Introduction
The battery system in a UPS represents the heart of the power protection benefit. This key element
performs two functions: (1) it delivers energy during a power outage, and (2) it stores energy efficiently for
extended periods of time. That stored energy is instantaneously available when needed to support the
critical load on the UPS. In order to perform the above functions reliably, the charge level of the battery
must be maintained. At the same time, battery charging should be controlled to maximize system
efficiency and, more importantly, to maximize the float service life of the battery system.

The unfortunate fact is that Valve Regulated Lead Acid (VRLA) batteries are often marketed as having a
10-year design life. However, real world data shows that in UPS applications, the battery is replaced every
four to five years on average. Because the battery often accounts for 30% of the cost of the UPS, users
frequently request that UPS vendors extend the service life of the battery as much as possible.
Considering that the benefit of longer service life is lower life cycle cost and capital expense, it is not
surprising that users desire tangible evidence that battery monitoring and battery management systems
actually perform as advertised.

Two types of battery charging schemes have traditionally been used for UPS battery systems. The older
and more commonly known is the “float” charge, which involves applying a constant voltage charge to the
battery continuously for purposes of maintaining full charge during day-to-day operation of the UPS. This
works quite well in many conventional battery applications. However, battery life may not be optimal, due
to overcharging, for batteries that are used very occasionally as in standby applications such as a UPS. In
a UPS, the battery system may sit in float mode for many months, without ever experiencing a discharge.
Float charging for long periods of time means that “trickle charge” energy is constantly forced into a
battery which is effectively already full. This results in very gradual degradation of the lead plates (positive
grid corrosion), and it can impact float service life.
®
Standby applications are better suited for “opportunistic” charging schemes. The system Eaton utilizes is
called ABM technology, which is essentially a set of charger controls and automated battery tests. It is
implemented in Eaton single-phase UPSs from 500 VA to 18 kVA and three-phase models from 10 kVA to
3.3 MVA. Opportunistic charging schemes like ABM allow for periods of time where the battery is being
fully charged, and periods of time when the charger is disabled. This reduces the time that the battery is
subject to grid corrosion when compared to a traditional float charger — a reduction in grid corrosion that
yields a measurable increase in battery life for UPS applications.

ABM Operational Summary


As shown graphically in figure 1, ABM consists of three operating modes:
1) Charge mode
2) Rest mode
3) Test mode

WP09-18 www.eaton.com/powerquality January 2018


Page 2 of 5

Figure 1: Depiction of ABM modes

Charge Mode
The UPS enters the charge mode under any of the following conditions:
• Whenever the UPS is commanded to turn on
• After any utility power outage lasting longer than 15 seconds
• Whenever the battery is replaced (or the battery breaker is opened and re-closed)
In charge mode, constant voltage charging of the batteries is used to recharge a discharged battery after a
power outage, or whenever the ABM process is restarted. Charge voltage target is set to the
manufacturers’ float level, and charge current is greater than 0.1 C A. Constant voltage charging lasts only
as long as it takes to bring the battery system up to a predetermined float level (there is a 100-hour
maximum time limit). Once this level is reached, the UPS battery charger remains in constant voltage
mode, maintaining a float level. The current is at trickle charge levels during this time, and a 24-hour clock
is started. At the end of 24 hours of float charging, the UPS automatically performs a battery test (see
figure 1) at two different load levels to verify that the battery is performing, and to collect data for
comparison to previous and subsequent automatic battery tests. If the test fails, an alarm is activated on
the UPS and also through the remote monitoring system that may be connected to the UPS. At the end of
the test, the charger resumes constant voltage mode and remains in that state for an additional 24 hours.

WP09-18 www.eaton.com/powerquality January 2018


Page 3 of 5

Rest Mode
Rest mode begins at the end of charge mode; that is, after 48 hours of float charging, and after a
successful battery test. In rest mode, the battery charger is completely turned off. The battery system
receives no charge current during this mode, which lasts about 28 days. Then, the charge mode is
repeated as described above. Since the battery clearly spends most of its time in rest mode, as a result,
the following benefits are realized:
1) The battery is not subjected to constant forced charge current; therefore, overcharging is not
possible.
2) Thermal runaway is not a concern with the charger off.
3) The battery system cannot be damaged by ripple currents, since the charger is off.
4) Positive grid corrosion is greatly reduced, allowing extended service life.
During rest mode, the open circuit battery voltage is monitored constantly, and battery charging is initiated
if any of the following occur:
• A power outage lasting longer than 15 seconds
• The open circuit voltage (OCV) of the battery drops below a predetermined threshold after 10
days of rest mode
(If OCV drops below the predetermined threshold during the first 10 days, an alarm is triggered)
• 28-day timer expires (end of rest mode)
• The battery is replaced, or the breaker is opened and re-closed

Test Mode
There are two other battery tests that are performed as a part of the ABM cycle. The first is meant to
detect battery conditions which could lead to thermal runaway. The bulk charging period is timed and if the
float voltage is not reached in a predetermined time, an alarm is triggered and the charger is shut down.
The second test is performed after the charge cycle is completed (i.e., at the beginning of rest mode). The
battery is discharged at about 15% load for up to 6 minutes, then at 50% load for 45 seconds.. Upon
reaching this point, the battery voltage is measured. If the voltage is below a specified threshold,
dependent on the load, then an alarm is signaled indicating the battery is nearing the end of its service life
and should be replaced.

Other Modes
ABM may be disabled by the user or an Eaton field technician at any time. In this case, the UPS battery
charger operates as a conventional float charger only. This is recommended when a wet cell or flooded
electrolyte battery is used with the UPS. ABM is intended for use with VRLA batteries. As a result, wet
batteries do not benefit from ABM controls.

Many observers express concern regarding the ability for the battery to maintain capacity if called upon to
support the UPS near the end of its rest mode. In other words, how much battery capacity is available on
day 27 of a 28-day rest mode? Using a 15-minute battery as an example, under this condition, the battery
would provide all but about 30 seconds of its 15-minute backup time. This is proportionally true for other
battery sizes, as well. The intent in selecting the 28 day rest period is to limit the loss of capacity to
approximately 5%.

ABM Performance
The ABM process above describes the benefits of using a “opportunistic” charging scheme. Those
benefits, specifically extended service life, are in fact substantiated by data and empirical testing
performed by Eaton as well as other independent sources. Some of this testing is recent and some of it
was performed as many as 25 years ago.

ABM is not a new battery management feature. In fact, Eaton has been using ABM in its UPS products for
27 years, and it has proven itself beneficial in the field for more than two decades.

WP09-18 www.eaton.com/powerquality January 2018


Page 4 of 5

Battery Life Data

9
8
7
Back up time min.

6
5 ABM
4 Trickle
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Tim e in test, m onths

Figure 2: Accelerated Life Testing of ABM at 40 degrees C

In figure 2, the testing was performed at a very high ambient temperature to provide meaningful data in a
shorter period of time. The service life enhancements become evident after about only seven months of
this accelerated test. This test was done with conventional UPSs and VRLA batteries.

Battery Life Test

14

12

10
Back up time min.

8
Cyclic
Float
6

0
0 6 12 18 24 30 36 42 48 54 60 66
Time in test, months

Figure 3: Long Term Cyclic Charge vs. Float Test

In figure 3, the effect of a cyclic charging regime over several years is demonstrated. This testing was
done almost 20 years ago, by a battery manufacturer not associated with Eaton or any UPS vendor.

WP09-18 www.eaton.com/powerquality January 2018


Page 5 of 5

Figure 4: Calculated Service Life Extension for ABM Charge Algorithm

Note that in figure 4, the curve identified as “23/23 days” represents a float charger, and ABM (as
implemented today) is best represented by the curve labeled “12/23 days.” At an ideal 25°C (77°F), there
is a theoretical increase of six years in battery service life reflected in this analysis.

The above information shows a clear benefit of cyclic charging in UPS applications, both in simulated and
in actual performance tests. These results would not be expected with non-VRLA batteries or in
applications such as motive power chargers where the battery is discharged/recharged daily and therefore
not deployed in a standby application.

Summary
ABM is unique in the UPS industry, but similar opportunistic designs are utilized by battery manufacturers
and battery charger designers worldwide. The criticality and cost of the battery subsystem of any UPS
dictates that special consideration be given to battery longevity. Additionally, with environmental concerns
relating to battery removal and disposal becoming more prevalent, it is desirable to reduce the frequency
of battery replacements during the life of the UPS electronics. ABM offers a significant benefit over
conventional “battery monitors” which don’t provide charging control, and “multi-stage chargers” which
protect the battery, but do not provide useful extension of battery service life.

Over the past 27 years, ABM has proven itself in both large and small UPS products, from the desktop to
the data center, and from the medical lab to the factory floor. Anywhere a UPS is installed, a battery
system is depended upon to provide backup power protection for critical business processes and even for
personnel safety. The battery is all too often ignored as a maintenance-free product, not requiring
attention or inspection. This neglect, though common, can be costly and possibly disastrous. The ABM
system, by its nature, helps to provide early detection of problem batteries and thus protect the battery
from unnecessary failures like electrolyte dry out and thermal runaway, while functioning to extend the
useful life of this key component of power quality.