K2 -199.9 to 500.0°
C However, 1 : 4-20mA
E -199.9 to 700.0°
C 2 : 0-1V
more than
3 : 0-10V
J -199.9 to 900.0°
C 200° C E : 1 additional event relay output
T -199.9 to 400.0°
C or less than (EV4)
U -199.9 to 400.0°
C 0°C is Program features
N : None
L -199.9 to 900.0°
C ±0.5%±1digit P : Available
WRe5-WRe26 0 to 2310°C 3 additional event open collector
0 to 400°C: signals + 5 additional external inputs
W-WRe26 0 to 2310°
C - : None
±0.5%±1digit 7 : 3 additional event open collector
0 to 400°C: signals
Out of 8 : 5 additional external inputs
9 : 3 additional event open collector
PtRh40-PtRh20 0 to 1880°
C specifications
signals + 5 additional external
400 to 800° C: inputs
±1.5%±1digit Heater snapping wire alarm
Platinel 0 to 1390°
C 0 : None
1 : Available
Pt100 1 -199.9 to 850.0°
C * If you want to select "1" for the
Pt100 2 -199.9 to 200.0°
C 12th digit, select "1" or "5" for
RTD
1
PSE-802B
CP350/370 SERIES
Measuring value(PV)
●Program specifications
(Parameter item in setting mode) Step & pattern number:
4 patterns and 12 steps or 1 pattern and 48 steps
S5 S6
SV S7 S8
S3 S4
S1 S2 S9 S10
S11 S12
S0
2
●Event specifications ■ Available accessory
Event output points:
Relay output 2 points (EV1, EV2) standard Name Model NOTE
Max. 2 points relay output (EV3/EV4) option
Max. 3 points open collector output
(EV5/EV6/EV7) option Shunt resistor (250Ω) EZ-RX250 For DC 4 to 20mA current
Alarm type: (available EV1 to EV4)
Absolute value alarm... High/low, stand by
enable/disable CX-CR1 For light load
Deviation alarm... High/low, standby enable/ Contact protection
disable element for relay output
Absolute deviation value alarm ...High/low, CX-CR2 For heavy load
enable/disable
Output value alarm ...High/low, enable/disable
Fail, heater disconnection alarm, timer function For heater Disconnection
Event type: 34 types (max.) of alarm events External CT CTL-6-S-H
detection
27 types of status events (max.)
Event dead band: Can be set by the resolution being 0.1 times
the setting resolution of SV.
Event output phase: Normal/reverse switchable event output at
Ready: Off/calculation switchable
Event output (EV1 to EV4): ●Option
Output signal ... non-voltage contact Name Content
Contact rating:
Resistance load ... 100 to 240V AC Max 3A, Control calculation: SPLIT system/PID system
30VDC, Max 3A The setting range of SPLIT system
Inductive load ... 100 to 240V AC Max 1.5A, Control output 2 .Direct ... 0.0 to 60.0%
30VDC Max 1.5A .Reverse ... 40.0 to 100.0%
Minimum load ... 10mA, 5VDC or more Insulation: Not insulated with outputs
Electrical life of relay ... a hundred thousand Insulated with internal circuit
times or more
Protect element of contact ... Non internal: Event points:
enable to set other elements Event relay output ... two points (max.)
Event output (EV5 to EV7): (EV3/EV4)
Output signal ... Transistor open collector output Additional events Event open-collector output
Output rating ... 24V DC, 50mA or less output ... three points (max.) (EV5/EV6/EV7)
Insulation: Insulated with internal circuit (20MΩ or more Event type: alarm events ... 34 types (max.)
/500VDC) status events ... 27 types (max.)
Insulated with relay output
Non-insulated with transmitter open collector Output signal proportionate by SV, MV, etc.
output Output signal:
4 to 20mA DC
(Load resistance 600Ω or less)
●Display specifications Selected 0 to 1V DC or 0 to 10V DC.
Display type: 4-digit LED display, two lines Transmission (Output impedance approx. 10Ω
Status display 8 independent LEDs signal output Load resistance 50kΩ or more)
Display contents: First LED (yellow-green) display Accuracy rating: ±0.3% of FS
At operation mode: Process value (PV) Resolution: Approx. 1/30,000
At setting mode: Parameter item Output update period: Approx. 0.5 second
Second LED (red) display Insulation: Insulated with internal circuit
At operating mode Set-point value (SV), (20MΩ or more /500V DC)
Control output value (OUT)
At setting mode: Parameter item Input points: Six points (max.)
Status (red) display Input signal:
EV1: Lights when EV1 or status 1 is activated No-voltage contact, open-collector signal
EV2: Lights when EV2 or status 2 is activated Function:
AT: Lights when auto-adjustment 1. RUN/READY selectable by external input
RUN: Lights when auto-operation 2. Remote/Local selectable by external input
OUT: Lights when the control output value 3. Auto/Manual selectable
MAN:Lights when manual operation 4. Start Timer
SV: Lights when the SV value displayed in External input 5. Alarm event RESET
second display 6. Select Parameter Group No.
OUT: Lights when the output value displayed 7. Program operation
in second display (RUN/ADVANCE/RESET)
Automatic return: Returns to operation mode if any key is not 8. Select program pattern No.
pressed Insulation: Insulated with internal circuit
for more than approx 3 minute in setting mode (20MΩ or more for 500VDC)
Key lock: Exist
Communications type: RS485
Protocol: MODBUS (RTU), MODBUS (ASCII),
●General specifications PRIVATE
Rated power voltage: General power supply specifications 100 Communication Communication function: Select transmission
to 240VAC (50/60Hz) interface setting/data or digital transmission or digital
Ambient temperature: -10 to 50ºC (max. 40ºC for closed- remote transmission
installation) Insulation: Insulated with internal circuit
Ambient humidity: 10 to 90% (no dew condensation) (20MΩ or more / 500VDC)
Maximum power consumption:
Approx. 10V A without option Input signal: ±5.0 to 50.0A AC
Approx. 16V A with option Heater Accuracy rating: 5.0% of FS ±1 digit
Front material: Nonflammable ABS disconnection External CT: "CTL-6-SH" made by U-RD
Casing: Nonflammable polycarbonate detection recommended
Color: Gray
Mounting method: Panel mounting Front panel protection:
Weight: CP350 Approx. 240g without option Panel sealing Equivalent to IEC60529 IP65
Approx. 330g with option specification (self-declaration)
CP370 Approx. 330g without option & Terminal cover *Not possible during closed instrumentation
Approx. 420g with option Terminal cover protects terminal box
3
■Terminal board
1 NC A 11 EV5 21 SA
Communication
2 Measurement Thermocouple + RTD B 12 EV6 22 SB
interface
input DC/AC Event
(RS485)
output
3 - B 13 EV7 23 SG/COM(DI1)
Relay output
4 EV1 Relay output 14 COM 24 External input DI1
P.S.
Event
5 output
EV2 15 DI2 25 Heater CT
disconnection
alarm (CT)
6 COM 16 DI3 26 CT
Transmission signal
7 Output 1 On-off
N.O + 17 DI4 27 Transmission output+/EV4
External
(Control pulse type Others signal output
input
output) (Relay output) event output Transmission signal
8 COM - 18 DI5 28 output -/COM
94
48 96 100
7
132
70 120
92 +0.8
0
92 +0.8
0
92+0.8
0
120
120
+2 +2
48×N−3 0 96×N−4 0
92 +0.8
0
N: Quantity N: Quantity