RAIN WATER CALCULATIONS:

Bases of Calculations:
 The rate of rain fall per hour for Riyadh city is 38 mm (1.5 inch).
 Size of vertical storm water conductors or leaders shall be sized according to
Table (13.6.1) and table (13.6.2).
As per national standard plumbing code (NSPC) page no. (325) table (13.6.1) and
page no. (326) table (13.6.2).
Refer to attachment no. (1)
 Roof area as per maximum area which drained at one leader.

1. Roof Floor
1.1 Rain water stack size calculations Area 1
 From roof floor plan the rain water drainage DWG at the maximum area drained to
one RD
 From table (13.6.1) at the rain fall 1.5 inches (38 mm) per hr, the diameter of
conductors or leader at 4 inches (110mm) to be equivalent to rain water area
10380 ft2 (964.33m2) which greater than the maximum collection area of 188.65
m2 (2030.6 ft2).
OK Safe

1.2 Rain water stack size calculations Area 2


 From roof floor plan the rain water drainage DWG at the maximum area drained to
one RD
 From table (13.6.1) at the rain fall 1.5 inches (38 mm) per hr, the diameter of
conductors or leader at 4 inches (110mm) to be equivalent to rain water area
10380 ft2 (964.33m2) which greater than the maximum collection area of 188.65
m2 (2030.6 ft2).
OK Safe

Project. Agency Building 01 Subject: Department Technical Manual


1.3 Rain water stack size calculations Area 3
 From roof floor plan the rain water drainage DWG at the maximum area drained to
one RD
 From table (13.6.1) at the rain fall 1.5 inches (38 mm) per hr, the diameter of
conductors or leader at 4 inches (110mm) to be equivalent to rain water area 10380 ft2
(964.33m2) which greater than the maximum collection area of 249.5 m2 (2685.59ft2).
OK Safe

1.4 Rain water stack size calculations Area 4


 From roof floor plan the rain water drainage DWG at the maximum area drained to
one RD
 From table (13.6.1) at the rain fall 1.5 inches (38 mm) per hr, the diameter of
conductors or leader at 4 inches (110mm) to be equivalent to rain water area 10380 ft2
(964.33m2) which greater than the maximum collection area of 249.5 m2 (2685.59ft2).
OK Safe

1.5 Rain water stack size calculations Area 6


 From roof floor plan the rain water drainage DWG at the maximum area drained to
one RD
 From table (13.6.1) at the rain fall 1.5 inches (38 mm) per hr, the diameter of
conductors or leader at 4 inches (110mm) to be equivalent to rain water area 10380 ft2
(964.33m2) which greater than the maximum collection area of 330.86 m2 (3561.34ft2).
OK Safe

1.6 Rain water stack size calculations Area 6


 From roof floor plan the rain water drainage DWG at the maximum area drained to
one RD
 From table (13.6.1) at the rain fall 1.5 inches (38 mm) per hr, the diameter of
conductors or leader at 4 inches (110mm) to be equivalent to rain water area 10380 ft2
(964.33m2) which greater than the maximum collection area of 330.86 m2 (3561.34ft2).
OK Safe

Project. Agency Building 01 Subject: Department Technical Manual


Subject Rain Water Calculations Attachment Reference
Building Nile Hilton Attachment No. Documents Drawings
Review Subject Mechanical (Plumbing) works 09 Table7-2.2.1 ---
PROJECT:
110 RAIN WATER RISER 110 RAIN WATER RISER

Area 1 Area 3 Area 5


188.65 m2 249.5 m2 Elevator 4
330.86 m2

UP
68 69 70 71 72 72 72 72 77

74

Elevator 2 75 REVISIONS
76
77 NO. DATE DESCRIPTION DRAWN
78
51
52
53
54
Elevator 1 55
56

67 66 65 64 63 62 61 60 59 58 57

DN

Area 6
330.86 m2
Elevator 4

188.65 m2 249.5 m2
Area 2 Area 4

110 RAIN WATER RISER 110 RAIN WATER RISER


PROJECT:

DRAWINGTITLE

RAIN WATER AREAS


ROOF FLOOR PLAN

ALL DRAWINGS ARE THE SOLE PROPERTY OF SAUDI ICON DRAWINGS


SHALL NOT BE REPRODUCED IN ANYWAY KIND OR FORM WITHOUT
THEIR WRITTEN PERMISSION

0 1 2 3

SCALE DATE DRAWNBY CHECKEDBY APPROVEDBY

1:50 17-SEP

JOBREF DRAWINGNO. REV.

00