Professional Documents
Culture Documents
Abstract
There has been considerable debate over the development of simplified calculation methods for thermal resistance (R-value) and
thermal transmittance (U-value) for light steel frame constructions that designers can easily use. Such simplified methods have presented
a particular difficulty for light steel framed constructions as compared with many other forms of construction because they must
accommodate the effects of non-homogenous layers and thermal bridges where the difference between the thermal conductivity of
materials is large.
This paper describes the development of a simplified method for calculating U-values of light steel frame constructions suitable for
incorporating into U-value calculation software. The new method is based on research carried out by returning to first principles to use
finite element modelling to analyse the heat flows through steel framed constructions, and comparing these with predictions made by
simplified methods. It was found that for warm frame constructions, where all the insulation is placed outside the steel frame, the normal
U-value calculation method as set out in BS EN ISO 6946 can be applied. However, for constructions where some or all the insulation is
placed within the thickness of the steel frame, the methodology in BS EN ISO 6946 has to be adapted to allow for the increased effect of
the steel.
A new method is proposed that is similar in principle to that used in BS EN ISO 6946 but adapted to increase accuracy for these types
of construction. It is designed to be easily implemented in U-value calculation software. It was found that with the proposed method the
mean error of prediction compared with finite element modelling is less than 3% with a maximum error of 8% for a range of 52 assessed
constructions. This method has been adopted for use in the UK to demonstrate compliance with the amendments to the thermal Building
Regulations.
r 2006 Elsevier Ltd. All rights reserved.
0360-1323/$ - see front matter r 2006 Elsevier Ltd. All rights reserved.
doi:10.1016/j.buildenv.2006.07.001
ARTICLE IN PRESS
M. Gorgolewski / Building and Environment 42 (2007) 230–236 231
increasing for use in both individual houses and apartment area of the element (Fig. 2). However, the steel has a thermal
blocks. The use of light steel framing can help to address conductivity that may be over 1500 times higher than the
issues of skills shortage, provide high construction stan- insulating material on either side. It has been shown that
dards, achieve precise tolerances and increase off-site ignoring the effect of the steel can lead to an over-estimate of
manufacture. the thermal resistance by up to 50%, depending on the
Light steel frame constructions typically comprise details of the construction [3]. It can also create a significant
C- and Z-shaped, galvanised, cold-form steel sections, temperature difference between the centre of the cavity and
usually between 0.9 and 2.4 mm thickness that are the stud area, leading to the possibility of wall staining called
produced by roll forming. The technology has developed ghosting occurring on cold spots.
from specific applications such as purlins and lintels to the During the last two decades, a variety of material
wider building market. Construction can use individual configurations have been investigated to increase the
light steel components assembled on site in a stick-built thermal effectiveness of light steel frame structures [4].
format to construct load bearing or non-load bearing These options include diminishing the contact area between
frame structures similar to timber frame. However, the studs and the sheathing, reducing the steel stud web
increasingly panellised or volumetric construction using area by perforating the web, replacing the steel web with a
preassembled components is used (Fig. 1). less conductive material, and placing foam insulation caps
Light steel framing can potentially incorporate a high in locations where the thermal bridges are most critical.
standard of thermal insulation resulting in comfortable, However, the most common way to overcome this problem
energy-efficient dwellings. However, steel members conduct is to introduce rigid insulation board on the outside of the
heat extremely well and when steel framing sections steel structure to create a partial or total ‘‘warm frame’’.
penetrate through the insulation they cause significant
thermal bridging. This can sharply reduce the effective 2.1. Constructions assessed
thermal resistance of the envelope. In typical light steel
frame assemblies the steel web forms less than 0.5% of the Three generic design types were considered, as follows
(see Fig. 3):
1. Warm frame wall with all the insulation outside the steel
frame: This wall construction is common in UK
domestic designs and has the advantage that the steel
framing is kept at a temperature close to the internal
temperature. This type of construction already lies
within the scope of BS EN ISO 6946.
2. Cold frame construction with insulation only between
the steel studs but no insulation to the external side of
the studs. This construction has a higher degree of
thermal bridging and is generally not recommended for
dwellings in the UK.
3. Hybrid construction with insulation between the steel
studs in conjunction with a continuous layer of
insulation to the external side of the steel framing. This
type of construction is common for domestic walls and
Fig. 1. Typical light steel framing system. roofs.
102
50 mm clear cavity
50
50 50 mm rigid insulant
20 20 mm plywood or OSB
100 100 mm insulation
15 40 600 15 mm plasterboard
100 mm deep
by 40 mm wide
C section studs
Thermal path a Thermal path b using 1.5 mm steel
Fig. 2. A typical hybrid light steel wall: thermal path b has a far smaller thermal resistance than path a.
ARTICLE IN PRESS
232 M. Gorgolewski / Building and Environment 42 (2007) 230–236
1 or 2 layers of plasterboard
Optional
sheathing board 1 or 2 layers Light steel studs with
of plasterboard mineral wool between
Light steel studs
Insulated sheathing
Thermal insulation board with foil face
with foil face or or breather membrane
breather membrane
Wall ties
Wall ties
Table 1 lists the variables that were considered in the 4. Description of the modelling
modelling and the ranges that were assessed.
The stud spacing is typically 600 mm. To allow for Fig. 4 illustrates a generalised form of the constructions
possible future variation, however, spacings of between 300 that were modelled using finite element software. The ‘‘C’’
and 800 mm were considered in order to assess the effect. shape of the steel channel stud is shown (labelled D)
The variation in stud spacing also provides an opportunity sandwiched between layers B and E. Layer A in the
to test simplified calculation methods against the effect of diagram is to the outside of the steel studs and may
varying the steel frame fraction. (The steel frame fraction typically consist of render, insulation board or an air
refers to the fraction of the wall area which is taken up by cavity. Layer B is a continuous sheathing layer that may be
the framing as opposed to insulation and this fraction is insulation (warm frame) or OSB board (cold frame). Layer
analogous to the timber and mortar fractions used in the C either may consist of insulation or can be an air void.
context of other types of constructions). Layer E is the internal lining and is typically made of
gypsum board, and could, in principle, be gypsum board
3. Approach laminated to insulation and is therefore shown as a double
layer. Alternatively, the double layer could be considered
A number of simplified calculation procedures have been to be board covered by a plaster skim coat.
developed in countries such as Denmark, Canada, USA The outside environment for the purposes of these
and New Zealand for assessing U-values of light steel frame calculations could in principle be either the external
constructions [5–8]. Some are similar to the BS EN ISO environment or it could be a void or cavity behind external
6946 approach of calculating an upper and lower limit to cladding. In the latter case the coldest temperature would
thermal resistance (Rmax and Rmin), but whereas BS EN be slightly higher than typical external temperatures but
ISO 6946 then choose the mean of the upper and lower this difference was ignored owing to the relatively minor
ARTICLE IN PRESS
M. Gorgolewski / Building and Environment 42 (2007) 230–236 233
5.1. The upper and lower limits of thermal resistance It was noted that if U ¼ p Rmax+(1p) Rmin, then there
was a correlation between the value of p and the ratio Rmin/
In order to interpret the data it is useful to carry out a Rmax. Even using the simple assumption that p ¼ Rmin/
calculation of the upper and lower limits of thermal Rmax yielded reasonable agreement between the simple
resistance, as defined in EN ISO 6946. These limits are calculation procedure and the results from modelling, as
labelled Rmax and Rmin. can be seen in Fig. 6.
Rmax, the upper limit of thermal resistance, is obtained With this method the average absolute error is reduced
by considering the heat flow paths to be parallel and the to 6%. The worst-case error is still about 28% but the
resistance is calculated from the area-weighted average of worst-case over-optimistic error is only 9%. A further
the individual thermal transmittances of the various refinement to this approach was to modify ‘‘p’’ slightly so
parallel heat paths in the construction. Rmin, the lower that p ¼ 0.8 Rmin/Rmax+0.1. This significantly reduces the
ARTICLE IN PRESS
234 M. Gorgolewski / Building and Environment 42 (2007) 230–236
0.800
0.600
0.500
0.400
0.300
0.200
0.100
0.000
0.000 0.200 0.400 0.600 0.800 1.000 1.200
U-value obtained from modelling
Fig. 5. The U-value as predicted by EN ISO 6946 plotted against that obtained by finite element modelling.
1.200
1.000
U-value (simplified)
0.800
0.600
0.400
0.200
0.000
0.000 0.200 0.400 0.600 0.800 1.000 1.200
U-value obtained from modelling
Fig. 6. The U-value as predicted by experimental method 1 (p ¼ Rmin/Rmax) plotted against that obtained by finite element modelling.
1.200
0.800
0.600
0.400
0.200
0.000
0.000 0.200 0.400 0.600 0.800 1.000 1.200
U-value obtained from modelling
Fig. 7. The U-value as predicted by experimental method 2 plotted against that obtained by finite element modelling.
1.000
U-value (simplified)
0.800
0.600
0.400
0.200
0.000
0.000 0.200 0.400 0.600 0.800 1.000 1.200
U-value obtained from modelling
Fig. 8. U-value predicted by method 3 plotted against those obtained by finite element modelling.
stud depth all had an influence on the value of p. This third through the sheathing. These fixings influence the heat loss
method is described in the following formula: from the wall/roof/floor by offering an easier path for heat
to flow between the steel flanges and the external
p ¼ 0:8ðRmin =Rmax Þ þ 0:44 0:1ðw=40 mmÞ
environment. In order to determine how strong this effect
0:2ð600 mm=sÞ 0:04ðd=100 mmÞ, was, a number of finite element model simulations were
where w is the flange width, s the stud spacing and d the carried out both with and without fixings.
stud depth. It was found that a reasonable estimate of the adjust-
The level of agreement between method 3 and the results ment to the U-value could be obtained by using the
of the finite element modelling was found to be good, as following formula, which is a proposed amendment to that
can be seen in Fig. 8. The average absolute error is only used for metal fasteners in BS EN ISO 6946:
2.7% with a maximum error of 8% and a maximum over-
DU f ¼ alf Af nf ðRi =RT Þ2 =d i ,
optimistic error of 3%.
where a is a constant set at 0.8 for warm frame and 1.6 for
6. Correcting for metal fixings hybrid/cold frame, lf the thermal conductivity of the fixing,
Af the cross-sectional area of the fixing, nf the number of
In many constructions, part of the insulating layer is fixings per unit of area, Ri the thermal resistance of the
penetrated by metal fixings such as metal wall ties or screws insulation layer penetrated by the fixings, RT the total
ARTICLE IN PRESS
236 M. Gorgolewski / Building and Environment 42 (2007) 230–236
thermal resistance of the element and di the thickness of the frame construction enabling U-values to be easily calcu-
insulation penetrated by the fixings. lated.
For typical stainless steel wall ties used in the UK this
method gives a DUf of 0.0077 W/m2K, whereas the finite References
element modelling indicates an increase in U-value for such
fixings of 0.008 W/m2K. This suggests good agreement. It is [1] DTLR. Conservation of fuel and power, approved document L1.
notable that when fixings did not actually penetrate any UK: The Stationery Office; 2001.
[2] European Committee for Standardisation. Building components and
insulation, such as in the cold frame designs, the fixings still building elements—thermal resistance and thermal transmittance—
exerted a small effect; however, this effect was found to be calculation method, EN ISO 6946:1996.
very minor in comparison with the effect of fixings which [3] Kosny J, Christian J. Reducing the uncertainties associated with
did penetrate insulation. It was concluded that the above using the ASHRAE zone method for R-value calculations of metal
frame walls. ASHRAE Transactions 1995;101(Pt. 2) SD95-5-3.
formula was adequate for describing the effect of fixings.
[4] Kosny J, Childs P, Gorgolewski MT. Making steel framing as
thermally efficient as wood most current developments from ORNL
7. Conclusions Steel in Sustainable construction. Luxemburg: IISI world congress;
2002.
It has been found that the use of the Rmin/Rmax ratio is a [5] Kosny J, Christian J. Reducing the uncertainties associated with
useful basis for estimating U-values for constructions with using the ASHRAE zone method for R-value calculations of metal
frame walls. ASHRAE Transactions 1995;101(Pt. 2) SD95-5-3.
linear thermal metal bridges. Several methods were [6] Adams JC, De Meo LJ, Stark GK. Evaluation method for the
assessed and from these the third experimental method thermal performance of lightweight framed wall assemblies; 1996.
outlined above shows very good agreement with modelled [7] Canadian Commission on Buildings and Fire Codes. Model national
results. It is similar in principle to the method outlined in energy code for houses. National Research Council Canada; 1997.
BS EN ISO 6946, but with a more complex algorithm to [8] Trethowen HA. Calculating R-values using the isothermal planes
method. Building Research Association of New Zealand; 1998.
find the weighting between Rmax and Rmin. This method [9] European Committee for Standardisation. Thermal bridges in
has been adopted in the UK for Building Regulations building construction—Heat flows and surface temperatures. BS
compliance and its application is described in detail in BRE EN ISO 10211-1; 1996.
Digest 465 [11]. The method has also been incorporated [10] Doran SM. U-values of light steel frame constructions. BRE project
report 16289, Building Research Establishment, UK; 2002.
into U-value calculation software [12] which can be used to
[11] Doran SM, Gorgolewski MT. U-values for light steel frame
demonstrate compliance with the new Approved Docu- construction. BRE Digest 465, Building Research Establishment,
ments L1 and L2. This general U-value calculation UK; 2002.
software now includes separate routines for light steel [12] See /http://projects.bre.co.uk/uvaluesS.