Professional Documents
Culture Documents
Submitted by:
Nathaniel A. Famisan
2015-12571
In Partial Fulfillment
of the Requirements in
CE 156: Design of Steel Structures
Submitted to:
For structural engineers, their intuitive ability to make decisions are guided
by computational results, highlighted especially during the structural framework
design component. This is where the selection of arrangement and sizes of
structural elements takes places so that service loads may be carried safely at the
same time that displacements are inspected in order to fall within acceptable limits.
This report covers the first phase of this course’s project, wherein the
researcher is asked to design a proposed 3-storey office building to be located in
Palawan, Philippines. The specifications (dimensions for partitions and length-
width configurations) of the 3-storey office building are shown below from Figures
1 to 3. Note that all dimensions derived are expressed in millimeters (mm).
LEGEND:
Framework Joint. Original (Uniform) Column.
Transverse Girders. Transverse Secondary Beams.
Longitudinal Girders. Longitudinal Secondary Beams.
2
Figure 2: Dimensioning for the Right Side Elevation View of the Building.
Figure 3: Dimensioning for the Left Side Elevation View of the Building.
For this project, the researcher opted to utilize the Howe type of truss,
referring back to the frame system of the building’s structure. The calculated roof
angle was θ ~ 9.335⁰. The schematic diagram of the Howe truss configuration for
3
this project is shown below in Figure 4 via SketchUp 2019 software. Note that
all pertinent dimensions for the truss system are expressed in millimeters (mm).
The structural plans for this project are indicated in the succeeding images.
Figures 5A and 5B illustrate the 3D models of the office building excluding and
including the general roof truss system as per original construction plans. Figures
6A to 6C correspond to the building’s 3 stories, while Figure 7 shows the rough
sketch of the partitions based on the third floor (3F) as per rendering of the original
layout using SketchUp 2019 software.
Note that the open areas built for locating the staircases for the second and
third floors (2F and 3F) are omitted from the loadings since they do not cause any
loading. Moreover, tentatively for this introductory project phase report, the
researcher opts for the assumption of identical column layouts but different
selections of steel structural beam selections across the office building’s 3 floors,
and therefore still subject for revisions upon doing the analytical procedures for the
succeeding project phase reports on the design of truss members for axial
members as well as of compressive column layouts.
LEGEND:
Original (Uniform) Column. Tributary Area.
Transverse Girders. Transverse Secondary Beams.
Longitudinal Girders. Longitudinal Secondary Beams.
4
Figure 5A: Perspective View of the Building
Excluding the General Roof Truss System
5
Figure 6A: Ground Floor (GF) Configuration.
6
Figure 6C: Third Floor (3F) Configuration.
Dead loads are fixed-position gravity service loads that are usually known
accurately but not until the design is completed. These include the structural
components’ self-weight, interior floor finishes, ceiling and utilities, and interior and
7
exterior partitions. These were inspected in the preliminary design of the office
building, with respective loads indicated below in Table 1.
In contrast, live loads are gravity loads acting when the structure is in service
(or in general use) but vary in magnitude and location. These are prescribed by
empirical and conservative state and local building codes due to safety concerns in
the structure’s construction and usability. These were inspected in the preliminary
design of the office building, with respective loads indicated below in Table 2.
This report also accounts for the special case for roof live loads given the
researcher’s option to choose the materials for the roofing phase of the office building’s
8
construction project. Since uniform roof loads are involved in the design of structural
members arranged to create continuity, full dead loads on all spans as well as full roof
live loads on adjacent and alternate spans alike are jointly considered. These were
inspected in the preliminary design of the office building, indicated below in Table 3.
To account for the minor detailed loadings in the interior design of the building,
special loads were also inspected to determine whether such components induce
uniform or concentrated load in the overall design load path of the structure, as
indicated below in Table 4.
The load combinations for the design of the office building are displayed
below as per Section 203.3.1 (Basic Load Combinations) from NSCP 2015:
• 1.4(D+F) (203-1)
• 1.2(D+F+T) + 1.6(L+H) + 0.5(Lr or R) (203-2)
• 1.2D + 1.6(Lr or R) + (f1L or 0.5W) (203-3)
• 1.2D + 1.0W + f1L + 0.5(Lr or R) (203-4)
• 1.2D + 1.0E + f1L (203-5)
• 0.9D + 1.0W + 1.6H (203-6)
• 0.9D + 1.0E + 1.6H (203-7)
9
where f1 = 1.0, for floors in places of public assembly, for live loads in excess of
4.8 kPa, and for garage live load, or f1 = 0.5 for other live loads.
• D = dead load.
• E = earthquake load set forth in Section 208.6.1.
• Em = estimated maximum earthquake force that can be developed in the
structure as set forth in Section 208.6.1.
• F = load due to fluids with well-defined pressures and maximum heights.
• H = load due to lateral pressure of soil and water in soil.
• L = live load, except roof life load, including any permitted live load
reduction.
• Lr = roof live load, including any permitted live load reduction.
• P = ponding load.
• R = rain load on the undeflected roof.
• T = self-straining force and effects arising from contraction or expansion
resulting from temperature change, shrinkage, moisture change, creep
in component materials, movement due to differential settlement, or
combinations whereof.
• W = load due to wind pressure.
10
H2F = C (m) 3.100
Pglass (m) 48.575
W (m) 22.333
L (m) 33.500
2
A2F (m ) 668.675
11
Bottom Chord 6.140 lb/ft 0.090 kN/m 9 24.333 - 19.631
1 3.070 lb/ft 0.045 kN/m 18 0.333 - 0.269
2 3.070 lb/ft 0.045 kN/m 18 0.667 - 0.538
3 3.070 lb/ft 0.045 kN/m 18 1.000 - 0.807
Vertical Chord
4 3.070 lb/ft 0.045 kN/m 18 1.333 - 1.076
5 3.070 lb/ft 0.045 kN/m 18 1.667 - 1.345
6 6.140 lb/ft 0.090 kN/m 9 2.000 - 1.613
1 3.070 lb/ft 0.045 kN/m 18 2.055 - 1.658
2 3.070 lb/ft 0.045 kN/m 18 2.135 - 1.722
Diagonal Chord 3 3.070 lb/ft 0.045 kN/m 18 2.261 - 1.824
4 3.070 lb/ft 0.045 kN/m 18 2.427 - 1.958
5 3.070 lb/ft 0.045 kN/m 18 2.625 - 2.118
Purlins 4.500 lb/ft 0.066 kN/m 252 12.330 - 204.124
SUMMATIVE DEAD LOAD (kN) 1,255.350
LL Roof Live Load - - 0.600 kPa 8 - 111.021 532.900
SUMMATIVE LIVE LOAD (kN) 532.900
TOTAL ROOFTOP LOAD (kN) 1,788.250
12
7,489.726 10,450.274
OVERALL LOAD
17,940.000
The live and dead load calculations for each of the second and third floors,
as well as the roofing system, are displayed above from Tables 5A to 8. It is
assumed that steel decks are installed below each of the second and third floors,
and the roofing system also contains a ceiling. The overall dead load carried by the
3-storey office building, which is equivalent to the weight parameter that will affect
the overall earthquake load that it will experience, is 7,489.726 kN. Meanwhile, the
live load counterpart measures 10,450.274 kN.
The projection that the live load is greater than the dead load adheres to the
preliminary assumptions given the assumed standard occupancy of the building.
Subsequently, the overall maximum design gravity load carried by the 3-storey
office building, as shown from the same referred data, measured 17,940 kN.
V. Deflection Limits
With this, it is important to determine the deflection limits that highly affect
the suitability of a structural design for its usage requirement. The deflection limits
for this project were determined and expressed in terms of length, l, of a particular
beam, as shown below in Table 9.
For the general parameters of this structural criteria report, the National
Structural Code of the Philippines (NSCP) (2015), specifically its Chapter 2, and
the American Institute of Steel Construction (AISC) Manual (2011) are used to
set the parameters. For the designated dead load of the desired roofing system of
13
the building, the specifications of the galvanized iron sheeting to be used in the
construction were derived from Continental Steel & Tube Company
(https://titanium-stainless-steel.continentalsteel.com/) for further inspection.
The researcher also opted to obtain the specifications of the steel deck for
the upper floors of the office building from Galvadeck Steel Decking Profile
(https://www.filbuild.com/b2b/united_steel_technology/25_galvadeck_steel
_decking_profile_dimensions_section_properties.html) for tabulation.
VII. Discussion
The dimensions are derived from Mathcad 2019 computations using the
researcher’s student number (2015-12571), as shown in Figure 8. Note that the
original equations, as stipulated in the previous construction drawings, are
expressed in meters (m), necessitating further conversion to millimeters (mm).
As shown from Tables 1 to 8, the tentative total design load for each of the
3 stories and the roofing system consists of the dead loads (comprising both the
superimposed dead loads and the self-weights of pertinent components as per
NSCP (2015) guidelines) and live loads, depending on the use of each floor
throughout the building’s overall serviceability.
A uniform procedure was utilized in producing the load calculations for each
of the floors’ self-weights. For instance, the equivalent loading on the secondary
beam in the structure is obtained as a product of the indicated pressure load and
ratio of the tributary widths (which are half the lengths of their neighboring beams
or girders, whichever is applicable). This is then used to derive the reactions as
concentrated loads on the girders present in a section of interest in the structure.
14
Aside from this, the loading on the interior column is obtained as a product of the
indicated pressure load and pertinent tributary area in the structure.
For the second and third floors, their respective composite slabs are
identical in composition, comprising of the ceiling and floor specifications shown
earlier in Table 1. The superimposed dead load for the composite slab is the sum
of all the mentioned components’ loadings, as shown below in Figure 9.
15
Figure 10: Snapshot of Mathcad Preliminary Calculations for the
Superimposed Concrete Hollow Block Dead Load.
16