Professional Documents
Culture Documents
20-00618
ACTIVITY #4
building structure, creates safe and healthy surroundings for the occupants, and
systems is an understanding of the needs that the systems are designed to address.
These needs include, for example, building material response to high humidity or
mechanical design should be balanced with the program’s needs. These issues
include such things as functionality, cost, aesthetics, and energy consumption. Thus,
the selection of mechanical systems and the subsequent design of those systems is
air into the building while air leaks out of the building through holes in the shell, bath
and range fan ducts, and intentional vents (if any exist).
simple and inexpensive to install. A typical supply ventilation system has a fan and
duct system that introduces fresh air into usually one, but preferably several, rooms
that residents occupy most, such as bedrooms and the living room. This system may
Supply ventilation systems allow better control of the air that enters the house
ventilation systems minimize outdoor pollutants in the living space and prevent back
drafting of combustion gases from fireplaces and appliances. Supply ventilation also
allows outdoor air introduced into the house to be filtered to remove pollen and dust
Supply ventilation systems work best in hot or mixed climates. Because they
pressurize the house, these systems have the potential to cause moisture problems
in cold climates. In winter, the supply ventilation system causes warm interior air to
leak through random openings in the exterior wall and ceiling. If the interior air is humid
enough, moisture may condense in the attic or cold outer parts of the exterior wall,
remove moisture from the make-up air before it enters the house. Thus, they may
contribute to higher heating and cooling costs compared with energy recovery
ventilation systems. Because air is introduced into the house at discrete locations,
outdoor air may need to be mixed with indoor air before delivery to avoid cold air drafts
in the winter. An in-line duct heater is another option but increases operating costs.
EXHAUST SYSTEM
exhausts air from the house, thus causing a change in pressure that pulls in make-up
from the outside through leaks in the building shell and intentional, passive vents.
Exhaust ventilation is most appropriate for colder climates, since in warmer climates,
depressurization can draw moist air into wall cavities where it may condense and
centrally located, single exhaust point in the house. A better design is to connect the
fan to ducts from several rooms, preferably rooms where pollutants are generated,
rooms to introduce fresh air rather than rely on leaks in the building envelope. Passive
vents may, however, require larger pressure differences than those induced by the
The ventilation system in a building consists of air moving devices such as fans
and blowers and a network of ducts to exhaust the contaminated indoor air and to
bring in air from the outside of the building. Ducts are channels, tubes, or pipes that
Duct systems should be designed to have air flow through the ducts with as
little friction or resistance as possible. The amount of air that flows through a duct
depends on the cross-section area (duct opening area) of the duct and the air speed.
Air moving too slowly will allow contaminants such as dusts to settle and accumulate.
These particles will eventually clog the duct. Air moving too fast wastes power, can
create noise problems, and may cause excessive abrasion, especially in branches
and elbows, due to increased friction between the air transporting dust particles and
the duct.
Duct systems typically require large amounts of air to move relatively small
system can achieve the required air concentration while using the least amount of
fuels and the process of venting combustion gases. Inadequate combustion air can
lead to dangerous problems. The duct work installed to bring fresh, outside air to the
furnace and/or hot water heater. Normally 2 separate supplies of air are brought in:
Where combustion air openings are provided with volume, smoke or fire
dampers, the dampers shall be interlocked with the firing cycle of the appliances
served, to prevent operation of any appliance that draws combustion air from the room
or space when any of the dampers are closed. Manual dampers shall not be installed
in combustion air ducts. Ducts not provided with dampers and that pass through rated
Code.
Chimney
A primarily vertical structure containing one or more flues, for the purpose of
carrying gaseous products of combustion and air from a fuel-burning appliance to the
outdoor atmosphere.
Vent
passageway for conveying combustion products and air to the atmosphere, listed and
necessary draft and capacity for each appliance connected to completely exhaust the
surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be
designed to resist the effects of condensation that would cause deterioration of the
chimney or vent.
Smoke Control
A smoke control system is a system that controls the movement of smoke and
air in a building. It can be made up of multiple different components and use several
environment long enough for all occupants to egress the building. The design
objective for a smoke control system can vary depending on the situation in which it
is being used, for example a hospital might have a design objective of containing
smoke to the zone of fire origin. These systems can also be part of the existing HVAC
systems keep smoke from entering specific areas using pressurization and are
tenable environments in the means of egress from large volume spaces or prevent
the movement of smoke into surrounding spaces. Smoke management systems are
passive fireproofing. It refers to the process of filling openings and joints between walls
and floors with fire-resistant material, inhibiting the spread of fire between
to help prevent the spread of fire through the different compartments of a building.
Without having fire stops correctly installed, smoke and flames can quickly travel
through a building, damaging the property and risking the lives of its occupants. Fire
stops also help emergency services to suppress the fire before it spreads beyond
control.
HYDRONICS
Hydronics, in simple terms, refers to a central heating system that utilizes hot
water to heat your home. It is the most comfortable, versatile, economical, and
effective heating option available. These systems are used extensively in Europe
where the high cost and limited availability of fuel require homeowners to seek the
most economical and effective heating options. The installation of hydronic heating
conductor of heat. The heated water is circulated throughout the home using your
choice of underfloor tubing, slim baseboard radiators, or decorative wall panels that
deliver the heat evenly to each room in your home. The water is then returned to the
boiler to be re-heated and re-circulated. Because of its physical properties, water
releases heat gradually when passed through the radiator in each room. This creates
a very comfortable living environment where heat distribution is even and controllable,
as there are no fans blowing high volumes of air creating hot and cold spots.
The water loses only a fraction of its warmth as it travels throughout your home
and requires less fuel to reheat it to circulation temperature. With a hydronic system
you’ll reduce your fuel consumption by up to 40 per cent. Weather responsive controls,
computer sensors and individual room thermostats ensure that your system operates
efficiently and provides you with warmth and comfort unmatched by conventional
furnaces.
A closed heating appliance intended to supply hot water or steam for space
less than or equal to 15 pounds per square inch (psi) (103 kPa) for steam and 160 psi
(1103 kPa) for water. High-pressure boilers operate at pressures exceeding those
pressures.
Building steam heating system pressures rarely exceed 125 pounds. Low-
pressure steam heating systems offer the advantage of moderate steam temperatures
when compared with higher pressure steam and low-pressure boilers; they require
less stringent monitoring than do high-pressure boilers under most codes. Steam
heating systems using radiators directly within the space are not common in modem
buildings but are found quite frequently in older buildings. Objections to steam include
return lines to corrode. An additional disadvantage is that the entire system, including
Systems exist that can operate under sub atmospheric and vacuum conditions
and produce steam at lower temperatures. These systems require good maintenance
to maintain the vacuum. Orifices installed in the inlet to the radiation restrict the flow
of steam, creating sub atmospheric conditions within the radiation unit itself because
of the vacuum maintained at the radiator outlet. In effect, the steam temperature can
be “reset” down by varying the pressure within the radiator. This can be effective in a
properly maintained system but currently is not in common use. In many early heating
systems, the main steam riser is extended from the basement or boiler room level up
into the attic space. There the steam piping system is divided into branches, and the
steam is down fed to the radiation around the perimeter of the building. The main
reason for one or more large risers is the economics of pipe sizing resulting from a
single riser. When steam is supplied vertically, the condensate, by its very nature,
flows down against the steam. This requires oversized steam pipes to prevent water
horizontal runs. The pipe should be pitched uniformly, approximately 1 inch in 50 feet.
Every time the horizontal steam main encounters an obstruction, the gravity flow of
accommodated.
Steam systems require careful maintenance of the steam traps. Typically,
radiation systems found in spaces has a thermostatic trap. Large coils often have a
float and a thermostatic trap, in the case of a low-pressure steam coil, and a bucket
trap for high-pressure steam coils. One of the operating characteristics of low-
pressure steam heating systems is that the air trapped within the radiation system
must be eliminated. Traps are typically designed to provide for the removal of air.
Standing cast iron radiation systems can be provided with a separate air vent because
When steam traps leak, the entire heating system supply and return operates
at essentially the steam supply temperature, creating excessive fuel use. It is not
unusual for the energy loss to amount to 20 to 25 percent of the energy consumption
of a building. A facility without a steam trap maintenance program will probably have
more than 50 percent of the traps not working. With modern electronic temperature-
properly.
Steam used in heating coils tends to freeze up rapidly when used for heating
fresh air. In a multizone unit, or any air-handling unit with a long steam coil, the end of
the coil located farthest from the steam inlet tends to be colder. In the case of a
multizone air-handling unit, if a small zone is attached to the hot deck on the far end
of the coil, the coil will often have insufficient heating capacity because of a lower air
temperature provided by the colder end of the coil. Double-feed coils are available for
situations where long coils are used. This eliminates most of the problems of cold
it can be distributed without pumps. As a result, steam heating systems have low
energy transportation costs. Typically, the only energy required, other than that for the
boiler burner, is the pump required to return the condensate back into the boiler. In
Hot water heating systems have many advantages, including relatively small
pipe sizes, flexibility relative to routing throughout a building, the ability to vary the
water temperature through a wide range, ease of zoning, and quiet operation. Their
system, providing heating and air conditioning from the same piping system and often
the same air conditioning and heating device, such as a fan coil unit and air-handling
unit.
and maintained. Entrained air in a hot water heating system causes corrosion and
circulation problems. The initial water introduced into the system can attack the pipe
for a brief period; however, that action soon stabilizes itself. If the water is not replaced,
drained off, or lost through leakage, corrosion essentially stops. A mistaken notion on
the part of many heating system operators is that chemical treatment should be added
periodically to a hot water heating system. This is true only if that judgment is based
on careful analysis. The introduction of a small amount of new water will cause only a
mild amount of corrosion. It is not unusual to open gravity hot water heating systems
that have been operating for 65 years in residences and find essentially no corrosion
of the piping. Excessive chemical treatment of hot water heating systems can destroy
radiation and zone valves. Facilities personnel should question regular chemical
Hot water heating systems can be zoned in much the same fashion as a steam
system; however, they have the additional advantage of being able to have the
temperature varied within each zone. In a high-rise dormitory building with individual
room radiators, it is entirely possible to zone the entire face of the building based on
exposure and vary the water temperature to maintain uniform temperatures in all
spaces in the zone. Rooms with manual radiation control can provide uniform space
temperatures throughout the day as the sun strikes the face of the building in the
morning and the far side in the afternoon. Uniform temperatures are also maintained
throughout the night. A manual radiation valve within each space permits the occupant
to select his or her own specific temperature adjustment within the range of the
Hot water heating systems, because of their reset capability, have lower heat
losses and greater energy economies. Typically, hot water heating systems are
designed for a 20°F temperature differential between the temperature of the water
leaving the heating source and that of the water at return. This differential is seldom
for large temperature differentials if they are for heating only. Differentials of 40°F and
60°F can be used, which reduces the pipe size and pumping costs considerably. This
approach requires careful sizing of the radiation devices, because of the large
temperature drop experienced. In long pieces of fin tube radiation, the far end can
become excessively cold. Where a hot water heating distribution system also serves
as a chilled water system, in most cases the pipe sizing is determined by the chilled
A properly sized hot water heating system will operate with relatively low
pumping costs. It can be provided with multiple pumps or one large individual pump
with a standby pump and single- or multiple-zone water temperature control valves.
A hot water heating system should be designed so that air can be eliminated
from all high points, as well as from radiation and coils. The system is often used with
all-air air conditioning systems and particularly with variable volume systems. The
control of the radiation can be integrated with the air conditioning control for each zone
to a lower point during unoccupied hours of operation and for heat reclaim purposes.
The heat can consist of condenser water from an air conditioning cycle or heat pump
REFRIGERATION
extracting heat and in which a compressor is used for compressing the refrigerant
vapor.
converted into liquid and vapor forms. The compressor is responsible for compressing
(condensation pressure). After that, the refrigeration fluid at high pressure and
temperature that is higher than the temperature of the environment where the system
is located. This way, the condenser is capable of rejecting heat from the refrigerant
fluid to the environment. This process of heat rejection reduces the total energy of the
refrigerant fluid taking it from the condition of superheated vapor to the condition of
The refrigerant fluid in the liquid state typically runs through a filter dryer,
responsible for removing the eventually present humidity from the system. On the way
out the filter dryer , the refrigerant then expands in the expansion device (a capillary
tube or expansion valve, for example) having its pressure reduced, which causes part
It is the process of transforming the refrigerant from liquid into vapor that causes
intermediate heat exchanger, or a so-called CT-SL HX (capillary tube suction line heat
exchanger). In general terms, this heat exchanger has the function of reducing the
enthalpy in the evaporator inlet (specific cooling capacity gain) and raising the
the heat exchanger (evaporator) that allows the removal of energy from the
refrigerator). When absorbing energy from the refrigerated environment (reducing the
freezer’s temperature), the refrigerant ends its evaporation process and, typically, all
the remaining liquid is transformed into vapor which flows towards the compressor
Systems work in different ways, but all have a common goal to detect a fire and protect
the building, its occupants, and valuables. A common fire protection system is a smoke
detector and a sprinkler. If a fire sparks, smoke sets off the detector causing the
sprinkler system to activate. The water protects against the spread of fire. While this
is an effective method, when dealing with certain critical equipment or special hazards,
automatic fire suppression systems using clean agents are a better choice. These
One of the main benefits of a fire protection system is that in the long run, it
saves money. Think of a business and what investments are made in manufacturing
operations for a significant period, it could cost a company millions of dollars. A prime
example is a machine shop that manufactures parts. If the shop were to experience a
fire and shut down for multiple days or weeks, the business would suffer immensely.
Equipment may need to be replaced, and valuable contracts could be lost. Businesses
must take into consideration all factors when they look at the price of a fire protection
system.
the fire, while also notifying the authorities to send emergency professionals to your
location.
ELEVATORS AND ESCALATORS
Elevators
landing levels, comprising an enclosed space, or car, whose dimensions and means
of construction clearly permit the access of people, and which runs between rigid
vertical guides. A lift, therefore, is a vehicle for raising and lowering people and/or
goods from one floor to another floor within a building directly (single push-button
Elevators are driven directly by an electric motor (electric lifts; see figure 1) or
gearless, depending on car speed. The designation “traction” means that the power
from an electric motor is transmitted to the multiple rope suspension of the car and a
Hydraulic lifts have become widely used since the 1970s for the transport of
goods and passengers, usually for a height not exceeding six floors. Hydraulic oil is
used as pressure fluid. The direct-acting system with a ram supporting and moving
Escalators
Inside comprises of a couple of chains which are folded over two apparatuses.
to see lifts with 100 HP engines. The chains, gears, and the engine are encased in a
structure called the support. Bracket keeps running along the floors that the lift should
benefit.
progression in the lift get together has its own two arrangements of wheels which
proceed onward separate tracks. The upper wheels are the one which moves with the
chain though the lower wheels guarantee that the dimension of the progression is kept
up at some random snapshot of activity. As all of us more likely than not watched,
each progression in the lift is collapsible. It crumples to a level surface toward the start
and toward the finish of the elevator. It represents the sheltered and smooth ride for
the user.
The side snatch rail, the rail keeps running with the lift. It is intended to give
extra help to the user. These rails likewise keep running toward the elevators and at
a similar speed. It is an incredible element for the elderly user and as a rule each user
of elevators. This rail or as more usually alluded to the handrail has an arrangement
of little wheels under it. It’s made up of elastic and is fueled by a similar engine which