Small temperature Substantial tCIIIIM'IIItiU r


rise drop (if n() hrul lu
of spray wulrr)

S,.mall Small

Weekly to Weekly to bimnnllrl


monthly

Slow Slow

On-off On-off

Figure 5-11
Pan subject to Subject to sev, Wetted element humidifier, HUMID-
corrosion; corrosion ami AlAE (Courtesy of Hamilton
bacteria can be bacteria prohl• m Humidity, Inc.)
present

High Low to medium

with availability of steam, water, electricity, etc.


Low Low
High Very high

dbook, Armstrong Machine Works, Three Rivers, Mlrlr/•11!1 Breaker comb

at tion is quite simple. The motor section, •


:or against water, drives both disk and pumr 1111
he Water is drawn from the reservoir throu11lr 1!1•
he pump tube and is placed on top of the "'-llllill
he disk. The water is cast centrifugally aaalnNI llrt
Disc
1t- breaker comb, which in turn atomize• th
m. - ter. Primary air enters the disk and pi
is the water particles and produces partial
ration. This partially vaporized water I Figure 5-12
ier introduced either into the space or th
.ne where the surrounding air cdmpletes th The Walton Atomizer (Courtesy
Walton Laboratories, Inc.)
ra- oration process.
185
Illustrative Problem S-6 downstream from humidifier.
Given in the problem, W2 = 70
An evaporative pan type humidifier is to be grains/lb da. The final air condi-
used in a duct system to humidify the air sup- · tion must lie on the constant hu-
plied to a building. The supply air upstream of midity ratio line w2. The quantity
the humidifier has a dry-bulb temperature of of air passing through system is
90°F and a wet-bulb temperature of 58°F. The from Eq . (4-7),
downstream air leaving the pan humidifier
must have a humidity ratio of 70 grains/lb da. cfm X 60 8000 X 60
The quantity of air flowing through the duct ma =
VI 13 .92
upstream of the humidifier is 8000 cfm. If the
water in the pan is maintained at 212°F by a rna = 34,480 lb/hr
steam immersion coil, determine the follow-
ing: (a) moisture addition to the air and (b) re- The quantity of moisture added to each pound 88.5-
sulting psychrometric properties of the air of air is w2 - WI = 70 - 21 = 49 grains/
Figures-·
downstream from the humidifier. lb da or 0.007 lb vapor/lb da. The heat added
to each pound of air by the evaporating water Solution for Ex81
Solution: is (W2 - W 1)hw, where hw is the enthalpy of
the evaporating water; in this case hw = h8 at With h 2 = 32.95 Btu/lb da and W2 = 70 g1
Step 1: Sketch the equipment.
212°F and 14.696 psia and is 1150.5 Btu/lb grains/lb da on Fig. 5-14, find t 2 = 91°F, t w2 vt
Step 2: Determine initial condition u? air steam. = 68 .8°F. (ans) tu
upstream of humidifier. Locate A straight line on Fig. 5-14 joining points 1 tl1
point 1 on psychrometric chart, Heat added to air/lb air = (4917000)( 11 50.5) and 2 represents the humidifying process. rr
Fig. 5-14 at tl = 90°F, twl =
\ 58°F. From the chart find W1 =
= 8.05 Btu/lb air Step 4: Total moisture added to the air.
The total moisture added to the
21 grains/lb da, h 1 = 24.9 Btu/lb
The enthalpy of air leaving the humidifier air determines the manufacturer's
da, and V1 = 13 .92 fe/lb da.
must be h2 = h 1 + enthalpy addition .,. 24.9 rating of the humidifier, and for
Step 3: Determine final condition of air + 8.05 = 32.15 Btu/lb da. this problem is ma(W2 - WI) -
: 3tl-'l!
2 Pounds/hr moisture
Heated = 34,480 ( 70 - 21) = 241 lb/hr (ans)
Heated hum idified 7000
dry ai r ai r

Illustrative Problem 5-7


)
Atomizing spray-type humidifiers (similar ·
to Walton atomizers-Figure 5-12) are to~ be
installed in a space within a building where the
Makeup water
totar air circulation rate is 8000 cfrp and the
in~ide air is 70°F DB and 50 percent RH .
Figure 5-13 Fresh outside air is to be heated and introduced
Schematic: Open-pan humidifier to the space at the rate of 1500 cfm. The
(Illustrative problem 5-6) heated outside air has a humidity ratio of 11
APPLIED PSYCHROMETRICS 187

downstream frpm humidifier.


Given in the problem, W2 = 70
grains/lb da. The final air condi-
tion must lie on the constant hu-
midity ratio line W2 • The quantity
of air passing through system ·is w
~
from Eq. (4-7),

cfm X 60 8000 X 60 1-'-----+--


tw 2
= 70
ma =
VI 13.92
ma = 34,480 lb/hr
I
--- ft'5a 1 w, = 21
The quantity of moisture added to each pound 90
of air is w2 - WI = 70 - 21 = 49 grains/
Figure 5-14
lb da or 0.007 lb vapor/lb da. The heat added
to each pound of air by the evaporating water Solution for Example 5-6
is (W2 - Wdhw, where hw is the enthalpy of
the evaporating water; in this case hw = h8 at With h2 = 32.95 Btu/lb da and W2 = 70 grains/lb da. The space is heated by steam con-
212°F and 14.696 psia and is 1150.5 Btu/lb grains/lb da on Fig. 5-14, find t 2 = 91°F, tw2 vection units. Determine the amount of mois-
steam. = 68.8°F. (ans) ture to be added to the space air to maififain
A straight line on Fig. 5-14 joining points 1 the desired space temperature and relative hu-
Heat added to air/lb air = (4917000)(1150.5) and 2 represents the humidifying process. midity.
= 8.05 Btu/lb air Step 4: Total moisture added to the air.
Solution:
The total moisture added to the
The enthalpy of air leaving the humidifier air determines the manufacturer's Step 1: Establish known conditions for
must be h2 = h 1 + enthalpy addition = 24.9 rating of the humidifier, and for points on psychrometric chart,
+ 8.05 = 32.15 Btu/lb da. this problem is ma(W2 - WI) . Figure 5-15. The space air con-
:::: 3'l·'1! dition (ra) may be established at
2 Pounds/hr moisture 70°F DB and 50 percent RH. At
70 - 21) this point find lwra = 58SF WB,
Heated
humidified
= 34,480 ( 7000 = 241 lb/hr (ans) Wra = 55 grains/lb da, and Vra =
air 13.51 fe/lb da. Also, establish
the humidity ratio of the outside
Illustrative Problem 5-7
ventilation air (oa) as W08 = 11
grains/lb da.
Atomizing spray-type humidifiers (similar
to Walton atomizers-Figure 5-12) are to be Step 2: Construct the space wet-bulb tem-
installed in a space within a building where the perature line on the chart and ex-
Makeup water
total air circulation rate is 8000 Cfrp and the tend downward and to the right
inside air is 70°F DB and 50 percent RH . until it intersects with the humid-
ure 5-13 Fresh outside air is to be heated and introduced ity ratio of the outside air (W0 a =
pen-pan humidifier to the space at the rate of 1500 cfm. The 11 grains). This point of intersec-
1ve problem 5-6) heated outside air has a humidity ratio of 11 tion is the dry-bulb temperature to
_ _ . ·~· ·· · - ·- - , -, -· '' '""'•''- • n•vo

q, = qL = 42,S80 = 0.244 (3S,2S6)(ilt) draw


Llt = 4.9S°F the f;
Fi.
This checks the sop value found in Step 3. air-h;
point
w 5-8 COMBINED HEATING AND
throu

t HUMIDIFICATION OF AIR
During cold weather it may be necessary to
-and/o
flow :
..J11G- --· I Wra =55 provide for both heating and humidification of
air to be circulated in a building to maintain
I II ~-.
1
I woa = 11 comfort conditions. The heated air must be in-
troduced into the space to be conditioned at a
70 75 98
sufficiently high dry-bulb temperature and hu-
Figure 5-15 midity ratio to offset heat losses and to main-
when
tain a satisfactory humidity condition.
Solution for Example 5-7 or the
Figure S-16 is a typical heating and venti-
and l
lating air-handling unit. The unit consists of
moist!
several sections: a mixing box section where
which the outside air must be pre- midification. The dry-bulb temperature of the Sir
return air from the conditioned space is mixed
heated before introducing to the space is to be 70°F; therefore, the S°F differ-
with outside air for ventilation in a fixed or ffla an
space, toa = 98°F DB, twoa = ence ? S - 70) cooling of the air represents
variable ratio which is adjusted by damper po-
S8 .S WB, and V08 = 14.09 ft 3/lb the sensible heat required to evaporate the
da. sition, a heating coil and humidifier section,
moisture from the humidifiers.
and a fan section . The unit shown is called a
Step --3-: The outside air at the condition Step 4: The moisture addition to the space
found in Step 2 is mixed with may be found from Return air
space air found in Step 1: Steam , hot w;
Moisture addition = ma08 (Wra - WoJ electrici1
mara X tra + fflaoa X toa
tmix
mara + maoa

mara = 6500 X 60
13.51
= 2 8,868 lb!hr Moisture addition = 40.1S lb/hr Mixing
box
air
1500 X 60 Latent heat required to evaporate water is
maoa = 6388 lb/hr equal to the mass of water times the latent heat
14.09
of evaporation, or h18 at S8.S°F, which is
28,868 X 70 + 6388 X 98 1060.S Btu/lb (Table A-1).
tmix = 28,868 + 6388

tmix = 7S°F Latent heat (qL) = 40.1S x 1060.S • Filter

42,S80 Btu/hr
In Fig . S- IS find the point of intersection be- Figure 5-16
tween tmlx = 7S°F DB and twmix = S8.S WB . This latent heat is supplied by the space air as Schematic: Typical hea
This is the condition of the space without hu- it cools to space conditions from tmix = 7S°F. humidifying unit
,.,

q3 = qL. = 42,S80 = 0 .244 (3S,2S6)(~t) draw-through unit because of tho lncullon ol


~t = 4.9S°F the fan with respect to the other cornJX>ncnts.
Figure S-17 is a generalized sketch of an
This checks the sop value found in Step 3. air-handling system where moist air enters at
i point 1 and leaves at point 2. As the air passes

/50% w
t •
S-8 COMBINED HEATING AND
HUMIDIFICATION OF AIR
through the system, it may have sensible heat
and/or moisture added. The system is a steady-
flow system and the following equations apply:

- During cold weather it may be necessary to

~I
e I Wra =55 provide for both heating and humidification of rna,hl + ,q.2 + rnwhw = rna2h2 (5-18)
= 58.5 air to be circulated in a building to maintain
oa 1
comfort conditions. The heated air must be in- rna, = ma2 (5-19)
~--~~==:=t-W = 11
75 98 oa troduced into the space to be conditioned at a
sufficiently high dry-bulb temperature and hu- rna 1W 1 + rnw = rna 2W2 (5-20)

1ure 5-15 midity ratio to offset heat losses and to main-


where mw is the pounds of water evaporated,
tain a satisfactory humidity condition.
lor Example 5·7 or the pounds of vapor (steam) added per hour,
Figure S-16 is a typical heating and venti-
and hw is the corresponding enthalpy of the
lating air-handling unit. The unit consists of
moisture added in Btu/lb of moisture. ,
several sections: a mixing box section where
midification. The dry-bulb temperature of the Since rna 1 = rna 2, we divide Eq. (S-18) by
return air from the conditioned space is mixed
e space is to be 70°F; therefore , the S°F differ- with outside air for ventilation in a fixed or rna and we have
ence (7S - 70) cooling of the air represents variable ratio which is adjusted by damper po-
b the sensible heat required to evaporate the
moisture from the humidifiers .
sition, a heating coil and humidifier section, h, + ~ + rn~w = h2 (5-21)
and a fan section. The unit shown is called a ma ma
Step 4: The moisture addition to the space
may be found from Return air

Steam. hot water , or


Moisture addition = rnaoa (Wra - WoJ electricity

= 6388 ( ss7~11)
Moisture addition = 40. 1S lb/hr Mixing '
box
air
Latent heat required to evaporate water is
equal to the mass of water times the latent heat
of evaporation, or h18 at S8 .S°F, which is
1060.S Btu!lb (Table A-1).
Steam
Filter humidifier
Latent heat (qL) = 40.1S X 1060.S =
42,S80 Btu/hr '•
Figure 5-16

This latent heat is supplied by the space air as Schematic: Typical heating,
it cools to space conditions from tmix = 7S°F. humidifying unit
190 APPLIED PSYCHROMETRICS

m heat from the air to provide the latent heat for 3000 cfm at a barometric pressure of 29.92 in. St
m., "2
t, vaporization . This is the process used to cool Hg. While passing through the chamber, the
t2
and humidify air with recirculated spray water air absorbs sensible heat at the rate of 153,000
w, w2
in an air washer with no external heating or Btu/hr and picks up 83 lb/hr of saturated steam
h, h2
- .- cooling of the spray water. The process is . at 230°F. Determine the dry-bulb and wet-bulb
I \ called evaporative cooling , to be discussed temperatures of the air leaving the device . w2 =
later.
mw , hw
\ By solving Eq. (5-23) for rnaand substitut- Solution (Method 1 ):
ftlllillh latent
ing into Eq . (5-22) and rearranging terms , we
Figure 5-17 (See Figure 5-18)
have
Schematic: Device for heating Step 1: Determine psychrometric proper- W2 =
humidifying air ties of air at initial condition. On
fl.h = h2 - h1 = I~S2 + hw
psychrometric chart (Fig. 5-18), or
!l.W w2 - WI mw
at 40°F DB and 35°F WB find v1
Also, from Eqs. (5-18) and (5-19) we have lqS2 + mwhw
= 12.64 felda , W1 = 22 grains/ W2 =
"\,. (5-26) lb da, h 1 = 13.0 Btu/lb da.
fflw
lqs2 = maCh2 - hi) - mwhw (5-22)
Step 2: Determine mass of air flowing .
Equation (5-26) defines the enthalpy-humidity From Eq. (5-7) . Fron
and from Eq. (5-20) we have
ratio where:
= cfm X 60 3000 X 60 ,
fflw maCW2 - WI) (5-23)
1. The rate of air flow has disappeared. mal = ffla2 = = 12.64
VI

Substitution of Eq. (5-23) into Eq. (5-21) 2. The ratio !l.hl!l.W is the slope of a line 14,240
gives on the psychrometric chart related only ffl 0 = 14,240 lb/hr or --
60 f
to the total space load and the moisture =I
added. = 237.3 lb/min
h1 + ~+ (W2 - W1)hw = h2 (5-24)
ma 3. If the condition of the air at point I or
point 2 is set, the values of h and W for
Equation (5-24) is the general equation which the other point may be allowed to vary
states that the enthalpy of the air leaving, h2, but must always be on a straight line on
is equal to the enthalpy of the air entering, h~> the psychrometric chart having a slope
plus the sensible heat added plus the latent heat of !l.hl!l. W.
added by the moisture.
If the process were adiabatic ( 1q,2 = 0), Some psychrometric charts include an
then Eq . (5-24) becomes alignment quadrant which gives various values
of !l.h!!l.W which provides a means for deter-
h1 + (W2 - W1)hw = h2 (5-25) mining the direction of heating and humidify-
ing process line on the chart. The following
In the process represented by Eq. (5-25), ide- example illustrates the process.
ally the air entering at point I is brought to its •
"temperature of adiabatic saturation," com- 86
monly known as the " thermodynamic wet- Illustrative Problem 5-8 Figure 5-
bulb temperature" (see Section 4-14). The
process represents cooling of the air at con- Moist air at 40°F DB and 35°F WB enters a Solutlon for Exampl
No. 1)
stant wet bulb as the water absorbs sensible heating and humidifying device at the rate of
APPLIED PSVCHROM! llliC~ '191

hrtll from the air to provide the latent heat tor 3000 cfm at a barometric pressure of 29.92 in. Step 3: Determine psychrometric pmpl'l
vuporlzation. This is the process used to cool Hg . While passing through the chamber, the ties of air at the final condition .
1nd humidify air with recirculated spray water air absorbs sensible heat at the rate of 153,000 From Eq. (5-20)
In an air washer with no external heating or Btu/hr and picks up 83 lb/hr of saturated steam
ooling of the spray water. The process is at 230°F. Determine the dry-bulb and wet-bulb
called evaporative cooling, to be discussed temperatures of the air leaving the device . Wz = WI + fflw
-
later. ffla
By solving Eq . (5-23) for rna and substitut- Solution (Method 1 ): 22 83
g into Eq. (5-22) and rearranging terms ,· we =--+--
(See Figure 5-18) 7000 14,240 '
Step 1: Determine psychrometric proper- W2 = 0 .00898 lb vapor/lb da
!lh q52 + ties of air at initial condition. On
- = hz - hi hw
= 1
!lW Wz- WI fflw psychrometric chart (Fig. 5-18), or
at 40°F DB and 35°F WB find v 1
IqS2 + mwhw = 12.64 felda, WI = 22 grains/ W2 = 0 .00898 X 7000
(5-26)
fflw lb da, h1 = 13 .0 Btu!lb da.
= 62.86 grains/lb da (ans)
Step 2: Determine mass of air flowing.
Equation (5-26) defines the enthalpy-humidity From Eq. (5-7).
ratio where: From Eq. (5-21)
cfm X 60 3000 X 60
1. The rate of air flow has disappeared. mal = fflaz = = 12.64 " hz = hI +~
, + mwhw
--
VJ
ma ffla
2. The ratio !lh!!lW is the slope of a line 14,240
on the psychrometric chart related only ma = 14,240 lb/hr or - -
60 _From Table A- 1 hw at 230°F = hg at 230°F
to the total space load and the moisture
added. 237.3 lb/min = 1157.1 Btu!lb steam

3. If the condition of the air at point I or


point 2 is set, the values of h and W for ~,

the other point may be allowed to vary


but must always be on a straight line on
the psychrometric chart having a slope
of llh!!lW.
w
Some psychrometric charts include an
alignment quadrant which gives various values
of !lh!!lW which provides a means for deter-
t
mining the direction of heating and humidify- W2 = 62.8
ing process line on the chart. The following
example illustrates the process . -~~
-w, = 22
86
Illustrative Problem 5-8
Figure 5-18
Moist air at 40°F DB and 35°F WB enters a Solution for Example 5-8 (Method
heating and humidifying device at the rate of No.1)
192 APPLIED PSYCHROMETRieS

0-~ ~
h2 13 .00 + 153,000 + 83 X 1157.1 Solution: (Method 2): (See Figure 5-19.) line between . the alignment circle
14,240 14,240 and a SHR value of 0.614. Paral-
Step 1: Determine the sensible-heat ratio lel to this construction line draw .t,
h2 = 13.00 + 10.74 + 6. 74 (SHR) for the heating and humi- the process line through the t.
h2 = 30.48 Btu/1~ da (ans.) difying . process . From the solu- known point 1 at 40°F DB and
tion of Method 1 above, it was 35°F WB . Point 2 must be on this
NOTE: In the above solution for h2 , the value determined that the sensible-heat process line.
10.74 represents the sensible heat added, and addition to the air was q. = '
the value 6.74 represents the latent heat added 10.74 Btu/lb da and the latent Step 3; Determine location of point 2. Re-
per pound of air passing through the device. heat addition was qL = 6.74 (' ferring again to Method 1 solu-
Btu/lb da. The SHR is defined as tion, Step 3, the humidity ratio of
Step 4: Locate the final air condition on
the sensible heat divided by the the air leaving the device was w2
psychrometric chart. Draw a hor-
total heat for a process. For this = 62.86 grains/lb da. Determine
izontal line on psychrometric
problem the point of intersection of W2 and ·
chart for w2 = 62.86 grains/lb
the process line drawn in Step 2
da. Draw an inclined line on chart
q. 10.74 above. This determines point 2 on
for h2 = 30.48 Btu/lb' da to inter- SHR 0.614
qs + qL 10.74 + 6.74 the psychrometric chart, and we
sect W2 line. This point of inter-
can read the dry-bulb temperature
section is the final air condition
Step 2: Plot the SHR on the psychrome- of 84°F and wet-bulb temperature
leaving the device , point 2. At
tric chart. In Fig. 5-19 at a point of 65.2°F.
point 2, read the dry-bulb temper-
ature as 86°F and the wet-bulb where the 78°F DB line intersects
NOTE: The small variation in the results ob-
temperature as 65 .8°F. with the 50 percent RH curve,
tained is quite possible with the graphical-type
you will note a small circle. This
Step 5: Connect point 1 and 2 by a solution. When using the SHR scale, extreme
is the alignment circle for the
straight line. This line represents care must be used if a high degree of accuracy
SHR scale located on the upper
the process of heating and hu- is to be expected.
right of the Fig. 5-19. Using a
midification within the device. straight-edge, draw a construction
Solution: (Method 3): (See Figure 5-~0.)
After the development of Eq. (5-26) it was
a: indicated that some psychrometric charts pro-
I
(/)
vide an alignment quadrant to identify the en-
thalpy-humidity ratio (Llh! LlW) for a heating
and humidifying process. Figure 5-20 is a
schematic drawing of such a chart and quad- 5-~
0.614
rant. us
Step 1: Determine the enthalpy-humidity
ratio for the process. By Eq. (5- Wil
• 26), in!
in!
Llh =~ + hw
ch:
ca1
LlW mw
Figure 5-19 in1
Solution for Example 5-8 (Method 153,000 + 1157. 1 th
No.2) = 83 th
APPLIED PSYCHROMt TRICS 193

line between . the alignment circle


Solution: (Method 2): (See Figure 5-19.) and a SHR value of 0 .614. Paral-
Step 1: Determine the sensible-heat ratio lel to this construction line draw
(SHR) for the heating and humi- the process line through the
difying process . · From the solu- known point 1 at 40°F DB and
tion of Method 1 above, it WjS 35°F WB. Point 2 must be on this
determined that the sensible-heat process line.
addition to the air was q. =
Step 3; Determine location of point 2. Re-
10.74 Btu/lb da and the latent
ferring again to Method 1 solu-
heat addition was qL = 6 .74 (
tion, Step 3, the humidity ratio of
Btu!lb da. The SHR is defined as
the air leaving the device was w2
the sensible heat divided by the
total heat for a process. For this
= 62 .86 grains/lb da. Determine
the point of intersection of w2and . Figure 5-20
c problem the process line drawn in Step 2
b Alignment quadrant used with some
above. This determines point 2 on psychrometric charts (See Illustrative
rt q. 10.74
10.74 + 6.74 = 0.614 the psychrometric chart, and we problem 5-8, Method 3).
r- SHR = q. + qL can read the dry-bulb temperature
r- of 84°F and wet-bulb temperature
•n Step 2: Plot the SHR on the psychrome- of 65 .2°F. ~h
~W = 3004 (say 3000) (ans)
\t tric chart. ln Fig. 5-19 at a point
:r- where the 78°F DB line intersects NOTE: The small variation in the results ob-
Ib with the 50 percent RH curve, tained is quite possible with the graphical-type Step 2: On the quadrant draw a construc-
you will note a small circle . This solution . When using the SHR scale, extreme tion line from its center through
is the alignment circle for the care must be used if a high degree of accuracy 3000 on the scale. Parallel to this
a SHR scale located on the upper is to be expected. line, draw the heating and hu-
nts
right of the Fig. 5-19 . Using a midifying process line on the psy-
lU-
straight-edge, draw a construction chrometric chart through the
Solution: (Method 3): (See Figure 5-20.)
known conditions at point 1.
After the development of Eq . (5-26) it was
indicated that some psychrometric charts pro- Step 3: Determine the position of point 2

/J a:
I
(/)
vide an alignment quadrant to identify the en-
thalpy-humidity ratio (~hi~W) for a heating
and humidifying process. Figure 5-20 is a
schematic drawing of such a chart and quad-
on the process line by using either
Eq . (5-20) or (5-21)

S-9 HEATING AND HUMIDIFICATION


0 .614 rant. USING SPRAY EQUIPMENT
Step 1: Determine the enthalpy-humidity Frequently, spray water equipment is used
_.., t w2 = 62 .8 ratio for the process . By Eq. (5- with or without various arrangements of heat-

______ iw2
.......
26),

~h=~+hw
ing coils to preheat and/or reheat the air pass-
ing through the spray chamber. The spray
chamber is frequently called an air washer be-
cause it performs the secondary task of clean-
~w mw
ing, removing <fust and other particulate from
Figure 5-19 153,000 + 1157. 1 the airstream. However, for our discussion at
tor Example 5-8 (Method this point, we will be concerned primarily with
~o. 2)
194 APPLIED PSYCHROMETnl'"'

the spray chamber as n tltwin• In humidify tiona! view of a large, central station washer. washer housing is a rectangular steel casing, a
the air. It consists of a spray chamber in which a num- closed at top and sides and mounted on a shal- w
In Sections 5-5 null ~ tlthcre was a discus- ber of spray nozzles and risers are installed. low watertight tank base. Inlet baffles distrib- so
sion of the behuvitu ul uir and water in contact The washer illustrated has one bank of spray ute the entering air uniformly through the co
with each ot her. llumidification of air by nozzles. Sometimes two, and occasionally chamber, and at the leaving end eliminators re- C
spraying wntcr Into it is a direct application of three, banks are installed. Nozzles used for air move the entrained water droplets in the air- th
the principles of evaporation and heat ex- washers ordinarily have a capacity of approxi- stream preventing so-called carryover. The an
chunsc between air and water when in contact mately 1Y4 to 2 gpm per nozzle. The quantity eliminators also pick up dirt particles. The f0
with each other. of water delivered by each bank can be varied eliminator plates are so designed and installed fr
In most instances air washers are used in by installing a larger or smaller number of noz- so that the direction of air flow is changed a
industrial applications where the device per- zles. The water is forced through the nozzie by number of times while flowing through them. th
forms the two objectives of humidification and pumping at pressures from 20 psi to 40 psi to In this way the air impinges against the wet be
cleaning of the air. Figure 5-21 shows a sec- obtain good aton'lization of the water. The surfaces of the plates and the dust particles and ha
water droplets are deposited on the plates. The T
[Lilli INA TOftS
plates are washed down by a continuous th
stream of water from flooding nozzles. Air th
washers will not always remove greasy parti- is
cles and soot. Tobacco smoke will ordinarily ai
pass through an air washer. c:
Some odors can be removed from the air 0
passing through an air washer. An odor is usu-

Second stage Fir

:.;..--. <

Tank

Heat +t
exchanger
•water supply
(a) Single bank ai r washer (b) Two·stage air •
Figure 5-21
Industrial Tube Air-Washer (Courtesy Figure
of The Trane Company.) Types of ali
APPLIED PSYCHROMC"I Rl

washer housing is a rectangular steel casing, ally due to the vapor of some compound mi xed
tional view of a large, central ~tation w•~hc1 closed at top and sides and mounted on a shal- with the air. Many of these vapors will dis
ify
It consists of a spray chamber in which 1 1\11111 low watertight tank base. Inlet baffles distrib- solve in water. Of course, as the water b
ber of spray nozzles and risers are ln•l lllh'!il ute the entering air uniformly through the comes saturated with the soluble vapors, it be-
us-
The washer illustrated has one bank chamber, and at the leaving end eliminators re- comes less and less able to remove odors from
act
nozzles . Sometimes two, and OOGIIil! move the entrained water droplets in the air- the air. Furthermore, the water itself acquires
three, banks are installed~ Nozzlel ullll I
by
stream preventing so-called carryover. The an odor due to the material in solution; there-
1 of
washers ordinarily have a capacity eliminators also pick up dirt particles. The fore, under these conditions it must be changed
ex- eliminator plates are so designed and installed frequently or continuous overflow used.
mately 11/4 to 2 gpm per nozd
ttact
of water delivered by each bank so that the direction of air flow is changed a Air washers iife designed to be installed on
by installing a larger or smaller number of times while flowing through them. the suction side of the fan. They should never
d in
zles . The water is forced throU In this way the air impinges against the wet be installed on the discharge side unless they
per- have been specially built for this purpose.
pumping at pressures from surfaces of the plates and the dust particles and
and water droplets are deposited on the plates. The There will be· no difficulty with water leaking
obtain good atomization o
sec-
plates are washed down by a continuous through the joints of the washer installed on
stream of water from flooding nozzles. Air the suction side of a fan. However, if a washer
washers will not always remove greasy parti- is installed on the discharge side of a fan , the
cles and soot. Tobacco smoke will ordinarily air pressure developed by the fan is likely to
pass through an air washer. cause water leakage through the joints , in spite
Some odors can be removed from the air of rubber gaskets usually installed.
passing through an air washer. An odor is usu- If a set of eliminator plates is installed after

Second stage

- ...,
.::;
<
.,
-
'
Tank

exchanger
Pump
water supply
(c) Two-stage counterflow
(a) Single bank air washer (b) Two·stage air washer air washer

Figure 5-22
Figure 5-21
Types of air washers
al Tube Air-Washer (Courtesy
,f The Trane company.)
196 APPLIED PSYCHROMCTR IC

each bank of sprays, u wushcr having two adiabatic saturation of air when the air dry- oft'
banks is known as a two-stugc washer. A two- bulb temperature is lowered at constant wet tive
stage washer is illustrated in Fig. 5-22b and c. bulb as some of the water evaporates to hu- cen
Sometimes a two-stage washer may have two midify the air. In hot, dry climates a device of fici<
or three banks of spray nozzles in each stage. this type becomes a very simple, useful unit
Ordinarily , the water in air washers is recircu- for summer cooling. Eh
lated. When the air is to be humidified, either Referring again to Fig. 5-23 , as the air is
the air or the water, or sometimes both, are preheated, its dry- and wet-bulb temperatures
heated before entering the washer. If the air is increase, but the humidity ratio remains con-
to be cooled and dehumidified in the washer, stant. Passing through the spray chamber, the
or
the water must first be cooled. Heating or cool- Heater Pump wet-bulb temperature remains constant as the
or dry-bulb temperature decreases and the humid-
ing of the water can be ·accomplished by sup-
ch iller
plying either hot or chilled water to the heat ity ratio increases . The reheating process in-
e~changer shown in the ~r~ywater piping of creases the dry-bulb and wet-bulb temperatures
F1g. 5-22. at constant humidity ratio. Therefore, we have
The total cross-sectional w · area of air three elementary processes in series, a sensi- alsc
washers is usually based on an air velocity of ble-heating process, an adiabatic saturation
w,
~
500 fpm. If higher air velocities are used, trou- process, and another sensible-heating process.
ble may be experienced with entrained mois- W3, W4 Humidifying efficiency (frequently called ef-
ture being carried over from the washer. fectiveness) is a measure of the completeness
Some washers, smaller in size than the in- of the humidifying process using a spray wh<
dustrial type, are used in built-up air-handling w,.w 2 chamber. This efficiency is dependent on sev- oft
units with various arrangements of heating and eral factors: ber.
tempering coils, as well as means for heating t, t3 t2 t4 tern
or cooling the spray water used in the washer. a. number of spray nozzles, and banks of hun
Figure 5-23 air,
Figure 5-23 is a schematic drawing of such a nozzles, and the direction of the sprays
built-up air-handling unit. The arrangement is Schematic: Heating and humidifying with respect to the air flow direction of~
general, and only the components actually re- devices using spray washer tun
b. production of a fine water mist by the
quired to perform the heating and humidifying
nozzles, which depends on the nozzle
process would be included. On the sketch is recirculated water with no preheating or llh
design, size and water pressure
shown the variation in air properties as the air reheating of air.
passes through the unit. c. air velocity through the chamber
There are several common arrangements Arrangement 1 normally uses recirculated 30'
d. ratio of mass of air to water flow
that are used: spray water having no external heating and fin;
uses a reheating coil to heat the humidified air e. time of contact between water and air, Th
to a final temperature that may be required to or actually the length of the unit pre
1. Preheat the air prior to its contact with
provide sensible heating of a building. Ar- sh<
recirculated spray water, followed by re-
rangement 2 is seldom used if the incoming air Under favorable conditions, nearly com- ce~
heating of the air.
temperature is expected to be below 32°F at plet~ saturation of the air at the air wet-bulb wi1
2. Heat the spray water only. any time. Arrangement 3' is used for special temperature may be obtained. The amount of the
cases when arrangement 2 cannot meet the re- moisture added to the air depends on the enter- ne:
3. Moderately preheat the air then pass it
quirements. Since it involves additional equip- ing air wet bulb and on the spray chamber de- (a)
through heated spray water.
ment and piping, it is a more expensive sys- sign,. Commercial air washers are less than 100 ter
4. Pass the air through spray washer using tem. Arrangement 4 is the familiar process of percent effective. That is, complete saturation am
APPLIED PSYCHROMETRICS 197

adiabatic saturation of air when the air dry- of the air is not obtained. The saturation effec-
bulb temperature is lowered at constant wet tiveness will normally range from 80 to 90 per-
bulb as some of the water evaporates to hu- cent. Referring to Fig. 5-23, the saturation ef-
midify the air. In hot, dry climates a device of ficiency is defined as
this type becomes a very simple, useful unit
for summer cooling. Eh
Referring again to Fig. 5-23, as the air is
Actual change in air dry-bulb temperature
preheated, its dry- and wet-bulb temperatures
increase, but the humidity ratio remains con- Maximum possible change in dry bulb
stant. Passing through the spray chamber, the
or
Pump wet-bulb temperature remains constant as the
or dry-bulb temperature decreases and the humid-
chiller ity ratio increases . The reheating process in- t2 - t3 X 100
Eh (5-27)
creases the dry-bulb and wet-bulb temperatures t2 - tw

at constant humidity ratio. Therefore, we have


three elem~ntary processes in series, a sensi- also
ble-heating process, an adiabatic saturation
w, process, and another sensible-heating process. W3- w2 -x 100
~------=-Lw ,W
3 4 Humidifying efficiency (frequently called ef- Eh = Ws- W2 (5-28)

fectiveness) is a measure of the completeness


of the humidifying process using a spray where t2 and t 3 are the dry-bulb temperatures
w,.w 2 chamber. This efficiency is dependent on sev- of the air entering and leaving the spray cham-
eral factors: ber, respecHvely; tw is the constant wet-bulb
t, t3 t2 t4 temperature for the process; w2 and w3 are the
a. number of spray nozzles, and banks of humidity ratios of the entering and leaving
Figure 5-23 nozzles, and the direction of the sprays air, respectively; and Ws is the humidity ratio
Schematic: Heating and humidifying with respect to the air flow direction of the air saturated at the wet-bulb tempera-
devices using spray washer ture.
b. production of a fine water mist by the
recirculated water with no preheating or
reheating of air.
nozzles, which depends on the nozzle
design, size and water pressure
c. air velocity through the chamber
Illustrative Problem 5-9
" z-/(;)
Five thousand cfm of air at 40°F DB and
&-- <3

Arrangement 1 normally uses recirculated 30°F WB are to be heated and humidified to a


d. ratio of mass of air to water flow
spray water having no external heating and final condition of 90°F DB and 30 percent RH.
uses a reheating coil to heat the humidified air e. time of contact between water and air, The process of heating will be done by using a
to a final temperature that may be required to or actually the length of the unit preheating coil and a reheating coil arranged as
provide sensible heating of a building. Ar- shown in Fig. 5-23. The humidification pro-
rangement 2 is seldom used if the incoming air Under favorable conditions, nearly com- cess is to be done by using a spray chamber
temperature is expected to be below 32°F at plete saturation of the air at the air wet-bulb with recirculated unheated water. Assume that
any time. Arrangement 3· is used for special temperature may be obtained. The amount of the humidifying process will have an effective-
cases when arrangement 2 cannot meet the re- moisture added to the air depends on the enter- ness of 82 percent. Determine the following:
quirements. Since it involves additional equip- ing air wet bulb and on the spray chamber de- (a) the psychrometric properties of the air en-
ment and piping, it is a more expensive sys- sign. Commercial air washers are less than 100 tering and leaving the spray washer, (b) the
tem. Arrangement 4 is the familiar process of percent effective. That is, complete saturation amount of preheat and reheat required in
198 APPLIED PSYCHROMETRICS

Btu!hr, and (c) the amount of water evaporated leaving spray chamber must be tio scale and extend horizontal line to the left
into the air in lb/hr. on this line. to intersect the 100 percent RH line. This point
m
locates the wet-bulb temperature for the hu-
Solution: (See Fig. 5-24.) Step 4: Determine the psychrometric prop- midifying process as 59.2°F. ~~ere this con- m
erties of the air entering and leav- stant wet-bulb line interseCts .the ,preheat pro-
Step 1: Locate initial and final air condi-
ing the chamber. The humidifying cess line and the reheat process line will be the -
tion on the psychrometric chart. 5-1
process is assumed to have an ef- entering and leaving air col)ditlon, respec-
All
fectiveness of 82 percent, there- tively, for the humidifying process, points 2
fore, with w~ = w3 and w2 and 3. From Fig. 5-24 then - -
Initial Condition (1) Final Condition (4)
wl Eq. (5-28) becomes and
II = 40°F DB t4 = 90°F DB. 4'c;-~ ~(/X cha
tw 1 = 30°F WB tw4 = 67 .2°F WB w4- wl Point 2 Point 3 nali
W 1 = 10 grains/lb w4 = 63 grains/lb Eh = Ws- WI
t2 = 100°F DB t3 = 66.6°F DB
be
da da and
tw2 = 59.2°F WB tw3 = 59.2°F WB
h 1 = 11.2 Btu/lb da h4 = 31 .6 Btu/lb da
where w4 is the humidity ratio of the air leav- w2 = 10 grains/lb da w3 = 63 grains/lb da tina
V1 ,;, 12.62 fe/1b da v4 = 14.04 retlb da air
ing the spray chamber. Solving Eq. (5-28) for h2 = 25.6 Btu/lb da h3 = 25.8 Btu/lb da
W., we have v2 = 14.13 retlb da V3 = 13.44 fe/lb da onl;
Step 2: Construct the horizontal preheat air
line through point 1 and extend to atut
the right. The air condition enter- Ws =
w4-
Eh
w1 + W1 Step 5: Determine the quantity of preheat
cha
and reheat. From Eq. 4-7
ing spray chamber must be on and
this line. 63 - 10 + 10 cfm X 60 5000 X 60 I
0.82 ma = cha1
Vt 12.62
Step 3: Construct the horizontal reheat tric
line through point 4 and extend
Ws = 74.6 grains/lb da
ffl 0 = 23,772 lb/hr prO<
(ans)
to the left. The air condition In Fig. 5-24 locate Ws of 74.6 on humidity ra- atur
Remember this mass flow rate is constant cun
throughout the flow system. The volume flow cun
rate (cfm) changes because the specific volume to u
is changing. By Eq. 5-4,
Hea
w
1iJs
2 = ffl 0 (h2 - h1) = 23,772(25.6 - 11.2)
or
f 1iJs2 = 342,300 Btu/hr (preheat) (ans)

:X: ws = 74.6 By Eq. 5-4


w3 =w4 whe
= 63 3iJs4 * ma(h4 - h3) = 23,772(31.6 - 25.8)
ffla
3qs4 = 137,800 Btu/hr (reheat) (ans)
~
Y< W1 =W2
- = 10 mw
90100 Step 6: Mass of water evaporated. Each
hA a
pound of air absorbs w3 - w2
Figure 5-24 grains of moisture; therefore, by psyc
Solution for Example 5-9 Eq . (5-23) tA ' a
APPLIED PSYCHROMETRICS 199
I

! 7~
63 10
)
leaving spray chamber must be tio scale and extend horizontal line to the left
on this line. to intersect the 100 percent RH line. This point rnw = rna(W3 - W2) = 23,772(
locates the wet-bulb temperature for the hu-
Step 4: Determine the psychrometric prop- midifying process as 59.2°F ....Where this con- mw = 179.9 lb/hr (evaporated) (ans)
erties of the air entering and leav- stant wet-bulb line interseCt's the preheat pro-
ing the chamber. The humidifying cess line and the reheat proces~ line will be the
5-10 HEATING AND HUMIDIFYING
process is assumed to have an ef- entering and leaving air condition, respec-
AIR WITH HEATED SPRAY WATER
fectiveness of 82 percent, there- tively, for the humidifying process, points 2
fore, with w~ = w3
and w2 and 3. From Fig. 5-24 then - As noted in Section 5-9, air may be heated
W 1 Eq. (5-28) becomes and humidified by passing it through a spray
=- or? lo 1 chamber where the spray water is heated exter-
Point 2 Point 3 nally. The initial spray water temperature must
be high enough so that as it contacts the air
t2 = 100°F DB t3 = 66.6°F DB
tw2 = 59.2°F WB tw3 = 59.2°F WB
and transfers its heat to the air and cools, the
where w4 is the humidity ratio of the air leav- w2 = 10 grains/lb da w3 = 63 grains/lb da final air temperature must be above the initial
ing the spray chamber. Solving Eq. (5-28) for ~ =! 25 .6 Btu/lb da h3 = 25 .8 Btu!lb da air temperature. The water temperature can fall
W., we have v2 = 14. 13 te/lb da v 3 = 13 .44 te!lb cta only to the wet-bulb temperature of the leaving
air (ideally). The changes in the water temper-
ature and air temperature within the spray
w. = Step 5: Determine the quantity of preheat
chamber depend on the relative masses of air
and reheat. From Eq. 4-7
and water circulated.
63--=--!.Q + lO If both the air and water temperature are
cfm X 60 5000 X 60
0.82 ma = changing, the process line on the psychrome-
v, 12.62 tric chart is not a straight line. The path of the
w. = 74.6 grains/lb da
rna = 23 '772 lb/hr process is a ·pursuit curve of the water temper-
(ans)
In Fig. 5-24 locate w. of 74.6 on humidity ra- ature which is represented on the saturation
Remember this mass flow rate is constant curve (100 percent RH). To draw the pursuit
throughout the flow system. The volume flow curve on a psychrometric chart, it is necessary
rate (cfm) changes because the specific volume to use the following relationship.

/J 'W
is changing. By Eq. 5-4,
Heat absorbed by air = heat given up by water
,q.2 = rna (h2 - h,) = 23 ,772(25 .6 - 11.2)
or

If
1q.2 = 342,300 Btu/hr (preheat) (ans)
'reheat Frt- rna(hB - hA) = rnwCp(tA' - tB) (5-29)

~, I:;:::
6 By Eq. 5-4
where
w3 = 63 3qs4 = rna(h4 - h3) = 23,772(31.6 - 25.8)
2
rna = lb/hr of air flow through spray chamber
IW 1 =W 3qs4 = 137,800 Btu/hr (reheat) (ans)

rnw = lb/hr of water sprayed


90 100 = ,J Step 6: Mass of water evaporated. Each hA and h8 = air enthalpy values from
pound of air absorbs w3 - w2
1re 5-24 psychrometric chart for two points, A and B
grains of moisture; therefore, by
=
lr Example 5-9
1 Eq . (5-23) tA' and t8 • spray water temperatures (in °F)
200 APPLIED PSYCHROMETRICS

•.
,:

/- ~. w,
rtJI I WD
.:l
"'
~
a.
E
------------~------------+-w A

"'
;:
Figure 5-25 "'
:~
c
Construction of pursuit curve
(heating and humidifying with heated
spray water

cP = specific heat of water, assumed constant A and the final air dry bulb, point D, continued
and equal to unity to intersect the saturation curve (shown
dashed) defines the humidifying efficiency (ef-
fectiveness) of the process. For Fig. 5-25 the Figure 5-26
Figure 5-25 represents a procedure for the value of Eh would be (W0 - WA)I(W. - WA)
development of the pursuit curve on the psy- expressed as a decimal. Spray Water Alr-Washe
Humidification (Courte
chrometric chart. To draw the curve, the initial This method of plotting the pursuit curve is Trane Compan:
air condition, point A, and the initial water time consuming, and a simpler solution of
temperature, point A 1 , are plotted and then such problems using heated spray water may
connected by a straight line. Select point B on be obtained by the use of Fig. 5-26. This
this line a short distance from A. The water graph is based upon the assumption that the lllu
Actual change in air enthalpy
temperature at point B 1 may then be calcu1ated heat absorbed by the air is equal to the heat
from Eq. (5-29) with known values of rna and given up by the water. Also, the final water CF = Theoretical change in air enthalpy
mw. Connect points B and B 1 with a straight temperature and final air wet-bulb temperature wa~
line. Next, select a point such as C a short dis- are the same. Actually, the final water temper- or
is s
tance from B and again use Eq. (5-29) to cal- ature will be higher than the final air wet-bulb For
culate the water temperature at point C 1 • The temperature. Nevertheless, this chart enables !!.h actual
CF = - - - - - (5-30) wat
procedure is continued until the final water many problems involving washers to be solved !!.h theoretical
oft
temperature, D 1 , is approximately equal to the easily by first finding the theoretical solution •
wet-bulb temperature of the air passing and then applying a correction factor (CF). t In effect, this correction factor corresponds to
~
through D. A straight line drawn through point The correction factor is determined by the humidifying efficiency, Eh, determined by
Eqs. (5-27) and (5-28).

tTrane Air Conditioning Manual, The Trane Company, LaCrosse, Wisconsin, 1965, p. 227.
nditioning Manual , The Trane Company, LaO
APPLIED PSYCHROMETAICS 201

Initial wet bulb


temperature of air

t~~~====~~~~~~~~~~~~~~~~~~\00
?,0
roo

- ~ w,

-==:. . ~::::::~~~~~~~100
~ 9o
~
.§"'"'
120
110 t::-'t,

30 25
40135
WD L~~:::::.-_::"'-<::::::::-- ~
____..-so
- 9</; ~
."
20 18
.~
1o ..$'~ ~
</; ~ 16 14
.roo ~~ ;:>~ .:
<(
13 12
11
I~ ~ - ~___/~-=r: -~"'- '0..--.w
~~- ~I~ -A. /'/1§5 <{~"'
t:
-------'>..._------t-WA ----*=OOr- ~ 9
.. .
~
"'3:
"'" ~ 8
80 7
·e 5-25 -
.~

c
of pursuit curve
ldlfylng with heated
'f water 0 4.5
~
0..
(:J 4
A and the final air dry bulb, point D, continued
to intersect the saturation curve (shown 3.5
dashed) defines the humidifying efficiency (ef-
fectiveness) of the process. For Fig. 5-25 the Figure 5-26
value of Eh would be (W0 - WA)I(Ws - WA) Spray Water Air-Washer Chart for
expressed as a decimal. Humidification (Courtesy of The
This method of plotting the pursuit curve is Trane Company.)
time consuming, and a simpler solution of
such problems using heated spray water may
be obtained by the use of Fig. 5-26. This
graph is based upon the assumption that the Actual change in air enthalpy Illustrative Problem 5-10*
heat absorbed by the air is equal to the heat CF = Theoretlca
. I c hange m
. rur
. enthaIpy
given up by the water. Also, the final water An air quantity of 15,000 cfm enters a
temperature and final air wet-bulb temperature washer at 70°F DB and 50°F WB. The washer
or
are the same. Actually, the final water temper- is supplied with 150 GPM of water at 90°F.
ature will be higher than the final air wet-bulb For a correction factor of 0.85 determine the
f:lh actual (5-30) water temperature in the tank and the condition
temperature. Nevertheless, this chart enables CF = !lh theoretical
many problems involving washers to be solved of the .air leaving the washer.
easily by first finding the theoretical solution
In effect, this correction factor corresponds to
and then applying a correction factor (CF). t Solution : (See Fig. 5-27.)
the humidifying efficiency, Eh, determined by
t The correction factor is determined by Step 1: Determine final water temperature
Eqs. (5-27) and (5-28).

any , LaCrosse, Wisconsin, 1965, p. 227. :j:Trane Air Conditioning Manual, The Trane Company, LaCrosse, Wisconsin, 1965 , p. 232.
202 APPLIED PSYCHROMETRICS

a. inlet air temperature by changing the perat


amount of heating medium to the preheat table
coil sensi
cons
b. inlet water temperature by controlling
the heating capacity of heat exchanger
c. water quantity by taking a bank of noz-
zles out of service.
w tl :
Illustrative Problem 5-11 <I> I

'---t------J r An air-conditioning unit for an industrial


building must provide 4500 cfm of outside air
V1 :

WI :
70 hi :
entering a preheat coil at 5°F DB and 50 per-
Figure 5-27 cent RH. The preheat coils heat the air to 40°F
Solution to Problem 5-10
DB. The outside air then mixes with 13,500
cfm of recirculated air at 70°F DB and 40 per-
cent RH. The mixed air passes through a
and theoretical final air wet-bulb Btu/lb da. Theoretical change in washer supplied with 90 GPM of water at
·temperature. The water-to-air ra- enthalpy is h2 - hi = 37.2 - ll0°F and has a correction factor of 0.83 . The
tio is 150/15 = 10 gpm/1000 cfm 20.2 = 17.0 Btu/lb da. The ac- humidified air is then reheated to a dry-bulb
of air. Using Fig. 5-26, set the tual change in enthalpy is the the- temperature of 115°F before entering the sup-
right end of the straight-edge on oretical change times the · correc- ply fan which delivers it to a duct system for
the right scale at 10 gpm/1000 tion factor. Actual enthalpy distribution within the building. Determine (a)
cfm; set the left end of the change = 17.0 X 0.85 = 14.45 the psychrometric properties of the air as it
straight-edge on the initial water Btu/lb da. The actual enthalpy of flows through the conditioning equipment and
temperature of 90°F on left scale. air leaving washer will be h3 = (b) if the heat exchanger supplying heat to the
Where a line between these two 20.2 + 14.45 = 34.65 Btu/lb da. spray water were turned off so that the water
points crosses the initial air wet In Fig. 5-27 construct a constant- in the washer were recirculated without any
bulb of 50°F' read the final water enthalpy line at 34.65 and extend heat being added, what would be the properties
temperature of 73 .5°F, which is to intersect line 1-2 at point 3. At of the air through the conditioning equipment?
also the theoretical final air wet- point 3 find t3 = 73.5°F, tw3 =
bulb temperature. 70. 7°F. (ans) Solution: (Part a): (See Figs. 5-28 and
5-29.)
Step 2: Determine actual leaving air con- NO'
dition from washer. In Fig. 5-27 A water-to-air ratio of 5 gpm per 1000 cfm Step 1: Make a sketch of the mechanical use
at entering air condition of 70°F is common for a single-bank washer, while ap- arrangement of the equipment,
DB and 50°F WB find hi = 20.2 proximately 10 to 15 gpm per 1000 cfm are Fig. 5-28. (Circled numbers es-
Btu/lb da. Theoretically, the air usual ratios for two- and three-bank washers .
• tablish points where air conditions
could be heated and humidified Initial water temperature will vary within the are to be established.)
to saturation at 73.5°F, and line range of 60°F to 120°F depending upon the in-
Step 2: Determine the properties of the
1-2 represents the process through let and outlet air temperatures. Ordinarily, the
preheated outside air (point 2).
the washer. The enthalpy of satu- operator has the following items he can vary to
rated air at 73 SF is h2 = 37.2 control the performance of the washer: The properties of the outside air from low-tern- be·
APPLIED PSYCHROMETRICS 203

a. inlet air temperature by changing the perature psychrometric charts are listed in the
amount of heating medium to the preheat table below. Since the preheating process is a
coil sensible-heating process, it is carried out at
constant humidity ratio W 1 = W2 •
b. inlet water temperature by controlling
• the heating capacity of heat exchanger
c. water quantity by taking a bank of noz- Outside Air (1) Preheated Outside Air
zles out of service. (2)
w t 1 = 5°F t2 = 40°F (given)
Illustrative Problem 5-11 <!>t = 50 percent <!> 1 = 10 percent

--+------'1
70
An air-conditioning unit for an industrial
building must provide 4500 cfm of outside air
entering a preheat coil at 5°F DB and 50 per-
Vt = 11.72 fe/Jb da

W 1 = 3.50 grains/Jb da
h 1 = 1.7 Btu/lb da
v2 = 12.60 retJb da
w2 = 3.50 grains/Jb da
h2 = 10.2 Btu!lb da

re 5-27 cent RH . The preheat coils heat the air to 40°F


DB . The outside air then mixes with 13,500
Problem 5-10
cfm of recirculated air at 70°F DB and 40 per- Step 3: Determine the amount of preheat
cent RH . The mixed air passes through a required. By Eq. 5-7 ,
Btu/lb da. Theoretical change in washer supplied with 90 GPM of water at
enthalpy is h2 - h 1 = 37.2 - 110°F and has a correction factor of 0.83. The
x cfm lb/hr
20.2 = 17.0 Btu/lb da. The ac- humidified air is then reheated to a dry-bulb ffla 1 = ffl a2 = Vt
tual change in enthalpy is the the- temperature of 115°F before entering the sup-
oretical change times the correc- ply fan which delivers it to a duct system for 60 X 4500
ma2 = 11.72 23,038 lb/hr
tion factor. Actual enthalpy distribution within the building. Determine (a)
change = 17.0 x 0.85 = 14.45 the psychrometric properties of the air as it = 384 lb/min
Btu/lb da. The actual enthalpy of flows through the conditioning equipment and
air leaving washer will be h3 = (b) if the heat exchanger supplying heat to the
20.2 + 14.45 = 34.65 Btu/lb da. spray water were turned off so that the water By Eq. 5-4,
In Fig. 5-27 construct a constant- in the washer were recirculated without any
enthalpy line at 34.65 and extend heat being added, what would be the properties 1iJs2 = maih2 - ht)
to intersect line 1-2 at point 3. At of the air through the conditioning equipment? = 23,038(10.2 - 1.7)
point 3 find t3 = 73.5°F, tw3 =
70. 7°F. (ans) Solution: (Part a): (See Figs. 5-28 and
lqs
2
= "195,820 Btu/hr
5-29.)
NOTE: If approximate Eq. (5-9) had been
A water-to-air ratio of 5 gpm per 1000 cfm Step 1: Make a sketch of the mechanical used, the result would be
~ common for a single-bank washer, while ap- arrangement of the equipment,
proximately 10 to 15 gpm per 1000 cfm are Fig. 5-28. (Circled numbers es- 1iJs2 = (1.10 cfm)(t2 - t 1)
usual ratios for two- and three-bank washers. tablish points where air conditions
Initial water temperature will vary within the are to be established.) 1.10(4500)(40 - 5)
range of 60°F to l20°F depending upon the in-
Step 2: Determine the properties of the
1iJs
2
= 173,250 Btu/hr (approximate)
let and outlet air temperatures. Ordinarily, the
preheated outside air (point 2).
operator has the following items he can vary to The difference of about 22,500 Btu/hr may
~ control the performance of the washer: The properties of the outside air from low-tein- be accounted for by the fact that the constant
204 APPLIED PSYCHROMETRICS •

Return air
(13,500 CFM)

@ Supply

"'~'-]-t-~,--~~~~T---:::=~=•,
Moisture
eliminators air
f I >
< II I:IZi I I ~
Outside I I J '""""
air
4500 CFM
"~ Mixing
box
"@)
CD 0~
:'-.

"Tempering"
preheat coil
90GPMat110° F
Figure 5-29
Solution of Example 5-11.
Sh ell and
tube heat
exchanger
... , ..
Figure 5-28 cfm = m X v = 384 X 12.60 = 4838 cfm
Schematic arrangement of one of the
two units of Illustrative Problem 5-11 then

(4838)(40) + (13,500)(70) The


t4 = gprr
18,338
in Eq. (5-9) was determined by considering m3 = 60,089 lb/hr l
standard air (v = 13. 34 fe /lb) . The actual spe- t4 = 62.08°F (use t4 = 62°F) 4.9
1001.5 lb/min (say 1000 lb/min)
cific volume of the outside air in this problem 110
is 11.72 fe!lb . The exact Eq. (5-4) should al- In Fig. 5-29 draw a straight line connecting
By Eq . (5-14)
ways be used when the actual specific volume Mixture temperature points 2 and 3. Where this line intersects the
is significantly different from standard. dry-bulb temperature of 62°F locate point 4
and find v4 = 13.25 fetlb da, W4 = 33
Step 4: Determine mixture condition of mz X tz + m3 X t3
(t4) = . + . grains/lb da, h4 = 20.0 Btu/lb da, and tw4 =
preheated outside air and return mz m3 49.8°F.
air.
(384)(40) + (1000)(70) The
In Fig. 5-29 locate point 3 at 70°F DB and t4 = 1384
St~p 5: Determine the washer perfor-
mance and calculate the leaving four
40 percent RH, find v3 = 13.48 fetlb da. By
Eq . (5-7),
t4 = 61.6°F • water temperature (t1w), and the
entering and leaving air condi- per
NOTE: The mixture temperature (t4 ) could tions for the washer. rea
m3 = also be approximated by use of Eq. (5-17). as
The entering air condition to the washer has ent
60 X 13,500 + cfm3 X t3
cfm 2 X t2 already been determined, point 4 , in Step 4. Btl
t = --~--~----~--~
13.48 cfm2 + cfm3 The volume of air entering the washer is wo
• APPLIED PSYCHROMETRICS 205

1air
0 CFM)

Supply •
Moisture
air
eliminators

A ._ .6
'at 1 .- •s
,... r
I
,tw
115
Figure 5-29

ihell and Solution of Example 5-11a and 5-11b


ube heat
'xchanger
-~

ure 5-28 cfm = mX V = 384 X 12.60 = 4838 cfm Cfffi4 = rna~ · X V4 = (1384)(13.25)
gement of one of the
= 18,338 cfm
stratlve Problem 5-11 then

(4838)(40) + (13,500)(70) The water-to-air ratio then is 90/18.338 = 4.9


t4 =
18,338 gprn/1000 cfm.
m3 = 60,089 lblhr Using Fig. 5-26 with water-to-air ratio of
= 1001.5 lb/min (say 1000 lb/min) t4 = 62.08°F (use t4 = 62°F) 4.9 and the inlet water temperature Uew) =
110°F, at tw4 = 49.8°F, find
By Eq. (5-14) In Fig. 5-29 draw a straight line. connecting
Mixture temperature points 2 and 3. Where this line intersects the
Final water temperature (t1w) = 74°F
dry-bulb temperature of 62°F locate point 4
m2 x t2 + m3 x t3 and find v4 = 13.25 fe/lb da, w4 = 33 Theoretical final wet-bulb temperature
(t4) grains/lb da, h4 = 20.0 Btu/lb da, and tw4 = =
m2 + m3 49.8°F.
of air leaving 74°F.
(384)(40) + (1000)(70)
t4 = 1384
Step 5: Determine the washer perfor- The actual condition of the air leaving may be
mance and calculate the leaving found by applying the correction factor 0.83.
t4 = 61.6°F water temperature (t1w). and the On Fig. 5-29, locate t1w = 74°F on the 100
entering and leaving air condi- percent relative humidity curve. At this point
NOTE: The mixture temperature (t4 ) could tions for the washer. read the theoretical enthalpy of the air leaving
also be approximated by use of Eq. (5 -17). as 37.6 Btu/lb da. The theoretical rise in air
The entering air condition to the washer has enthalpy is 37.6 - h4 = 37.6 - 20.0 = 17.6
cfm2 + cfm3 x t3
X t2 already been determined, point 4, in Step 4.
t = --~--~----~~~ Btu/lb da. The actual change in enthalpy
cfm2 + cfm3 The volume of air entering the washer is would be (17.6)(0.83) = 14.6 Btu/lb da.
206 APPLIED PSYCHROMETRICS

Most summer air-conditioning applications


Therefore, the actual enthalpy of the air leav- washer saturated at a dry-bulb temperature of
require the simultaneous removal of both sen-
ing would be 20.0 + 14.6 = ~4.6 Btu/lb da, 49. 8°F, or the drop in dry-bulb temperature
sible and latent heat quantities to maintain
hs. would be 62 - 49.8 = 12.2 degrees. The cor-
comfort conditions for people, or for maintain-
Draw a straight line on Fig. 5-29 connect- rection factor, or humidifying effectiveness,
ing stability of an industrial process. Deter-
ing point 4, the entering air condition, and the must be applied in this case to the dry-bulb
mination of the required supply air quantity ·
leaving water condition. Construct a constant- · temperature change or the humidity ratio
and its properties are the important steps in
enthalpy line (h 5 = 34.6) to produce an inter- change. Therefore, the actual change in dry-
the satisfactory design of air-conditioning sys-
section at point 5, the actual leaving air con- bulb temperature would be (12.2)(0.83) =
tems.
dition from the spray washer. Read t5 = 72°F, 10.1 degrees. Therefore, the actual dty-bulb
In Section 5-3 sensible cooling of moist air
tw5 = 70.6°F, W 5 = 111 grains/lb da, and temperature of the air leaving the washer
was discussed. However, as may be recalled,
v5 = 13.75 ft/lb da. would be 62 - 10.1 = 51.9°F = h·
we were concerned at that time with the pro-
On Fig. 5-29 locate the intersection of t7 =
Step 6: Determine the final air properties cess of warm supply air providing the sensible
51.9°F and tW? = 49.8°F. Find h7 = 20.1
after reheating (point 6) . heat to overcome heat loss from the condi-
Btu!lb da, W7 = 50 grains /lb da, and v7 =
tioned space. We are now concerned with sup-
The reheating process is a sensible-heating 13.04 fe!lb da.
plying air to a conditioned space at a suffi-
process at constant humidity ratio W6 = W5 =
Step 2: Determine final air properties after ciently reduced dry-bulb temperature below the
111 grains/lb da. On Fig. 5-29 locate intersec-
reheating. space design dry-bulb temperature to absorb
tion of W = 111 and t6 = 115°F and find the
the sensible heat gains to the space. The sup-
following properties of the reheated air: h 6 = The reheating process is a sensible-heating
ply air must also be at a sufficiently reduced
45.2 Btu/lb da, v 6 = 14.85 ft/lb da, and tw6 = process at constant humidity ratio (W8 = W7 =
humidity ratio to absorb the latent heat gains
81.6°F. 50 grains/lb da) . On Fig. 5-29 draw a constant
to the space.
humidity ratio line from point 7 to intersect t 8
Step 7: Determine the required amount of Figure 5-30a represents a typical cooling
at l15°F. At point 8 find tw8 = 72.2~F. hs =
reheat. By Eq. (5-4), coil using chilled water in the tubes. If the
35.5 Btu/lb da, and v8 = 14.65 fe/lb da.
chilled water circulated through the tubes is
ils6 = inaih6 - hs) Step 3: Determine the amount of reheat at a temperature low enough to maintain the air-
required. By Eq. 5-4, side surface temperature of the coil below the
(1384)(60)(45.2 - 34.6)
dew-point temperature of the entering air, the
iJs6 = 880,200 Btu/hr ilsg = Tna 7 (hg - h7) properties of the air passing through the de-
humidifying coil may be represented as shown
(1384)(60)(35.5 - 20.1)
Solution: (Part b) (Refer to Fig. 5-29) in Fig. 5-30a. The dry- and wet-bulb tem-
ilsg = 1,278,800 Btu/hr peratures, humidity ratio, and enthalpy of the
All air properties up to and including point
4 are the same as found in part a. entering air are reduced. The psychrometric
5-11 COOLING AND process of cooling and humidification of the air
Step 1: Determine air properties leaving DEHUMIDIFICATION OF AIR from condition 1 to condition 2 is represented
spray washer when the spray wa- on Fig. 5-30b if all the air uniformly and per-
The preceding sections of this chapter have
•ter is unheated. fectly contacts the chilled surface of the coil.
been concerned primarily with the heating
When no heat is added to the spray water, and/or humidification of air to provide supply The moisture could be condensed from the air at No
the water will quickly assume the wet-bulb air to a conditioned space which would over- a vatiable temperature from the initial dew- Eq
temperature of the entering air (tw4 = 49 .8°F). come heat losses and provide for satisfactory point temperature (A) to the final saturation ch;
The air condition as it passes through the spray humidity conditions . We will now concern temperature (t2 ). If the condensed moisture is an'
chamber would follow the constant wet-bulb ourselves with cooling and dehumidification of brought to the final temperature (t2 ) before on
temperature of 49.8°F as the air is humidified air supplied to a space. This air would be used draining from the system, we may write the lin
and cooled . to overcome the heat gains and moisture gains following steady-flow energy and material-bal- no
Theoretically , the air would leave the spray of the space. ance equations. ce1
206 APPLIED PSYCHROMETRICS

Most summer air-conditioning applications


Therefore, the actual enthalpy of the air leav- washer saturated at a dry-bulb temperature of
require the simultaneous removal of both sen-
ing would be 20.0 + 14.6 = 34.6 Btu/lb da, 49.8°F, or the drop in dry-bulb temperature
sible and latent heat quantities to maintain
hs . would be 62 - 49.8 = 12.2 degrees. The cor-
comfort conditions for people, or for maintain-
Draw a straight line on Fig. 5-29 connect- rection factor , or humidifying effectiveness,
ing stability of an industrial process. Deter-
ing point 4, the entering air condition, and the must be applied in this case to the dry-bulb
mination of the required supply air quantity ·
leaving water condition . Construct a constant- · temperature change or the humidity ratio
and its properties are the important steps in
enthalpy line (h5 = 34.6) to produce an inter- change. Therefore, the actual change in dry-
the satisfactory design of air-conditioning sys-
section at point 5, the actual leaving air con- bulb temperature would be (12.2)(0.83) =
tems .
dition from the spray washer. Read t5 = 72°F, 10.1 degrees. Therefore, the actual dty-bulb
In Section 5-3 sensible cooling of moist air
tw5 = 70.6°F, W5 = 111 grains/lb da, and temperature of the air leaving the washer
was discussed . However, as may be recalled,
v5 = 13.75 ft/lb da. would be 62 - 10. 1 = 51.9°F = t7 •
we were concerned at that time with the pro-
On Fig. 5-29 locate the intersection of h =
Step 6: Determine the final air properties cess of warm supply air providing the sensible
51.9°F and tW? = 49 .8°F. Find h7 = 20. 1
after reheating (point 6). heat to overcome heat loss from the condi-
Btu/lb da, W7 = 50 grains /lb da, and v7 =
tioned space . We are now concerned with sup-
The reheating process is a sensible-heating 13 .04 fe/lb da.
plying air to a conditioned space at a suffi-
process at constant humidity ratio W6 = W5 =
Step 2: Determine final air properties after ciently reduced dry-bulb temperature below the
111 grains/lb da. On Fig. 5-29 locate intersec-
reheating. space design dry-bulb temperature to absorb
tion of W = 111 and t6 = 115°F and find the
the sensible heat gains to the space. The sup-
following properties of the reheated air: h6 = The reheating process is a sensible-heating
ply air must also be at a sufficiently reduced
45 .2 Btu/lb da, v6 = 14.85 ft/lb da, and tw6 = process at constant humidity ratio (W8 = W7 =
humidity ratio to absorb the latent heat gains
81.6°F. 50 grains/lb da) . On Fig. 5-29 draw a constant
to the space .
humidity ratio line from point 7 to intersect t 8
Step 7: Determine the required amount of Figure 5-30a represents a typical cooling
at ll5°F. At point 8 find tw8 = 72.2°-F , h8 =
reheat. By Eq. (5-4), coil using chilled water in the tubes. If the
35.5 Btu/lb da, and Vg = 14.65 fe/lb da.
chilled water circulated through the tubes is
ils6 = ma/h6 - hs) Step 3: Determine the amount of reheat at a temperature low enough to maintain the air-
required. By Eq . 5-4, side surface temperature of the coil below the
(1384)(60)(45.2 - 34.6)
dew-point temperature of the entering air, the
iJs6 = 880,200 Btu/hr /Jsg = ffla 7 (hg - h7) properties of the air passing through the de-
humidifying coil may be represented as shown
(1384)(60)(35.5 - 20. 1)
Solution: (Part b) (Refer to Fig. 5-29) in Fig . 5-30a. The dry- and wet-bulb tem-
/lsg = 1,278 ,800 Btu/hr peratures , humidity ratio , and enthalpy of the
All air properties up to and including point
4 are the same as found in part a. entering air are reduced. The psychrometric
5-11 COOLING AND process of cooling and humidification of the air
Step 1: Determine air properties leaving DEHUMIDIFICATION OF AIR from condition 1 to condition 2 is represented
spray washer when the spray wa- on Fig. 5-30b if all the air uniformly and per-
The preceding sections of this chapter have
•ter is unheated. fectly contacts the chilled surface of the coil.
been concerned primarily with the heating
When no heat is added to the spray water, and/or humidification of air to provide supply The moisture could be condensed from the air at No
the water will quickly assume the wet-bulb air to a conditioned space which would over- a vatiable temperature from the initial dew- Eq
temperature of the entering air (tw4 = 49.8°F) . come heat losses and provide for satisfactory point temperature (A) to the final saturation ch;
The air condition as it passes through the spray humidity conditions. We will now concern temperature (t2 ) . If the condensed moisture is anj
chamber would follow the constant wet-bulb ourselves with cooling and dehumidification of brought to the final temperature (t2 ) before on
temperature of 49. 8°F as the air is humidified air supplied to a space. This air would be used draining from the system , we may write the lin
and cooled. to overcome the heat gains and moisture gains following steady-flow energy and material-bal- no
Theoretically, the air would leave the spray of the space. ance equations. ce1
APPLIED PSYCH ROMETHICS 20
Cooling and
IV- washer saturated at a dry-bulb temperature o Most summer air-conditioning applications
dehumidifying cor I
Ia, 49 .8°F, or the drop in dry-bulb temperature require the simultaneous removal of both sen-
t,
would be 62 - 49.8 = 12.2 degrees . The cor- sible and latent heat quantities to maintain t2
:t- rection factor, or humidifying effectiveness, comfort conditions for people, or for maintain- tw,
he must be applied in this case to the dry-bulb ing stability of an industrial process. Deter-
lt- · temperature change or the humidity ratio mination of the required supply air quantity w,
w2
!r- change. Therefore, the actual change in ~ry ­ and its properties are the important steps in
h,
n- bulb temperature would be (12 .2)(0.8.3) = the satisfactory design of air-conditioning sys- h2
F, 10. 1 degrees . Therefore, the actual dty-bulb tems .
lld temperature of the air leaving the washer In Section 5-3 sensible cooling of moist air
would be 62 - 10.1 = 51.9°F = 17 • was discussed. However, as may be recalled,
On Fig. 5-29 locate the intersection of 17 = we were concerned at that time with the pro-
es
51.9°F and 1W'J = 49.8°F. Find h7 = 20.1 cess of warm supply air providing the sensible
Btu/lb da, W7 = 50 grains /lb da, and v7 = heat to overcome heat loss from the condi- (a)

1g 13.04 fellb da. tioned space. We are now concerned with sup-
plying air to a conditioned space at a suffi-
Step 2: Determine final air properties after
c- ciently reduced dry-bulb temperature below the
reheating.
1e space design dry-bulb temperature to absorb
The reheating process is a sensible-heating the sensible heat gains to the space. The sup-
process at constant humidity ratio (W8 = W7 = ply air must also be at a sufficiently reduced
50 grains/lb da). On Fig. 5-29 draw a constant humidity ratio to absorb the latent heat gains ---,w,
humidity ratio line from point 7 to intersect 18 to the space. ~ 1 W2
of
at l15°F. At point 8 find 1w8 = 72.2°F, h8 = Figure 5-30a represents a typical cooling
35.5 Btu/lb da, and v8 = 14.65 fellb da. coil using chilled water in the tubes. If the
chilled water circulated through the tubes is
Step 3: Determine the amount of reheat
at a temperature low enough to maintain the air-
required. By Eq. 5-4, (b)
side surface temperature of the coil below the
dew-point temperature of the entering air, the Figure 5-30
/lsg = rna? (hg - h7)
properties of the air passing through the de- Schematic Illustration of cooling and
(1384)(60)(35.5 - 20. 1) humidifying coil may be represented as shown dehumidification
/lsg = 1,278,800 Btu/hr in Fig. 5-30a. The dry- and wet-bulb tem-
lt peratures, humidity ratio , and enthalpy of the
5-11 COOLING AND entering air are reduced. The psychrometric malhl = ma2h2 + qc + mwhw (5-31)

g DEHUMIDIFICATION OF AIR process of cooling and humidification of the air


mal ma2 (5-32)
l-
from condition 1 to condition 2 is represented
The preceding sections of this chapter have on Fig. 5-30b if all the air uniformly and per- mal WI ma2W2 + mw (5-33)
been concerned primarily with the heating fectly contacts the chilled surface of the coil.
and/or humidification of air to provide supply The moisture could be condensed from the air at Note that these three equations are similar to
b air to a conditioned space which would over- a variable temperature from the initial dew- Eqs. (5-18), (5-19), and (5-20) with the signs
I. c ome heat losses and provide for satisfactory point temperature (A) to the final saturation changed on iJs and mw. The process of cooling
y humidity conditions. We will now conc~m temperature (12 ). If the condensed moisture is and dehumidification between points 1 and 2
b ourselves with cooling and dehumidification of brought to the final temperature (12 ) before on Fig. 5-30b may be represented by a straight
d air supplied to a space. This air would be used draining from the system, we may write the line (1-2) on the psychrdmetric chart. There is
to overcome the heat gains and moisture gains following steady-flow energy and material-bal- no problem here because we are normally con-
y of the space. ance equations. cerned with only the. initial and final air con-
208 APPLIED PSYCHROMETRICS

dition . Combining Eqs. (5-31) and (5-32) we or


have
iJL ~ rna(WJ - W2)(1055) (5-36)
q, = rna (h, - h2) - rn.Jzw (5-34)
wra = 64
If standard air is assumed with W1 and W2 ex-
and from Eqs. (5-32) and (5-33) we have pressed in units of grains/lb da, Eq. (5-36) be-
comes
~
~~
---1 ... -·~
I W = 58.7
W =56.7

rnw = rna (W, - W2) (5-35)


. (1055)(0.075)(60)(cfm)(W 1 - W2) a
qL = 7000 55 F 60 F 65 F 78 F
In the above equations hw would be the en- g
thalpy of saturated water at the final air dew- Figure 5-31 r.
point temperature or at a specified water tem- or Schematic psychrometric chart for
perature. Illustrative Problem 5-12
We may also look at the process of Fig.
5-30b and assume that air supplied to a space
qL = 0 .68 cfm(W 1 - .W2) (5-37)

at condition 2 will absorb sensible and latent "ra" refers to room air condi-
where
heat as it changes to condition 1. If condition tion.) From Eq. (5-9)
1 is the space design conditions to be main- qL = latent heat absorbed by supply
tained, then air may be supplied to the space
at condition 2. air from condition 2 to iJs = 1.10 CFMsa {tra - tsa)
By using Eq . (5-9) with the temperature condition 1 (in Btulhr)
difference expressed as t 1 - t2 and assuming or
cfm = supply air quantity at standard
various values of t2, it is possible to determine
the quantity of standard air required to absorb conditions iJs 50,000
the sensible heat load; or the air quantity to be W1 and W2 space and supply air humidity cfmsa = 1.1 O{tra - tsa) 1.10(78 - 55)
supplied may be arbitrarily selected and the re- cfmsa = 1976 (ans)
ratios, respectively,
quired supply air temperature (t2) may be cal-
culated for a given sensible heat load. In either (grains/lb da) Step 2: Determine the humidity ratio of
case it will be necessary to establish the hu- i1
the supply air.
midity ratio (W2) of the supply air if there is to d
Illustrative Problem 5-12 Each pound of air supplied at 55°F must n
be a simultaneous removal of latent heat as
have a humidity ratio sufficiently depressed d
well as the sensible heat. Assume that a given space has a calculated
As may be seen in Fig . 5-30b, the humidity below the design humidity ratio of the space s
sensible heat gain of 50,000 Btu/hr and a latent to absorb the latent heat load while rising to s
ratio of the supply air (W2) is Jess than that of heat gain of 12,500 Btu!hr with a space design
the conditioned space (W1). At low partial the space condition, or the vertical distance 0
condition of 78°F and 45 percent RH. Deter- (Wra - WsJ = aw. From Eq. (5-37) ~
pressures , approximately 1055 Btu are re- mine the supply air quantities and respective
quired to condense or evaporate 1 lb of water. properties if the supply air temperature is as-
Equation 5-35 gives the amount of moisture signed values of 55°F, 60°F, and 65°F. _t.
change in the air. Therefore, the latent heat Supply Air
(qL) associated with this moisture may be Temperature t,.-t.. cf
Solution: (See Fig. 5-31)
found by multiplying Eq. (5-35) by h1g =
1055, or Step 1: Using a supply air temperature 55 23 19
t58 = 55°F, determine the quan- 60 18 25
65 13 34
iJL = rn.Jzw = rna(W, - W2)hfg tity of supply air. (Subscript
APPLIED PSYCHROME:TRICS 20

or qL
11W = Wra - w•• = 0.68 CFMsa
qL ~ ma{Wt - W2)(1055) (5-36)
12,500
w,. = 64 0 .68(1976)
If standard air is assumed with W1 and W2 ex·
pressed in units of grains/lb da, Eq. (5-36) be· • ~
.,.... ~~I I W = 58 .7
W = 56 .7 11W = Wra - Wsa = 9 .3 grains/lb da
comes
From the psychrometric chart at tra = 78°F
. (1055)(0.075)(60)(cfm)(W 1 - W2) and RHra = 45 percent, find Wra = 64
55 F 60 F 65 F 78 F
qL = 7000 grains/lb da. Therefore, the required humidity
Figure 5-31 ratio of the supply air will be
or Schematic psychrometric chart for
Illustrative Problem 5-12 Wsa = Wra - 11W = 64 - 9.3

qL = 0 .68 cfm(W 1 - W2) (5-37) w•• = 54.7 grains/lb da

"ra" refers to room air condi· Step 3: Plot the values of t58 = 55°F and
where tion .) From Eq. (5-9) w.. = 54.7 grains/lb da on Fig.
qL = latent heat absorbed by supply 5-31.
air from condition 2 to qs = 1.10 CfMsa (Ira - tsa) Step 4: Perform similar calculations to
condition 1 (in Btulhr) determine the values of w•• for
or r•• = 60°F and 65°F. The results
cfm = supply air quantity at standard are shown in the table b.elow.
conditions q. 50,000
cfmsa = tsa) Step 5: Plot the above corresponding val-
1.10(78 - 55)
W1 and W2 = space and supply air humidity ues of tsa and Wsa on Fig. 5-31.
cfm•• = 1976 (ans)
ratios, respectively,
By observing the plotted points on Fig. 5-31,
(grains/lb da) Step 2: Determine the humidity ratio of it may be noted that a straight line may be
the supply air. drawn through them and , when extended to the
Illustrative Problem 5-12 Each pound of air supplied at 55°F must right, will pass through the space design con-·
have a humidity ratio sufficiently depressed dition of 78°F DB and 45 percent RH . If this
Assume that a given space has a calculated below the design humidity ratio of the space same line is extended to the left, it will inter-
sensible heat gain of 50,000 Btu/hr and a latent to absorb the latent heat load while rising to sect the 100 percent RH curve at a temperature
heat gain of 12,500 Btu/hr with a space design the space condition, or the vertical distance of 49.6°F DB . This point is called the room
condition of 78°F and 45 percent RH. Deter· (Wra - w••) = 11W. From Eq. (5-37) apparatus dew point (tradp)
mine the supply air quantities and respective
properties if the supply air temperature is as·
signed values of 55°F, 60°F, and 65°F.
Supply Air
Temperature t,.-t.. cfm .. w.. - w.. w..
Solution: (See Fig. 5-31)
55 23 1976 9.3 54.7
Step 1: Using a supply air temperature 60 18 2525 7.3 56.7
t
58
= 55°F, determine the quan- 65 13 3496 5.3 58 .7
tity of supply air. (Subscript
210 APPLIED PSYC.HROMETRICS
t
It should be apparent that there could be an a: where RSHR refers to the ratio of the room DI
J:
infinite number of possible supply air temper- en loads. The slight variation in the above two an-
atures along this sloping line between 49.6°F swers may be accounted for by the difficulty of
and 78°F which would absorb the space sensi- 0 .800 reading accurate enthalpy values from the psy- B
ble and latent heat loads simultaneously. Also, chrometric chart. m
it may be noted by our calculations that, as the Whenever the space sensible and latent heat - 3
supply air temperature approaches the 100 per- loads are known, the slope of process line 1-2 th,
cent RH curve, the required cfm5a decreases may be determined by the sensible heat ratio. su
and would reach a minimum when the air This room sensible heat ratio (RSHR) is plot-
leaves the cooling device saturated at 49.6°F. Figure 5-32 ted on the psychrometric chart through the
It should also be apparent from the preceding Schematic psychrometric chart room design conditions parallel to the refer-
discussion that the supply air condition is depen- Illustrating sensible heat ratio (SHR) ence line through the alignment circle (78°F
dent on the slope of the line on Fig. 5-31 . While DB and 50 percent RH) and the sensible heat
the method of solution used in this illustrative of the supply air. The vertical line 3-1 referred ratio scale, as illustrated on Fig. 5-32.
problem is quite workable, a more simple and to the enthalpy scale defines the latent heat ca- From the above discussion, when the room
direct method is normally used by air-condi- sensible and latent loads are known, the nu- ps
pacity of the supply air. The line 2-1 referred
tioning engineers . to the enthalpy scale defines total heat capacity merical value of the room sensible ratio may cle
of the supply air. Therefore, be calculated. The sensible· heat ratio scale and ref1
5-12 SENSIBLE HEAT RATIO (SHR) alignhtent circle on the psychrometric chart is the
The sensible heat capacity, qs = h3 - h2 = used to establish the required slope of the per
In Section 5-8 and Problem 5-8 (Method 2) RSHR line. The actual process line is drawn
there was a brief discussion of the sensible 27.3 - ·21.8 = 5.5Btu/lbda parallel to this reference line and through the
heat ratio (sometimes called sensible heat fac- room design conditions. The required supply
tor, SHF). This ratio becomes a very useful The latent heat capacity, qL = h 1 - h3 =
air conditions entering the space mu,st be lo-
tool for the solution of problems concerned 28.7 - 27.3 = 1.4 Btu/lb da cated on this line.
with the cooling and dehumidification of air.
In Problem 5-8 the sensible heat ratio was de- The total heat capacity, q, = h 1 - h2 =
fined as 28.7 - 21.8 = 6.9 Btu/lb da

The sensible heat ratio is


SHR = . qs . = ~ (5-38)
qs + qL q,
SHR = qs = ~
Using the same basic data of Problem 5 -12 qs + qL 5.5 + 1.4
with the space condition at 78°F DB and 45 = 0.797 (say 0.800)
percent RH, and the supply air at a condition
of 55°F DB, W58 = 54.7 grains/lb da, we may The same result is found by taking the ratio of
replot these conditions on Fig. 5-32. Label the sensible and total heat loads of the space.
these points l and 2, respectively. From the
psychrometric chart the enthalpy values may
Using room sensible heat (RSH) and room la- •
tent heat (RLH), we have
be found as h 1 = 28.7 Btu/lb da and h2 =
21 .8 Btu/lb da. Construct the right triangle as RSH dB---.
shown, determine point 3, and find h3 = 27.3 RSHR = RSH + RLH 57 80
Btu/lb da .
The horizontal line 2-3 referred to the en- 50,000 = 0.800 Figure 5- 33
thalpy scale defines the sensible heat capacity 50,000 + 12,500 Solution to Probler
APPLIED PSYCHROMETRICS 211

where RSHR refers to the ratio of the room Dlustrative Problem 5-13
cc loads. The slight variation in the above two an-
J:
en swers may be accounted for by the difficulty of A room has a sensible heat gain of 76,000
reading accurate enthalpy values from the psy- Btu!hr and a RSHR of o.g5 . The room is to be
0.800
chrometric chart . maintained at gooF DB and 40 percent RH . If
• Whenever the space sensible and latent heat 3000 cfm of air is supplied to the room, find
loads are known, the slope of process line 1-2 the required dry bulb and humidity ratio of the
may be determined by the sensible heat ratio. supply air.
This room sensible heat ratio (RSHR) is plot-
ted on the psychrometric chart through the Solution: (See Fig. 5-33.)
Figure 5-32 room design conditions parallel to the refer-
Step 1: Determine the location of the
Schematic psychrometric chart ence line through the alignment circle (7goF
Illustrating sensible heat ratio (SHR)
RSHR line on the psychrometric
DB and 50 percent RH) and the sensible heat
chart.
ratio scale, as illustrated on Fig. 5-32.
of the supply air. The vertical line 3-1 referred From the above discussion, when the room Construct the reference RSHR line on . the
to the enthalpy scale defines the latent heat ca- sensible and latent loads are known , the nu- psychrometric chart through the alignment cir-
pacity of the supply air. The line 2-1 referred merical value of the room sensible ratio may cle and o.g5 on the SHR scale. Parallel to this
to the enthalpy scale defines total heat capacity be calculated. The sensible· heat ratio scale and reference line construct the RSHR line through
of the supply air. Therefore, alignment circle on the psychrometric chart is the room design conditions of gooF DB and 40
used to establish the required slope of the percent RH . ·
The sensible heat capacity, qs = h3 h2 = RSHR line. The actual process line is drawn
- Step 2: Determine properties of the supply
parallel to this reference line and through the
27 .3 - 21.g = 5.5 Btu/lb da room design conditions. The required supply
air. By Eq. 5-9,

The latent heat capacity, qL = h1 - h3 air conditions entering the space ml(st be lo-
2g.7- 27.3 = 1.4Btu/lbda
cated on this line. iis = (1.10 cfm••)(trm - t•• )

The total heat capacity , q1 = h 1 - h2 =


2g .7 - 21.g = 6.9 Btu/lb da

The sensible heat ratio is

SHR = iis = ~ a:
I
iJs + iJL 5.5 + 1.4 en
= 0.797 (say o.gOO)

The same result is found by taking the ratio of


the sensible and total heat loads of the space.
7-40%_ t w
Using room sensible heat (RSH) and room la- 1\:RSHF >jRoom air (ra)
·

tent heat (RLH), we have Supply air (sa)


dB----. RSHR = 0.85
RSH 57 80
RSHR = RSH + RLH
Figure 5-33
50,000 = o.goo Solution to Problem 5-13
50,000 + 12,500
76,000 = 1. 10(3000)(80 t ..) q.
RSHR = q. + iJL the supply air any combination of dry- and cula
t,. = 57°F wet-bulb temperatures that intersect on the .The
RSH 42,000 RSHR line. In practice, however, the combi- ben
Locate the point where the dry-bulb temper- RSH + RLH 42,000 + 14.000 nation of dry- and wet-bulb temperatures se- tern
ature 57°F intersects the RSHR line. This is RSHR = 0.75 lected for the supply air must be one that can eve
the condition of the supply air. Read Wsa . = be obtained with the equipment used to cool prin
55 .5 grains/lb da, RHsa = 80 percent, hsa = Step 2: Determine the dew-point temper- the air. Air is ordinarily delivered to the con-
22.2 Btu/lb da, 1.,58 = 53.4°F. ature of the supply air. Determine ditioned room in the same state that it leaves a
the point where t 58 = 56°F inter- the cooling equipment. The conditioning
sects the RSHR line. From the t
Illustrative Problem 5-14 equipment selected must, therefore, be able to
chart at this point find tdp = .reduce the dry- and wet-bulb temperatures of
50.5°F (ans)
lllu
A room within a building has a sensible the supply air to a point that will fall on the
heat gain of 42,000 Btu/hr and a latent heat Step 3: Determine supply air quantity . By RSHR line for the room in question .
gain of 14,000 Btu/hr. The room design con- Eq. 5-9, Air can be cooled to many different combi-
75°
ditions are 76°F DB and 63°F WB. Air is to be nations of dry- and wet-bulb temperatures, the .
gai
supplied to the room at 56°F DB . How much iJs = (1 . 10 cfm58 )(tnn - fsa) exact combination depending on the design
he a
supply air must be used and what will be the 42,000 = 1.IO(cfm58 )(76 - 56) of the cooling equipment. Equipment of the
cha
supply air dew-point temperature? type ordinarily used tends to provide supply '
cfm58 = 1909 (say 1900 cfm) (ans) sue
air having high relative humidities, in the
RH
Solution: (See Fig. 5-34.) 5-13 THE CONDITIONED AIR order of 90 percent relative humidity, though
pel
SUPPLY lower or higher relative humidities are obtain-
Step 1: Determine the RSHR and plot the
able.
RSHR line on the psychrometric Theoretically, the designer of an air-condi- In any actual . air-conditioning installation
chart. By Eq. 5-38, tioning system may select for ~e condition of
• the sensible and lat~nt heat gains can be cal-

a:
I
U)

--- w
RSHR
= 0.75

dB--.
56 76
t • dB___.
55 75
Figure 5-34
Figure 5-
Solution to Problem 5-14
Solutlon to Prot
APPLIED PSYCHROMETAI''

;HR=~ the supply air any combination of dry- and culated by methods presented in later chapters .
qs + qL wet-bulb temperatures that intersect on the .The required dry- and wet-bulb temperatures to
RSH 42,000 RSHR line. In practice, however, the combi- be maintained in the conditioned space are de-
nation of dry- and wet-bulb temperatures se- termined by the type of QCCupancy. So in
RSH + RLH 42,000 + 14,000
lected for the supply air must be one that can every installation the problem resolves itself
RSHR = 0.75 be obtained with the equipment used to cool primarily into finding two quantities:
Step 2: Determine the dew-point temper- the air. Air is ordinarily delivered to the con-
ature of the supply air. Determine ditioned room in the same state that it leaves a. the amount of supply air required
the point where t 5a = 56°F inter- the cooling equipment. The conditioning
b. the condition of the supply air
sects the RSHR line. From the equipment selected must, therefore, be able to
chart at this point find tdp = reduce the dry- and wet-bulb temperatures of
lllustrative Problem 5-15
50.5°F (ans)
the supply air to a point that will fall on the
RSHR line for the room in question.
Step 3: Determine supply air quantity. By A conditioned room is to be maintained at
Air can be cooled to many different combi-
Eq. 5-9, 75°F DB and 50 percent RH. The sensible heat
nations of dry- and wet-bulb temperatures, the .
gain of the room is 14,000 Btu/hr. The latent
exact combination depending on the design
i:J.s = (1.10 cfmsa)(trm - fsa) heat gain of the room is 3000 Btu/hr. If the
of the cooling equipment. Equipment of the
42,000 = 1.10(cfm5a)(76 - 56) characteristics of the cooling equipment are
type ordinarily used tends to provide supply
such that the air leaving it has a 90 percent
cfmsa = 1909 (say 1900 cfm) (ans) air having high relative humidities, in the
RH, find the required dry- and wet-bulb tem-
order of 90 percent relative humidity, though
·13 THE CONDITIONED AIR peratures of the supply air.
lower or higher relative humidities are obtain-
UPPLY able.
Solution:
Theoretically, the designer of an air-condi- In any actual . al!-conditioning installation
oning system may select for the condition of the sensible and latent heat gains can be cal- Step 1: Determine RSHR

c: c:
I I
(/) U)

50% I
--- w
RSHR
= 0.75
w
'RSHR
= 0.82

t dB____.
55 75
t
34 Figure 5-35
blem 5-14 Solution to Problem 5-15
214 APPLIED PSYCHROMETRICS
wra = 86 grains/lb da (ans) A
RSHR = RSH = 14,000 25,000 Btu/hr and a latent heat gain of K:\00 de
RSH + RLH 14,000 + 3000 Btu/hr. If the room is to be maintained ot K0°F Step 3: Determine the supply air quantity m:
DB by thermostat, find the resulting Rl l und (cfmsa). By Eq. 5-9, re.
RSHR = 0.823 (say 0.82)
humidity ratio in the cond'itioned room . !low co
much air is being supplied to the room? q. = (1.10 cfm.a)(t.a - t.a)
Step 2: Construct RSHR line on psychro-
metric chart. 25,000 = (1.10 cfm58 )(80 - 63)
.· On Fig. 5-35 locate room design conditions Solution: (ans)
cfmsa = 1337
. at 75°F DB and 50 percent RH. Using the Step 1: Determine the RSHR .
alignment circle and the SHR scale, construct Problems 5-15 and 5-16 dealt with selecting
the reference RSHR line. Parallel to this ref- RSH 25,000 the condition of the supply air; no reference
erence line construct the actual RSHR line RSHR = RSH + RLH = 25 ,000 + 8300 has been made of selecting the volume of sup-
through the room design condition and extend ply air. To begin by arbitrarily selecting the air
to the left to intersect the 100 percent RH
RSHR = 0.7507 (say 0.75)
volume is equivalent to fixing the dry- and
curve. Where this RSHR line interesects the 90 wet-bulb temperatures of the supply air with-
Step 2: Locate RSHR line on psychro-
percent RH curve, find the condition of the air out first ascertaining whether air at these tem-
metric chart.
leaving the cooling apparatus, which is also peratures can be obtained by use of the condi-
the supply air condition to the space. Read On Fig. 5-36 locate the supply air condition tioning equipment. This point is illustrated by
158 = 55°F, 1w = 53.4°F. (ans) at tsa = 63°F, RHsa = 90 percent. Using the the following problem.
58
alignment circle and the SHR scale, construct J ,
Illustrative Problem 5-16 the reference RSHR line. Parallel to this ref- Illustrative Problem 5-17
erence line construct the actual RSHR line
Air leaves a bank of cooling coils at 63°F through the supply air condition and extend to The sensible. heat gain to a room is 18,200
DB and 90 percent RH. The room to which the the right to intersect the 80°F DB line. At this Btu/hr and its latent heat gain is 4500 Btu/hr.
air is delivered has a sensible heat gain of point find RHra = 57 percent,

a:
I
(/)

~
RSHR <:>-- ·
= 0.75
w
"----+----+-------J
dB--.
63 80
t •
dB--.
71

Figure 5-
Figure 5-36
Solutlon to Pro
Solution to Problem 5-16
APPLI ED PSYCHFIOMrl Ill

Wra = 86 grains/lb da (ans) A conditioned air supply of 1200 cfm is tu hr


25,000 Btu/hr and a latent heat gain of 8300 delivered to the room. If the room is tu he
Btu/hr. If the room is to be maintained at 80°F Step 3: Determine the supply air quantity maintained at 85°F DB and 69°F WB , find the
DB by thermostat, find the resulting RH and (cfm.J. By Eq. 5-9 , required wet- and dry-bulb temperatures of the
humidity ratio in the conditioned room. How conditioned supply air.
much air is being supplied to the room? • qs = (1. 10 cfmsa)(tra - tsa)
Solution:
25 ,000 = (1.10 cfm )(80 -
83 63)
Solution: Step 1: Determine the dry-bulb tempera-
cfmsa = 1337 (ans)
Step 1: Determine the RSHR. ture of the supply air (t83 ). By Eq.
(5-19) ,
Problems 5-15 and 5-16 dealt with selecting
R HR = RSH = 25 ,000 the condition of the supply air; no reference
iJs = (1.10 cfm8 3 )(tra - t83 )
S RSH + RLH 25,000 + 8300 has been made of selecting the volume of sup-
RSHR = 0. 7507 (say 0. 75) ply air. To begin by arbitrarily selecting the air 18,200 = 1.1 0(1200)(85 - t88)
volume is equivalent to fixing the dry- and tsa = 71.1 °F (say 71 °F)
Step 2: Locate RSHR line on psychro- wet-bulb temperatures of the supply air with-
metric chart. out first ascertaining whether air at these tem- Step 2: Calculate the RSHR.
peratures can be obtained by use of the condi-
On Fig. 5-36 locate the supply air condition tioning equipment. This point is illustrated by RSH 18,200
at tsa = 63°F, RHsa = 90 percent. Using the the following problem.
alignment circle and the SHR scale, construct
RSHR = RSH + RLH 18,200 + 4500
the reference RSHR line. Parallel to this ref- Illustrative Problem 5-17 RSHR = 0.802 (say 0.80)
erence line construct the actual RSHR line
through the supply air condition and extend to The sensible heat gain to a room is 18,200 Step 3: Locate RSHR line on psychro-
the right to intersect the 80°F DB line. At this Btulhr and its latent heat gain is 4500 Btu/hr. metric chart.
point find RHra = 57 percent,

a:
/J I a:
I
I
(/)

(/)

o ______
_.ra
.-- RSHR
= 0.75
• "'S..---+-1 RSHR
•u
= 0.80
w
w

t dB____.
t
71 85
80
Figure 5-37
re 5-36
Solution to Problem 5-17
Problem 5-16
216 APPLIED PSYCHROMETRICS

On Fig. 5-37 locate the room air condition Return air


at 85°F DB and 69°F WB . Using the SHR
scale,. construct the reference RSHR line. Par-
allel to this reference line and through the Bypassed return air
room design conditions draw the actual RSHR
line and extend to the left. Where the. dry- ·
bulb temperature of the supply air tsa = 71 °F Supply
intersects the RSHR line find, twsa = 63 .5°F, air
RHsa = 68 percent.
This would be a difficult supply arr condi-
tion to obtain without extensive modification
of the system. It is always best to select the
supply air condition before determining the re- Dehum idifier
quired supply air quantity, as was done in when used
Problem 5-16. 78
Figure 5-38
BYPASSED RETURN AIR: Figure 5-38 is Figure 5
a schematic drawing of a system where a por- Schematic: Return air bypass system
Solution to PrCl
tion of the air drawn from the conditioned
room is admitted to the inlet of the supply fan
without passing through the cooling equip- 50 percent RH. The specifications require a to- Draw RSHR line on chart through room de-
ment. The air supplied to the fan in this man- tal air volume flow of 6000 Cfm to be circu- sign conditions and extend to the left 'to inter-
ner is known as "bypassed return air." The air lated. Find the following: sect the 90 percent RH curve. At this point
entering the fan is a mixture of chilled air and find t = 57.5°F DB and tw = 55.8°F WB.
the bypassed return air. Only the chilled air a. the dry- and wet-bulb temperatur.es of This .is the condition of the chilled SUP.Plv air.
portion of the mixture can absorb sensible and the chilled air leaving the cooling coil if .1; 7 Cf· I (,. ; /3 . 1- L
its RH is 90 percent Step 2: Find volume flow of chilled sup-
latent heat in the conditioned space. The rea-
ply air. By Eq. (5-9),
son is that the dry-bulb and dew-point temper- b. the volume of air to be cooled and de-
atures of the bypassed return air are equal to humidified
those of the room air, whereas the air chilled i:Js = (1.10 cfm.a)(tra - tsa)
by the coil is at a lower dry-bulb and dew- c. the volume of return air to be bypassed 80,000 = (1.10 cfmsa)(78- 57.5)
point temperature. In problems involving mix- d. the dry- and wet-bulb temperatures of cfm53 = 3548 (volume flow of chilled air)
tures of bypassed return air and conditioned the mixture of chilled and bypassed re-
air, the bypassed return air may be neglected turn air delivered to the room Step 3: Determine volume flow of return
entirely, and the problem figured as though
air.
chilled air alone were being delivered to the Solution:
conditioned room. The total volume flow of air was set at 6000 '
Step 1: Determine RSHR line and locate cfm. Therefore, the bypassed return air would
Illustrative Problem 5-1St on psychrometric chart. be·
'J-3. q.~ • rl
A room has a sensible heat gain of-so,OOO RSHR RSH 80,000 Bypassed Return Air (cfmra) = 6000 - 3548
RSH + RLH 80,000 + 20,000 I
Btulhr and a latent heat gain of 20,000 Btu!hr;$ , f-C
= 2452 cfm
The room is to be maintained at 78°F DB and RSHR 0.80
as-. s~-
tExtracted from Trane Air Conditioning Manual, The Trane Company, LaCrosse, Wisconsin, p. 106, 1965 ,
with permission. tExtracted from Trane Air Conditioning Manual , The Tra
APPLIED PSYCHROMF l IW'

Return air

u..
Bypassed return air I
en

50%
RSHR
---
' w = 0.80

Ou tsi de ai r Dehum idifier


~+----+---------' t
wh en used 78
Figure 5-38 Figure 5-39
Schematic: Return air bypass system Solution to Problem 5-18

50 percent RH . The specifications require a to- Draw RSHR line on chart through room de- Step4: The mixture condition of chilled air
tal air volume flow of 6000 Cfm to be circu- sign conditions and extend to the left to inter- · and bypassed return air may be
lated. Find the following: sect the 90 percent RH curve. At this point found as follows . By Eq. 5-17,
..-., find t = 57SF DB and tw = 55.8°F WB .
a. the dry- and wet-bulb temperatur,es of This .is the condition of the chilled SUP.IPlv air. cfm88 X t58 + cfmra X tra
the chilled air leaving the cooling coil if I Cf· l <. ; Jo • ·t.-1. tmix
Step 2: Find volume flow of chilled sup- cfmtotal
its RH is 90 percent
ply air. By Eq. (5-9), 3548 X 57 .5 + 2452 X 78
b . the volume ~f air to be cooled and de-
6000
humidified iJs = (1.10 cfmsa)(tra - tsa)
tmix 65 .87 (say 65.9°F)
c. the volume of return air to be bypassed 80,000 (1.10 cfm88)(78 - 57 .5)
d. the dry- and wet-bulb temperatures of cfmsa = 3548 (volume flow of chilled air) The mixture temperature <tmix) must be the
the mixture of chilled and bypassed re- air temperature entering the room and must fall ·
turn air delivered to the room Step 3: Determine volume flow of return on the RSHR lir:e (0.80). At the point of inter-
air. section with tmix = 65 .9°F, find twmix =
Solution: 59.8°F, Wmix = 67 grains/lb da.
The total volume flow of air was set at 6000
Old fallacies die hard. t One that has been
Step 1: Determine RSHR line and locate cfm. Tderefore, the bypassed return air would
most persistently long-lived is the belief that
on psychrometric chart. be
uncomfortable drafts result in a conditioned
room if the temperature of the supply air is
RSHR = RSH = 80,000 Bypassed Return Air (cfmra) 6000 - 3548
low. It is just as possible to have a drafty room
Fe RSH + RLH 80,000 + 20,000 2452 cfm with a warm air supply as with a cold air sup-
RSHR = 0.80

ane Company , LaCrosse, Wisconsin , p. 106, 1965 ,


t Extracted from Trane Air Conditioning Manual, The Trane Company , LaCrosse, Wisconsin , p. 107 , 1965 .
218 APPLIED PSYCHROMETRICS

ply. The whole matter of draft p~ention is requirements must still be supplied, even The same effect as results from the above
one of properly introducing supply dir~ ·nto a though practically all return air is used. arrangement can be accomplished by throttling
room . Poorly designed and improperly 1 ated Where the volume of air that must be cir- the conditioned air supply by dampers or by
air outlets will always cause drafts , reg dless culated is larger than the volume of air that varying the speed of the supply air fan . Both
of the temperature of the supply air. With should be conditioned, the difference between of these introduce air distribution problems if
properly located air inlets of correct design, the two-that is, the balance of the air needed carried beyond certain limits, while the bypass
there is little danger of drafts when introdvcing to make up the total which must be circu- system insures a constant rate of air supply .
air at temperatures usually needed to maintain lated-should be withdrawn from the room
r4he required temperature and humidity of a and bypassed. (The use of bypass is suggested Dlustrative Problem 5-19
conditioned room . In spite of this, specifica- here not as a method of draft prevention or of
tions fixing the lowest dry-bulb temperature at temperature control but only as a method of A room in which the sensible heat gain is
which an air supply may be introduced are oc- meeting the requirements of specifications that 160,000 Btu/hr and the latent heat gain ~7y_
casionally encountered. Usually these specifi- call for needlessly large volumes of air.) This 40,000 Btu/hr is to be maintained at 761lF-uB
cations fix the minimum temperature of the excess quantity of return air actually required and 50 percent RH . The specifications require
supply air at a point 10 to 15 degrees below to maintain the given room temperature and that the air supply shall be delivered to the I
the dry-bulb temperature being maintained in humidity should be conditioned. room at a temperature no lower than 6~e-:ll C'.,
the conditioned room. Usual temperature dif- Whenever possible, this excess return air chilled air leaves the conditioner at 90 percent
ferences are 17 to 25 degrees. should be eliminated because it contributes RH. Find the following:
Fixing both the dry-bulb temperature of the nothing toward the maintenance of the desired
room and the lowest dry-bulb temperature at room conditions. The bypassed return air is a. the quantity of air to be conditioned by
which the air supply may be introduced is carried around through the duct system as so the cooling coils
equivalent to fixing both the temperature rise much dead weight only in order to circulate the
and the volume of the air supply. As the tem- specified larger air volume. The circulation of b. the total air quantity to be delivered to
perature rise of the air supply has been set, and larger air volumes than are needed has some the room
because the sensible heat gain of the room is a disadvantages. First, there is an increase in the c. the quantity of return air to be bypassed.
given amount, it is apparent that by ·choosfng first cost of the installation because of the
the dry-bulb temperature of the air supply, the larger ducts and fans needed. Second, there is
volume of chilled air that must be delivered is an increase in the operating cost because of the
automatically determined. This has been illus- larger fan motor required to circulate the ex-
trated in previous problems. Because of this, cess air.
many specifications call for definite volumes of The use of bypass return air is a means of
air to be supplied; these volumes have been controlling room design conditions at partial
calculated on some minimum assumed temper- loads. Whenever the actual room sensible heat
ature which may, or may not, be stated. load is less than the maximum design load (la-
Another situation that requires the circula- tent load has a tendency to remain more con-
tion of larger air volumes than are desirable stant thatl sensible load), the room temperature
sometimes arises in the larger cities because of will be decreased if the design quantity of con-
their ventilation ordinances. If larger volumes ditioned air is supplied. When the room loads
of air then are needed are cooled and dehumi- are at the maximum design values, the return •
dified, the humidity in the conditioned space air bypass would be closed, but as these loads dB---+-·t.a ·
will frequently be too high. However, the re- decrease , the bypass damper would be opened 61 76
quirement that the entire air supply be taken proportional to the decrease in the room load ,
from outdoors is often waived, but the volume thus preventing a decrease ·in the room temper- . Figure
of air circulated according to these ventilation ature. Solution to P1
APPLIED PSYCHROMETRICB 219

Solution:
requirements must still be supplied, even The same effect as results from the above
though practically all return air is used. arrangement can be accomplished by throttling Step 1: Determine RSHR line and locate
Where the volume of air that must be cir- the conditioned air supply by dampers or by on psychrometric chart.
culated is larger than the volume of air that varying the speed of the supply air fan . Both
should be conditioned, the difference between • of these introduce air distribution problems if
carried beyond certain limits, while the bypass 160,000 = 0.80
the two-that is, the balance of the air neede<;l RSHR
to make up the total which must be circu- system insures a constant rate of air supply. 160,000 + 40,000
lated-should be withdrawn from the room
and bypassed. (The use of bypass is suggested Illustrative Problem 5-19 Step 2: Determine required quantity of
here not as a method of draft prevention or of chilled air (subscript "ca"). By
temperature control but only as a method of A room in which the sensible heat gain is Eq. (5-9),
meeting the requirements of specifications that 160,000 Btu/hr and the latent heat gain ~1 y. *'IL
call for needlessly large volumes of air.) This 40,000 Btu/hr is to be maintained at 76'¥-uB I
qs = (1.10 Cfffica)Ura - tea)
excess quantity of return air actually required and 50 percent RH. The specifications require
that the air supply shall be delivered to the I 160,000 = (1.10 cfmcJ(76 - 55.3)
to maintain the given room temperature and
humidity should be conditioned. room at a temperature no lower than 6~e~ '·II cfmca = 7027
Whenever possible, this excess return air chilled air leaves the conditioner at 90 percent
should be eliminated because it contributes
nothing toward the maintenance of the desired
room conditions. The bypassed return air is
RH. Find the following:

a. the quantity of air to be conditioned by


Step 3: Determine total quantity of supply
.
air.
.
carried around through the duct system as so the cooling coils According to the problem, the supply air to
much dead weight only in order to circulate the b. the total air quantity to be delivered to the conditioned space must have a temperature
specified larger air volume. The circulation of of 61°F. Therefore, the total quantity of supply
the room
larger air volumes than are needed has some air would be
disadvantages. First, there is an increase in the c. the quantity of return air to be bypassed.
first cost of .the installation because of the
larger ducts and fans needed. Second, there is
an increase in the operating cost because of the
larger fan motor requiied to circulate the ex- u...
cess air. I
CJ)
The use of bypass return air is a means of
controlling room design conditions at partial
loads. Whenever the actual room sensible heat
load is less than the maximum design load (la- 50% RSHF
tent load has a tendency to remain more con- =O.BO
stant than sensible load), the room temperature w
will be decreased if the design quantity of con-
ditioned air is supplied. When the room loads
are at the maximum design values, the return
air bypass would be closed, but as these loads
l
61 76
decrease, the bypass damper would be opened
proportional to the decrease in the room load, Figure 5-40
thus preventing a decrease .in the room temper-
Solution to Problem 5-19
ature.
qs = {1.10 cfm 58 )(1ra - 158 )
Outside C
160,000 (1.10 cfm 53 )(76 - 61) air~

cfmsa 9697
Room apparatus

8.-....- --
Step 4: Determine quantity of bypass air. D
dew point (tradp)
~ ~ · _.-;Roo m air
II: ~.-uo A
Bypassed air cfmsa ~ cfffica
9697 - 7027
Bypassed air = 2670 cfm

5-14 COOLING COIL PERFORMANCE Figure 5-41

In Section 5-13 ~ertain conditions were as- Actual perfo~~nce of an extended Relations
surface cool7'g and dehumidifying GSHR (cc
sumed for the supply air. The major assump-
coli
tion was that the air leaving the cooling coil
was at a relative hvmidity of 90 percent. Fur- air at this point, the room loads could no
ther, it was assum¥ that the air entering the and room return air at condition A . Whenever absorbed to produce the desired room co
cooling coil was recirculated return air from possible, outside air used for ventilation tions at point A. From the above discussior
the conditioned space. The latter assumption should be brought in through the dehumidify- may see that the design engineer may se
would be correct only when no outside air was ing equipment in order to reduce the effects of coils of varying depth, vary the refrige
introduced to the conditioned space for proper the outside air on the room Load to a mini- temperature, or vary the face velocity to ob
ventilation. The actual condition of the air en- mum . This practice also increases the effective- the proper coil performance.
tering the cooling apparatus would normally be ness of the coil because the higher temperature The actual surface temperature of the c•
a mixture of return air from the conditioned and moisture content of the entering mixture, ing coil could range from G to H on Fig. 5
space and outside fresh air for ventilation. compared to room air, raises the performance and is not of primary importance in evalua
Several factors influence the air-side perfor- level of the coil and increases the rate of heat coil performance. If point D represents
mance of a cooling and dehumidifying coil us- transfer. condition of air entering the coil and poir
ing a volatile refrigerant or chilled water. For In practice, the surface temperature of an the desired leaving condition, then a stra
a given coil configuration these factors are: extended surface dehumidifying coil is seldom line from D through F extended to the 100 1
uniform . The typical condition of the airstream cent RH curve establishes a single uniform
a. entering air condition, that is, dry- and as it passes through the coil is represented by surface temperature at point E which would
wet-bulb temperatures the curved line D 123451" with the refrigerant sult in the same leaving air condition . Poir
b. velocity of air flow, that is, usually es- temperature inside the coil at t,. The numbered is called an equivalent or effective coil surf
tablished by the coil face velocity (FV) , points (2, 3, 4, and 5) represent the number of temperature, IE, which can be considered
rows of coil depth and indicate the air condi- the uniform coil surface temperature w
c. coil depth in rows of tubes perpendicular tion produced by coils of varying depth with would produce the same leaving air conditi
to the airstream direction the refrigerant temperature and coil face veloc- as the variable coil surface temperature that
d. refrigerant temperature ity constant. If the refrigerant temperature curs when the coil is in operation . t It sho
and/or coil face velocity is changed, a different • be realized that the straight line DFE does
Figure 5-41 illustrates the actual perfor- . curve would result . The point of intersection
mance of an extended surface (finned) cooling between the RSHR line (AB) and the coil per-
tExtracted in part from Carrier System Design
and dehumidifying coi l. Line AB represents the formance curve, point E, represents the air Company , Syracuse, N.Y., 1972 , pp . 1- 120.
RSHR for a particular situation . The air enter- condition required to satisfactorily absorb the tExtrnctcd in part from Carrier System Design
ing the cooling coil is at point D , which rep- room sensible and latent heat gains . If an exact Company, Syracuse, N.Y., 1972 , pp . 1- 11 8.
resents a mixture of outside air at condition C number of rows of coil depth did not deliver
APPLIED PSYCHROMf Hll

I
Outsid e air (oa)
Outsi~e C
air- .cl
Mixture condition
entering cooling

~ Room apparatus apparatus (ea)


~~-----zo
2 1 I

RSH R A Room air


...
dew point (t,adp)
~«==
F
\\ "J
Room design condition (ra)

Supply air to room and


leaving aircondition from
cooling apparatur (t,. = t 18 )

Figure 5-41 Figure 5-42


Actual perfo~"J-"nce of an extended Relationship between RSHR and
surface cool_!rg and dehumidifying GSHR (cooling Coli Performance)
coli

air at this point, the room loads could not be necessarily represent a condition line describ-
and room return air at condition A. Whenever
absorbed to produce the desired room condi- ing the air condition as the air passes through
possible, outside air used for ventilation the coil. Rather, it represents the relationship
tions at point A. From the above discussion we
should be brought in through the dehumidify-
may see that the design engineer may select between the entering and leaving air conditions
ing equipment in order to reduce the effects of
coils of varying depth, vary the refrigerant and defines the effective coil surface tempera-
the outside air on the room load to a mini-
temperature, or vary the face velocity to obtain ture, tE . It also defines the grand sensible heat
mum. This practice also increases the effective-
the proper coil performance. ratio (GSHR) which represents the actual load
ness of the coil because the higher temperature
The actual surface temperature of the cool- conditions for the cooling coil. The point tE is
and moisture content of the entering mixture,
ing coil could range from G to H on Fig . 5-42 referred to as the coil apparatus dew point
:ompared to room air, raises the performance
and is not of primary importance in evaluating (tadp). This point E should not be confused
level of the coil and increases the rate of heat
coil performance. If point D represents the with point B, which is the room apparatus dew
ransfer.
condition of air entering the coil and point F point (tradp)· When no outside air is used (an
In practice, the surface temperature of an
the desired leaving condition, then a straight unusual situation), lines AB and DE coincide
:xtended surface dehumidifying coil is seldom
line from D through F extended to the 100 per- and the coil and room apparatus dew-point
miform. The typical condition of the airstream
cent RH curve establishes a single uniform coil temperatures will be the same. They will also
s it passes through the coil is represented by
surface temperature at point E which would re- be the same when the air leaving the cooling
1e curved line D 12345t, with the refrigerant
sult in the same leaving air condition . PointE coil is saturated at 100 percent relative humid-
!mperature inside the coil at t,. The numbered
is called an equivalent or effective coil surface ity.
oints (2, 3, 4, and 5) represent the number of
temperature, t£, which can be considered as
>ws of coil depth and indicate the air condi-
on produced by coils of varying depth with r the uniform coil surface temperature which
would produce the same leaving air conditions
GRAND SENSIBLE HEAT RATIO
(GSHR)::j: The grand sensible heat ratio is the
te refrigerant temperature and coil face veloc-
as the variable ~..'oil surface temperature that oc- ratio of the total sensible heat to the grand total
y constant. If the refrigerant temperature
curs when the coil is in operation. t It should heat load that the conditioning apparatus must
tdlor coil face velocity is changed, a different
be realized that the straight line DFE does not handle , including the outdoor heat loads. This
trve would result. The point of intersection
:tween the RSHR line (AB) and the coil per-
rmance curve, point £, represents the air tExtracted in part from Carrier System Design Manual, Part I, Load Estimating, Carrier Air Conditioning
Company, Syracuse, N.Y., 1972, pp. 1-120.
ndition required to satisfactorily absorb the
:!:Extracted in part from Carrier System Design Manual, Part I , Load Estimating, Carrier Air Conditioning
:>m sensible and latent heat gains. If an exact Company, Syracuse, N.Y. , 1972, pp . 1-118 .
mber of rows of coil depth did not deliver
ratio is determined from the following equa- mixture condition of the air entering the appa-
The required air quantity suppucu •v ... ~ - r--.
tion: ratus .
(cfmsa) is equal to the air quantity required
Referring again to Fig. 5-42, the point of
through the apparatus (cflll,ta), neglecting leak-
TSH TSH intersection between the GSHR line and the
= --- age losses. In Eq . (5-43) the term tea is the
GSHR (5-39) RSHR line must represent the air condition
TSH + TLH GTH mixture condition of the air entering the cool-
leaving the apparatus and entering the condi-
ing apparatus. The value of tea can only be de-
tioned space (t1a = t58). This neglects fan and
or, from Fig. 5-42 termined by trial and error, unless 100 percent
duct heat gains, duct leakage losses, and so
outside air is ( specified.
forth . In practice, these heat gains and losses
h,- hF BYPASSING OUTSIDE AIR:t Outdoor
GSHR are taken into account in estimating the cooling
ho - hF load. Therefore, the temprrature of the air air should not be bypassed .. Obviously, the ef-
leaving the apparatus is not necessarily equal fect of bypassing outdoor air is exactly the
In Eq. (5-39) to the temperature of the air supplied to the same as though this outdoor air were blown
space. This temperature difference is usually directly into the room by a separate fan. The
TSH = room sensible heat (RSH) + outside small (2 or 3 degrees); therefore, in our work fact that the outdoor air is mixed with the
air sensible heat (OASH) in the following problems, we will assume chilled air before being delivered to the condi-
(t1a = t58 ) unless otherwise stated. tioned space does not alter the truth of this
or statement.
REQUIRED AIR QUANTITY:t The quan- If outdoor air is delivered directly to a con-
tity of air required to offset simultaneously the
TSH = RSH + (1.10 cfilloJ(t0 a - t,a) (5-40)
room sensible and latent heat loads and the
ditioned room or, what amounts to the same
thing, is bypassed through the cooling coil, the
quantity of air required through the cooling ap-
and sensible and latent heat gains of the room will
paratus to handle the total sensible and latent be increased by exactly the amount of heat that
heat loads may be calculated using the condi-
TLH = room latent heat (RLH) + outside air tions on their respective RSHR and GSHR
the outdoor air surrenders in cooling down to
latent heat (OALH) the room dry-bulb and dew-point temperatures .
lines. For a particular application, when both Therefore, an additional amount of chilled air
the RSHR and GSHR lines are plotted on the supply will be required to offset the sensible
or
psychrometric chart, the quantity of air re- and latent heat gains due to the delivery of out-
quired to satisfy the room loads may be calcu-
TLH = RLH + (0.68 cfllloa)(W0 a - W,a) lated from
door air directly to the room.
(5-41) Unconditioned outdoor air, when delivered
to a conditioned room, will usually lower the
The slope of the GSHR line represents the ra- RSH sensible heat ratio of that room, thus making it
(5-42)
tio of sensible and latent heat that the cooling cfmsa = 1. 1O(tra - tsa) necessary to chill the supply air to a lower
apparatus must handle. The GSHR can be plot- temperature than would otherwise be needed.
ted on the psychrometric chart without know- The quantity of air required through the cool- Hence, if outdoor air is bypassed, not only
ing the condition of the supply air, in much the ing apparatus to satisfy the total air condition- must a larger volume of chilled air be pro-
same manner as the RSHR line, using the cal- ing load (including supplementary loads) may vided, but it must also be cooled to a lower
culated GSHR, the mixture condition of air en- be calculated from
I temperature.
tering the apparatus, the sensible heat ratio
TSH BYPASS FACTOR: Many practicing engi-
scale, and the alignment circle on the chart.
Cflll,ta = 1.1 0 Uea - tla) . neers take into account coil bypass factor (BF)
The resulting GSHR line is plotted through the (5-43)

tExtracted from Trane Air Conditioning Manual, 1
tExtracted in part from Carrier System Design Manual, Part 1, Load Estimating, Carrier Air Conditioning tCarrier, W. H. , " The Contact-Mixture Analogy ,
Company , Syracuse, N.Y ., 1972 , pp . 1-119.
Vapor," Transactions ASME, Vol. 59, p. 49 , 193'
APPLIED PSYCHnOMl 1111 ~

a- mixture condition of the air entering the appa-


The required air quantity supplied to the space when estimating the coil cooling l<lud nud NUp
ratus. ply air quantity . Some manufacturers rule thl' ll
(cfmsa) is equal to the air quantity required
Referring again to Fig . 5-42·, the point of cooling coils according to bypass factors. The
through the apparatus (cfll\ia) , neglecting leak-
intersection between the GSHR line and the theory:j: on which this practice is based is that
age losses. In Eq. (5-43) the term tea is the
9) RSHR line must represent the air condition all the air passing through a finned-tube cool-
mixture condition of the air entering the cool-
leaving the apparatus and entering the condi- ing coil does not contact the chjlled surface of
ing apparatus . The value of tea can only be de-
tioned space (t1a = tsa) . This neglects fan and the coil unless the coil is several rows deep
termined by trial and error, unless 100 percent
duct heat gains, duct· leakage losses, aneta so normal to the direction of air flow . In other
outside air is specified.
forth . In practice, these heat gains and iosses r
words the air leaving an extended surface cool-
are taken into account in estimating the cooling BYPASSING OUTSIDE AIR:t Outdoor
ing coil is a mechanical mixture of air which
load. Therefore, the temperature of the air air should not be bypassed .. Obviously , the ef-
has contacted the chilled surface and chilled to
leaving the apparatus is not necessarily equal fect of bypassing outdoor air is exactly the
that temperature and air which escapes (by- .
to the temperature of the air supplied to the same as though this outdoor air were blown
passed) through the coil in the same condition
space. This temperature difference is usually directly into the room by a separate fan . The
e as when it entered.
small (2 or 3 degrees); therefore, in our work fact that the outdoor air is mixed with the
The bypass factor is equal to the difference
in the following problems, we will assume chilled air before being delivered to the condi-
between the leaving air temperature and the
(t1a = t.J unless otherwise stated. tioned space does not alter the truth of this
mean surface temperature of the coil, divided
statement. by the difference between the entering air tem-
REQUIRED AIR QUANTITY:t The quan- If outdoor air is delivered directly to a con-
tity of air required to offset simultaneously the perature and the mean surface temperature of
I) ditioned room or, what amounts to the same
room sensible and latent heat loads and the the coil. Referring to Fig . 5-42, the bypass
thing, is bypassed through the cooling coil , the
quantity of air required through the cooling ap- factor would be
sensible and latent heat gains of the room will
paratus to handle the total sensible and latent be increased by exactly the amount of heat that
r
heat loads may be calculated using the condi- the outdoor air surrenders in cooling down to BF = tF - tE
tions on their respective RSHR and GSHR the room dry-bulb and dew-point temperatures. to - tE
lines . For a particular application, when both Therefore, an additional amount of chilled air
the RSHR and GSHR lines are plotted on the supply will be required to offset the sensible where tF = dry-bulb temperature of air
psychrometric chart, the quantity of air re- and latent heat gains due to the delivery of out- leaving coil
quired to satisfy the room loads may be calcu- door air directly to the room.
lated from Unconditioned outdoor air, when delivered
tE = coil mean (effective) surface
to a conditioned room, will usually lower the temperature
RSH (5-42) sensible heat ratio of that room, thus making it
cfmsa = 1. 1O(tra - tsa) t0 = dry-bulb temperature of air
necessary to chill the supply air to a lower
temperature than would otherwise be needed. entering coil
The quantity of air required through the cool- Hence, if outdoor air is bypassed, not only
ing apparatus to satisfy the total air condition- must a larger volume of chilled ' ir be pro- More generally, we may use the following
ing load (including supplementary loads) may vided, but it must also be cooled to a lower expression for the bypass factor:
be calculated from temperature.

TSH BYPASS FACTOR: Many practicing engi- BF = t,a - tadp (5-44)


neers take into account coil bypass factor (BF) tea - tadp
Cfll\Ja = 1.10 (tea - tla) (5-43)

tExtracted from Trane Air Conditioning Manual , The Trane Company, LaCrosse, Wisconsin, p. 109, 1965.
1ual, Part I , Load Estimating, Carrier Air Conditioning :j:Carrier, W. H. , " The Contact-Mixture Analogy Applied to Heat Transfer with Mixtures of Air and Water
Vapor," Transactions ASME, Vol. 59, p. 49 ,. 1937.
224 APPLIED PSYCHROMETRICS

Since the line DFE is a straight line, it is where 0.56 is the bypass factor of a single row
closely true that coil at a face velocity of 500 fpm and n is the
number of rows of coil depth. oa

W 18 - Wadp (5-45)
The bypass factor+ is a function of the
BF = Wea - Wadp physical and operating characteristics of the
air-conditioning a{'paratus and, as such, repre-
The quantity 1 - BF is frequently referred to sents that portion of the air which is considered
as the "contact factor" and may be considered to pass through the conditioning apparatus
to be that portion of the air leaving the cooling completely unaltered.
coil at the coil apparatus dew point. The physical and operating characteristics
affecting the bypass factor are as follows:
l _ BF = tea - tla _ W ea - Wla Figure 5-43
1. A decreasing amount of available appa-
tea - tadp - Wea - W adp (5-46) Effect of changing size of bypass
ratus heat-transfer surface results in an
factor (BF)
hea - hla increase in the bypass fact~r; that is, less
hea - hadp rows of coils, less coil surface area,
wider spacing of coil tubes . The effect of varying the bypass factor on
In Eqs. (5-44), (5-45), and (5-46) subscripts the conditioning equipment is as follows:
used are as follows: 2. A decrease in the velocity of air through
the conditioning apparatus results in a
decrease in bypass factor; that is, more 1. Smaller bypass factor
ea = entering air condition to cooling a. Higher adp-DX equipment selected
time for the air to contact the heat-trans-
apparatus fer surface. for higher refrigerant temperature and
Ia = leaving air condition from cooling chilled water equipment would be se-
Decreasing or increasing the amount of lected for less water flow or higher
"""" apparatus temperature chilled water. Possibly
heat-transfer surface has a greater effect on by-
adP\= air properties at the coil ap~atus pass factor than varying the velocity of air smaller refrigeration machine.
dew pqint ___/' through the apparatus . b. Less air-smaller fan and fan motor.
To properly maintain room design condi- c. More heat-transfer surface-more
The bypass factor of a coil of n rows deep tions, the air must be supplied to the space at rows of coil or more coil surface area
equals the bypass factor for one row raised to some point along the RSHR line. Therefore, as available.
the nth power. Experimentationt has indicated the bypass factor varies, the relative position d. Smaller piping if chilled water is
that the approximate bypass factor for ex- of the GSHR line and RSHR line changes, as used.
tended surface, %-in. OD tube, 13/32-in . high shown by the dotted lines on Fig. 5-43. As the 2. Larger bypass factor
helical fins, spaced 14 per inch, may be pre- position of the GSHR line changes, the enter- a. Lower adp-Lower refrigerant tem-
dicted by the followir.g empirical relationship: ing and leaving air conditions at the apparatus, perature to select DX equipment, and
the required air quantity , bypass factor, and more water flow or lower water tem-
BF = 0.56" the apparatus dew point also change. perature for chilled water equipment .
• Possibly larger refrigeration machine.
b. More air-larger fan and fan motor.
c. Less heat-transfer surface-less rows
t Carpenter, James H., " Fundamentals of Psychrometries," Carrier Air Conditioning Company , Syracuse,
New York , p. 17 , 1962.
of coil or less coil surface available.
+Extracted in part from Carrier System Design Manual, Part 1, Load Estimating, Carrier Air Conditioning d. Larger piping if more chilled water is
Company , Syracuse, N.Y., 1972, pp. 1-121 to 1-123 . osed.
APPLIED P S YC HI~ O MI I HI

is where 0.56 is the bypass factor of a single row It is, therefore, an economic oaltllll'C ul 11"1
coil at a face velocity of 500 fpm and n is the cost and operating cost in selecting lhc p111pl'r
number of rows of coil depth. oa bypass factor for a particular application . Tu
The bypass factor+ is a function of the ble 5-2 gives suggested ranges of bypass fuc
45) tors for various applications.
physical and operating characteristics of the
air-conditioning apparatus and, as such, repre-
to sents that portion of the air which is consi~red Illustrative Problem 5-20
ed to pass through the conditioning apparatus
ng completely unaltered. A conditioned r9P.!Y having ~.gsible and la-
The physical and operating characteristics tent heat gains of 40,000 and .6500 Btu/hr, ·re-
affecting the bypass factor are as follows: specJ}.vely, is to be maintained~77°F DB and
Figure 5-43 63°F WB . The outdoor air is af 95°F DB and
1. A decreasing amount of available appa- 78°~'\vB. The specifications require that 2400/./.J
16) Effect of changing size of bypass
ratus heat-transfer surface results in an
factor (BF)
Cf14 of air be delivered to the room. Of this
increase in the bypass fact~r; that is , less amount 25 percent is to be outdoor air and 75
rows of coils, less coil surface area, percent return air from the room. Find the fol-
wider spacing of coil tubes. The effect of varying the bypass factor on lowing:
ItS the conditioning equipment is as follows :
2. A decrease in the velocity of air through
a. the required dry- and wet-bulb tempera-
the conditioning apparatus results in a
1. Smaller bypass factor tures of the supply air to the conditioned
decrease in bypass factor; that is, more
a. Higher adp---DX equipment selected room
time for the air to contact the heat-trans-
fer surface. for higher refrigerant temperature and b. the dry- and wet-bulb temperatures of
chilled water equipment would be se- the air entering the cooling coils
Decreasing or increasing the amount of lected for less water flow or higher
temperature chilled water. Possibly c. the required condition of the chilled air
heat-transfer surface has a greater effect on by-
smaller refrigeration machine. supply leaving the cooling coils
pass factor than varying the velocity of air
through the apparatus. b. Less air-smaller fan and fan motor. d. the quantity of the air to be chilled by
To properly maintain room design condi- c. More heat-transfer surface--more the cooling coils ·
p tions, the air must be supplied to the space at ~
rows of coil or more coil surface area
•'<.
available. e. the quantity of air to be bypassed
0 some point along the RSHR line. Therefore, as
d the bypass factor varies , the relative position d. Smaller piping if chilled water is
used. Solution: (See Fig. 5-44)
of the GSHR line and RSHR line changes, as
~ shown by the dotted lines on Fig. 5-43 . As the 2. Larger bypass factor Step 1: Determine dry-bulb temperature
position of the GSHR line changes, the enter- a. Lower adp-Lower refrigerant tem- of supply air and RSHR line. By
ing and leaving air conditions at the apparatus, perature to select DX equipment, and Eq. 5-9,
the required air quantity, bypass factor, and more water flow or lower water tem-
the apparatus dew point also change. perature for chilled water,equipment. q. = (1.10 cfm••)(tra - r••)
Possibly larger refrigeration machine . 40,000 = 1.10(2400)(77 - r••)
b. More air- larger fan and fan motor. r•• = 61.8°F
c . Less heat-transfer surface- less rows
metrics," Carrier Air Conditioning Company, Syracuse, RSHR = RSH = 40,000
of coil or Jess coil surface available.
d. Larger piping if more chilled water is RSH + RLH 40,000 + 6500
1nual, Part 1, Load Estimating, Carrier Air Conditioning
23. used. RSHR = 0.86
226 APPLIED PSYCHROMETRICS

Table 5-2
Typical Bypass Factors*

Coli
Bypass
Factor Type of Application Example

0.30 to 0 .50 A small total load or a load that is Residence


somewhat larger with a low sensible
heat ratio (high latent load)

0.20 to 0 .30 Typical comfort application with a Residence, small retail shop, factory
relatively small total load or a low
sensible heat ratio with a somewhat
larger load
dB--:4 7
tadp
61.8 77
0. 10 to 0.20 Typical comfort application Department store , bank, factory

0.05 to 0.10 Applications with high internal sensible Department store , restaurant, factory
Flgur'
loads or requiring a large amount of
outdoor air for ventilation Solution to Probl

0.00 to 0 .10 All outdoor air application Hospital operating room, factory

*Extracted from Carrier System Design Manual, Part I , Load Estimating, Carrier Air Conditioning Company, Syracuse, If the GSHR line is extended downward and
N .Y., 1972, p . 1-127.
to the left to intersect the 100 percent RH
I"') On psychrometric chart (Fig. 5-44) draw Step 3: Determine the GSHR line and the
curve, the apparatus dew point is found,
tadp = 47°F.
RSHR line (0.86) through room design condi- required condition of the chilled
Step 4: Determine bypassed air and
tions. Where tsa = 61.8°F intersects the RSHR air leaving the cooling coil.
chilled air.
line, find twsa = 56.8°F, Wsa = 60 grains/lb da. By Eq. 5-44,
The chilled air leaving the cooling coil must
be on the RSHR line and also on the GSHR
Step 2: Determine entering air conditions
line. This air condition has already been estab- BF = tla - tadp 61.8 - 47
to cooling coil.
lished at tsa = 61.8°F, twsa = 56.8°F . There- tea ~ tadp 81.5 - 47
Locate outside air condition (95°F DB and fore,
78°F WB) on Fig. 5-44. Connect outside air BF = 0.43
condition to room design conditions with a t1a = tsa = 61.8°F
straight line. The mixture condition must lie on Bypassed air = BF X cfmsa 0.43 X
this straight line. By Eq. (5-14), twla = twsa = 56.8°F 2400 = 1032 cfm
By Eq . 5-46
W,a = Wsa = 60 grain/lb da
0.25 X 95 + 0 .75 X 77 •
tmix = tea - tla 81.5 - 61.8
1.00 Since the entering and leaving air conditions BF =
tea - tadp 81.5 - 47
tmix = 8 1.5°F = tea from the coil have been determined , the GSHR
1
line is a straight line joining these two air con- I - BF = 0 .5'7
Locate tea = 81.5°F on straigh.t line be- ditions . On Fig. 5-44 draw the GSHR line and
tween outside air and room air and find twea = determine from the SHR scale and alignment hilled ui r • ( I - BF) (cfm88) = 0 .57 X
67 .2°F, Wea • 77 grains/lb da. circle that GSHR = 0 .65 . 2400 136R cfm
APPLIED PSYCHROMETRIC$ 227

Table 5-2
I Bypass Factors*
0:: I GSHR
• ~J=0.65
Example

tt is Residence
sensible

tha Residence, small retail shop, factory


--
---
--
_.-i

1 1 ~/..5 I
a low
new hat
dB_!_..I
tadp 47
I
61.8 77
1 I
95 RSH R = 0.86-
t
Department store, bank, factory
Act. RSHR = 0.739
sensible Department store, restaurant, factory
Figure 5-44
1ount of
Solution to Problems 5-20 and 5-21

Hospital operating room, factory

1, Load Estimating, Carrier Air Conditioning Company, Syracuse, If the GSHR line is extended downward and Illustrative Problem 5-21
to the left to intersect the 100 percent RH
curve, the apparatus dew point is found, Using the same basic data of Problem 5-20,
raw Step 3: Determine the GSHR line and the tadp = 47°F. determine the actual RSHR caused by the by-
ndi- required condition of the chilled passing of outside air.
Step 4: Determine bypassed air and
IHR air leaving the cooling coil.
chilled air.
da. By Eq. 5-44, Solution: (Refer to Fig. 5-44)
The chilled air leaving the cooling coil must
be on the RSHR line and also on the GSHR Step 1: Determine the sensible and latent
ions
line. This air condition has already been estab- BF = t,. - tadp 61.8 - 47 heat quantities associated with the
lished at tsa = 61.8°F, twsa = 56.8°F. There- tea - t adp 81.5 - 47 outside air which is bypassed.
and fore,
: air BF = 0.43 Problem 5-20 stated that 25 percent of the
b a t1a = tsa = 61.8°F air circulated was to be outside air, or 0.25 x
;! on
Bypassed air = BF X cfmsa 0.43 X 2400 =:= 600 cflllca· Of this amount, 43 percent
tW(a = twsa = 56.8°F 2400 = 1032 cfm was bypassed (BF = 0.43). Therefore, by-
By Eq. 5-46 passed outside air is 0.43 x 600 = 258 cfm.
W 1• = Wsa = 60 grain!lb da The sensible and latent heat loads caused
tea - tla 81.5 - 61.8 this bypassed air may be found as follows:
Since the entering and leaving air conditions 1 BF = \
tea - tadp 81.5 - 47
from the coil have been determined, the GSHR Bypassed outside air
line is a straight line joining these two air con- 1 - BF = 0.51 ..Sensible heat load = 1.10(258)(t a - t,.J
be- ditions. On Fig. 5-44 draw the GSHR line and 0

a
determine from the SHR scale and alignment Chilled air = (1 - BF) (cfm 5.) 0.57 X 1.10(258)(95 - 77)
circle that GSHR = 0 .65 . 2400 = 1368 cfm Sensible heat load 5100 Btu/hr
228 APPLIED PSYCHROMETRICS

and sensible heat to the sum of the effective room


sensible and latent heat. Effective room sensi-
Bypassed outside air ble heat (ERSH) is the sum of room sensible
heat plus that portion of outdoor air sensible oa
Latent heat load = 0.68(258)(W08 - W..J
heat which is considered as being bypassed,
= 0.68(258)(117 .5 _;_ 64) unaltered, through the conditioning apparatus.
Latent heat load = 9390 Btu/hr The effective room latent heat (ERLH) is the
sum of the room latent heat plus that portion
New sensible heat for room of outdoor air latent heat which is considered
= 40,000 + 5100 = 45,100 Btu/hr as being bypassed, unaltered, through the con-
ditioning apparatus . The ESHR may be ex-
New latent heat for room
pressed in the following relationship:
= 6500 + 9390 = 15,890 Btu/hr Figure 5-45

Actual RSHR Schematic: Showing relationship


ERSH between GSHR, ESHR, RSHR, and
New sensible heat ESHR (5-47)
ERSH + ERLH apparatus dew point
New sensible heat + New latent heat
45,100 RSH + (OASH)(BF)
45,100 + 15,890 RSH + (OASH)(BF) + RLH + (OALH)(BF)
AND BFt A simplified approach for deter-
Actual RSHR = 0.739 mining the required air quantity is to use the
The bypassed outdoor air loads that are in- psychrometric correlation of ESHR, tadp• and
Draw actual RSHR line on psychrometric cluded in the calculation of ESHR are, in ef- BF. The formula for calculating the air quan-
chart through room design conditions and ex- fect, loads imposed on the conditioned space tity, using BF and tadp is
tend to intersect the 100 percent RH curve. At in exactly the same manner as infiltration
this point of intersection it may be noted that loads. The infiltration loads come through ERSH
the actual RHSR Line passes through the room doors and windows; the bypassed outdoor air (5-48)
cffficta = l.lO(tra _ tactp)(1 - BF)
design conditions and the coil apparatus dew load is supplied to the space through the air
point. distribution system.
This air quantity simultaneously offsets the
It should be noted at this point that ESHR
EFFECTIVE SENSIBLE HEAT RATIO: room sensible and room latent heat loads and
is equal to actual RSHR calculated in Problem
From the results of Problems 5-20 and 5-21 it also handles the total sensible and latent heat
5-21.
may be concluded that there must be psychro- loads for which the conditioning apparatus is
Plotting the ESHR on the psychrometric
metric relationships between bypass factor designed, including outdoor air loads and the
chart locates the apparatus dew point <tactp).
(BF), apparatus dew point <tactp), GSHR, and supplementary loads.
The GSHR passes through the tadp and the en-
RSHR. tering air condition to the cooling apparatus.
To relate BF and tadp to load calculations, IUustrative Problem 5-22
Where the GSHR line and RSHR line inter-
the effective sensible heat ratio (ESHR) term
sect, locates graphically the leaving air condi-
was developed. The ESHR is interwoven with A small department store has a calculated
tion from the apparatus and entering the space.
BF and tadp and thus greatly simplifies the cal-
Figure 5-45 illustrates the graphical arrange- s~nsible heat load 9f J,SCfJJOO Btu/hr and a Ia-
culation of air quantity and apparatus selec- • tent heat load of 315;ooo Btu/br. The summer
ments of these conditions .
tion. t outsjpf air design conditions ~ 95°F DB and
The ESHR is the ratio of the effective room AIR QUANTITY USING ESHR, ADP, 75°F WB . The1~nside design conditions are
1-)80°F DB and 6SOF,.,\YB . Outside air required
tCarrier System Design Manual, Part I, Load Estimating, Carrier Air Conditioning Company , Syracuse, for ventilation is 1500 cfm. Determine the fol -
N.Y., 1972, p. 1-127 . lowing:
APPLIED PSYCHROMETRICS 229

sensible heat to the sum of the effective room a. outdoor air heat lo~ds
.
sensible and latent heat. Effective room sensi- b. grand total heat load
ble heat (ERSH) is the sum of room sensible
heat plus that portion of outdoor air sensible oa c. effective sensible heat ratio
heat which is considered as being bypassed, d. apparatus dew point
unaltered, through the conditioning apparatus.
The effective room latent heat (ERLH) is the e. dehumidified supply air quantity
sum of the room latent heat plus that portion f. entering and leaving air conditions at the
of outdoor air latent heat which is considered apparatus.
as being bypassed, unaltered, through the con-
ditioning apparatus. The ESHR may be ex- Solution:
pressed in the following relationship: Figure 5-45
Step 1: Determine outside air loads.
Schematic: Showing relationship
ESHR = _.....:E=R..:.:S..:.:H:.____ between GSHR, ESHR, RSHR, and Outside air sensible heat
· (5-47)
ERSH + ERLH apparatus dew point
(OASH) = (1 . 10 cfmo.)(t0 a - tra)
RSH + (OASH)(BF)
= 1.10(1500)(95 - 80)
RSH + (OASH)(BF) + RLH + (OALH)(BF)
AND BFt A simplified approach for deter- OASH = 24,750 Btu/hr (ans)
mining the required air quantity is to use the
The bypassed outdoor air loads that are in- psychrometric correlation of ESHR, tadp• and Outside air latent heat
tric cluded in the calculation of ESHR are, in ef- BF. The formula for calculating the air quan- (OALH) = (0.68 cfmoa)(Woa - Wra)
ex- fect, loads imposed on the conditioned space tity , using BF and tadp is
in exactly the same manner as infiltration = 0.68(1500)(98 .5 - 68.5)
At
hat loads. The infiltration · loads come through ERSH
OALH = 30,600 Btu/hr (ans)

om doors and windows; the bypassed outdoor air cfffida = 1.10(tra - tadp)(1 - BF)
(5-48)
Step 2: Determine grand total heat load.
·ew load is supplied to the space through the air
distribution system. Grand total heat load
This air quantity simultaneously offsets the
It should be noted at this point that ESHR
'10:
is equal to actual RSHR calculated in Problem
room sensible and room latent heat loads and (GTH) = RSH + RLH + OASH + OALH
1 it also handles the total sensible and latent heat
'0-
5-21.
loads for which the conditioning apparatus is
GTH = 150,000 + 30,000
Plotting the ESHR on the psychrometric + 24,750 + 30,600
tor designed , including outdoor air loads and the
chart locates the apparatus dew point <tadp).
and
The GSHR passes through the tadp and the en-
. supplementary loads. GTH = 235,350 Btu/hr (ans)

tering air condition to the cooling apparatus.


ns, Illustrative Problem 5-22 This is the total heat load the cooling appa-
Where the GSHR line and RSHR line inter-
rm ratus must handle.
sect, locates graphically the leaving air condi-
ith A small department store has a calculated
tion from the apparatus and entering the space. Step 3: Determine the ESHR and tadp·
cal- sensible heat load 9f. J;S81JOO Btu/hr and a la- Eq. 5-47,
Figure 5-45 illustrates the graphical arrange-
lee- tent heat load of 16~000 Btu/ijr. The summer
ments of these conditions .
outs~ air design conditions .ft1rf 95°F DB and
om AIR QUANTITY USING ESHR, ADP, 75°F WB. The/ttnside design conditions are ESHR = ERSH
'l-780°F DB and 6)°F,.}YB. Outside air required ERSH + ERLH
for ventilation is 1500 cfm. Determine the fol- RSH + OASH(BF)
Estimating, Carrier Air Conditioning Company , Syracuse,
lowing: RSH + OASH(BF) + RLH + OALH(BF)
230 APPLIED PSYCHROMETRICS

From Table 5-2 select a bypass factor of 0 .1 5. 153,700 constructing these two lines and finding their
1.10(80 - 53)(1 - 0.15) point of intersection. This is not as accurate as
150,000 + 24,750(0. 15) determination by calculation. By calculation
ESHR = 153,700 + 30,000 + 30,600(0.15) Cfffida = 6088 (ans)
we have, by Eq. 5-44,
Step 5: Determine the entering and leav-
ESHR = 153,700 ing air conditions at the appa-
BF = tla - tadp
188,300 tea - t adp
ratus.
ESHR = 0 .8 16 (say 0.82)
The entering air dry-bulb temperature is the tla = tadp + BF(tea - tadp)
temperature of the mixture of 1500 cfm of o~t­ 53 + 0.15(83. 7 - 53)
On the psychrometric chart (Fig. 5-46) lay side air and 6088 - 1500 cfm of return air
off ESHR line through room design conditions from i11e inside. By Eq. 5-17 , tla = 57.6°F
and extend to intersect the 100 percent RH
(1500)(95) + (6088 - 1500)(80) On the psychrometric chart (Fig. 5-46) con-
curve . At this point find
tea = struct the GSHR line by joining the point rep-
6088
resenting the coil entering air condition with
tadp = 53°F
tea = 83.7°F the tadp = 53°F. Where t1a = 57 .6°F intersects
the GSHR line find tw18 = 55 .6°F, Wla = 62
Step 4: Find dehumidified supply air Where tea = 85. 7°F intersects with the grains/lb da. The leaving air condition from
quantity. By Eq . 5-48, straight line between outside air and room de- the cooling apparatus is equal to the supply air
sign conditions find twea = 67 . 7°F, W.a = 76 condition to the space. Therefore
grains/lb da.
ERSH The condition of the air leaving the cooling tsa = tla = 57 .6°F
Cfffida = 1.1 O(trm - tadp)( 1 - BF) apparatus must fall on the GSHR and RSHR
lines. This point may be found graphically by tw58 = t"''a = 55.6°F
Wsa = Wla = 62 grain/lb da

SENSIBLE HEAT RATIO LINES:


Solution of Problem 5-22 involved the deter-
a: mination of the apparatus dew point by finding
I
(/)
the intersection between the ESHR line and the
100 percent RH curve on the psychrometric
chart. When the ESHR line does not intersect
the 100 percent RH curve, or, when the appa-
ESHR ratus dew point is too low, a new procedure
= 0.82 must be used to determine the apparatus dew
w point.

~r-------+-~ t
• Low values of ESHR or RSHR occur when
low relative humidities must be maintained in
a conditioned space or when the room latent
t 1a = 57.6 80 95 heat load is high in relationship to the sensible
heat load. This latter condition frequently oc-
Figure 5-46 curs at partial-loa4 conditions because the la-
Solution to Problem 5-22 tent load in a room tends to stay relatively con-
APPLIED PSYCHFlOMETniCS 23 1

15 . . 153 ,700 . constructing these two lines and finding their stant, whereas the sensible heat lolld 11111y vury
1.10(80 - 53)(1 - 0. 15) point of intersection. This is not as accurate as widely (solar load decreasing) .
determination by calculation. By calculation When low values of ESHR and RSIIR nrl'
CfiJl,Ja = 6088 (ans)
5) we have, by Eq. 5-44, encountered, it nearly always means that the
chilled air leaving the cooling apparatus must
Step 5: Determine the entering and Ifav- tla - tadp be reheated before it is introduced to the con-
ing air conditions at th~ appa- BF =
tea - tadp ditioned room as supply air. Therefore, the
ratus.
leaving air condition from the cooling appa-
The entering air dry-bulb temperature is the t1a = tadp + BF(tea - tadp) ratus will not be equal to the supply air condi-
temperature of the mixture of 1500 cfm of out- 53 + 0.15(83 .7 - 53) tion to the conditioned room.
lay side air and 6088 - 1500 cfm of return air The method used to solve a problem involv-
>ns from 111e inside. By Eq. 5-17, tla = 57 .6°F ing low values of ESHR and RSHR will be
~H illustrated by the following problem.
(1500)(95) + (6088 - 1500)(80) On the psychrometric chart (Fig. 5-46) con-
tea = struct the GSHR line by joining the point rep- Illustrative Problem 5-23
6088
resenting the coil entering air condition with
tea = 83.7°F the tadp = 53°F. Where t1a = 57.6°F intersects A room within a particlllar building has a
the GSHR line find tw1a = 55.6°F, Wla = 62 sensible heat gain of 100,000 Btu/hr and a la-
air Where tea = 85.7°F intersects with the grains/lb da. The leaving air condition from tent heat gain of 38,900 Btu/hr. The room is
straight line between outside air and room de- the cooling apparatus is equal to the supply air to be maintained at 80°F DB and 40 percent
sign conditions find twea = 67. 7°F, Wea = 76 condition to the space. Therefore RH when the outside air at design conditions
grains/lb da. are 90°F DB and 74°F WB. Outside air for
The condition of the air leaving the cooling tsa = t1a = 57 .6°F ventilation is to be 2000 cfm. Determine the
apparatus must fall on the GSHR and RSHR following:
lines. This point may be found graphically by
tWsa = t >VIa = 55.6°F.
Wsa = W 1a = 62 grain/lb da a. outdoor air heat load
b. effective sensible heat ratio
SENSIBLE HEAT RATIO LINES:
Solution of Problem 5-22 involved the deter- c. supply air condition to the space
/} a:
I
(/)
mination of the apparatus dew point by finding
the intersection between the ESHR line and the
100 percent RH curve on the psychrometric
d. supply air quantity
e. apparatus dew point

M~a
chart. When the ESHR line does not intersect
f. t?ntering and leaving air conditions at the
r the 100 percent RH curve, or, when the appa-
ESHR cooling apparatus

~i--
ratus dew point is too low, a new procedure
= 0.82 must be used to determine the apparatus dew g. reheat quantity , if any.
'ra 65 I w point.
Low values of ESHR or RSHR occur when Solution:

----+----+----'
80 95
t low relative humidities must be maintained in
a conditioned space or when the room latent
heat load is high in relationship to the sensible
Step I: ·Determine outside air loads.

OASH ( 1.10 Cfl11oa)(t0 a - tra)


heat load. This latter condition frequently oc-
lgure 5-46 curs at partial-loaq conditions because the la- ( 1.10)(2000)(90 . - 80)
1 to Problem 5-22 tent load in a room tends to stay relatively con- OASH 22,000 Btu/hr

\
RSH
0:
cfmsa = 1.1 O(tra - tsJ
I
(/) 100,000
w 1.10(80 - 60)

t RSHR
cfmsa = 4545

---
74
I

Wsa =W Ia
= 0.72 RSHR

RSHR
=

=
RSH = 100,000
+ RLH 100,000 + 38,900
0.719 (say 0.72)
0
·1' I I =50
Draw RSHR line on psychrometric chart
dB_. Wa d .P = 44 . 9
.
(Fig. 5-47). Where t5a = 60°F intersects the
RSHR line, find twsa = 53.3°F, Wsa = 50
tla =51 60 80 grains/lb da.
Figure 5-47 Step 4: Determine mixture condition of
Solution to Problem 5-23 air entering the cooling appa-
ratus.

OALH = (0.68 cfffioa)(Woa - Wra) From Table 5-2, assume BF = 0.15. The mixture entering the cooling apparatus
consists of 2000 cfm at outside air conditions
(0.68(2000)(101 - 62) and 4545 - 2000 cfm of inside recirculated
100,000 + 22,000(0.15)
OALH = 53,000 Btu!hr ESHR air. By Eq. 5-17
103,300 + 38,900 + 53,000(0.15)
Outside
103,300 2000(90) + (4545 - 2000)(80)
air heat load = OASH + OALH tmix = tea =
150,150 4545
22,000 + 53,000
tea = 84.4°F
75,000 Btu/hr ESHR = 0.688
On a straight line connecting outside air
Grand total
When plotted on. the psychrometric chart, conditions and inside air conditions, locate
heat load = RSH + RLH tea = 84.4°F. Find twea = 68.5°F, Wea = 79
this ESHR line intersects the 100 percent RH
+ OASH + OALH curve at approximately 35°F, which is a very grains/lb da.
100,000 + 38,900 low value and would give a low supply air Step 5: Determine the coil apparatus dew
+ 22,000 + 53,000 temperature to the conditioned space. point and the condition of the air
GTH = 213,900 Btu/hr (ans.) leaving the cooling coil.
Step 3: Assume a reasonable supply air tem-
perature to the conditioned space The air leaving the cooling coil must be at the
Step 2: Determine effective sensible heat same humidity ratio as that of the supply air,
and calculate supply air quantity.
ratio (ESHR). W1a = Wsa = 50 grains/lb da. By Eq. 5-46,
The temperature difference between supply
ESHR = W ea - Wla
air and room air could be between 15 and 25 1 - BF = W Ia - Wadp
RSH + OASH(BF) degrees normally. Select supply air tempera-
RSH + OASH(BF) + RLH + OALH(BF) ture t5a = 60°F. By Eq. 5-42,
+Extracted from Trane Air Conditioning Manual, The Tn
APPLIED PSYCHROMETRICS 233

RSH W = W _ Wea - Wlo


cfmsa adp ea l _ BF
l.10(tra - t5J
a:
/J I
(/) 100,000 = 79 - 79 - 50
1 - 0.15
1.10(80 - 60)
Wadp 44.9 grains/lb da
·• cfmsa = 4545
=

RSHR RSH 100,000 On psychrometric chart (Fig. 5-47) locate


= 0.72 RSHR
I RSH + RLH 100,000 + 38,900 tadp = 45 .4°F where Wadp =;= 44.9 intersects
Wsa =W Ia RSHR = 0.719 (say 0.72) the 100 percent RH curve.
= 50 Join tea to tadp by a straight line (GSHR
Draw RSHR line on psychrometric chart line) . Where W1a = Wsa = 50 intersects the
.
dp = 44 9 (Fig. 5-47). Where tsa = 60°F intersects the
0

GSHR line, find the leaving air condition from


RSHR line, find twsa = 53.3°F, Wsa = 50 the cooling coil. At this point t1a = 51 °F,
80 grains/lb da. tWJa = 49.5°F.
re 5-47 Step 4: Determine mixture condition of Step 6: Determine amount of reheat re-
Problem 5-23 air entering the cooling appa- quired.
ratus.
Since the air leaving the cooling apparatus
From Table 5-2, assume BF = 0.15. The mixture entering the cooling apparatus is at a lower dry-bulb temperature than the re-
consists of 2000 cfm at outside air conditions quired supply air dry-bulb temperature, reheat
100,000 + 22,000(0. 15) and 4545 - 2000 cfm of inside recirculated is required. This would be a sensible-heating
ESHR air. By Eq. 5-17 process. By Eq. 5-9,
103,300 + 38,900 + 53,000(0. 15)
2000(90) + (4545 - 2000)(80)
103,300 tmix = tea = Reheat = (1.10 cfmsa)(t5 a - t1J
4545
150, 150 = 1.10(4545)(60 - 51)
tea = 84.4°F Reheat = 45,000 Btu/hr (ans.)
ESHR = 0.688
On a straight line connecting outside air
conditions and inside air conditions, locate Reheating of the chilled air supply, for the
When plotted on. the psychrometric chart,
tea = 84.4°F. Find twea = 68.5°F, Wea = 79 cases when low sensible heat ratios are found,
this ESHR line intersects the I 00 percent RH
grains/lb da. can be accomplished in several ways. Steam or
curve at approximately 35°F, which is a very
hot water reheat coils or electric resistance
low value and would give a low supply air Step 5: Determine the coil apparatus dew coils are sometimes used. Hot water from the
temperature to the conditioned space. point and the condition of the air refrigeration condenser may be used in the re-
leaving the cooling coil. heat hot water coil. The so-called run-around
Step 3: Assume a reasonable supply air tem-
The air leaving the cooling coil must be at the system may be used. The run-around system
perature to the conditioned space
same humidity ratio as that of the supply air, uses a ·precooling water coil followed by a de-
and calculate supply air quantity .
W1a = Wsa = 50 grains/lb da. By Eq. 5-46, humidifying coil and the reheat water coil con-
nected as indicated in Fig. 5-48. t The run-
The temperature difference between supply Wea - Wla around cycle has the advantage of an operating
air and room air could be between 15 and 25 1 - BF = w1a - Wadp cost that is small in comparison with other
degrees normally . Select supply air tempera-
ture t5a = 60°F. By Eq. 5-42,
+Extracted from Trane Air Conditioning Manual, The Trane Company, LaCrosse, Wisconsin, p. 115, 1965 .
234 APPLIED PSYCHROMETRICS

Precooling coil
5-15 COOLING OF MOIST AIR
USING SPRAY WASHERS
4
t,
Air spray washers were discussed generally
tw1
t4
in Section 5-9 and 5-10. However, the discus-
sion there was concerned primarily with the
tw 4---l.------
heating and humidification of air. Problem 5-9
tdp,
involved th~ process of humidification of air
by use of recirculated spray water without
tdp4
heating or cooling of the spray water. This
process of humidification also reduced the dry-
Final air
condition
condition
bulb temperature of the air. Therefore, we may a
say that this represents a cooling and humidi- t
fying process. This process is commonly re-
ferred to as evaporative cooling. 5
Water circulating pump
J v
The evaporative-cooling process is a simul-
Figure 5-48
taneous removal of sensible heat and addition s
Schematic: Run-around reheat cycle of moisture which takes place at constant wet-
bulb temperature, the wet-bulb temperature of b
methods. This is because the refrigeration ca- coils to the reheating coils by the circulating the entering air. The spray water temperature S•
pacity needed to dehumidity the supply air is water, the greater will be the required area of remains constant at the air wet-bulb tempera-
reduced by the amount of reheating done once the coils, and the larger will be the amount of ture, and the water is continuaily recirculated
the system is in operation. Water is recircu- circulating water needed. without external heating or cooling.
lated continuously through the precooling and Theoretically, the chilled air supply leaving Evaporative co.oling is commonly used for
reheating coils. Sensible heat withdrawn from the cooling coils can be reheated by being applications where inside relative humidity is 0
the warm air on its way to the dehumidifying mixed with air at a higher dry-bulb tempera- to be controlled without, necessarily, any con-
coil is carried by the circulating water to the ture. Actually, however, this method works trol of the inside temperature, except to hold it
reheating coils. These reheating coils then re- out poorly. In the average air-conditioning in- within certain limits. Evaporative cooling may
turn the sensible heat to the chilled air leaving stallation air for reheating purposes can be ob- be used in industrial applications where humid-
the dehumidifying ·coil. Any sensible heat tained from only two sources: from outdoor air ity alone is critical, and also in dry climates
added to the flowing air by the reheating coils or from the conditioned room. Outdoor air is where evaporative cooling gives some relief by
is equal to the heat removed by the precooling not always suitable because of its unstable removing sensible heat.
coils. Consequently, there is a decrease in the temperature, and return air cannot be used for
required refrigerating capacity when using the this purpose when the sensible heat percentage
Illustrative Problem 5-24
run-around cycle to reheat the chilled air is low. 6
supply. Outdoor air should not be introduced into a 6
When reheating, the smallest possible quan- conditoned room without first being cooled and An industrial building has a calculated sen-
ti
tity of sensible heat should be added to the air dehumidified. If outdoor air is used for reheat- sible heat load of 1,500,000 Btu/hr. The latent
• heat'load is considered negligible. The inside
6
supply in order to hold the required additional ing, it must of necessity be mixed directly with
refrigerating capacity to a minimum. When us- the chilled air supply, without being cooled relative humidity is to be maintained at 50 per-
ing the run-around cycle, the quantity of sen- and dehurnified. The introduction lowers the cent. The outside air at design conditions is at
sible heat added during reheating should also sensible heat ratio of the room (see ESHR), l00°F DB and 65°F WB . Using all outdoor air
be kept as small as possible. The larger the thus aggravating the very condition that it is passing through an evaporative cooler having a
amount of heat transferred from the precooling desired to correct by reheating. humidifying efficiency of 90 percent, deter-
mine the following: R
APPLIED PSYCHAOMETAICS 235

5-15 COOLING OF MOIST AIR a. the building inside dry- and wet-bulb
nidifying coil Reheating coil
USING SPRAY WASHERS temperatures at design conditions
4
Air spray washers were discussed generally b. the supply air quantity
in Section 5-9 and 5-10. However, the discus-
. •.
sion there was concerned primarily with the
heating and humidification of air. Problem 5-9
Solution: (See Fig. 5-49)
Step 1: Determine entering and leaving air
involved the_ process of humidification of air
conditions at the evaporative
by use of recirculated spray water without
cooler.
heating or cooling of the spray water. This
process of humidification also reduced the dry- The entering air conditions are the outside
Final air bulb temperature of the air. Therefore, we may air conditions of tea = t 0 a = 100°F, and
condition say that this represents a cooling and humidi-
fying process. This process is commonly re-
..
tw = 65°F. On the psychrometric chart (Fig.
5-49) locate the entering air condition. The
ferred to as evaporative cooling. wet-bulb temperature Ctw = 65°F} is the con-
Vater circulating pump
The evaporative-cooling process is a simul- ••
ure 5-48 taneous removal of sensible heat and addition stant wet-bulb temperature for the process .
of moisture which takes place at constant wet- The leaving air dry-bulb temperature may
1-around reheat cycle
bulb temperature, the wet-bulb temperature of be found by use of Eq. (5-27) using new sub-
the entering air. The spray water temperature scripts or
coils to the reheating coils by the circulating
water, the greater will be the required area of remains constant at the air wet-bulb tempera-
the coils, and the larger will be the amount of ture, and the water is continuaily recirculated tea - tla X 100
Eh
circulating water needed. without external heating or cooling. tea - tw
Theoretically, the chilled air supply leaving Evaporative copling is commonly used for
the cooling coils can be reheated by being applications where inside relative humidity is or
mixed with air at a higher dry-bulb tempera- to be controlled without, necessarily, any con-
~ ture . Actually, however, this method works trol of the inside temperature, except to hold it _ Eh(tea - t )
t1a tea w
out poorly . In the average air-conditioning in- within certain limits. Evaporative cooling may 100
~ stallation air for reheating purposes can be ob- be used in industrial applications.where humid-
= 100 - 90000 - 65)
.t tained from only two sources: from outdoor air ity alone is critical, and also in dry climates
100
s or from the conditioned room. Outdoor air is where evaporative cooling gives some relief by
removing sensible heat. t1a = 68.5°F
g not always suitable because of its unstable
e temperature, and return air cannot be used for
Locate the point of intersection where t 1a =
e this purpose when the sensible heat percentage Dlustrative Problem 5-24 68 .5°F crosses the wet-bulb temperature line of
r is low.
65°F. This point represents the leaving air condi-
Outdoor air should not be introduced into a An industrial building has a calculated sen- tion from the evaporative cooler; find t 1a =
conditoned room without first being cooled and sible heat load of 1,500,000 Btu/hr. The latent
dehumidified. If outdoor air is used for reheat- 68.SOF, tw,. = 65°F , and W1a = 87 grains/lbda.
heat load is considered negligible. The inside
tl ing, it must of necessity be mixed directly with relative humidity is to be maintained at 50 per-
·- the chilled air supply, without being cooled Step 2: Determine inside air dry- and wet-
cent. The outside air at design conditions is at
and dehumified. The introduction lowers the bulb temperature.
100°F DB and 65°F WB . Using all outdoor air
o sensible heat ratio of the room (see ESHR), passing through an evaporative cooler having a The room sensible heat ratio (RSHR) is
e thus aggravating the very condition that it is humidifying efficiency of 90 percent, deter- 1.00 because there is no latent heat gain. A
g desired to correct by reheating. mine the following: RSHR of unity would be represented by a line
236 APPLIED PSYCHROMETRICS

w Figure 5-50

L-----+---+-----+---'
dB__.
t 1a = 68.5 83.8 100
t Cooling and humidifying with chilled
water sprays

ature rises in spite of the fact that it is hu-


Figure 5-49 midifying the air. In this case the air surren-
Solution to Problem 5-24 ders sufficient sensible heat to warm the spray
water and also to evaporate a small portion of
it. Because, in this case, the initial temperature
of constant humidity ratio or dew point. The be the same. However, as may be observed by
of the water is less than the initial wet-bulb
air condition leaving the evaporative cooler is inspection, the inside dry- and wet-bulb tem-
temperature of the air, the water temperature t
the condition of the supply air to the space. peratures would be higher, and the CFMsa re-
will rise and both the dry- and wet-bulb tem- I
Construct a horizontal line through the air con- quired would be less since the temperature rise
dition leaving the cooler and extend to the of the supply air would be greater.
peratures of the air will fall. The maximum t
final temperature to which the water can pos- I
right to intersect the 50 percent RH curve. This Air may be cooled and humidified by pass-
sibly rise is to some point that lies below the I
point of intersection represents the inside con- ing tbe air through water sprays when the wa-
final wet-bulb temperature of the air. f
ditions at design. Find Ira = 83.8°F and lw... = ter temperature is lower than the initial air wet-
If the water temperature is held constant at
69.8°F. bulb temperature. To do so, the water temper-
a point below the initial dew-point temperature
ature must be higher than both the initial and
Step 3: Determine the supply air quantity . of the air, cooling and dehumidification of the
final dew-point temperatures of the air. If the
air will take place along a line such as AC in
The air leaving the evaporative cooler and water temperature could be maintained con-
Fig. 5-51. However, if, as is the usual case, I
entering the building must absorb the sensible stant at some point between the initial wet-bulb
the water temperature rises while in contact
heat gain as the air increases in temperature and dew-point temperatures of the air, the con-
with the air, the condition of the air would be s
from lsa = l1a = 68 .5°F to Ira = 83.5°F. This dition of the air as it passes through the humid-
represented by a curved line such as AD, with ~

would be a sensible-heating process of the sup- ifier could be represented by a straight line
the air actually leaving at condition E. When f
ply air. By Eq. 5-42, such as AC in Fig. 5-50. Point C represents the
the initial water temperature is below the initial 1:
constant water temperature and point B repre-
dew-point temperature of the air, the water 1
RSH 1,500,000 sents the final condition of the air leaving the
cfm = = -~-..:__-
temperature rises as it is brought in contact s
humidifier. If the water temperature is not con-
sa 1.1 O(tro - 153) 1.10(83.5 - 68 .5) with the warm air. In the case represented by t·
stant but changes as it contacts the air (the
cfmsa = 89,100 Fig. 5-50 the water humidified the air. In the il
usual condition), the condition of the air fol-
case represented by Fig. 5-51 the water will v
lows a curved path such as AD, leaving the
If the RSHR had been less than unity for dehumidify the air if sufficient water is pro- p
humidifier at point E. The final water temper-
Problem 5-24, the method of solution would vided to hold the final water temperature down tl
ature would be at point D . The water temper-
to a point below the initial dew-point temper- t(
,
APPLIED PSYCHROMETRICS 237

w Figure 5-50 Figure 5-51

--+---+-----t--'
68.5 83.8 100
I Cooling and humidifying with chilled
water sprays

ature rises in spite of the fact that it is hu-


Cooling and dehumidifying with
chilled water sprays

ature of the air. In the actual device sufficient


lgure 5-49 midifying the air. In this case the air surren- water is provided to accomplish this.
ders sufficient sensible heat to warm the spray As long as the final water temperature is
1 to Problem 5-24
water and also to evaporate a small portion of kept below the initial dew-point temperature of
it. Because, in this case, the initial temperature the air, the air will be both cooled and dehu-
"he be the same. However, as may be observed by of the water is less than the initial wet-bulb midified. However, if the final water tempera-
is inspection, the inside dry- and wet-bulb tem- temperature of the air, the water temperature ture is allowed to rise above the initial air dew
;e. peratures would be higher, and the CFMsa re- will rise and both the dry- and wet-bulb tem- point, the air will still be cooled, but it will be
m- quired would be less since the temperature rise peratures of the air will fall. The maximum humidified as well. Although the water tem-
he of the supply air would be greater. final temperature to which the water can pos- perature can rise above the initial air dew
his Air may be cooled and humidified by pass- sibly rise is to some point that lies below the point, the water temperature cannot rise to the
m- ing the air through water sprays when the wa- final wet-bulb temperature of the air. final wet-bulb temperature of the air.
ter temperature is lower than the initial air wet- If the water temperature is held constant at In a single-stage air washer (Fig. 5-22a) the
bulb temperature. To do so, the water temper- a point below the initial dew-point temperature flow of water and air are parallel to each other,
ature must be higher than both the initial and of the air, cooling and dehumidification of the hence both the initial and final temperature of
ty. final dew-point temperatures of the air. If the air will take place along a line such as AC in the water must be lower than the final dew-
water temperature could be maintained con- Fig . .S-51. However, if, as is the usual case, point temperature of the air if dehumidification
nd
stant at some point between the initial wet-bulb the water temperature rises while in contact is to take place. This is true only for a single-
Jle
and dew-point temperatures of the air, the con- with the air, the condition of the air would be stage washer. When a two-stage washer (Fig.
JCe
dition of the air as it passes through the humid- represented by a curved line such as AD, with 5-22b) is used, the situation is somewhat dif-
his
ifier could be represented by a straight line the air actually leaving at condition E. When ferent. In many such washers the chilled water
lp-
such as AC in Fig. 5-50. Point C represents the the initial water temperature is below the initial is divided equally between each spray bank ..
constant water temperature and point B repre- dew-point temperature of the air, the water The ·water is then supplied to each stage at the
sents the final condition of the air leaving the temperature rises as it is brought in contact same temperature. Problems involving such
humidifier. If the water temperature is not con- with the warm air. In the case represented by two-stage washers can be solved by consider-
.5) stant but changes as it contacts the air (the Fig. 5-50 the water humidified the air. In the ing each stage as a separate, single-stage
usual condition), the condition of the air fol- case represented by Fig. 5-51 the water will washer. Thus, for a two-stage washer, the
lows a curved path such as AD, leaving the dehumidify the air if sufficient water is pro- problem is solved exactly as though the air
for humidifier at point E . The final water temper- vided to hold the final water temperature down flowed through two washers in series. The
llld ature would be at point D . The water temper- to a point below the initial dew-point temper- temperature of the water supplied to each stal!e
238 APPLIED PSYCHROMETRICS

is exactly the same, but the air temperature en- The reverse problem is also common, that
tering the second washer has been lowered be- is, determining the quantity of heat that can be 80
cause it has already been cooled in the first removed from the air flowing through the
washer. washer when the water available is limited be- 4~
45
With a given amount of heat to be trans- cause its cost is high, or because the yield of a
30t25
o>
~.
~
so
ferred from the air to the water, the tempera- well is fixed. 15 "o-~-~~ ss. .~
.~
~ ~ '
ture rise of the water is determined by the Figure 5-52 is a chart which may be used ~ ~ 6.o
~~ ·~
~

quantity of water supplied. Sufficient water to aid in the calculation of the final condition <i:10
0 "''"'%
should be supplied to a single-stage washer so of water and air in a washer. Primarily the 9 .0
~ 8.0
~/. '0~ (l,
(:5 ~
that its final temperature will be lower than the chart is based on the fundamental fact that the LL o....,.~
u 7.0 )7 . "'
final dew point to which the air is cooled. To heat surrendered by the air is equal to the heat 0
0
-:;..
provide a factor of safety, the final water tem- gained by the water. Also, when air and water ~ 6.0
perature should be 1 degree lower than the re- ~ 5.5
are brought into .intimate contact with each 0.
quired final dew-point temperature. other in the washer, the final temperature of ~ 5.0
If the cooling water is obtained from a city the water will be equal to the final wet-bulb s:"' 4.5
main or a deep well, its initial temperature is temperature to which the air is cooled. Ac- 0
fixed. If the water is cooled by a refrigeration tually, the final water temperature will be ~ 4.0
<:J
system, the water should be cooled to such a lower than the final wet-bulb temperature of
temperature that the rise in water temperature the air. Nevertheless, this chart enables many 3.5
in the spray washer will be 8 to 14 degrees. A problems involving washers to be solved, by
rise of 10 degrees is usually a good average. finding the theoretical solution and then apply-
3.0
The quantity of water to be circulated through ing a correction factor [see Eq. (5-30)]. The
an air washer for a given heat load can be correction factor is normally about 0.85. Figure!
computed from the following expression:
Illustrative problem 5-25 Spray Water Alr-W
Cooling and Deh
heat absorbed by spray water = heat given Outside air at 95°F DB and 72°F WB is to (Courtesy of The T1
up by air be cooled in a spray washer where the initial
water temperature is 50°F. The quantity of air
or to be cooled is 16,000 cfm and the quantity of
water available is 100 gpm. Determine the fol-
q lowing:
gpm (549)
500(tlw - few)
1. Find the final temperature to which the F ina·l wat e r
air can theoretically be cooled.
where
2. If the washer correction factor is 0.85,
gpm = water flow rate (gal/min) estimate the final conditions of the air
500 = (60 minlhr)(8.34 lb/gal) and final water temperature.

q= heat transferred from air to water Solution: (See Fig. 5-53)

(Btu/hr). Step 1: Determine the water-to-air ratio. dB- - .


difference in water
t 1a = 66 .:
t1w - tew 100 gpm
Water-to-air ratio
temperature, water temperature 16,000/1000 Figure 5-
rise in spray washer = 6.25 gpm/1000 cfm Solutlon to Prol

239
The reverse problem is also common, that Initial Wet Bulb Termperature of A ir

-~\., , 50
35
ure en- is, determining the quantity of heat that can be
red be- removed from the air flowing through the '
he first washer when the water available is limited be-
25
~
--<'.
"? so
cause its cost is high, or because the yield of a 15
"o---<'.~,.~ s~
v•
40-+- 40
e trans- "? ~t'!
well is fixed . •· ~,. ~ 6.o
~ 1)
~
.
.empera- Figure 5-52 is a chart which may be used ~ 10 '}% u..
0
1 by the to aid in the calculation of the final condition 9 .0
~ 8 .0 t/.<:5"'~~t'! 6. 45 ~­
z
nt water of water and air in a washer. Primarily the u.. o..,A" ~
~asher so
u 7.0 )'. !!>
"'a;
chart is based on the fundamental fact that the 0 ~
c.
0 E
r than the heat surrendered by the air is equal to the heat ~ 6 .0 50 ~
)oled . To gained by the water. Also, when air and water a; 5.5
c. ~
~ater tern- are brought into .intimate contact with each ~ 5 .0 ~
ian there- other in the washer, the final temperature of ~ 4.5
55 :~"'
the water will be equal to the final wet-bulb 0
rom a city temperature to which the air is cooled. Ac- ~ 4 .0
(.9
perature is tually, the final water temperature will be
!frigeration lower than the final wet-bulb temperature of 3 .5 60
ito such a the air. Nevertheless, this chart enables many
lemperature problems involving washers to be solved, by
degrees . A 3 .0
finding the theoretical solution and then apply- 65
od average . ing a correction factor (see Eq. (5-30)). The Figure 5-52
l.ted through correction factor is normally about 0.85.
Spray Water Air-Washer Chart for
load can be Cooling and Dehumidification
·ession: Illustrative problem 5-25 (Courtesy of The Trane Company.)
Outside air at 95°F DB and 72°F WB is to
1eat given be cooled in a spray washer where the initial
water temperature is 50°F. The quantity of air
to be cooled is 16,000 cfm and the quantity of
water available is 100 gpm. Determine the fol ·
lowing:
(5-49) 1. Find the final temperature to which the
ew) air can theoretically be cooled.
72
2. If the washer correction factor is 0.85,
estimate the final conditions of the uir w
all min) and final water temperature.
lb/gal)
rom air to water
Solution: (See Fig. 5-53) f
Step 1: Determine the water-to-air ratio . t 1a = 66.2 95
100 gpm
Figure 5- 53
ter Water-to-air ratio = 16,00011000
Solution to Problem 5-25
Mr tP.mnerature
240 APPLIED PSYCHROMETRICS

Step 2: Determine theoretical final air On Fig. 5-53 where (h1Jacr intersects pro-
temperature. cess line between theoretical entering and leav-
Exhaust air
ing air conditions, read actual leaving air con-
Using Fig. 5-52 draw a straight line from 10,000 CFM
dition as
50°F initial water temperature on right scale to Recirculated air
the water-to-air ratio 6 .25 on left scale. Where 20,000 CFM
straight line crosses 72°F, the initial air wet-
tla = 66.2°F
bulb temperature , read theoretical final water =
-
fw 1a 63.0°F Outside air
temperature and wet-bulb temperature of 10,000 CFM
61.2 F . (ans) Step 4: Estimate actual final water tem-
On psychrometric chart (Fig. 5-53) draw a perature. ®
straight line from the initial air condition (95°F
DB, 72°F WB) to the theoretical final air wet- Theoretically, the water would be heated by
bulb temperature of 61.2 located on 100 percent the air from 50°F to 61.2°F. Evidently, if it
RH curve. This straight line represents the theo- absorbs only 0.85 of the theoretical quantity of
retical process of cooling the air from its initial heat, its actual temperature rise would be only Ct
conditions to saturation at 100 percent RH. 0.85 (61.2 - 50) = 9.52°F. Therefore, the
Figure 5
estimated final water temperature would be
Step 3: Estimate the actual final air con- 50 + 9.52 = 59.52°F. Schematic: Equlpmt
ditions leaving the washer. As .may be noted in this problem, the initial for Illustrative probh
letters Identify corre:
From Fig. 5-53 determine the theoretical and final dew-point temperature of the air are
on Fig. 5
entering and leaving enthalpy of the air. the same. Therefore, the air has been cooled
from 95°F to 66.2°F, but no dehumidification
1. Determine the actual condition of the air
hea = 35 .5 Btu/lb da has taken place.
leaving the air washer of each unit.
h1a = 27.3 Btu/lb da (theoretical) Illustrative Problem 5-26t 2. If the air is supplied directly to the au-
ditorium from each of the units , how
By Eq. 5-30 An auditorium is supplied with 60,000 Cfm much sensible and latent heat could be
of conditioned air to maintain inside design absorbed by the supply air? What is the
Correction factor conditions of 78°F DB and 50 percent RH. A RSHR?
total of 20,000 cfm of outside air at 95°F DB
= actual change in air enthalpy Solution:
and 76°F WB is used . The auditorium is
theoretical change in air enthalpy
served by two air-handling units each having a Step I: Determine the condition of the air
CF = (hea - hla)acl precooling coil and a double-bank, single-stage · leaving the air-handling unit.
h Ja)lheor
( hea - air washer. Each washer operates at 0.87 cor-
rection factor. Figure 5-54 illustrates the me- On the psychrometric chart (Fig. 5-55) lo-
(hea - hla)acl = 0.85(35 .5 - 27.3) cate points A, B, and C for the conditions
chanical arrangement of one of the two air-
= 6.97 handling units. Well water used for condensing given . Connect A and B and B and C with
straight lines .
water in the refrigeration machine flows
Then through the precooling coil and reduces the Point D represents a mixture condition of
temperature of the outside air by 6 degrees . precooled outside air at B and return air at C.
(hla)acl = heo - 6.97 = 35 .5 - 6.97 Each washer is supplied with 300 gpm of spray The dry-bulb temperature of this mixture may
= 28.53 Btu/lb water at 42°F. be found as follows:
By Eq. 5-17
t Extracted from Trane Air Conditioning Manual, The Trane Company , LaCrosse, Wisconsin , pp. 228-230,
with permiss ion . cfm8 X t8 + cfmc X tc
to =
total cfm

APPLIED PSYCHROMETRICS 241
On Fig. 5-53 where (h1Jact intersects pro-
cess line between theoretical entering and leav-
Ex haust air .
ing air conditions, read actual leaving air con-
10,000 CFM
dition as
Reci rculat ed air
20 ,000 CFM
Spray eliminato r
tla = 66.2°F
J iJ1 -- . - -... iil1 .- I Supply

-
tw,, = 63 .0°F Outside air
10,000 CFM

Step 4: Estimate actual final water tem-


perature. 0
Theoretically, the water would be heated by
the air from 50°F to 61.2°F. Evidently, if it
absorbs only 0.85 of the theoretical quantity of
heat , its actual temperature rise would be only Ch iller
0.85 (61.2 - 50) = 9.52°F. Therefore, the
Figure 5-54
estimated final water temperature would be
50 + 9.52 = 59.52°F. Schematic: Equipment arrangement
As .may be noted in this problem, the initial for Illustrative problem 5-26 (Circled
letters Identify corresponding points
and final dew-point temperature of the air are on Fig. 5-55.)
the same. Therefore, the air has been cooled
from 95°F to 66.2°F, but no dehumidification
1. Determine the actual condition of the air (10,000)(89) + (20,000)(78)
has taken place.
leaving the air washer of each unit. 30,000
Illustrative Problem 5-26t 2. If the air is supplied directly to the au- tv = 81.67°F
ditorium from each of the units, how
An auditorium is supplied with 60,000 Cfm much sensible and latent heat could be Locate tv = 81.67°F on line BC. This repre-
of conditioned air to maintain inside design sents the air condition entering the air washer.
absorbed by the supply air? What is the
conditions of 78°F DB and 50 percent RH. A RSHR? Find twv = 68.4°F, hv = 32.() Btu/lb da,
total of 20,000 cfm of outside air at 95°F DB Wv = 83 grains/lb da.
and 76°F WB is used. The auditorium is Solution:
300 GPM
served by two air-handling units each having a Step 1: Determine the condition of the air Water-to-air ratio
30,000/ 1000
precooling coil and a double-bank , single-stage · leaving the air-handling unit.
air washer. Each washer operates at 0.87 cor- 10 gpm/1000 cfm air
rection factor. Figure 5-54 illustrates the me- On the psychrometric chart (Fig. 5-55) lo-
cate points A, B , and C for the conditions Using Fig. 5-52 , connect initial water tem-
_chanical arrangement of one of the two air- perature of 42°F on right scale with 10
handling units. Well water used for condensing given. Connect A and B and B and C with
straight lines. gpm/1000 cfm on left scale . Where this
water in the refrigeration machine flows straight line intersects with initial air wet-bulb
through the precooling coil and reduces the Point D represents a mixture condition of
precooled outside air at B and return air at C. temperature Uwo = 68.4°F), read the theoreti-
temperature of the outside air by 6 degrees.
Each washer is supplied with 300 gpm of spray The dry-bulb temperature of this mixture may cal final air wet-bulb and water temperatures as
water at 42°F. be found as follows: 52°F. Locate 52°F on the 100 percent RH
By Eq. 5-17 curve and mark point G. Connect points D and
G with a straight line. This is the theoretical
e Trane Company , LaCrosse, Wisconsin, pp . 228-230, cfm8 X t8 + cfiilc X tc
tv= process line for the air passing through the
total cfm washer.
242 APPLIED PSYCHROMETRICS

gpm/1 000 cfm of air is to be used in an air


washer. Determine the following:

a. the initial temperature that the water


must theoretically have
h 0 = 32.6
b. the actual initial water temperature, if a
hF = 28.1 correction factor of 0.85 is assumed
hE = 22.9 c. an estimate of the final condition of the t
air leaving the washer I
w t
Solution:

L___..f--------:-_1
8
Step 1: Determine the theoretical initial
a
water temperature.
dB__.
56 Using J;ig. 5 -52 locate where the initial d
Figure 5-55 wet-bulb temperature of 68°F and final wet- f(

bulb temperature of 55°F intersect in the ma- tl


Solution to Problem 5-26 trix. Lay a straight-edge through this point and 3.
through the water-to-air ratio of 15 gpm/1000
cfm. Read the required water temperature from tl
Latent heat capacity = he - hF the right scale at 50.0°F. Sf
The washer has a correction factor of 0.87. bl
Determine the theoretical change in air en- = 29.9 - 28 .1 Step 2: Determine actual initial water
thalpy as hv - he = 32.6 - 21.4 = 11.2 = 1.8 Btu!lb da. temperature.
1:
Btu/lb da. The actual change in air enthalpy On psychrometric chart (Fig. 5-56) locate ti:
would be (0.87)(11.2) = 9. 7 Btu/lb da. There- By Eq. 5-8
fore, the actual enthalpy of the air leaving the
washer would be 32.6 - 9.7 = 22.9 Btu!lb
da = ' hE. Locate hE = 22 .9 on line DG and iJs = (4.5 cfm88)(hF - hE)
find tE = 56°F, twE = 54.6°F, and WE = 61 = 4.5(30,000)(5.2)
grains/lb da. iJs = 702,000 Btu/hr
Step 2: Determine sensible and latent iJL = (4.5 cfm.a)(hc - hF)
quantities that the air will ab-
sorb. = 4.5(30,000)(1.8)
iJL = 243,000 Btu/hr
On Fig. 5-55 locate point F by drawing a
5.2
horizontal line through E and a vertical line RSHR = = 0.74
through C. Find hF = 28.1 Btu/lb da. 5.2 + 1.8
Illustrative Problem 5-27 dB--+-
Sensible heat capacity = hF - hE
Figure 5-
= 28 .1 - 22.9 Air initially at 80°F DB and 68°F WB is to
= 5.2 Btu/lb da. be cooled to 55°F WB . Water at the rate of 15 Solutlon to Prob
APPLIED PSYCHROMETRICS 243

gprn/1000 cfm of air is to be used in an air initial air condition (80°F DB, 68°F WB) at A.
washer. Determine the following: Find hA = 32.2 Btu!lb da.
Theoretical final air wet bulb given is 55°F.
a. the initial temperature that the water At 55°F WB and 100 percent RH, read h8 =
must theoretically have 23.3 Btu/lb da.
Actual heat to . be surrendered by air is
b. the actual initial water temperature, if a
hA - h8 = 32.2 - 23.3 = 8.9 Btu/lb da.
correction factor of 0 ..85 is assumed
Since the correction factor given is 0.85 and
c. an estimate of the final condition of the the actual heat lost by the air amounts to 8. 9
air 'leaving the washer Btu/lb da, it is evident that the problem must
be solved as though the air were to surrender
w Solution: 8.9/0.85 = 10.47 Btu/lb da.

_ _____.1 Step 1: Determine the theoretical initial


water temperature.
The theoretical wet bulb temperature of the
air may be found as follows:
The initial air enthalpy hA = 32.2 Btu/lb
Using Fig. 5-52 locate where the initial da. The theoretical quantity of heat to be sur-
wet-bulb temperature of 68°F and final wet- rendered is 10.47 Btu/lb da. Therefore, the
lgure 5-55 bulb temperature of 55°F intersect in the ma- theoretical final enthalpy of the air should be
1 to Problem 5-26 trix. Lay a straight-edge through this point and 32.2 - 10.47 = 21.7 Btu/lb da.
through the water-to-air ratio of 15 gprn/1000 On Fig. 5-56 draw the line of constant en-
cfm. Read the required water temperature from thalpy of 21.7 Btu/lb . Where this line inter-
the right scale at 50.0°F. sects the 100 percent RH curve, find the wet-
Latent heat capacity = he - hp
n. Step 2: Determine actual initial water
bulb temperature of 51.8°F, point C.
!0-
= 29.9 - 28.1 On Fig. 5-52 use a straight-edge between
temperature.
l.2 = 1.8 Btu/1b da . 15 gprn/1000 cfm and intersection of 68°F ini-
lpy On psychrometric chart (Fig. 5-56) locate tial wet-bulb temperature and 51.8°F final wet
:re- By Eq. 5-8
the
l/lb
md
iJs = (4.5 cfm5a)(hF - hE)
61 = 4.5(30,000)(5.2)
iJs = 702,000 Btu/hr
:ent qL = (4.5 cfm53)(hc - hp)
ab-
= 4.5(30,000)(1 .8)
qL = 243,000 Btu/hr
w
__t
1g a
5.2
line RSHR =
5.2 + 1.8
= 0.74
~...----
Illustrative Problem 5-27 dB____.
Figure 5-56
Air initially at 80°F DB and 68°F WB is to
Solution to Problem 5-27
be cooled to 55°F WB. Water at the rate of 15
244 APPLIED PSYCHROMETRICS

bulb . At right read the initial water tempera- Step 3: Estimate final air condition leav-
ture as 45 .5°F, point D of Fig. 5-56. This is ing washer. CHA
the initial water temperature that will actually
cool the air to a final wet-bulb temperature of Draw line AC on Fig. 5-56. This represents Re
55°F. the theoretical process line of the air passing
Theoretically, the rise in water temperature through the washer. The actual final wet-bulb
would be 51.8 - 45 .5 = 6.3 degrees . Since temperature of the air was stated as 55°F.
Where 55°F WB intersects line AC, find point 5-1 . Moist air at 35°F DB and 32°F WB 1s to b
the correction factor is 0 .85, the actual rise in
F, which is the approximate air leaving condi- 50 percent RH . Using the psychrometric chart ;
water temperature would be 0 .85 X 6 .3 =
tions. Find tF = 56.8°F, hF = 23 .2 Btu/lb da, determine the following :
5.36 degrees . Therefore, the actual final water
(a) The initial and final values of humidit:
temperature would be 45 .5 + 5.36 = 50.9°F, WF = 62 grains/lb da.
ume, and dew-point temperature
pointE of Fig. 5-56.
(b) If the initial air volume entering the
CFM , determine:
(1) required heating capacity (Btu/hr)
(2) required moisture addition (lb/hr)
(3) pounds per hour of air flowing thn
5-2. Three thousand cfm of air at 40°F DB and
cfm of air at 90°F DB and 74°F WB in a stea<
dry-bulb and wet-bulb temperatures, humidity ra
ing mixture.
5-3. Moist air at an initial condition of 40°F DI
and humidified to a final condition of 90°F DB aJ
of humidification is to be carried out in a spn
. recirculated spray water with no external heating
The spray washer has a humidifying effectiver
and reheating of the air will be done by heat-1

\
volume flow rate is 8000 cfm, determine:
(a) How much preheat and reheat capacity
(b) How much water must be added to t
gpm?
5-4 . Using the same initial and final air conditi
the range of preheated air temperatures that wo
pan type humidifier containing water maintainec
coils. Assume that the air pressure is 14.7 psia.
5-5. A building interior is to be heated by force
at 105°F DB . The calculated sensible heat los
Btu/hr with the building interior maintained a1
when the outdoor air is at 30°F DB and 24°F'
that 25 percent of the air circulated must be o
loss is all sensible heat, determine the followin,
(a). the required supply air quantity in lb/1
(b) if humidification is performed by sp1
,
'

Step 3: Estimate final air condition leav-


ing washer. CHAPTER 5

Draw line AC on Fig. 5-56. This represents Review


the theoretical process line of the air passing
through the washer. The actual final wet-bulb
temperature of the air was stated as 55°F. 5-l. Moist air at 35°F DB and 32°F WB is to be conditioned to 70°F DB and
Where 55°F WB intersects line AC, find point 50 percent RH . Using the psychrometric chart and any required calculations,
F, which is the approximate air leaving condi- determine the following :
tions. Find tp = 56 .8°F, hp = 23 .2 Btu/lb da, (a) The initial and final values of humidity ratio, enthalpy, specific vol-
WF = 62 grains/lb da. ume, and dew-point temperature
(b) If the initial air volume entering the conditioning device is 5000
CFM, determine:
(1) required heating capacity (Btu/hr)
(2) required moisture addition (lb/hr)
(3) pounds per hour of air flowing through the conditioner
5-2. Three thousand cfm of air at 40°F DB and 35°F WB are mixed with 5000
cfm of air at 90°F DB and 74°F WB in a steady-flow device. Determine the
dry-bulb and wet-bulb temperatures, humidity ratio, and enthalpy of the result-
ing mixture.

5-3 . Moist air at an initial condition of 40°F DB and 32°F WB is to be heated


and humidified to a final condition of 90°F DB and 30 percent RH . The process
of humidification is to be carried out in a spray chamber (air washer) using
. recirculated spray water with no external heating or cooling of the spray water.
The spray washer has a humidifying effectiveness of 88 percent. Preheating
and reheating of the air will be done by heat-transfer coils. If the initial air
volume flow rate is 8000 cfm, determine:
(a) How much preheat and reheat capacity is required , Btu/hr?
(b) How much water must be added to the spray chamber as makeup,
gpm?
5-4 . Using the same initial and final air conditions of Problem 5-3, determine
the range of preheated air temperatures that would permit the use of an open-
pan type humidifier containing water maintained at 212°F by immersed heating
coils . Assume that the air pressure is 14.7 psia.
5-5. A building interior is to be heated by forced circulation warm air supplied
at l05°F DB. The calculated sensible heat loss from the building is 560,000
Btu/hr with the building interior maintained at 68°F DB and 60 percent RH
when the outdoor air is at 30°F DB and 24°F WB. Proper ventilation requires
that 25 percent of the air circulated must be outdoor air. If the building heat
loss is all sensible heat , determine the following :
(a) the required supply air quantity in lb/hr and cfm
(b) if humidification is performed by spraying steam into th~ airstream
246 APPLIED PSYCHROMETRICS

after the mixing of outdoor and recirculated air, how much steam in lb/hr 'Return air
is required, assuming the steam is at 16 psia, dry and saturated? Exhaust
(c) How much heat must be supplied by the heat-transfer coil after hu- 70° F DB , 50% RH

midification?
5-6. Air at 60°F DB and 50°F WB is to be preheated and then humidified to a
final condition of l00°F DB and 40 percent RH in a steady-flow device. Hu- air
midificaHon is to be performed by spraying steam into the air. The steam pres-
sure is 20 psia and has a quality of 80 percent.
(a) To what temperature must the air be preheated before humidification? Heating coil Humidi
(b) If 4000 cfm of air at the initial condition enters the process, how
much steam in lb/hr is required to humidify the air? Figure 5-57
(c) What must be the heating capacity of the preheating coil in Btu/hr? Sketch tor Problem !

5-7. A building has a calculated heat loss of 400,000 Btu/hr and a sensible
heat ratio of 0.80. The building interior is to be maintained at 70°F DB and 50 (b) Determine the capacity of the heating device in
percent RH when the outdoor air is .at 35°F DB and 40 percent RH. Outdoor (1) The humidifier is a spray washer using rec
air required for ventilation is 3000 cfm. Air supplied to the building interior is without heating or cooling of the water.
to be at ll5°F DB . Humidification of the supply air to the building interior, if (2) The humidifier is a steam humidifier using
required, will be done by using dry saturated steam at 18 psia after the air has
and saturated.
passed through the heating device. (c) Make a sketch of a psychrometric chart showin
(a) How much air must be supplied to the building interior, lb/hr and points 'which pertain to the solution of the problem
cfm?
(b) How much steam, if any, is required for humidification, lb/hr? 5-10. A high humidity chamber is to be maintained at 7~
(c) Find the required temperature rise of the air through the heat-transfer RH when outdoor design conditions are 30°F DB and
device, and heat transfer in Btu/hr. sensible heat loss from the chamber is 260,000 Btu/hr.
(d) Make a sketch of a psychrometric chart showing all process lines and within the chamber it will be necessary to use 75 perc<
points which pertain to the solution of the problem. percent recirculated air for the supply air mixture.
The proposed equipment to condition the air is sho
h 5-8. Moist air at 60°F DB and 30°F dew-point temperature enters a humidify- preheat coil will heat the outdoor air to 70°F. The spra)
ing device at the rate of 4000 cfm. Dry saturated steam at 30 psia is sprayed fying effectiveness of 90 percent and will use recirculatt
into the airstream. Following humidification, the air is heated by a heat-transfer heating or cooling of the spray water. The steam humid
device to a final condition of 90°F DB and 55°F dew-point temperature .
(a) How much steain must be added to the air, lb/hr? Return air
(b) How much heat must be supplied by the heat-transfer device, Btu/hr? IOJ\\OOUO. (75° F, DB , 70% RH)
(c) What are the dry- and wet-bulb temperatures after humidification?
(d) Make a sketch of a psychrometric chart showing all process lines and
points which pertain to the solution of the problem.
5-9. A building interior is to be maintained at 70°F DB ant 50 percent RH
when outdoor design conditions are 30°F DB and 26°F WB. Heat losses from
the building are 250,000 Btu/hr sensible and.:-44, 100 Btu/hr latent. Latent heat
transfer is due to infiltration of cold, dry outdoor air. Ventilation requires that Preheat coi I Spray washer Reheat ct
1000 cfm of outdoor air be introduced into the supply air. The supply air to
the building interior is to be at l00°F DB . The conditioning equipment is Figure 5-58
shown in Fig. 5-57. Sketch tor Problem
(a) Determine the quantity of supply air required , lb/hr and cfm .
APPLIED PSYCHROMETRICS 247

culated air, how much steam in lb/hr


16 psia, dry and saturated? .....
Exhaust Return air
~d by the heat-transfer coil after hu-
70° F DB , 50% RH

e preheated and then humidified to a Fan Supply


:nt RH in a steady-flow device. Hu- Outdoor 1 11 1 1 ~
a1r
~ steam into the air. The steam pres-
cent.
be preheated before humidification?
condition enters the process, how Heating coil Humidifier
midify the air?
Figure 5-57
y of the preheating coil in Btu/hr?
Sketch for Problem 5-9
s of 400,000 Btu/hr and a sensible
to be maintained at 70°F DB and 50
'F DB and 40 percent RH. Outdoor (b) Determine the capacity of the heating device in Btu/hr, if
[r supplie~ to the building interior is (1) The humidifier is a spray washer using recirculated spray water,
;upply air to the building interior, if without heating or cooling of the water.
ed steam at 18 psia after the air has (2) The humidifier is a steam humidifier using steam at 16 psia, dry
and saturated . .
to the building interior, lb/hr and (c) Make a sketch of a psychrometric chart showing all process lines and
points which pertain to the solution of the problem.
lred for humidification, lb/hr?
5-10. A high humidity chamber is to be maintained at 75°F DB and 70 percent
: of the air through the heat-transfer
RH when outdoor design conditions are 30°F DB and 80 percent RH . The
sensible heat loss from the chamber is 260,000 Btu/hr. Due to contamination
chart showing all process lines and
f the problem.
within the chamber it will be necessary to use 75 percent outdoor air and 25
percent recirculated air for the supply air mixture.
oint temperature enters a humidify- The proposed equipment to condition the air is shown in Fig. 5-58 . The
lturated steam at 30 psia is sprayed preheat coil will heat the outdoor air to 70°F. The spray washer has a humidi-
1, the air is heated by a heat-transfer fying effectiveness of 90 percent and will use recirculated spray water with no
55°F dew-point temperature. heating or cooling of the spray water. The steam humidifier will use dry satu-
o the air, lb/hr?
by the heat-transfer device, Btu/hr? Return air
mperatures after humidification? Exh"11<t (75° F, DB , 70% RH)
~-----.--~--~-
chart showing all process lines and
the problem.
d at 70°F DB ant 50 percent RH
B and 26°F WB . Heat losses from
-'44, I 00 Btu/hr latent. Latent heat
tdoor air. Ventilation requires that
the supply air. The supply air to Preh eat coil Spray washer Reheat coil Steam humidifier
. The conditioning equipment is
Figure 5-58

ir required, lb/hr and cfm. Sketch for Problem 5-10


;.::<H:J AI"'I"'LitU 1-'::)YGHHUMtTRICS

(c) The required bypass factor for the coolin1


rated steam at 20 psia. Supply air temperature to the chamber will be 110°F (d) The effective sensible heat factor.
dry bulb.
(a) Determine the dry- and wet-bulb temperatures, humidity ratio, and 5-14. Given the following design information for
enthalpy for the air at each numbered point in the system. Outside air conditions: 95°F I
(b) Determine the required supply air quantity, lb/hr and cfm. Inside air conditions: gooF I
(c) Determine the heating capacity required for the preheat coil and the Sensible heat gain: 226,0
reheat coil, Btu/hr. · Latent heat gain: 67 ,5'
(d) Determine the amount of water absorbed by the air in the air washer, Required quantity of outdoor air f<
lb/hr.
(e) Determine the amount of steam absorbed by the air in the steam
humidifier, lb/hr.
·~ Inside building volume: 70,0
If 12 air changes per hour are desired for propel
building, determine:
(f) Make a sketch of a psychrometric chart showing all process lines and (a) Air volume to be circulated, cfm.
points which pertain to the solution of the problem. (b) The sensible heat factor for the building.
(c) Dry- and wet-bulb temperatures of the ai
5-11. A given space within a buiiding is to be maintained at 7goF DB and 50
(d) Dry- and wet-bulb temperatures of the ai
percent RH. The calculated sensible heat gain to the space is 4g,ooo Btu'lhr,
and the latent heat gain is 12,000 Btu/hr. Supply air to the space is to have a 5-15. Given the following design information for l
dry-bulb temperature of 60°F. Outside air conditions: l05°F
(a) Calculate the space sensible heat ratio. Inside air conditions: 50 per'
(b) Determine the wet-bulb and dew-point temperatures , humidity ratio, Sensible heat gain: lgO,OC
and enthalpy of the supply air. Latent heat gain: 20,0C
(c) Calculate the quantity of supply air required, lb/hr and cfm. It has been decided to use 100 percent outdoor ai
The outdoor air will pass through a spray chamt
5-12. A building has a calculated sensible heat gain of 130,000 Btu/hr and a
water. The spray chamber will have an estimated I
latent heat gain of 32,500 Btu/hr. The inside design conditions are 7goF DB
and 50 percent RH. The outside design conditions are 90°F DB and 76°F WB. go percent. Determine:
(a) The resulting dry-bulb temperature in ti
Required outside air quantity for ventilation is 4000 cfm.
(a) For a cooling coil bypass factor of zero, what would be the apparatus tions .
(b) The required air flow, cfm.
dew-point temperature?
(c) The dry- and wet-bulb temperatures o
(b) If a cooling coil was selected that had a bypass factor of 0. 20, de-
chamber at design conditions.
termine
(1) Required supply air quantity, cfm. 5-16. Given the following design information for
(2) Entering and leaving air conditions at the cooling coil (dry- and Outside air .conditions: 95°F DE
wet-bulb temperatures) . Inside air conditions: gooF DE
(3) The refrigeration load on the cooling coil, Btu/hr and tons. Sensible heat gain: 230,000
Latent heat gain: 55,000
5-13. Given the following design ·information for a building:
Required outdoor air for ventilation
Outside air conditions: 90°F DB, 75°F WB.
(a) Using a cooling coil bypass factor of 0.
Inside air conditions: gooF DB, 50 percent RH.
(l) The apparatus dew-point temperatm
Sensible heat gain: 160,000 Btu/hr.
(2) The quantity of air supplied to the b
Latent heat gain: 40,000 Btu/hr.
building heat gains, cfm.
If the total quantity of supply air to the building is to be gooo cfm, 50 percent
(3) Entering and leaving air conditions
of which must be outdoor air for ventilation, determine:
wet-bulb temperature) .
(a) The required dry- and wet-bulb temperatures of the air leaving the
(4) Effective sensible heat factor.
cooling coil and entering the building.
(b) If the supply air dry-bulb temperature
(b) The dry- and wet-bulb temperatures of the air entering the cooling
cooling coil bypass factor is used, determi
coil.
APPLIED PSYCHROMETAICS 24

erature to the chamber will be II 0°F (c) The required bypass factor for the cooling coil.
(d) The effective sensible heat factor.
ulb temperatures, humidity ratio, and 5-14. Given the following design information for a building:
:red point in the system. Outside air conditions: 95°F DB, 75°F WB .
air quantity, lb/hr and cfm. Inside air conditions: gooF DB, 67°F WB.
1 required for the preheat coil and the Sensible heat gain: 226,000 Btu/hr.
Latent heat gain: 67,500 Btu/hr.
r absorbed by the air in the air washer, Required quantity of outdoor air for ventilation: 5400 cfm.
Inside building volume: 70,000 ft 3 .
tm absorbed by the air in the steam If 12 air changes per hour are desired for proper air circulation within the
building, determine:
ric chart showing all process lines and (a) Air volume to be circulated, cfm.
n of the problem. (b) The sensible heat factor for the building .
. to be maintained at 78°F DB and 50 (c) Dry- and wet-bulb temperatures of the air supplied to the building.
t gain to the space is 4g,ooo Btlii'hr, (d) Dry- and wet-bulb temperatures of the air entering the cooling coil.
. Supply air to the space is to have a 5-15. Given the following design information for a building:
Outside air conditions: 105°F DB, 70°F WB.
:at ratio. Inside air conditions: 50 percent RH.
:w-point temperatures, humidity ratio, Sensible heat gain: 1g0,000 Btu/hr.
Latent heat gain: 20,000 Btu/hr.
y air required, lb/hr and cfm. It has been decided to use 100 percent outdoor air to condition the building.
•le heat gain of 130,000 Btu/hr and a The outdoor air will pass through a spray chamber using recirculated spray
nside design conditions are 78°F DB water. The spray chamber will have an estimated humidifying effectiveness of
onditions are 90°F DB and 76°F WB. go percent. Determine:
.on is 4000 cfm. (a) The resulting dry-bulb temperature in the building at design condi-
r of zero, what would be the apparatus tions.
(b) The required air flow, cfm. "
that had a bypass factor of 0.20, de- (c) The dry- and wet-bulb temperatures of the air leaving the spray
chamber at design conditions .
ty, cfm. 5-16. Given the following design information for a building. •
mditions at the cooling coil (dry- and Outside air .conditions: 95°F DB , gooF WB .
Inside air conditions: gooF DB , 40 percent RH.
he cooling coil, Btu!hr and tons. Sensible heat gain: 230,000 Btu/hr.
ation for a building: Latent heat gain: 55,000 Btu/hr.
90°F DB, 75°F WB. Required outdoor air for ventilation: 5000 cfm.
gooF DB, 50 percent RH. (a) Using a cooling coil bypass factor of 0.15 , determine:
1
160,000 Btu/hr. (I) The apparatus dew-point temperature .
40,000 Btu/hr. (2) The quantity of air supplied to the building interior to absorb the
uilding is to be 8000 cfm, 50 percent building heat gains, cfm.
on, determine: (3) Entering and leaving air conditions at the cooling coil (dry- and
b temperatures of the air leaving the wet-bulb temperature) .
ng . (4) Effective sensible heat factor.
~tures of the air entering the cooling (b) If the supply air dry-bulb temperature has to be 60°F and the same
cooling coil bypass factor is used , determine:
250 APPI,.IED PSYCHROMETRICS

(1) The quantity of supply air required, cfm. BIDLIOGRAJ


(2) The required reheat capacity, Btu/hr.
5-17 . Given the following design information for a building:
Outside air conditions: 92°F DB, 76°F WB .
1. The Armstrong Humidification Handbook, Arm
Inside air conditions: 80°F DB, 50 percent RH .
Three Rivers , Michigan . -
Sensible heat gain: 68,500 Btu/hr.
Latent heat gain: ' 29,350 Btu/hr. 2. Trane Air Conditioning Manual , The Trane
Ventilation requires that all air supplied to the building interior Wisconsin.
must be outdoor air.
3. Carrier System Design Manual , Part 1, Load Esti
Temperature difference between inside design dry bulb and
ditioning Company , Syracuse, NY, 1972.
supply air is to be 20 degrees.
Using a cooling coil bypass factor of 0.10, determine: ~

(a) Room sensible heat factor.


(b) The supply air quantity, Btu/hr.
(c) Apparatus dew-point temperature.
(d) Reheat quantity, Btu/hr.
5-18. Cooling-load calculations for a building indicate a sensible heat gain of
200,000 Btu/hr and a latent heat gain of 25,000 Btu/hr at design conditions.
The outdoor air at design conditions is at 105° F DB and 65°F WB. A manu-
facturer can supply a spray water evaporative cooler using recirculated spray
water which has a humidifying effectiveness of 90 percent when the air flow is
9000 cfm.
(a) If 100 percent outdoor air is used in the amount of 9000 cfm through
the spray washer and enters the building as supply air, determine:
(1) The dry- and wet-bulb temperatures of the air leaving the spray
washer as supply air.
(2) The resulting dry- and wet-bulb temperatures and the relative
humidity of the air in the building.
5-19 . Given the following design information for a building:
Outside air conditions: 95°F DB, 75°F WB.
Inside air conditions: 80°F DB, 50 percent RH .
Sensible heat gain: 150,000 Btu/hr.
Latent heat gain: 50,000 Btu/hr.
Minimum required outdoor air for ventilation: 3000 cfm.
Supply air for this application is to be all outdoor air.
For a cooling coil bypass factor of 0.10, determine:
(a) Heat loads caused by outdoor air, Btu/hr.
(b) Apparatus dew-point temperature.
(c) Supply air quantity to use, cfm.
(d) Supply dry- and wet-bulb temperatures. \'

251

You might also like