Fire and The exterior walls on both sides of the fire wall shall have a 1-hour fire- 706.5.

1
Smoke resistance rating with ¾ hour protection The fire-resistance rating of
Protection the exterior wall shall extend not less than 1.2 m on each side of the
Features intersection of the fire wall to exterior wall.

Fire and The minimum overall dimensions of reinforced concrete columns for 722.2.4
Smoke fire-resistance ratings of 1 hour to 4 hours for exposure to fire on all
Protection sides.
Features
Fire and Insulating materials, where concealed as installed in buildings of any 720.2
Smoke type of construction, shall have a flame
Protection spread index of not more than 25 and a smoke developed index of not
Features more than 450.
Fire and Marking and identification.
Smoke Be located within 4.5 m of the end of each
Protection wall and at intervals not exceeding 9 m
Features measured horizontally along the wall or
partition. Include lettering not less than 75 mm in height 703.7
with a minimum 10 mm stroke in a contrasting color incorporating the
suggested wording, “FIRE AND/OR SMOKE BARRIER—PROTECT ALL
OPENINGS,”
or other wording
Fire and Openings in exterior walls in adjacent stories shall
Smoke be separated vertically to protect against fire spread 705.8.5
Protection on the exterior of the buildings where the openings
Features are within 1.5 m of each
Fire and Fire door assemblies required to have a
Smoke minimum fire protection rating of 20 minutes 716.5.3
Protection where located in corridor walls or smoke barrier
Features walls