Drive Internal
Components
Topics
• AC Drive Components
• Danfoss Drives
• MCT10 Software
• Local Control Panel
Safety Notes
DRIVES CONTAIN LIVE VOLTAGES AFTER
DISCONNECTION FROM MAINS.
WAIT AT LEAST 40 MIN. BEFORE MAINTENANCE.
• Exploded view
of a typical
D-Frame drive
Danfoss FC302 Connections
Danfoss FC302 Bit Switches
• Switches S201 (A53)
and S202 (A54) are
used to select a current
(0-20 mA) or a voltage
(-10 to +10V)
configuration of the
analog input terminals
53 and 54.
• Switch S801 (BUS
TER.) can be used to
enable termination on
the RS-485 port
(terminals 68 and 69).
Danfoss FC302 LCP Panel
Danfoss FC302 Control Card
• Logic Control – microprocessor
which supervises and controls all
drive functions.
• PROMs – contain parameters for
programmable options.
• EEPROM - data storage including
during power down.
• PWM IC – pulse width modulation
waveform for Power card.
• Control Terminals –
programmable function I/O,
analog and digital.
• Serial Link communications.
Danfoss FC302 Power Card
• Low level logic – high level power signal
isolation
• Monitoring DC bus voltage, line voltage, output
current etc.
• Gate drive firing signals.
• Scaling of current / voltage feedback signals.
• Fault processing for output short circuit and
ground fault conditions.
• Switch mode power supplies.
Danfoss FC302 Power Card
Danfoss FC302 LCP, Control
Card and Power Card
Danfoss FC302 Gate Driver Card
• Isolation /
buffering of
gate drive
signals to
IGBTs.
Danfoss FC302 - IGBT
• IGBT – Insulated Gate Bipolar Transistor
• Similar to Thyristor in construction but
IGBT can switch off at any time. Not just
at 0A like Thyristor.
IGBT
Collector
Gate
Emitter
Danfoss FC302 – Pulse Width
Modulation (PWM)
Imaginary 0V
DC Link - Voltage
PWM Duty Cycle
• The duty cycle of
PWM determines
the average voltage
of the output. t
• D=t/T T
DC +
Vout
DC -
DC -
Danfoss FC302 - IGBT
• The IGBT’s provide an output of variable voltage
and frequency, required for a constant torque
with increasing speed.
• There are 6 IGBT’s in the output inverter of the
drive, 2 per phase.
• The drive produces a high switching voltage
often in excess of 1000V, and due to this high
switching it is not possible to see motor voltage
with a standard multi meter. This also has an
effect on motor windings which have to be
insulated to 3000V.
Encoder Connection
• Extra Option Card
MCB102 required.
• 5V TTL Encoder
used for resistance
to noise.
Encoder Direction
• Two pairs of pulses
are created when
the encoder is
turned.
• A and B pulses are
90° apart.
• To change the
encoder direction A
and B pulse wires
can be switched with
each other.
Motor Direction
68 69 68 69 68 69 68 69
• Dipswitches on the
RS232/RS485
converter should be
set as shown in the
drawing.
Information
• The Danfoss Manuals are an invaluable
source of information.
– FC300 Service Manual
• Information about hardware fault finding and repair
– FC300 Programming Guide
• Information about all parameters
– FC300 Operating Manual
• Information about alarms, warnings and trouble-
shooting
End