MELDAS Series

M60 M60-S, Disable Parameter Lock

USA-E99089 -017*

MITSUBISHI ELECTRIC AUTOMATION

USA
List of Revisions

Rev Date of Revision Detail Author


* 06/06/05 First Edition Created TSS
M60 & M60-S
- M64A, M64, M65, M66, M64A-S, M64-S, M65-S & M66-S -
Disabling Parameter Lock

Purpose:
Disable the “Parameter Lock Function” to write new parameter values.

Overview:
This procedure will allow temporary disable the “Parameter Lock Function” by setting a PLC
register.

Tools Needed:
None

Instructions:
I. Access “PLC I/F” screen
A. Press [Diag/Data IN-OUT] key
B. Press [PLC I/F] key

II. Change “R1896” value to “0” to disable the parameter lock and change parameters
A. Enter the following data: DEVICE( R1896) DATA( 0) MODE(2)
B. Press the [INPUT] key – you will receive an alarm “Message M90 - Parameter Setup
Mode”. This is normal.

III. Modify parameters as necessary

IV. Change “R1896” value to “1” to enable the parameter lock again.
A. Access the “PLC I/F” Screen
B. Enter the following data: DEVICE( R1896) DATA( 1) MODE(2)
C. Press the [INPUT] key.

www.meau.com Mitsubishi Electric Automation, Inc. Page 1 of 1