You are on page 1of 2

DISCHARGING (Cell Readings)

Date: 15/11/2022
Battery Bank : 564-BB-0002B-2 Battery Capacity : 980Ah
Battery Type : VR Ni-Cd Manufacturer : ALCAD VTX 1L-980-1
No. of cells : 345 of 345 Discharging Started at : 14:15 hrs
Ambient Temperature : 29 ˚C Time of this Measurement : 18:15 hrs
TESTING PARAMETER Requirement Actual Value TESTING PARAMETER Requirement Actual Value
Discharging Current 196 A A Overall Battery Voltage 172 V 188.2 V
End Voltage per cell 1.0V/Cell Total No. Of Disch. Hrs. -
V/Cell hrs
Rate of Discharging 0.2C5 Electrolyte Temp.(Max) 45 ˚C ˚C

Cell No. Volt Temp ˚C Cell No. Volt Temp ˚C Cell No. Volt Temp ˚C
174. 1.063 210. 1.087 246.
175. 1.063 211. 1.092 247.
176. 1.077 212. 1.079 248.
177. 1.082 213. 1.105 249.
178. 1.086 214. 1.101 250.
179. 1.077 215. 1.082 251.
180. 1.078 216. 1.095 252.
181. 1.078 217. 1.097 253.
182. 1.073 218. 1.082 254.
183. 1.042 219. 1.098 255.
184. 1.048 220. 1.082 256.
185. 1.086 221. 1.098 257.
186. 1.079 222. 1.098 258.
187. 1.068 223. 1.093 259.
188. 1.088 224. 1.087 260.
189. 1.104 225. 1.112 261.
190. 1.099 226. 1.099 262.
191. 1.114 227. 1.106 263.
192. 1.093 228. 1.109 264.
193. 1.101 229. 1. 265.
194. 1.089 230. 1. 266.
195. 1.094 231. 1. 267.
196. 1.092 232. 1. 268. 1.060
197. 1.090 233. 1. 269. 0.068

198. 1.096 234. 1. 270. 0.706


199. 1.082 235. 1. 271. 0.680

200. 1.089 236. 1. 272. 1.022


201. 1.084 237. 1. 273. 0.646

202. 1.080 238. 1. 274. 0.937


203. 1.085 239. 1. 275. 0.685

204. 1.084 240. 1. 276. 0.665


205. 1.093 241. 1. 277. 1.

206. 1.087 242. 1. 278. 1.


207. 1.088 243. 1. 279. 1.

208. 1.088 244. 1. 280. 1.


209. 1.086 245. 1. 281. 1.

DISCHARGING (Cell Readings)

SITE TECHNOLOGY LTD.Co ADNOC OFFSHORE ( UMM LULU)


Name: ANANDU. SS Name:
Date: Date:
Signature: Signature:
Date: 15/11/2022
Battery Bank : 564-BB-0002B-2 Battery Capacity : 980Ah
Battery Type : VR Ni-Cd Manufacturer : ALCAD VTX 1L-980-1
No. of cells : 345 of 345 Discharging Started at : 14:15 hrs
Ambient Temperature : 29 ˚C Time of this Measurement : 18:15 hrs
TESTING PARAMETER Requirement Actual Value TESTING PARAMETER Requirement Actual Value
Discharging Current 196 A A Overall Battery Voltage 172 V 188.2 V
End Voltage per cell 1.0V/Cell Total No. Of Disch. Hrs. -
V/Cell Hrs
Rate of Discharging 0.2C5 Electrolyte Temp.(Max) 45 ˚C ˚C

Cell No. Volt Temp ˚C Cell No. Volt Temp ˚C Cell No. Volt Temp ˚C
282. 1. 317. 1.061
283. 1. 318. 1.083

284. 1. 319. 1.064


285. 1. 320. 1.036

286. 1. 321. 1.046


287. 1. 322. 1.022

288. 1. 323. 1.043


289. 1. 324. 1.075

290. 1. 325. 1.036


291. 1. 326. 1.075

292. 1. 327. 1.021


293. 1. 328. 1.065

294. 1. 329. 1.058


295. 1. 330. 1.045

296. 1. 331. 1.042


297. 1. 332. 1.070

298. 1. 333. 1.070


299. 1. 334. 1.070

300. 1. 335. 1.064


301. 1. 336. 1.075

302. 1. 337. 1.074


303. 1. 338. 1.077

304. 1. 339. 1.078


305. 1. 340. 1.056

306. 1. 341. 1.062


307. 1.114 342. 1.073
308. 1.098 343. 1.071

309. 1.092 344. 1.082


310. 1.087 345. 1.096

311. 1.104

312. 1.073
313. 0.938

314. 0.959
315. 1.046

316. 1.065

SITE TECHNOLOGY LTD.Co ADNOC OFFSHORE ( UMM LULU)


Name: ANANDU. SS Name:
Date: Date:
Signature: Signature: