Professional Documents
Culture Documents
To cite this article: K. Nam, D. K. Kang, W. Chung, C. H. Noh, J. Yu, N. I. Her, C. Hamlyn-Harris,
Y. Utin & K. Ioki (2013) Cryogenic Conduction Cooling Test of Removable Panel Mock-Up for ITER
Cryostat Thermal Shield, Fusion Science and Technology, 64:2, 131-135, DOI: 10.13182/FST13-
A18067
Article views: 13
K. Nam,a D. K. Kang,a W. Chung,a C. H. Noh,a J. Yu,b N. I. Her,b C. Hamlyn-Harris,b Y. Utin,b and K. Iokib
a
ITER Korea, National Fusion Research Institute, Daejeon 305-333, Republic of Korea, kwnam@nfri.re.kr
b
ITER Organization, CS 90 046, 13067 St Paul Lez Durance Cedex, France
This paper describes the fabrication of removable order to obtain low emissivity (< 0.05). The active
panel for ITER cryostat thermal shield (CTS) and its cooling is applied to most parts of the panels as first
conduction cooling test at cryogenic temperature. Two priority. Figure 1 shows the CTS with its overall
kinds of full-scale mock-ups of the removable panels have dimensions. The design value of radiation heat flux from
been developed, depending on different thermal the cryostat to the CTS is 24 W/m2.
conduction designs. Passive cooling characteristics of the Access to magnet components for maintenance is
mock-ups are investigated with the measured data of necessary in ITER.1 As the CTS is located outside the PF
temperature jump at the joint and maximum temperature coil, a removable panel on the CTS makes access to the
at the panel. The passive cooling of panel with copper magnet joint possible. There are also four removable
insertion satisfies the design requirement of temperature panels at lower CTS, which are to be opened during
jump (< 3 K), even though the heat load condition in the tokamak assembly. Figure 1 shows typical removable
cooling test is more severe than the design condition of panels. Total number of the removable panel is 115 and
CTS. It is clearly demonstrated that the copper strips its individual area varies in 0.2 ~ 1.8 m2. No active
bonded on the panel attenuate the temperature gradient of cooling is supposed and the passive cooling is introduced
the panel. Different thermal behaviors at the joint are locally for the removal panels. Cooling tube is not directly
also found for the two mock-ups. attached on the removable panel, but attached on the
frame, which is connected to the panel by bolted joint.
Thermal contact resistance should be minimized at the
I. INTRODUCTION joint for effective passive cooling. To achieve acceptable
thermal contact conduction, an effective pre-compression
The ITER cryostat thermal shield (CTS) should with metal-inserting such as copper gasket is required at
minimize radiation heat load transferred from the cryostat the joint. Design requirement for the thermal contact at
to the superconducting magnet that operates at 4.5 K. The the joint is such that the temperature difference across the
CTS operating at 80 K are constructed with stainless steel joint should be lower than 3 K. The effective thermal
of thickness ranging between 10 and 30 mm. Silver contact at the joint should be demonstrated by the mock-
electroplating is to be applied to the thermal shield in up test.
This paper deals with the experimental study on the
passive cooling panel for the ITER CTS. Two kinds of
20 m mock-ups are developed and their cooling tests are
performed at liquid nitrogen temperature level.
Temperature difference at the joint and the panel
6m
temperatures are measured for different radiation heat
flux conditions. Passive cooling characteristics are
investigated with the measured temperatures concerning
different designs of two mock-ups.
15 m
II.A. Description
5m
with bonded
1000
copper (2t)
contact pressure distribution illustrated by the film. The
50
fastening torque for mock-up assembly is set to be 600
304L plate (10t)
kgf-cm for which the contact pressure reaches 10 MPa.
Bottom view of panel
Mock-up B
III. EXPERIMENTAL APPARATUS
Fig. 2. Two mock-ups for the removable panel III.A. Temperature Measurement
220
200
Tube inlet
Panel (Ch 3)
Panel (Ch 11)
Temperature (K) (K)
180
Panel (Ch 12)
Frame (Ch 13)
Temperature
160
140
120
100
80
0 2 4 6 8 10 12 14 16 18 20 22 24
Time (hr)
Time (hr) Edge temperature (K) 84.1 98.8 110.1
Fig. 9. Temperature history during cool-down of Center temperature (K) 100.3 127.7 172.8
mock-up A (no heating of screen) Heat flux (W/m2) 11.4 22.2 52.9
Fig. 10. Estimation of heat flux into the mock-up by
IV. EXPERIMENTAL RESULTS the analysis with temperature measurement result
temperatures between the analysis and the measurement.
IV.A. Mock-up A Figure 10 shows the heat flux value obtained from the
analysis and temperature measurement. Temperature
The temperatures of panel, frame and tube inlet/outlet differences at the joint for the increased heat flux are
are monitored and recorded until steady state is reached. summarized in Table I-(b), (c). The average temperature
The steady state is determined when the panel center difference is below 3 K when the heat flux increases up to
temperature is maintained as constant (< 0.1 K variation) 22.2 W/m2. Two sides of the mock-up face the warm
during 2 hours. Figure 9 shows a typical temperature surface, while one side of the ITER CTS is exposed to the
history during cool-down of mock-up A. Coolant cryostat. Therefore, for the heat flux 22.2 W/m2 in the test,
temperature is maintained near liquid nitrogen about two times larger heat load is transferred to the
temperature. Panel center temperature (Ch 11) reaches mock-up compared with the design load of CTS
100.3 K. Table I-(a) summarizes the measurement of removable panel. The temperature difference is still below
temperature difference at the joint for no heating 3 K under larger heat load condition than ITER CTS.
condition. The temperature difference varies from 0.4 K
to 2 K and its average value is 1.1 K. IV.B. Mock-up B
Radiation heat load is increased by heating the screen
using the heaters around the vacuum chamber to Table II-(a) summarizes the temperature
investigate the effect of heat flux on conduction cooling. measurement result of the mock-up B under no heating of
The heat flux to the mock-up is measured indirectly from vacuum chamber. The screen temperature is measured as
the measured temperature of panel. Square panel is 258 K. Total 7 points at the joint are measured for the
analyzed with inputs such as edge temperature (average mock-up B. By comparing with the mock-up A result,
value from the experiment) and heat flux into the panel. temperature gradient at the panel decreases approximately
The heat flux is obtained by matching the panel center from 16 K to 10 K due to the bonded copper plate on the
(7,17)
TABLE III. Temperature Difference at the Joint for
Different Heat Loads
Fig. 11. Measurement points at the joint of mock-up B
Heat load ǻT at the joint
panel. Figure 11 shows measurement points at the joint 0.95൮Q* 1.1 K
Mock-up A
for the mock-up B. It is revealed that top and bottom 1.85൮Q* 2.3 K
edges show smaller temperature difference (0.6 ~ 1.4 K), 0.98൮Q* 2.0 K
while side edges show larger values (2.1 ~ 3.6 K). The Mock-up B
1.76൮Q* 2.9 K
main distinction is that the copper plates are extended *Q is the design heat load corresponding to the heat
from the side edges to the center. Radiation heat into the flux (24 W/m2) of ITER CTS.
panel mostly flows through the extended copper plate due
to its large thermal conductance. Therefore, left and right ACKNOWLEDGMENTS
sides of the joint shows larger temperature difference due
to the larger heat flow through the bonded copper plates. This work is supported by the Ministry of Education,
Table II-(b), (c) show the results for the heating of Science and Technology of Republic of Korea under an
screen around the mock-up. The heat flux to the mock-up ITER Project Contract.
is estimated using the modified Stefan-Boltzmann
radiation equation3 with the measured screen temperature. REFERENCES
The emissivity of the mock-up and the screen are set as
0.05 and 0.3 respectively in the equation. When the screen 1. V. BYKOV et al, ³The ITER thermal shields for the
temperature is maintained near room temperature by magnet system: Design evolution and analysis,´
heating, the average temperature difference is still below Fusion Engineering and Design, 75-79, 155 (2005).
the design requirement (< 3 K). In this case, the heat load 2. C. H. NOH, K. NAM et al, ³Manufacture and Test of
is about 1.8 times bigger than the design load for the Mock-up for ITER Thermal Shield,´ Fusion
ITER CTS because two sides of the mock-up are exposed Engineering and Design, 85, 1880 (2010).
to the warm surface. 3. R. F. BARRON, Cryogenic Systems, pp. 386±387, 2nd
Ed., Oxford University Press, New York (1985).
V. SUMMARY AND CONCLUSIONS