Professional Documents
Culture Documents
Pumps (ESP)
Mohammad Khalifa
Sub Surface Manager – FC14
Agenda
21st May
2010
RESERVOIR
INFLOW PERFORMANCE
SIBHP
Vogel ?
BHP (psi)
Productivity
PI (bpd/psi)
Q (bpd)
RESERVOIR
INFLOW PERFORMANCE
SIBHP
BHP (psi)
Productivity
PI (bpd/psi)
Q (bpd)
RESERVOIR
INFLOW PERFORMANCE
SIBHP
BHP (psi)
Productivity
PI (bpd/psi)
Q
Q (bpd)
RESERVOIR
INFLOW PERFORMANCE
SIBHP
BHP (psi)
Productivity
PI (bpd/psi)
Q
Q (bpd)
WELL SYSTEM
OUTFLOW PERFORMANCE
BHP (psi)
etc.,etc….
Q (bpd)
WELL SYSTEM
OUTFLOW PERFORMANCE
BHP (psi)
f ( fluid, T, conduit, process)
Q (bpd)
WELL SYSTEM
OUTFLOW PERFORMANCE
BHP (psi)
f ( fluid, T, conduit, process)
Q
Q (bpd)
WELL SYSTEM
OUTFLOW PERFORMANCE
BHP (psi)
f ( fluid, T, conduit, process)
Q
Q (bpd)
BHP (psi)
BHP (psi)
Productivity
PI (bpd/psi)
f ( fluid, T, conduit, process)
Q (bpd) Q (bpd)
SIBHP
BHP (psi)
SYSTEM PERFORMANCE
BHP (psi)
PI (bpd/psi)
Q (bpd) Q (bpd)
BHP (psi)
Q
Q (bpd)
Q
Q (bpd)
Q BHP (psi)
Q (bpd) Q (bpd)
Q (bpd)
DEAD WELL
BHP (psi)
BHP DEFICIT
Q (bpd)
Q (bpd) Q (bpd)
Natural Flow
Fluid Gradient
Depth
SBHP
Natural Flow
Fluid Gradient
Depth
SBHP
Dead Well / No
Flow At Surface
Fluid Gradient
Depth
SBHP
ESP Assisted
Depth
PIP PDP
SBHP
ESP Assisted
Fluid Gradient
Depth
PIP PDP
SBHP
Worldwide, there are approximately 800,000 oil wells in production, 94% of them have
associated an artificial lift system.
The most popular artificial lift system is reciprocating pump (40%) of total population, then gas
lift (34%), electro submersible pumps (5%), progressive cavity pump at 6%.
MLE Cable
Submergible
Pump
Intake
Protector
Motor
Impeller Diffuser
Mohammad Khalifa 32
Pump Curve
Mohammad Khalifa 33
Pump Intake
► Integral.
► Bolt-on.
► Intake
► Gas Separator+Intake.
Provides the thrust bearing to carry the thrust load of the pump
Well Fluid is
totally isolated The seal is the
from the lower elastomer ..
part
Is there a limit ??
Coupling
Shaft
Coupling
Coupling
Typical measurements:
Intake pressure
Intake / Motor Temperature.
Vibration.
Discharge Pressure.
Current leakages in the system.
Choke
Typical measurements: Transformer
Intake pressure
Intake / Motor Temperature. Cable
Vibration.
Discharge Pressure.
Current leakages in the system. Motor
DMT
Tape-In Design
45 Electric Submersible Pumps /
Mohammad Khalifa
Cable Configuration
ETBO
ROUND
- Electrical Properties
- Mechanical Properties
FLAT
- Clearance ELB
CONDUCTOR
INSULATION
BARRIER
JACKET
ARMOR
INJECTION TUBE (optional)
1) The Net Vertical Lift or net distance which the fluid must be
lifted.
Wellhead
Wellhead Pressure
3
Ground Level Flow
1
2 Net Vertical Lift
Total Friction Loss
Flow Flow
60 Electric Submersible Pumps /
Mohammad Khalifa
Total Dynamic Head (TDH)
Total Dynamic Head (psi) =
PFL
Regardless of
where the pump is
set, or the angle,
the vertical lift will
not change.
Ground Level
Flow Flow
63 Electric Submersible Pumps /
Mohammad Khalifa
Total Dynamic Head (TDH)
Total Dynamic Head (psi) =
No
Worrie
s
Excuse me
Sorry
Certainly
This is the equation to convert from psi to feet but we still need to
know the specific gravity.
Wellhead Pressure*2.31
Wellhead "Feet" = ----------------------------------
sp.gr.
Since we are in 7" casing, we know that the largest protector we can
use is a 540 series. Let's look at the thrust ratings for both a standard
and hi-load bearing protector.
15,000
12,500 Hi Ex Bearing
Load (LBf)
10,000 Bronze
Bearing
7,500
5,000
From these curves, we can see the maximum load for the bronze
bearing is 9,500 lbs while the Hi Ex bearing will take up to 12,000 lbs.
Head Pump
Feet Motor Only
Load EFF
60
50
40
30 75
20 2.00 50
10 1.00 25
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500
81 Electric Submersible Pumps /
Mohammad Khalifa
Capacity - Barrels per Day
Physical Limitations
Since this is a floater pump, all we have to worry about is shaft thrust.
We can calculate the maximum number of stages as follows:
psi 2
# of Stages × × Area(in ) = Thrust(lbs)
stage
The maximum horsepower (60 Hz) allowable with the pump shaft is
410 on a high strength shaft.
50
40
30 75
20 2.00 50
1.4
10 21.00 25
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500
84 Electric Submersible Pumps /
Mohammad Khalifa Capacity - Barrels per Day
Physical Limitations
410 HP
----------------- = 268 stages.
1.53 Hp/stage
750 HP
----------------- = 490 stages.
1.53 Hp/stage
6000 psi
------------------ = 225 stages.
26.65 psi/stage
How about making sure the unit we size will actually fit in the well?
For example, consider that we are using a 456 motor and 400 series
pump and protector which are 4.562" O.D. and 4.000" O.D.
respectively.
In principle this unit is designed for 5.5" casing but not all casing is the
same.
Note that even though the nominal I.D. of 17 ppf casing is 4.892", we
are using, instead, the drift diameter of 4.767" for our calculations.
Even though this is a "worst case" diameter, more often than not the
casing will really be this diameter at some place in the tube. This is
especially common at both ends where the casing tends to neck down
just a little.
Because of this, the drift diameter is a much better number to use for
calculations of clearance.
Since the motor is only 4.562" O.D. and the pump and protector are
smaller, we can see that the unit will fit in anything up to 20 ppf
casing, right?
Actually not.
For one thing the motor will usually have lock plates
welded to the housing and head which will increase the
effective diameter. We also need to consider that we have Lockplate
to get electricity to the motor somehow (i.e. we have a
power cable to worry about).
In addition to the cable, we may or may not use cable guards which
would, if used, increase the effective diameter and we also have to
"attach" the cable to the unit with or without guards so cable band
thickness must be considered as well.
An easy way to look at the problem is by looking at the unit from the
end.
103
End View
Electric Submersible Pumps /
** May beMohammad
omitted by Special Order
Khalifa 4.000" dia. Protector housing & Pump
Physical Limitations
With a drawing like this, all possibilities are considered for the
downhole equipment. Almost every possible configuration of
equipment has been laid out in an end-view drawing already and
these are readily available in InTouch.
This is typically much larger than the motor lead extension and it must
fit in the annular space between the tubing coupling and the casing.
Since the ESP is smaller than the casing, it can pass some deviation
without any deflection at all.
Greater deviations will cause deflection (bending) of the Reda ESP unit.
Since it is not a rigid piece, it can handle some amount of deflection
without permanent damage and will straighten back out after it passes
the dogleg.
Clearance
Normally doglegs less than 3° per 100 feet present no problems for
the Reda ESP unit. Deviations greater than this need to be reviewed
on a case-by-case basis with Reda engineering.
10
40
know that the downhole unit is 30
20
operating correctly and pulling
11
10
nameplate amps (we checked it
NOON
1
with our amprobe at the junction
MIDNIGHT
box).
2 1
11
3
10
4
9 5
8
7 6 PM
10
40
30
random "spikes". 20
11
10
NOON
1
MIDNIGHT
2 1
11
3
10
4
9 5
8
7 6 PM
3
compensate. The most common cause for
10
40
30
these spikes is periodic heavy loading on 20
11
10
the power system as could be caused by Primary
NOON
1
startup of high horsepower equipment Power
MIDNIGHT
elsewhere on the system. Fluctuation
1
Could also be caused by lightning strikes "Spikes"
2
somewhere on the power system.
11
3
10
4
9
5
8
7 6 PM
10
40
11
10
NOON
1
MIDNIGHT
2 1
11
3
10
4
9 5
8
7 6 PM
3
cause the erratic amperage. Eventually enough
10
40
30
gas forms so that the pump "gas locks". When 20
11
10
NOON
1
fluid. Note that, even though the pump is not Gas
MIDNIGHT
producing fluid, the motor is continuing to run Locking
1
(amperage is not zero). This will cause the motor
2
11
to eventually burn since there is no fluid
3
movement to cool it.
10
4
9 5
8
7 6 PM
10
40
clearing. If possible, choke back the 30
20
11
10
production to raise the annular fluid
NOON
1
level. It may be necessary to lower the Gas
MIDNIGHT
pump if there is room in the well to gain Locking
1
additional submergence. It might also be
2
wise to resize to a smaller unit.
11
3
If a VSD is being used, reduce the
10
4
frequency. 9 5
8
7 6 PM
10
40
30
unit could not continue to run. The 20
11
10
overload must be set higher than 60
NOON
1
amps (or it is not working).
MIDNIGHT
2 1
11
3
10
4
9 5
8
7 6 PM
10
40
30
gravity fluid causes an increase in current until 20
11
it is all pumped out of the well -- then the 10
NOON
current drops to a normal value. If this Unloading
1
condition is to be expected, it may be Heavy
MIDNIGHT
1
necessary to temporarily raise the overload Kill Fluid
setting until the kill fluid is gone and then set it
2
11
to the normal 115% value. If this condition is
3
expected to last for more than a few minutes, it
10
may be necessary to use a larger motor than
4
9
normal so that the overload does not cause
5
8
high internal temperatures which may reduce 7 6 PM
10
40
30
very erratic. The unit stops for 3 20
11
hours and repeats the cycle. It 10
NOON
restarts just after noon and runs
1
longer but eventually stops.
MIDNIGHT
21
11
3
10
4
9 5
8
7 6 PM
10
40
30
intake. The low gravity gas mixed with the 20
11
10
high gravity fluid causes wide swings in
NOON
1
current. The unit eventually shuts off on U/L
and automatically restarts after three hours. Pump Off
MIDNIGHT
1
Possible solutions are to choke back on with Gas
production, lower the pump further in the Interference
2
11
hole, or resize to a smaller unit.
3
With a VSD, try lowering the frequency.
10
4
9 5
8
7 6 PM
10
40
30
20
11
10
NOON
1
MIDNIGHT
21
11
3
10
4
9 5
8
7 6 PM
10
40
30
interference in the pump. 20
11
10
Corrective measures are the same
NOON
as before. If this conditions
1
Pump Off
develops after several months (or
MIDNIGHT
(no Gas
1
years) of normal operation, it may
Interference)
be that skin damage is reducing
2
11
the well productivity. Stimulation
3
may restore the productivity to the
10
original level (or better).
4
9
5
8
7 6 PM
10
40
30
PM and 7:00 PM. 20
11
10
NOON
1
MIDNIGHT
2 1
11
3
10
4
9
5
8
7 6 PM
10
insufficient fluid in the wellbore and 30
20
2
it trips due to underload. Immediate
11
10
NOON
Pump Off
1
restart time. Long-term, the unit w/ False
MIDNIGHT
1
needs to be resized. Restarts
2
11
3
10
4
9
5
8
7 6 PM
10
40
30
20
11
10
NOON
1
MIDNIGHT
21
11
3
10
4
9 5
8
7 6 PM
60 9
pump although it is possible that 3
50
10
emulsion production could also cause 40
30
it. It may be possible to smooth out the 20
11
10
line by choking back or lowering the
NOON
1
pump. Producing free gas will usually
Free Gas
MIDNIGHT
reduce the stock tank production rate so
in Pump
1
it is beneficial to reduce the effect.
Many pumps are operated with this
2
11
kind of chart. As long as the underload
3
is set properly, there should be no
major problems. 10
4
9
5
8
7 6 PM
10
40
30
midnight when the unit shuts down 20
11
10
on overload.
NOON
1
MIDNIGHT
21
11
3
10
4
9 5
8
7 6 PM
10
40
30
idle load until enough heat built up 20
11
10
to cause the motor to burn which is
NOON
U/L
1
when it tripped on overload. This is
set below
MIDNIGHT
a case where the underload was set
1
"No Load"
to low. Underloads need to be
2
11
raised and unit should be resized.
3
10
4
9
5
8
7 6 PM
10
40
30
tank. This tank will have a level 20
11
10
controller which will shut the unit
NOON
1
off when it is full and allow it to
restart when the level drops to a
MIDNIGHT
1
certain point.
2
11
3
10
4
9 5
8
7 6 PM
10
40
30
20
problem in itself, if the unit is restarted while
11
10
NOON
1
Tank Level
While a check valve may help guard against
MIDNIGHT
Controller
1
this, they can leak and should not be relied
2
upon. To give complete protection, a
11
backspin relay should be used in the motor
3
10
control circuit. Otherwise, set the restart 9
4
10
40
30
an overload trip. 20
11
10
NOON
1
MIDNIGHT
2 1
11
3
10
4
9
5
8
7 6 PM
10
► Increased fluid gravity 30
20
11
► Sand production 10
NOON
► Viscosity increases (emulsion
1
formation)
MIDNIGHT
Overload
1
► Mechanical or electrical
problems downhole
2
11
► Electrical power supply
3
problems, etc. The complete
10
installation should be checked 4
out thoroughly.
9
5
8
7 6 PM
10
40
30
20
11
10
NOON
1
MIDNIGHT
2 1
11
3
10
4
9
5
8
7 6 PM
10
While this is not uncommon, it is not desirable 30
20
2
as these materials may adversely affect pump
11
10
NOON
1
Pump
be bailed prior to running the pump to remove
MIDNIGHT
the foreign material. If this is caused by
Handling
1
unconsolidated sand, it may be wise to Solids
2
partially choke the well on start up and slowly
11
3
increase production -- especially on wells
10
newly converted from rods which produced a 4
however.
10
30
chart shows this occurs over a fairly 20
11
10
predictable time interval.
NOON
1
MIDNIGHT
1
2
11
3
10
4
9
5
8
7 6 PM
10
40
considered. 30
20
11
This can also be caused by decreasing 10
NOON
surface voltage due to other heavy
1
Emulsion?
equipment on the line which is cycling on
MIDNIGHT
Surface Load?
1
and off. Try to reduce demand on the Generator?
system.
2
11
This may even be caused by a unit which is
3
on a generator if the regulator is faulty
10
4
causing fluctuation in voltage or speed 9 5
changes resulting in changing power 8
6 PM
frequency. Repair the generator.
7
Flow Flow
145 Electric Submersible Pumps /
Mohammad Khalifa
146 Electric Submersible Pumps /
Mohammad Khalifa
Troubleshooting
► Pi + Pd Increasing
► WHP Decreasing
► Motor Temperature Increasing (no flow to cool the
motor)
► Current (Running Amps) Decreasing (No load)
► No flow at Surface ..
Flow Flow
148 Electric Submersible Pumps /
Mohammad Khalifa
149 Electric Submersible Pumps /
Mohammad Khalifa
Troubleshooting
► Pi + Pd decreasing
► WHP Decreasing
► Current (Running Amps) Up & Down
Flow Flow
151 Electric Submersible Pumps /
Mohammad Khalifa
152 Electric Submersible Pumps /
Mohammad Khalifa
Troubleshooting
► Pd – Pi decreasing
► WHP Decreasing
► Current (Running Amps) Decreasing Slightly
► Flow Rate Decreasing
Flow Flow
154 Electric Submersible Pumps /
Mohammad Khalifa
155 Electric Submersible Pumps /
Mohammad Khalifa
ESP Field Assembly Procedure
Wellhead
Extension
CT Hanger