• For large rooms, place detectors so that the coverage circles overlap.
Common Spacing Rules: Spacing Vs. Radius of Coverage
Where:
H > 3 meters
Line Type Heat Detector Coverage
As heat from the fire drives the hot gases upward, the further they rise above
the fire the more the column of hot gases cools.
When the temperature of the rising gases reaches equilibrium with the ambient
temperature, the column stops rising and the gases spread out horizontally.
Projected Beam Smoke Detector
Loop 1 fault
•Check the Loop 1 wiring for any Short or open fault.
•Check the Wiring class configured for Class A or Class B.
Device Missing
•Check the device is installed properly.
•Check the wiring of the device.
Check whether the addressing done properly
Trouble Shooting
Device Not Blinking
.
•Check whether the device Disabled from the panel.
•Check whether the addressing done properly.
•Check the connection of the device.
Device Fault
•Check the connection of the device.
•Check the device properly configured in the panel.
•Check the loop Length should not exceed the recommended distance
•Check the EOL of the device.
Notification devices Active even after silenced
1.Check the configuration of the module for Reset or silenced.
Notification Devices Not activated
•Check the NAC wiring for any open or short.
•Check the auxiliary voltages are properly given on control Modules.
•Check whether the particular module is in the proper group
Trouble Shooting
Control Modules Not activated
•Check whether the module is programmed in output group for particular
logic.
Buzzer is still active after silencing the Panel
•Check whether the particular event is acknowledged in the panel
by pressing ACK button in the panel
Isolator base Yellow indication Steady ON
•Short Circuit on the field devices identified,
Please check the cabling and devices for Short circuit.
Repeater Panel Not working
Check the Communication cable properly terminated.
Check whether the configuration done from the programming menu of
main panel
and repeater panel.
Check whether the Data cable length between main and repeater
panel shall exceeds 1.2 Kms.
Check whether the data cables are laid along with HT cables.
Check whether the Repeater panel Installed in strong EMF area.