SPECIFICATION
SPAN-TS XXXX:YYYY
ICS: 93.080.30
© Copyright 2020
Suruhanjaya Perkhidmatan Air Negara (SPAN)
A document developed by SIRIM for SPAN
SURUHANJAYA PERKHIDMATAN AIR NEGARA (SPAN)
SPAN vision is towards a sustainable, reliable and affordable water service for all and
with the mission to regulate the water services industry through fair, effective and
transparent implementation of Water Services Industry Act 2006 (Act 655).
SPAN-TS is developed from SPAN initiatives as a regulatory body for the water supply and
sewerage services through collaboration with SIRIM which provides requirements,
specifications, guidelines or characteristics that can be used to ensure that materials, products,
processes and services are fit for their purpose.
© Copyright 2020
Page
Foreword .................................................................................................................... ii
1 Scope .............................................................................................................1
4 Classification ..................................................................................................7
5 Materials .........................................................................................................9
6 Design requirements.....................................................................................13
9 Marking.........................................................................................................25
Bibliography .............................................................................................................46
This SPAN-TS was developed by the Project Committee on Manhole tops for water
and sewerage application.
b) to assist the industries to certify their products against a given standard; and
This technical specification will be subjected to review to reflect current needs and
conditions. Users and other interested parties may submit comments on the contents
of this standard for consideration into future versions.
Compliance with this technical specification does not by itself grant immunity from legal
obligations.
1. Scope
This technical specification specifies requirements for manhole tops for sewerage and
water supply application with a clear opening of 600 mm and up to 1 000 mm, for
installation within areas subjected to pedestrian and/or vehicular traffic.
2. Normative references
The following normative references are indispensable for the application of this
technical specification. For dated references, only the edition cited applies. For
undated references, the latest edition of the normative references (including any
amendments) apply.
MS 144, Cold reduced mild steel wire for the reinforcement of concrete - Specification
MS 146, Hot rolled steel bars for the reinforcement of concrete - Specification
ISO 1459, Metallic coatings - Protection against corrosion by hot dip galvanizing
Guiding principles
ISO 1460, Metallic coatings - Hot dip galvanised coatings on ferrous materials -
Gravimetric determination of the mass per unit area
ISO 1461, Metallic coatings - Hot dip galvanised coatings on fabricated ferrous
products - Requirements
ISO 12944 (series), Paints and varnishes - Corrosion protection of steel structures by
protective paint systems
ISO 14713, Protection against corrosion of iron and steel in structures - Zinc and
aluminium coatings - Guidelines
© SPAN 2020 - All rights reserved 1
ISO 14737, Carbon and low alloy cast steels for general applications
ISO 630-1, Structural steels - Part 1: General technical delivery conditions for hot-rolled
products
ISO 630-2, Structural steels - Part 2: Technical delivery conditions for structural steels
for general purposes
ISO 630-3, Structural steels - Part 3: Technical delivery conditions for fine-grain
structural steels
ISO 630-4, Structural steels - Part 4: Technical delivery conditions for high-yield-
strength quenched and tempered structural steel plates
ISO 630-5, Structural steels - Part 5: Technical delivery conditions for structural steels
with improved atmospheric corrosion resistance
ISO 630-6, Structural steels - Part 6: Technical delivery conditions for seismic-
improved structural steels for building
BS EN 10130, Cold rolled low carbon steel flat products for cold forming - Technical
delivery conditions
EN 10025-1, Hot rolled products of structural steels - Part 1: General technical delivery
conditions
EN 13036-4, Road and airfield surface characteristics - Test methods. Method for
measurement of slip/skid resistance of a surface - The pendulum test
For the purposes of this technical specification, the following terms and definitions
apply.
NOTE. Examples for unobstructed areas are shown as the shaded area in Figure 1 a) to Figure 1 c). In
the case that the area of seatings in the frame is interrupted by functional areas, for example, areas for
drainage of water or means for access to manholes and spaces for hinges, locking and securing systems,
these functional areas are not considered for the calculation of mass per unit area. If there are more
clear area
clear area
clear area
The diameter of the largest circle that can be inscribed in the clear area (see 3.1) of
the frame.
NOTE. Examples are shown in Figures 2 a) to 2 f). The clear opening is expressed in millimetres (mm).
3.3 cover
The movable part(s) of manhole top which covers the manhole opening.
Accessory provided within a frame, grating or cover to achieve stability and quietness
in use.
Distance between the top of the frame and the bottom of the cover or grating adjacent
to the seating.
NOTE. Examples are given in Figure 3. The depth of insertion is expressed in millimetres (mm).
3.6 element
NOTE. Hinges, locking accessories and other accessories are not elements.
3.7 frame
If circular, the frame size shall be the outer diameter of the frame.
If rectangular or square, the frame size shall be the length and width of frame.
Distance between the top surface and the bottom surface of the frame
The surface of the underside of a frame which rests upon the supporting structure.
3.12 manhole
Total mass of the cover or the grating in kilograms divided by the clear area in square
metres.
Area reserved for pedestrians and only occasionally open to vehicular traffic for
delivery, cleaning purposes or in an emergency.
Area where vehicular traffic is prohibited during certain periods (e.g. pedestrian areas
during business hours and vehicular traffic outside these hours).
3.17 seating
Sum of the maximum individual clearances between adjacent elements of the frame
and cover.
NOTE. Examples are shown in Figure 4a),4 b),4 c) and d). The total clearance is expressed in millimetres
(mm).
6 © SPAN 2020 - All rights reserved
Σa = al + ar Σa = al + ac1 + ac2 + ar Σa = al + ac + ar
Σa = al + ar
Σa = al + ar
d) Example 4
Key
al clearance left
ac clearance centre
ar clearance right
3.20 vent
Overall effective drainage inlet area on the top surface of gully tops and in kerb units.
4.1 The appropriate class of manhole tops shall be used during installation. Manhole
tops are classified according to its place of installation and with the minimum test load
as specified in Table 1.
Figure 5 shows the location of some of these classes as specified in Table 1. The
selection of the appropriate class is the responsibility of the designer. When there is
any doubt off the minimum load cannot be ascertained, the stronger class should be
selected.
5. Materials
5.1 General
Manhole tops shall be made from any of the material listed in Table 2.
For any other material used in the field of application of this technical specification, all
requirements of this technical specification and any other relevant requirements
specified by the authority shall be met.
Manhole tops according to this technical specification shall be at least suitable for use
in wet and dry conditions and a slightly aggressive chemical environment, i.e. normal
conditions for domestic sewage and treated industrial effluent, and for most natural
soils and groundwaters. If more severe conditions are expected, additional
requirements for corrosion protection can be necessary.
© SPAN 2020 - All rights reserved 9
5.2 Corrosion protection
Corrosion protection of steel structures by protective paint systems shall comply with
ISO 12944-1 to 9 and protection of iron and steel in structures with zinc and aluminium
coatings shall comply with ISO 14713 respectively.
Steel manhole tops shall be resistant to corrosion. For use in normal conditions
corrosion resistance can be ensured, e.g. by hot-dip galvanising on a clean surface in
accordance with 5.2.2.1. Prior to application of any surface corrosion protection
system, manhole tops shall be fettled.
After a manhole top has been hot dip galvanised it can be straightened to overcome
any distortion prior to fitting the manhole cover in its frame. Any such straightening
shall not adversely affect the integrity of the hot dip galvanising or the structure of the
manhole top.
NOTE. Other supplementary coatings can be applied to the hot dip galvanised surface, e.g. coating or
paint systems.
The use of rolled steel is admissible only if a sufficient corrosion resistance is ensured.
This resistance can be achieved by hot-dip galvanising on a clean surface with a
thickness of equal or greater than the values given in Table 3. The minimum thickness
of rolled steel shall be 2.75 mm (except for contact and edge protection which shall
comply with 6.6).
Where applicable, the requirement for hot-dip galvanising requirement shall comply
with ISO 1460 and ISO 1461.
Where appropriate, the requirement for tolerance for cast shall comply with ISO 8062.
Cover fillings may consist of concrete or other filling material appropriate to the place
of installation.
In the case of covers placed on the market in filled condition the filling shall consist of
either:
In case of covers placed on the market in unfilled condition and the filling is applied
subsequently, the filling materials shall have a minimum performance comparable to
concrete or the surrounding pavement materials and shall fulfil the requirements of the
appropriate standards.
5.4.1 General
The concrete quality of any element shall be dense, homogenous and conform to the
requirements given in 5.4.1.1 to 5.4.1.6. For general aspects, constituent materials of
concrete and reinforcing steel, EN 13369:2013, 4.1, shall apply.
Manhole tops according to this technical specification shall be at least suitable for use
in “wet and dry” conditions and a slightly aggressive chemical environment, i.e. normal
conditions for domestic sewage and treated industrial effluent, and for most natural
soils and ground-waters. If more severe conditions are expected, additional
requirements for corrosion protection can be necessary.
The exposure class determined in accordance with EN 206 shall be a minimum of XC2.
If more severe conditions are expected higher exposure classes can be necessary. In
such cases the higher class shall be declared.
The compressive strength class of the concrete shall conform to the specific
environmental conditions in accordance with 5.4.1.1 but not be less than C35/45
according to EN 13369.
The ratio of water to cement plus any pozzolanic or latent hydraulic addition in the fully
compacted state shall not be greater than 0.5 and shall conform to the specific
environmental conditions in accordance with 5.4.1.1.
Concrete shall have such a composition that the minimum content of cement plus any
pozzolanic latent addition in the fully compacted state is consistent with the
serviceability conditions of 5.4.1.1 and 5.4.1.5 for the exposure classes.
The maximum amount of chloride ion in the concrete shall be evaluated by calculation
in accordance with EN 206:2013, 5.2.8.
Manhole tops made of cast iron can be supplied uncoated or coated. Coating materials
shall comply with the environmental and/or toxicological regulations at the place of
intended use.
NOTE. In general, coatings are for aesthetic purposes only and are not regarded as a corrosion protection
system.
Where the frame is made of a combination of any material according to this technical
specification and concrete, the concrete shall have a compressive strength of at least
C35/45 in accordance with EN 206:2013.
6.1 General
Manhole tops shall be free of defects which might impair their fitness for use.
When metal is used in combination with concrete or any other material, there shall be
adequate bond between the two materials.
The opening of manhole tops designed for man entry shall have minimum diameter of
600 mm.
Manhole tops of classes D 400, E 600 and F 900 shall have a depth of insertion A of
at least 50 mm.
6.4 Clearance
The clearance between the different elements of manhole tops is defined in 3.19. This
clearance can lead to horizontal displacement of the cover or grating in its frame. In
order to limit this displacement, the total clearance Σa, shall conform to the following
requirements:
b) for covers with three or more parts secured in the frame each individual:
c) for covers with three or more parts not secured in the frame, the total clearance Σa
resulting from the displacement of all parts shall not exceed 15 mm.
Where hinge is required, it shall be permanently welded to the frame and cover. The
hinge pin should be made of stainless steel minimum grade 304. The minimum hinge
pin diameter shall be 10 mm.
The opening angle of hinged covers shall be at least 100° to the horizontal.
© SPAN 2020 - All rights reserved 13
Where hinged covers have a radially profiled edge on the hinged side, it shall be
profiled so that the gauge of 170 mm x 170 mm x 20 mm, detailed in Figure 7, is
prevented from entering the gap between the adjacent frame and the curved edge of
the cover by more than 13 mm of its 170 mm depth, the gauge being vertical with its
length parallel to the profiled edge.
Dimensions in millimetres
20
Gauge
Frame
170
Cover
13
Figure 7. Gauge
The manhole tops shall be compatible with their seating. This shall be assessed by
assembling the cover and the frame.
These seating shall be manufactured in such a way as to ensure stability and quietness
in use. This may be achieved by machining of the contact surfaces, use of cushioning
inserts, three-point suspension design or any other appropriate method. When tested,
the cover/grating shall not have an increased change in height above the upper edge
of the frame by more than 0.5 × depth of insertion with a maximum value of 25 mm at
any point on the perimeter. (testing on compatibility of seating)
6.6 Edge and contact surfaces protection for manhole tops of steel reinforced
concrete
For manhole tops of classes C 250 and D 400 of steel reinforced concrete, edges and
contact surfaces between frame and cover shall be protected with cast iron or hot-dip
galvanised steel. The minimum thickness of spheroidal graphite iron or steel is as
stated in Table 4. The thickness of edge and contact surface protection shall be
measured in accordance with 8.3.6.
6.7 Securing of the cover within the frame (including child safety)
The cover shall be secured within its frame to meet the required traffic conditions
relevant to the place of installation defined in Clause 4.
Where required by specific provisions in the place of intended use, child safety features
and/or devices shall also be incorporated in the design of manhole tops.
a) securing feature; or
c) other methods.
The securing of covers/gratings within the frames shall be tested in accordance with
8.3.7. The securing method and design details shall be declared.
Where required by specific provisions in the place of intended use, the above
mentioned methods for securing of cover shall comply with these provisions.
NOTE. For purposes such as prevention of unauthorized removal, lifting of cover or vandalism additional
locking accessories can be required by the specifier. The selection of the appropriate locking accessory
is in the responsibility of the specifier. The provision of the appropriate locking accessory is, in this case,
not within the responsibility of the manufacturer.
NOTE. The design and performance of these additional features or devices are not covered by this
technical specification.
Where the cover has to be in a predetermined position relative to the frame, this is to
be ensured by an appropriate design.
The upper surface, of covers of classes D 400 to F 900, which is the surface in contact
with traffic, shall be flat within a tolerance of 1 % of the clear opening with a maximum
of 6 mm.
When tested in accordance with 8.4.13, the surface conditions shall be in accordance
with 7.4.
NOTE. In certain environments such as, but not limited to, legally required studded tyres or legal toxic
emissions limitations, the specifier can request further appropriate tests to be carried out to check if these
are fit for purpose at the place of installation.
Manhole tops in accordance with this technical specification can be designed with
sealing features to resist against accidental upward water pressure. In such a case the
frame shall be designed to be securely anchored.
Manhole tops according to this technical specification can also incorporate sealing
features to prevent or limit:
The sealing design depends upon the pressure underneath the cover and the
requirements in that specific situation. These requirements shall include gas tightness
or water pressure tightness or both.
The frame bearing area shall be designed in such a way that the bearing pressure, Pb
on the basis of the test load, FT shall not exceed 7.5 N/mm2 to provide a contribution
to stability under working conditions. The bearing pressure, Pb shall be calculated in
accordance with Formula (F.1) below:
16 © SPAN 2020 - All rights reserved
𝑃𝑏 = 𝐹𝑇/𝐴 F.1
where
2
Ab is the frame bearing area in mm .
2
NOTE. Pb is expressed in N/mm .
a) the bearing pressure in relation to the test load shall not exceed 7.5 N/mm2; and
The depth of the frame of manhole tops of class D 400, E 600 and F 900 shall be at
least 100 mm.
For class D 400 the frame depth may be reduced to 75 mm provided that the frame is
made either of cast iron or steel and provides anchoring facilities.
In the case of recessed covers, the manufacturer shall provide all necessary
specifications for filling, unless the filling is carried out at the manufacturer's plant.
The surface texture of such filled covers shall be appropriate to the place of installation.
The opening angle of hinged covers shall be at least 100° to the horizontal unless
additional stays are provided.
NOTE. Additional provisions can be required to prevent the cover or grating from accidental closing, e.g.
site or service conditions.
7. Performance requirements
7.1 Appearance
Manhole tops shall be free from visible defects which might impair their fitness for use.
When tested according to 8.2.3, manhole tops with a clear opening (CO) equal to or
greater than 250 mm shall withstand the test load according to Table 5 for each class
independent of the material. Where the clear opening (CO) is less than 250 mm, the
test load shall be as shown in Table 5, multiplied by CO/250 but not less than 0.6 times
of the test load according to Table 5.
Covers and frames made of materials as listed in Clause 5 shall not show cracks or
delamination in the course of the test when viewed without magnification. For steel
reinforced concrete, no cracks wider than 0.2 mm shall appear in the concrete. Crack
widths shall be measured on the surface optically by magnifier or equivalent. No loss
of adhesion between concrete and reinforcement shall occur after the total load
bearing.
The load bearing capacity shall be declared as corresponding class according to Table
5.
When tested according to 8.2.5, the permanent set of the cover after the application of
FP (2/3 of the test load FT) shall not exceed the values given in Table 6.
Covers and frames, made of materials according Clause 5, shall not show cracks or
delaminations in the course of the test when viewed without magnification. For steel
reinforced concrete, no cracks wider than 0.2 mm shall appear in the concrete. Crack
widths shall be measured on the surface optically by magnifier or equivalent. No loss
of adhesion between concrete and reinforcement shall occur after the total load
bearing.
CO CO
C 250 up to F 900
300a 500b
When secured according to 6.7 a) When secured according to 6.7 b)
or 6.6 c)
a
1.0 mm max when CO < 300 mm.
b
1.0 mm max when CO < 500 mm.
The upper surface of covers shall be in accordance with at least one of the following
requirements:
a) made of concrete, provided that the upper surface of the cover has been neither
ground nor polished;
NOTE. Additional provisions can be required to prevent the concrete cover or concrete filled cover from
potential skid, e.g. where concrete mix contains fine limestone aggregates.
b) the upper surface of covers shall have a structured upper surface with a defined
raised pattern or a coarse textured upper surface which permits free
drainage/dispersion of water to the surrounding area and complies with the
following dimensional requirements:
When measured from the total plan surface, the raised pattern shall have a height of
2 mm to 6 mm for classes C 250 and a height of 3 mm to 8 mm for classes D 400,
E 600, and F 900.
The raised pattern shall be distributed as far as possible evenly over the total plan
surface area of the manhole top.
The total surface area of raised pattern (∑An ) shall be not less than 10 % and not
more than 70 % of the total projected surface area (AT2).
The surface area of any single raised pattern defined as An shall be determined as
shown in Figure 8.
Parts of logo that are within the height requirements are considered as part of the
raised pattern and shall provide free drainage/dispersion of water.
c) shall have a USRV of not less than 35 when tested according to Annex C, where
the surface of the cover does not fulfil the requirements of a) and/or b).
If frames or parts thereof have a horizontal visible width exceeding 40 mm, the
requirements for covers according to 7.4.2 shall also apply for these frames.
8.1.1 All tests and measurement control as detailed in 8.2 and 8.3 shall be
undertaken where there is a change in design, type of material and method of
manufacturing.
8.1.2 The re-evaluation test shall be carried out at least once every 5 years provided
there are no changes in the raw materials and formulations used, fitting designs and
methods of processing.
8.1.3 Additional tests may be required for manhole tops made of other materials not
listed in Clause 5.
8.1.4 Where there is no detailed test method for the verification of any requirement
in this technical specification, the manufacturer shall state in his documents how such
verification is achieved (see 5.1, second paragraph).
8.1.6 Manhole tops shall be tested as complete units in their intended position of use
where cover is suitably positioned within the frame and the frame is supported in a
manner to replicate intended installation support structure.
8.2.1 General
The manufacturer shall verify the load capacity of each prototype unit by testing it in
accordance with Annex A.
The materials, manufacture and method of fabrication of the prototype specimen unit
shall comply with Clause 5 and represent those used in production. A minimum of three
test specimens shall be prepared for testing.
The test load of each class shall be equal to the relevant test load as specified in Annex
A.
The prototype specimen shall be tested as complete units in their condition of service
except for recessed covers delivered unfilled, which shall be load tested without filling.
Manhole tops shall be submitted to the load bearing capacity test according to Annex
A under the test loads FT according to 7.2.
A standard test piece of known length is stretched by a stated percentage for a period
of time and is then released. After recovery the length is measured and change in
length (i.e. unrecovered length) is expressed as a percentage of the original length.
The permanent set shall be tested in accordance with the requirements as stated in
Annex A and shall be measured to an accuracy of 0.1 mm.
a) the prototype specimen shall show no cracks in the course of the test; and
b) in the case of steel reinforced concrete covers, there shall be no loss of adhesion
between the concrete and the reinforcing steel.
When required by the purchaser or by the relevant authority, the test shall be
conducted in accordance with Annex B, there shall be no visible leakage under a
150 mm head of water for 10 min.
When required by the purchaser or by the relevant authority, the test shall be
conducted in accordance with Annex C, there shall be no drop in pressure for 3 min
when the unit is subjected to one of the following pressure:
For classes D 400 to F 900, the depth of insertion, A, shall be measured in millimetres.
8.3.5 Seating
The compatibility of the seating to ensure stability of the cover within its frame shall be
inspected against the manufacturer’s specification.
In addition, manhole tops of classes D 400 to F 900 shall be tested in accordance with
Annex E.
The thickness of the uncoated iron or steel edge protection to steel reinforced concrete
manhole tops shall be measured to an accuracy of 0.1 mm.
The thickness of the hot dip galvanising shall be measured to an accuracy of 5 m.
8.3.7 Securing of the cover within its frame (including child safety)
The securing of covers/gratings of classes C 250 to F 900 within the frames shall be
tested in accordance with Annex F.
The declared securing method shall be visually inspected with respect to the function,
the use of materials and the declared values corresponding to the design details.
If securing is achieved by 6.7b) weighing of the mass is sufficient. In this case, the
cover shall be weighed to an accuracy of 1 % and the clear area calculated to an
accuracy of 100 mm2.
The handling of covers shall be tested physically for loosening and opening according
to manufacturer's instructions.
The appropriate design feature that ensures a particular orientation of the cover or
grating in the frame shall be examined for fitness of purpose.
The skid resistance of the upper surface of the cover and the frame shall be determined
as follows:
NOTE. Where aggregates contain fine limestone, additional provisions to prevent the concrete cover or
concrete filled cover from potential skid can be necessary.
c) In case of products not conforming to 7.4.2 a) and 7.4.2 b), the surface condition
shall be measured according to Annex D.
All covers and frames shall have the following markings. These markings shall be clear and
durable, and where possible, be visible after the unit is installed, with the following:
b) the appropriate class (e.g. D 400) or classes for frames which can be used for several
classes (e.g. D 400 to E 600);
g) additional markings if manholes tops conducted and passed the water and gas tightness
test.
A.1 Scope
This annex sets out method of load test for manhole tops.
A.2 Principle
Manhole tops are subjected to a loading test according to loading requirement for the
appropriate class (see Clause 4).
Manhole tops shall be tested as complete units in their condition of service except for recessed
covers delivered unfilled, which shall be load tested without filling.
C 250 250
D 400 400
E 600 600
F 900 900
A.4 Apparatus
Preferably a hydraulic test press shall be capable of applying a load at least 25 % greater than
the respective test load for class C 250 and D 400, and at least 10 % greater than the
respective test load for classes E 600 and F 900.
The dimensions and shapes of test blocks are shown in Table A.2.
Shape and clear opening of the manhole tops Dimension of the test blocks
(mm) (mm)
600 CO 1 000
CO
CO
≥ 600
a) measurement of the permanent set of the cover after the application of two-third of the
test load (see A5.2); and
The test block shall be placed on the unit with its vertical axis perpendicular to the surface and
coincidental with the geometric centre of the cover or the grating (examples, see Figure A.1).
In the case of double triangular covers, the test block shall be positioned in the geometric
centre, as shown in Figure A.1. The cover shall rest normally in the frame.
The test load shall be uniformly distributed over the whole surface of the test block and any
irregularities compensated for by means of an appropriate intermediate layer, e.g. softwood,
fibreboard, felt or similar material positioned between the cover and the test block. The
dimensions of this intermediate layer shall be not larger than those of the test block. A similar
28 © SPAN 2020 - All rights reserved
intermediate layer, at the manufacturer's option, may also be positioned between the bed of
the testing machine and the bearing area.
When testing manhole tops with a non-flat surface, the contact face of the test block shall be
shaped to match the cover. Raised patterns and small deviations from a flat surface do not
require a shaped contact face of the test block.
A.5.2 Measurement of permanent set of the cover after the application of two-third of
the test load
Before the load is applied, take an initial reading at the geometric centre of the cover. The load
shall be applied at a rate of 1 kN/s to 5 kN/s up to two-third of the test load; the load on the
test specimen is then released. This procedure shall be carried out five times. Then take a
final reading at the geometric centre.
The permanent set shall then be determined as the difference of the measured readings
before the first and after the fifth loading. The permanent set shall not exceed the values given
in Table A3.
In the case of double triangular covers or gratings, the permanent set shall be measured on
both parts, as close as possible to the geometric centre (see A5.1, Figure A.1).
For test specimens of steel reinforced concrete, no cracks wider than 0.2 mm shall appear in
the concrete after this test. Crack widths shall be measured on the surface optically by
magnifier or equivalent. No loss of adhesion between concrete and reinforcement shall occur
after the total load bearing.
CO CO
C 250 up to F 900 300 a 500 b
When secured according to When secured according to
6.7 a) or 6.6 c) 6.7 b)
Immediately after the test according to A5.2, the test load shall be applied at the same rate
given in A5.2, until the test load is achieved. The test load to be maintained for 30 + 2 s . Units
0
made of materials 1) to 4) of Clause 5 shall not show cracks in the course of the test. In the
case of steel reinforced concrete covers, there shall be no loss of adhesion between the
concrete and the reinforcing steel.
a) class of unit;
b) date of testing;
d) frame depth;
f) bearing pressure;
h) opening angle;
i) deflection in millimetres;
l) any cracking or other (permanent) damage resulting from the test; and
B.1 Scope
This annex sets out the method of testing water tightness for covers, when installed in
accordance with the manufacturer's written instructions.
B.2 Principle
Manhole top in their frames are subjected to a ponding of water for a period of time to verify
that these covers are resistant to surface water infiltration.
B.3 Apparatus
The unit frame shall be used as a supporting frame for the test covers.
An assembly of rigid construction which ensures sealing against leakage at the top and bottom
surfaces of the supporting frame of the test cover during the application of a 150 + 10 mm head
-0
of ponding water to the top surface of the cover and full cover and frame interface (see Figure
B.1).
B.4 Procedure
b) Set up the unit in the same manner as it is intended to be installed in the field in accordance
with the manufacturer's instructions.
c) Apply water to the water ponding assembly and bring it up to a level of 150 mm above the
top face of the cover.
a) date of testing;
C.1 Scope
This annex sets out the method of testing gas tightness for covers when installed in
accordance with the manufacturer's written instructions.
C.2 Principle
Covers in their frames are subjected to pressurised air for a period of time to verify that these
covers are resistant to internal gas leakage.
C.3 Apparatus
Consisting of two rigid plates suitable for placing horizontally in contact with the top and bottom
surfaces of the test manhole top. The test unit shall be secured tightly between the plates by
clamping studs (see Figure C.1). The top of the frame shall be lined with a rubber gasket clear
of the cover/frame interface and the bottom plate shall be lined with a rubber gasket.
Capable of supplying air at 1.5 kPa or other specified pressure, to be used to introduce air into
the testing assembly through an air inlet hole at the bottom plate (see Figure C.1).
Capable of measuring air pressure in kilopascals shall be attached to the air inlet connector
tube.
An appropriate sensitive pressure gauge shall be connected to the air inlet hole at the bottom
plate (see Figure C.1). Alternatively, air leakage may be detected by connecting the air outlet
hole to a tube dipped in water in a container. The container shall be placed at the same level
as the bottom plate.
The cover and frame shall be tested for gas tightness as follows.
b) Set up the unit in the same manner as it is intended to be installed in the field in accordance
with the manufacturer's instructions.
c) If the design of the cover is such that the manufacturer recommends a holding-down
device, then that device shall be in place during the test.
d) Introduce compressed air at a pressure of 1.5 kPa or as specified into the test assembly
using the air compressor.
e) Maintain the unit under the test air pressure of 1.5 kPa or as specified for 3 min.
f) Record drop in pressure or visible escape of air, if any, which occurs during the test.
C.5 Report
a) date of testing;
c) description of number and type of coating applied to the unit prior to the test;
g) any drop in pressure or visible escape of air which occurs during the test; and
D.1 General
The measurement of USRV on a specimen shall be made using proprietary pendulum friction
test equipment to evaluate the frictional properties of the specimen. The pendulum friction
test equipment incorporates a spring loaded slider made of a standard rubber attached
to the end of the pendulum. On swinging the pendulum, the frictional force between the
slider and test surface is measured by the reduction in length of the swing using a calibrated
scale.
D.2 Apparatus
b) potable water.
The pendulum friction test equipment shall be recalibrated at least once a year. This shall be
carried out in accordance with EN 13036-4 by an approved calibration body.
Test samples shall be manhole covers or frames selected at random from the stock of manhole
tops held by the manufacturer. Representative samples free from any temporary coatings, not
yet used and free from any corrosion shall be selected and tested for each surface pattern
design and for each material of manufacture.
After this conditioning, if the validation results are still outside the range of the standard surface,
the apparatus shall be investigated and recalibrated if necessary.
The pendulum test equipment shall be conditioned for a period of at least 30 min prior to the
commencement of the test. The test equipment, test specimen and slider as well as water,
shall be kept at a temperature of (20 ± 5) °C, during this time.
Surface irregularities (e.g. casting imperfections, etc.), dust or other contaminants shall be
removed from the sample under test prior to testing.
Where possible the test shall take place within a 0.5 m x 0.5 m grid as shown in Figure C.1. If
it is clear that surface pattern varies across the test area, additional tests can be necessary to
take this into account.
Key
1. Test location 1
2. Test location 2
3. Test location 3
Testing shall be carried out at the three test locations as shown in Figure D.1, i.e. two shall
be parallel to the major axes of the cover and one at an angle of 45° to the major axes.
© SPAN 2020 - All rights reserved 37
Where the test sample is smaller than 500 mm × 500 mm, a similar test pattern shall be
adopted.
D.5.2.3 Setting up
The setting up of the pendulum, its zeroing and method of measurement shall be undertaken
as described in EN 13036-4. In addition, the base of the pendulum tester shall be weighted
with a suitable material of mass > 6 kg and < 10 kg to arrest any possible movement during
testing.
Where the surface patterning of the cover does not enable a pendulum strike distance of
126 mm to be achieved (i.e. slider in contact with cover material at start and end of strike
distance), a length of less than 126 mm may be chosen. In this case, the actual strike
distance shall be recorded, and the values obtained after testing shall be modified by a
correction factor. The correction factor shall be determined by reference to standard test
materials. Such reference materials shall be tested using the same strike distance as on
the sample and also using the standard distance of 126 mm. The correction factor shall be
the ratio of the two results.
The height of the pendulum arm shall be checked and adjusted so that in traversing the
specimen, the rubber slider is in contact with it over the whole width of the slider and over
the specified sweep length. The upper surfaces of the specimen and the rubber slider shall
then be wetted with a copious supply of water just in front of the centre of the test location
applied immediately before each swing of the pendulum, being careful not to disturb the slider
from its set position.
The pendulum and pointer shall then be released from the horizontal position and the
pendulum arm caught on its return swing, before it touches the test specimen a second time.
The position of the pointer on the scale shall be recorded. This is the pendulum test value.
This operation shall be repeated five times at each of the three locations shown in Figure
D.1, rewetting the specimen each time. The last three of the five readings shall be recorded
for each test location.
The mean value of the last three of the five readings shall be determined for each test location
according to Figure D.1. This shall be the skid value for each location. The mean of the
two lowest skid values shall be calculated.
Annex E
(normative)
Tilt test
E.1 General
The stable behaviour of covers according to 6.5 is to be tested by the tilt test.
At the edges of the cover and the frame a test block of 75 mm diameter (smallest test block
according to test samples, equipped with a rubber sheet of 75 mm diameter with a thickness
of 10 mm, hardness (60 ± 5)°, shore A according to EN ISO 868 at the bottom, shall be applied
at the test points according to Figure E.2 to Figure E.6 (if applicable). The axis centre of the
test block is positioned at the gap between cover and frame.
Key
Table E.1. Application of test load for different designs of manhole tops
Key
1. test point
Figure E.2. Circular covers/gratings
Cover(s)/grating(s) with In four places evenly distributed over the circumference, where one point of load
hinges shall be applied immediately adjacent to the hinge according to Figure E.3.
Key
1. test point
2. hinge
Figure E.3. Hinges
Cover(s)/grating(s) with In four places evenly distributed over the circumference, where one point of load
securing feature shall be applied immediately adjacent to one securing feature according to Figure
E.4.
Key
1. test point
2. road worthy anchorage
Table E.1. Application of test load for different designs of manhole tops (continued)
Key
1. test point
Annex F
(normative)
F.1. General
The aim of the test is to assess the securing of the covers(s) within the frame of a manhole
top by applying one or more pull-out forces to these covers/gratings and to measure their
vertical movement.
The pull-out force Fv and Fv,c, as applicable, and the vertical displacement, h of the cover(s),
measured in the test, shall be declared.
The securing methods, defined in 6.7 and shown in Table F.1 shall be tested with the vertical
pull-out test. The test shall be carried out after the tilt test described in Annex E.
1 hinged covers
5 other designs
The applied vertical pull-out forces shall be measured in newtons with a calibrated
dynamometer or similar apparatus with a resolution of at least 10 N, capable of applying a
force of at least 25 % greater than the maximum force.
The vertical direction of the pull-out force, Fv, shall be measured with an appropriate device
with an accuracy of ± 5°.
For safety reasons, it is recommended to fix the frame of the test samples.
The measurement device(s) shall have a range of at least 30 mm with a resolution of at least
0.1 mm and have a maximum overall accuracy of ± 5 % to measure the vertical movement.
The vertical pull-out force Fv shall be applied vertically on each single cover/grating by means
of a cable fixed at the geometric centre of the cover/grating. Examples are given in Figure F.1.
This anchoring device, as shown in Figure F.2 shall be installed in such a way that:
a) the distance between the top of the cover and the cable/chain/strap shall be 100+5
0 mm;
and
Key
h vertical displacement
Fv vertical pull out force
If, in the case of, as example gratings or specific covers, the geometric centre is not fit for the
securing of the anchoring device, washers/plates installed on top surface and underneath or
other accessories can be used to rebuild the centre, and allow the installation of the anchoring
device.
If the cover does not remain in a horizontal position while it is moving in a vertical direction, it
is necessary to determine the point of the largest change in position at which the measurement
shall be made.
The vertical displacement shall not exceed 50 % of the depth of insertion A in accordance with
6.3, but with a maximum of 25 mm. The appropriate value of A (with a minimum value, where
applicable) is to be determined.
The maximum vertical pull-out force shall be determined according to Formula (F.2). The clear
area shall be determined as shown in Figure F.3.
Where
NOTE. The Clear Area, CA, is used instead of Clear Opening, CO, to achieve a consistent evaluation of the
various dimensions and types of covers.
The clear area of each individual cover shall be determined either on a drawing or at the
sample in accordance with Figure F.4. The maximum vertical pull-out force shall be calculated
in accordance with Formula (F.2) and applied at each individual cover.
Where
𝐹𝑣𝑐 is the maximum vertical pull-out force of each individual cover in N; and
CAc is the clear area of each individual cover in mm2.
NOTE. The Clear Area, CA, is used instead of the Clear Opening, CO, to achieve a consistent evaluation of the
various dimensions and types of covers.
The load shall be applied on each single cover at a rate of 0.01 kN/s up to 0.05 kN/s up to the
lifting of the cover with a maximum of 25 mm or up to the maximum pull out force Fv,c as
calculated in F.2.4.2.
The test shall be carried out 3 times consecutively and only the smallest vertical pull-out force,
Fv, and its corresponding vertical displacement h shall be considered and declared.
In case of triangular covers with loose couplings, the loose couplings shall not be removed
before the test.
The vertical displacement h shall be measured between the top of the frame and the highest
point of the cover at the moment of lifting as shown in Figure F.2.
When the maximum permissible vertical displacement h is reached, the Fv or Fv,c shall be
measured and recorded.
The smallest pull-out force Fv and its corresponding vertical displacement h measured for a
single cover/grating in accordance with F.2.6 shall be declared.
In case of multiple covers the smallest pull out force Fv,c of each individual cover and its
corresponding vertical displacement h shall be declared.
Bibliography
[1] BS EN 124 series, Gully tops and manhole tops for vehicular and pedestrian areas
[3] Technical Standard for Sewage Collection and Conveyance - Part 1: Sewer Pipe,
Manhole, Pumping Station and Force Main, SPAN
[4] Uniform Technical Guidelines for water reticulation and plumbing, SPAN
SPAN and SIRIM STS would like to thank the organisations who have contributed their ideas,
time and expertise in the development of this technical specification.
All rights reserved. Unless otherwise specified, no part of this module may be reproduced or utilised in any form or
by any means, electronic or mechanical, including photocopying, recording or otherwise, without prior written
permission from SPAN.