Sub 08:00
RKH Ref. No. CM WO: 192411 RCU: FCU Time:
System
Qatar National Library Station; Emergency Exit 04; Level ACIFM/ Sub- ACIFM
Location of Event:
A/R06 Contractor: Technicians
☐ Customer ☒ Assets
Subsequent Impact: Safety: ☐ High* ☒ Med* ☐ Low* ☒ Operations
Experience Reliability / Life
* High: Immediate Safety Impact (within 1 week) Medium: Potential Safety Impact (~1week or more) Low: Potential Safety Impact (~1month or more)
Fault/ Defect Title: Faulty Air Vent & Isolation gate Valve not installed
Fault/ Defect Description: Corrective Maintenance (CM) reported by Station Master (SM):
192411: Heavy water leakage in firefighting pump room coming from CHWR
PIPE as per reported by SG patrolling.
When ACIFM inspected, it was found that water leakage is due to faulty air vent
installed on Chilled water pipes of FCU. It was also noted that there is no isolation
valve installed to isolate the air vent.
JV shall replace the defective air vent and also installed the missing PSH JV 27.08.2020
isolation valve before the air vent and shall make the unit in normal
operational condition
Root cause analysis shall be conducted on the above-mentioned defect, PSH JV 27.08.2020
corrective action shall be derived and implemented
Faulty Air Vent & Isolation gate Valve not installed for the airvent
Photo