You are on page 1of 1

Project Assignment 2

Service Hot water recirculation pump


Hot Water Riser Sizing
2/3 heat
heat lose lost in
Route Tag GPM Pipe size Length of pipe Length (ft) B to 1 Pipe sizeLength of pipeLength (ft) Btu/hr/f Sum GPM
in riser recirculati
on
10000
1 to 2 1 to 2 WATER HEATER 0
2 to 3 41 2" 16.1 52.821524 2 to 3 2" 16.1 52.82152 28 1479.003 986.0018 2465.004 0.2465
3 to 4 32 1 1/2" 4.1 13.451444 3 to 4 1 1/2" 4.1 13.45144 25 336.2861 224.1907 560.4768 0.056048
4 to 5 28 1 1/4" 4.1 13.451444 4 to 5 1 1/4" 4.1 13.45144 21 282.4803 188.3202 470.8005 0.04708
5 to 6 24 1 1/4" 4.1 13.451444 5 to 6 1 1/4" 4.1 13.45144 21 282.4803 188.3202 470.8005 0.04708
6 to 7 18 1 1/4" 4.1 13.451444 6 to 7 1 1/4" 4.1 13.45144 21 282.4803 188.3202 470.8005 0.04708
7 to 8 7 1" 4.1 13.451444 7 to 8 1" 4.1 13.45144 19 255.5774 170.385 425.9624 0.042596
8 to H1 3/4" 6 19.68504 8 to H1 3/4" 6 19.68504 17 334.6457 223.0971 557.7428 0.055774
Total 42.6 139.763784 H2 3/4" 6 19.68504 17 334.6457 223.0971 557.7428 0.055774
Eq length of fittings 50% 69.881892 H3 1 1/2" 12 39.37008 25 984.252 656.168 1640.42 0.164042
Cu Total 209.645676 H4 1 1/2" 12 39.37008 25 984.252 656.168 1640.42 0.164042
H5 3/4" 6 19.68504 17 334.6457 223.0971 557.7428 0.055774
H6 3/4" 6 19.68504 17 334.6457 223.0971 557.7428 0.055774
H7 1" 6 19.68504 19 374.0158 249.3438 623.3596 0.062336
H8 1" 6 19.68504 19 374.0158 249.3438 623.3596 0.062336
H9 1" 6 19.68504 19 374.0158 249.3438 623.3596 0.062336
H10 1" 6 19.68504 19 374.0158 249.3438 623.3596 0.062336
H11 1 1/4" 6 19.68504 21 413.3858 275.5906 688.9764 0.068898
H12 1 1/4" 6 19.68504 21 413.3858 275.5906 688.9764 0.068898
Total Developed length 209.645676 ft
Friction loss of 4'/100' 8.38582704 ft Total BTU 8548.229 5698.819 14247.05 1.424705

5% safety 8.805118392 ft
Pump head requried 10ft
Flow required 1.5 GPM

Recirculation pipe dia 1/2" CPVC Sch 40 with 15mm insulation