Professional Documents
Culture Documents
QCVN 09:2013/BXD
HANOI - 2013
Machine Translated by Google
QCVN 09:2013/BXD
PREFACE
QCVN 09:2013/ BXD on “Construction projects using energy efficiently” drafted by the
Vietnam Built Environment Association, submitted by the Department of Science, Technology
and Environment, and issued by the Ministry of Construction in accordance with Circular No. No.
15 / 2013/ TT-BXD dated September 26, 2013. National Technical Regulation QCVN 09:2013/
BXD replaces Vietnam Construction Code QCXDVN 09:2005 “Construction works using energy
can effective” was issued under Decision No. 40/2005/ QD-BXD dated November 17, 2005 of
the Minister of Construction.
National technical regulation QCVN 09:2013/ BXD is participated in research and comments
by international experts sponsored by international organizations, including: International Finance
Corporation (IFC – International Finance) Corporation), the United States Agency for International
Development (USAID), the Danish Department of Energy (Kingdom of Denmark).
5
Machine Translated by Google
QCVN 09:2013/BXD
I. GENERAL PROVISIONS
The National Technical Regulation “Energy efficient buildings” stipulates the technical requirements that
must be complied with when designing, building or renovating civil works (offices, hotels, hospitals,
schools, commerce, services, apartments) with a total floor area of 2500 m2 or more.
1) Building envelopes, other than those of storage spaces or warehouses, are not
use air conditioners;
This Regulation prescribes technical requirements that must be complied with by all organizations and
individuals having activities related to energy efficient construction works.
1.3. References
7
Machine Translated by Google
QCVN 09:2013/BXD
3) ARI 550/590-2003 – Performance rating of water-chilling packages using the vapor compression
cycle.
4) ASHRAE 90.1-2001 – Standard 90.1-2001 (IP Edition) -- Energy Standard for Buildings Except
Low-Rise Residential Buildings (IESNA cosponsored; ANSI approved; Continuous
Maintenance Standard).
5) SHRAE 90.1-2004 – Energy Standard for Buildings Except Low-Rise Residential Buildings.
6) DIN 4702-1 – Boilers for central heating; terms, requirements, testing, marking.
7) ISO 6946:2007 – Building components and building elements - Thermal resistance and
thermal transmittance - Calculation method.
8) TCVN 298:2003 – Components and components of buildings- Heat resistance and heat transfer
Calculation method.
1.4.1. Terms
1) Cooling air economizer: A component consisting of ducts and automatic controls that
enables fans to deliver cool air from outside the home into the house when weather
conditions permit to reduce Reduced energy consumption for air cooling or no need
for machine cooling.
2) Energy cost for the building: The total of all expenses paid for consumption
the annual energy of the building.
3) Refrigeration efficiency index COP: Ratio of obtained cooling capacity to input power
consumption on the same unit of measurement, tested according to national standards
or designed working conditions . COP value is determined to evaluate the energy
efficiency of electric air conditioners, air condensers, including compressors,
evaporators, and condensers. The COP value is also determined to evaluate the
energy efficiency of the integrated chilled water machine
8
Machine Translated by Google
QCVN 09:2013/BXD
units (excluding chilled water pumps, condensate cooling water pumps and cooling tower
fans).
4) Heat pump efficiency index COP: It is the ratio between the obtained heat capacity to the input
power consumption in the same unit of measurement, calculated for the entire heat pump
system in the designed working condition. .
5) Total heat transfer index OTTV: The total amount of heat transferred to the house through the
entire surface area of the building's shell including the non-transparent walls and glass doors
for 1m2 of the building's outer surface, W/ m2 .
6) Floor area of a building space: The horizontal surface area of a specified building space,
measured from the inside surface of the surrounding wall or partition panel, at the height of
the working plane (0) ,8m).
7) Radiance reduction factor due to shading structure: Ratio of solar radiation entering the room
through the window in the case of a shading structure outside the window, compared with
the case of an unstructured window sunshade.
8) Total heat transfer coefficient Uo: is the constant heat flux intensity over time passing through a
unit surface area of the covering structure when the temperature difference of the air
environment on both sides of the structure is 1 K. Measuring unit: W/m2 .K.
9) Total heat resistance Ro: The reciprocal of total heat transfer coefficient Uo: R0 = 1/Uo , unit
measured as m2 .K/W.
10) Lamp luminous efficiency: is the ratio between the luminous flux of the lamp and
the electrical power of the lamp, in lumens/W.
11) Ventilation-air-conditioning system efficiency: ratio of output energy (useful energy at the time
of use) to input energy with the same unit of measure in %. for a specified period,
12) Heat recovery efficiency: The ability to recover cold heat of air conditioning equipment, furnaces
steam…provides energy-saving effect.
9
Machine Translated by Google
QCVN 09:2013/BXD
14) Indirectly conditioned space: an enclosed space in a building that is cooled indirectly (not directly
cooled) and has heat transfer from this space to adjacent cooled air-conditioned spaces.
15) Lighting Power Density (LPD): The luminous power density is the ratio of the light power
Lighting power and illuminated area, W/m2 .
16) Natural light relay: a device that automatically opens or disconnects input energy for electrical
lighting placed near a window to both maintain appropriate illumination for work, when direct
or indirect natural light is present. contact does not guarantee or ensure the required illuminance.
18) Building shell : the building envelope, also known as the structure that covers the building,
includes non-transparent or transparent walls, windows, doors, roofs, roof doors, etc. to form
closed spaces inside. construction.
1) SHGC (Solar Heat Gain Coefficient) The heat absorption coefficient of glass, declared by the
manufacturer or determined according to applicable standards, is dimensionless. If the
manufacturer uses the shading factor SC, then SHGC = SC × 0.87;
2) SC Shading Coefficent.
3) T Absolute temperature K.
4) R0 Total thermal resistance (the reciprocal of total heat transfer coefficient U0) of the envelope structure
cover - m2 K/W;
5) Uo Total heat transfer coefficient (including heat exchange through 2 air boundary layers on both sides of
ten
Machine Translated by Google
QCVN 09:2013/BXD
10) ASHRAE American Association of Heating, Refrigeration and Air Conditioning Engineers
(American Society of Heating, Refrigerating and Air - Conditioning Engineers);
14) COPheat Heat Pump Efficiency Index -The ratio of the heat yield obtained to the
input power consumption kW/kW;
15) EER Energy Efficiency Ratio of air conditioners – air conditioners – Ratio of the
obtained cooling capacity to the effective electrical power, kW/kW;
16) FCU Fan Coil Unit – a heat exchanger consisting of many rows of smooth or finned
tubes, the heat carrier is cold water or hot water circulating inside the tubes to
supply cold/heat to the air by The fan blows through for the purpose of cooling/
heating the room. FCU is the terminal device of the central air conditioning system
with the chiller production machine;
19) OTTVT Total Thermal Transfer Value through the wall - Average intensity of heat transfer
through 1 m2 of outer wall into the house (Overall Thermal Transfer Value), W/m2 ;
20) OTTVM Total heat transfer index through the roof - Average intensity of heat transfer through
1 m2 of roof structure to the house,W/m2 ;
21) PIC Power Index (Power Input per Capacity) – Ratio of power consumption
measured in kW and cooling capacity in RT (refrigerated steel), kW/RT;
11
Machine Translated by Google
QCVN 09:2013/BXD
22) VLT (Visible Light Transmission)- The light penetration coefficient of the glass- represents the
percentage of light energy passing through the glass compared to the part of light energy
reaching the glass surface, %;
24) VSD Rotary speed regulator by changing the frequency of the power supply – referred to as the
inverter (Variable Speed Driver);
Sufficient natural lighting under normal allowable conditions, and at the same time minimizing solar
radiation entering the building's interior;
1) All external walls of the building on the ground (non-transparent walls) must have the maximum total
heat transfer value Uo.max not greater than or the minimum total heat resistance Ro.min not less
than the value. values specified in Table 2.1.
The directions
Region Uo.max, W/m2 .K Ro.min, m2 .K/W
of the wall surface
twelfth
Machine Translated by Google
QCVN 09:2013/BXD
2) Requirements for flat roofs and roofs with slopes below 15 degrees:
All types of roofs, including roofs with insulation, metal roofs and other types of roofs must have a total heat
transfer value Uo not greater than or a total heat resistance value Ro not less than the value specified in
table 2.2.
Note:
1) Shaded roof: If more than 90% of the roof surface is covered with a fixed layer of ventilated shading
structure, no insulation is required for that roof. The shading structure layer must be at least 0.3 m from
the roof surface to be considered as having ventilation between the roof layer and the roof shading layer
(2-layer roof with a convective air layer in the middle).
2) Roof made of reflective material: The heat resistance value Ro,min given in Tables 2.2 can be used
multiplied by a factor of 0.80 for roofs designed with reflective materials with reflectivity in the range of,70
0
0.75 to increase the reflectivity of the exterior roof surface.
3) Roof with a slope of 15 degrees or more: the minimum total heat resistance or maximum total heat transfer coefficient
of the roof can be determined by multiplying the Ro.min, Uo.max values in table 2.2 by the coefficients. 0.85 and 1.18
respectively.
a) The total area of windows on the façade for two types of doors that can be opened and fixed vertically
must ensure ventilation and take in natural light.
b) The total heat transfer index of the wall and roof must ensure: - OTTVT
4) Design windows with glass with appropriate SHGC coefficient instead of determining the OTTVT index of the
wall mentioned in 2.1.2 – Point 3) – b). SHGC of glass must be less than or equal to
13
Machine Translated by Google
QCVN 09:2013/BXD
maximum allowable value, and at the same time the VLT of the glass must not be lower than the value of VLTmin
Table 2.3. The SHGC coefficient of the glass depends on the WWR . ratio
NE, NE
WWR, % REMOVE
D or T WOMEN
VLTmin
or DN, TN
Note:
1) When the WWR does not match the values recorded in column 1 of table 2.3, the SHGC coefficient is interpolated
linear in 2 values corresponding to the adjacent upper and lower WWR;
2) Glass with a higher SHGC value than the table SHGC may be selected, provided that a shading structure with an
appropriate A-factor must be installed, such that the selected SHGC is less than or equal to the product of the
ÿ
SHGC. check multiplication table with factor A see also 2.1.2 – Score 5).
5) In case the facade has a sunshade structure, the SHGC coefficient in table 2.3 is allowed
14
Machine Translated by Google
QCVN 09:2013/BXD
Table 2.4. Factor A for long horizontal shading structures (CNN) continuously placed close to the upper
edge of the window or placed a distance d from the upper edge of the window with d/H < 0.1
Note:
1) Dimensions:
H - window height;
d - distance from the upper edge of the CS to the lower edge of the visor;
2) Applicable to the case that the industrial zone is located at a distance d from the upper edge of the CS with d/ H ÿ 0.1 - the
calculation error is less than 10%.
15
Machine Translated by Google
QCVN 09:2013/BXD
Table 2.5. Factor A for a continuous height vertical sunshade placed close to the side of the
window or a distance e from the side of the window e/B < 0.1
Note:
1) Dimensions: b –
extension of vertical shading structure; B -
window width; e - distance from the side of
the window to the inside of the vertical sunshade; b, e and B have the same
dimension of length.
2) Applicable to the case that the vertical sunshade is placed at a distance e from the side of the CS
e/ B ÿ 0.1 – calculation error less than 10%.
16
Machine Translated by Google
QCVN 09:2013/BXD
General requirements
For each specific space, the ventilation system can be natural ventilation (passive) or forced
ventilation (active - artificial ventilation or mechanical ventilation).
The natural ventilation systems must meet the requirements in clause 2.2.1 – Point 2).
Spaces are considered to have natural ventilation if they satisfy the requirements
after:
a) Ventilation holes and windows that can be opened to the outside with an area of not less
than 5% of the floor area. Easy access to these ventilation openings for the user;
b) There must be openable ventilation holes above the ceiling or on the wall facing the
source of wind from the outside. Such ventilation openings have an open area ratio of
not less than 5% of the floor area. These ventilation openings are easily accessible to
the user and they must be directly vented to the outside through openings of equal or
larger area;
c) The total area of the vents is not less than the total area of the louvers.
Spaces that are not naturally ventilated must be fitted with a mechanical ventilation system to
supply air from the outside to each space regularly occupied by a duct system.
chilled water generators must have COP efficiency indicators minimum at standard evaluation
conditions and not less than the values given in the following tables:
17
Machine Translated by Google
QCVN 09:2013/BXD
Note:
In addition to the COP, refrigeration equipment is also energy efficient using the IPLV
composite underload factor and the IEER composite energy efficiency index.
b) Automatic timer: the following devices must have a timer or automatic controls to open and close
the device according to defined time or set parameters:
The refrigerant pipes of the air conditioner and the cold water pipes of the central air
conditioning system must have an insulation layer greater than or equal to the insulation
thickness in tables 2.9 and 2.10.
Insulation thickness (mm) given in table 2.9 and table 2.10 is applied to insulation material
with thermal conductivity in the range of 0.032 ÷ 0.04 W/mK at an average temperature of
24°C. The minimum insulation thickness shall be increased for materials with a thermal
conductivity greater than 0.04 W/mK or may be reduced for materials with a coefficient of
thermal conductivity less than 0.032 W/mK.
For insulation materials with a coefficient of thermal conductivity outside the range stated, the
minimum thickness (bmin) is determined by the following formula:
18
Machine Translated by Google
QCVN 09:2013/BXD
(2.1)
ÿÿ
r ÿÿ
in there:
b0 - insulation thickness listed in tables 2.9, 2.10 and 2.11 for applicable pipe sizes, mm;
ÿ is the thermal conductivity coefficient of the substitute material at the applied temperature of the liquid,
W/mK
d) Insulation of the supply and return duct systems: the supply and return ducts must have an insulation
layer greater than or equal to the insulation thickness in Table 2.11. No insulation is required for the
exhaust duct.
e) Check and adjust: fans or pumps with a capacity of 5 kW (3.7 kW) or more must adjust the design flow
of the machine by adjusting the number of revolutions using a multi-transmitter. speed, two-speed
motor or inverter (VSD).
Limit the flow regulation of fan and pump by throttle valve. f) Cooling tower fan
control: cooling towers with fan motors with a capacity of 5 kW (3.7 kW) or more must use multi-speed
transmissions, two-speed motors or inverters ( VSD).
g) Chiller water cooling system: Central air conditioning systems using chilled water must be designed with
variable flow rate using an inverter pump.
h) Buildings using central air conditioning systems must have cold recovery equipment. Brand
The cold recovery rate of the appliance is at least 50%.
When mechanical ventilation and air conditioning systems are used, the following additional requirements
must be met: a) CO2 sensors: must be installed to increase the amount of air supplied to spaces with
QCVN 09:2013/BXD
b) Automatic timer control device: ventilation fans operating infrequently must have timers
or automatic control devices that can determine when and how long they work. .
c) Conduit welding: supply and circulating air ducts must meet the requirements for
connection of ducts and insulation according to current regulations.
Efficiency Index
Minimum COP
type of device Cold capacity Inspection procedures
of air
conditioner, kW/kW
TCVN 6307:1997
ÿ 14 kW and < 19 kW or
2.93
ARI 210/240
Zero cooled air conditioner
ÿ 19 kW and < 40 kW 3.02
117 kW 2.70
70 kW 2.70
20
Machine Translated by Google
QCVN 09:2013/BXD
Efficiency Index
Minimum COP
type of device Cold capacity Inspection procedures
of air
conditioner, kW/kW
Air-cooled condensers
40 kW 2.96
Note:
1) Refrigeration efficiency index: COP = Refrigeration capacity / Power consumption (kW/ kW);
3) The minimum refrigerating efficiency index given in the Table is calculated at 100% refrigeration capacity. To calculate
the efficiency index of air conditioners operating in 1 year period, ARI 340/360 gives the following formula:
in there:
IEER – Combined Energy Efficiency Index is an air conditioning efficiency index over time
operating for 1 year according to the load levels,
21
Machine Translated by Google
QCVN 09:2013/BXD
Energy consumption
Refrigeration
index
Refrigeration efficiency index
type of device PICMAX , kW/RT
capacity (kW) COPMIN,
kW/kW
Electricity Heat
- 1 level
22
Machine Translated by Google
QCVN 09:2013/BXD
Energy consumption
Refrigeration
index
Refrigeration efficiency index
type of device
capacity (kW) COPMIN, PICMAX , kW/RT
kW/kW
Electricity Heat
Note:
in there:
IPLV – Composite underload efficiency index is an air conditioner efficiency index calculated for total operating time
operated during the year according to the load levels;
23
Machine Translated by Google
QCVN 09:2013/BXD
Rated parameters
type Evaluation Flow Flow of water
Inspection
Refrigeration Wattage procedures
of device conditions replenishing
water through the tower
capacity range Fan
Sung
Water temperature
Note:
Air-cooled
Inlet air temperature:
condenser 0.5÷500 17÷34 m3 /min 75÷150 1.0÷1.3
CTC
including RT RT W/RT kW/RT
350 C
compressor
Water temperature
Water-cooled 0OLD
10÷1600 in: 29.4 Water flow rate
condenser CTC
RT Outlet water 9.08 11.40 l/min RT
temperature: 350 C
Note:
24
Machine Translated by Google
QCVN 09:2013/BXD
105 - - 70
o
Conditions apply:t = 32÷37 C, = 60%
o
Refrigerant temperature OLD
66÷80 32 57 70
105 - - 76
Note:
o
1) t - Outside air temperature, 2) C;
The above insulation thickness applies to copper pipes carrying refrigerant (liquid, refrigerant); 3)
Insulation thickness (mm) given in Table is based on insulation with coefficient of thermal conductivity ÿ
°
will be in the range of 0.032 ÷ 0.04 W/ mK at an average temperature of 24C.increased
The minimum insulationhaving
with materials thickness
a
thermal conductivity greater than 0.04W/ mK or can be reduced with materials with thermal conductivity coefficient
less than 0.032W/ mK and corrected according to formula (2.1).
25
Machine Translated by Google
QCVN 09:2013/BXD
Insulation thickness, mm
20÷50 16
50÷75 16
75÷150 19
150÷250 19
250÷600 25
Insulation thickness, mm
20÷50 25
50÷75 25
75÷150 30
150÷250 30
250÷600 38
Note:
1) For steel pipes the diameter given in the table is the nominal diameter (I,P,S-Iron pipe
standard);
2) Insulation thickness for steel pipes is used for both PE, PPR, PN16 plastic pipes, For PE and
PPR plastic pipes, the diameter shown in the table is the outside diameter; 3) Insulation
thickness (mm) given in Table is based on porous polymer insulation with closed cell structure,
thermal conductivity ÿ in the range of 0.032 ÷ 0.04 W/ mK at mid-C. The minimum insulation
24 . tank °thickness shall be increased for materials with a thermal conductivity greater than
0.04 W/ mK or may be reduced for materials with a coefficient of thermal conductivity less than
0.032 W/ mK and corrected for formula (2.1).
26
Machine Translated by Google
QCVN 09:2013/BXD
Insulation thickness, mm 15
Insulation thickness, mm 20
Note:
Insulation thickness (mm) given in Table is based on closed cell structure porous polymer
insulation, thermal conductivity ÿ between 0.032 ÷ 0.04 W/ mK at medium temperature C.
24 °Thickness Minimum insulation shall be increased for materials with a thermal conductivity
greater than 0.04 W/ mK or may be reduced for materials with a thermal conductivity of less
than 0.032 W/ mK and corrected for formula (2.1).
2.3. Light
1) Scope of application
This section specifies the maximum luminous wattage limit values to be used for building lighting
systems, as well as specifies the allowable efficiency limit values of common lighting fixtures (lamps
and ballast) and lighting control system. The following situations are not included in the requirements
of this section:
a) Lighting for performances, television programming, entertainment sections such as hotel ballrooms,
discos, areas where lighting is an important technical element for demonstration function;
27
Machine Translated by Google
QCVN 09:2013/BXD
e) Lighting special security areas as required by State laws or regulations of local authorities;
2) Minimum
illuminance Minimum illuminance (lux) for functional spaces must meet the requirements of
current technical standards.
a) The average lighting power density (LPD) for the whole building must not exceed the
maximum allowed level stated in Table 2.12. The average lighting power density of a
building is calculated as the total lighting capacity of the building divided by the total
occupied area.
Office 11
Hotel 11
Hospital 13
Schools 13
Trade in Services 16
Apartment 8
28
Machine Translated by Google
QCVN 09:2013/BXD
b) Other types of works with scale regulated by the Regulation but not in the list in table 2.12 are
allowed to take the maximum lighting power density value up to 13 W/m2 . c) Mixed works
with scale regulated by the Regulation, in which there are many different functional areas,
shall be calculated according to the function of each area. Each area must satisfy the requirements
for maximum lighting power density given in table 2.12.
d) The average lighting power density of the parking area is calculated as the total lighting capacity
of the parking area divided by the total area of the parking area.
The minimum luminous efficiency of a lamp is specified in accordance with tables 2.13 and 2.14.
From 14 to 20 72
Over 20 to 40 78
From 5 to 8 55
From 9 to 14 60
From 15 to 24 65
From 25 to 60 70
29
Machine Translated by Google
QCVN 09:2013/BXD
Each space surrounded by floor-to-ceiling partitions is a separate space that should have at least
one lighting control device. Each lighting control device is controlled manually or by automatic
induction for human activity in that space. Each control device must: a) control a maximum area
of 100 m2 ; b) The spaces listed in Table 2.16 must be installed with human sensors, which
directly connect and control the lighting system. The human sensor for lighting control is not
Hospital Optional
30
Machine Translated by Google
QCVN 09:2013/BXD
c) For parking areas, at least 70% of the lighting system should be controlled by human sensors (the
system percentage is calculated according to the lighting power supply capacity).
For a closed space with natural lighting, the artificial lighting should pay attention to the following
issues: a) The area that can be naturally lit is the area parallel to the window/outer glass wall in the
area. en the distance from the window/exterior glazing up to 1.5 times the height from the floor to the
highest point of the window glazing or siding.
b) All lighting fixtures located in an area that can be naturally lit must have a lighting control device in
the following manner:
– Use light sensor to automatically reduce lamp brightness, or turn on and off the light according to
the level of natural light. The light sensor should be positioned ½ depth of the area that can be
naturally lit. When the natural light measured by the sensor rises above the standard for that
space (e.g., 300 lux for an office), the sensor must signal to turn off the light.
- Allows to turn on and off lights separately in areas that can be naturally lit compared to the system
general lighting system.
c) When the space has simultaneous use of human sensors and light sensors, the human sensor has
a higher priority than the light sensor when controlling lights.
d) Hospitals, guest rooms in hotels and apartments are not required to apply regulation 2.3.3 – Point
2).
e) Spaces used for special purposes are excluded from regulation 2.3.3 – Point 2), but specific
explanations are required.
The auxiliary control unit to turn on and off the lights fixedly installed under the shelf, under the storage
cabinet, etc., is used in the following cases:
a) Decorative lighting for guest rooms of hotels, motels and guest rooms
luxurious;
QCVN 09:2013/BXD
Escalator
The escalator must have a control device to slow down or stop when there is no passerby.
The escalator must have one of the following energy-saving features: 1) Deceleration
control: the escalator must enter the slow-running mode after being unoccupied for up to 3
minutes. Photoelectric-triggered sensing devices shall be installed at the top and bottom
of the ladder area.
2) Use when there is a need: the escalator must turn itself off after no one passes for up to 15
minutes. Escalators used when there is a need must be designed with energy-saving soft-
start technology. The escalator must run automatically when needed. Activation is done
by photocells installed at the top and bottom of the ladder area.
2.4.2. Elevator
Lifts must have controls to reduce energy use. To meet this requirement, the following features
must be incorporated into traction-type lifts: 1) Use of multi-voltage, multi-frequency a.c. motors
2) Elevator cabins using energy-saving lighting and display lighting should ensure the average
luminous efficiency for all equipment inside. Average illuminance >55 lumens/W, lights
need to be turned off automatically after the elevator stops working for up to 5 minutes.
3) The elevator operates in idle mode during off-peak hours. For example, the power supply to
the elevator control system and other operating devices such as lights in the elevator
room, display screens, and ventilation fans will automatically turn off after the elevator
stops working for up to 5 minutes.
1) Measuring instrument
The distribution system to the construction site must have an internal measuring device to
record demand (kVA), energy consumption (kWh), total power factor in test meters. The
power distribution system in the building can be tested for energy
32
Machine Translated by Google
QCVN 09:2013/BXD
the amount of electricity consumed at the power load branches through the meter. It is required
to install test meters at power load branches with total installed capacity of more than 100 kVA
such as lighting systems, sockets, air conditioning systems, ventilation, hot water supply systems,
center consuming more than 100 kVA of electricity.
2) Auxiliary meter
There must be an additional meter for each tenant of the area and a provision that allows the
tenant's meter to be checked.
Note: When using a shared (central) air conditioning system, there is no need
to meet the tenant sub-meter requirement.
All power supplies greater than 100 A, 3-phase must maintain their phase-delayed power factor
between 0.90 and 1 right at the point of connection.
The electrical system in the building must ensure the maximum allowable simultaneous use
factor stated in Table 2.17 and the maximum allowable installed capacity in Table 2.18.
Table 2.17. The maximum concurrency factor ks according to the load branches
Light 0.9
Sockets 0.4
33
Machine Translated by Google
QCVN 09:2013/BXD
Luxury apartment 70
Hotel 80
School, hospital 65
All 3 phase induction motors with fixed wiring for construction have the efficiency value stated on the case
at full load not less than the value given in Table 2.19. The manufacturer's label on the engine shows the
minimum efficiency values, listed efficiency, and power factor at full load.
34
Machine Translated by Google
QCVN 09:2013/BXD
Note:
If a motor with intermediate power between two steps is encountered, the step efficiency value . applies
higher.
35
Machine Translated by Google
QCVN 09:2013/BXD
General requirements
The design load of the hot water heating system is calculated according to the size of the equipment and
must be in accordance with the manufacturer's regulations.
In case other hot water supply solutions (non-resistive) can be used with greater economic efficiency,
the building is not allowed to use the solution of hot water supply using resistance.
When the project has a large and concentrated demand for hot water supply, the installed capacity is
over 50 kW or the energy consumption is over 50,000 kWh/year, it is not allowed to use the solution of
hot water supply using resistance.
0C:
1) Range of domestic hot water supply temperature ÿ 60
Supplying hot water by solar energy combined with heat pump/electric heating; c) Hot
water supply by heat pump; d) Supply of hot water from a gas boiler; e) Supplying hot
0
2) Hot water and steam supply range 115 C (cooking, laundry, disinfection, sauna):
0
In the project, there is a need to simultaneously use hot water 60 C (for fertility needs
0
activated) and hot water/steam C (for the needs of cooking, laundry, sauna, antiseptic) then
0
ÿ115 preferable solution of heating water to C, then continue to heat the water, steam to
0
temperature 115 60 C by using gas and oil fuel boiler.
heating and supply equipment such as potable water heaters, heating, swimming pools, hot water
stored in tanks must meet the listed criteria. in Table 2.20. For heat pump water heaters, refer to table
2.21.
36
Machine Translated by Google
QCVN 09:2013/BXD
Minimum performance
type of device
ET, %
Note:
1. The minimum efficiency of a gas or oil water heater is given as a quantity Thermal
Efficiency ( ET, which includes heat loss from the heater compartments).
For resistive water heaters, the minimum efficiency is determined from the maximum standby loss (Standby Loss,
SL) when the temperature difference between the boiling water and the surrounding environment is 40 °C . ,
according to the following formula:
In there:
37
Machine Translated by Google
QCVN 09:2013/BXD
Table 2.21. Minimum COP energy efficiency index of hot water supply heat pump
- When running the air conditioner while providing hot water. 5.5
Resistive water heaters are not recommended unless used to support solar systems. The use
of electric heat pump water heaters is recommended because of their higher energy efficiency
compared to resistance water heaters.
Where permitted, solar water heating systems can be used to supply all or part of the hot water
needs of the building. Solar water heaters are at least 60% efficient and have a minimum
insulation R value of 2.2
2 m .K/W of the solar absorber back panel.
Insulation thickness for hot water pipes must be greater than or equal to the insulation
thickness given in tables 2.22 and 2.23.
38
Machine Translated by Google
QCVN 09:2013/BXD
115 50÷90
65÷80 50 20
90÷150 63 25
200÷250 63 25
Note:
2. Porous polymer insulation material with closed cell structure has a thermal conductivity coefficient in the range of 0.032
o C.
0.04 W/ mK applies to temperatures from 50 90
0 C.
3. Insulation thickness in Table 2.22 ensures that the outside temperature of insulation is less than
43 4. For insulation materials with thermal conductivity outside the range given the numerical value, the
minimum thickness bmin is determined by formula (2.1).
Table 2.23. Insulation thickness for PPR, PE pipes for hot water
65 19
80÷ 125 25
Note:
1) For apartments, insulation may not be required for PPR hot water supply pipes.
2) Insulation material with thermal conductivity between 0.034 0.04 W/ mK 3) For
insulation material with thermal conductivity outside the stated value range, the minimum thickness
bmin is determined determined according to formula (2.1).
39
Machine Translated by Google
QCVN 09:2013/BXD
1) A temperature control system is installed to limit the hot water temperature at the point of use to no more than
50
o C.
2) A temperature control system is installed to limit the maximum temperature of the water supplied to the bath
3) The temperature maintenance system used in hot water pipes must be equipped with an ON/OFF valve set
4) The circulation pumps used to maintain the temperature in the hot water tanks are controlled to operate in
accordance with the operating mode of the hot water supply equipment.
3.1. Design dossiers of new construction, repair and renovation works of construction scale within the scope of
QCVN 09:2013/BXD must include explanations on compliance with the provisions of this Regulation.
3.2 The verification, design appraisal, acceptance test of construction works are carried out in accordance with
current regulations, including content on compliance with regulations of QCVN 09:2013/BXD for works under QCVN
4.1. Department of Science, Technology and Environment (Ministry of Construction) is responsible for organizing the
4.2. The state management agencies in charge of construction in the localities are responsible for organizing the
inspection of compliance with the provisions of QCVN 09:2013/BXD in the design and construction of works in their localities
4.3. During the implementation of this Regulation, if there are any problems, all comments should be sent to the
Department of Science, Technology and Environment (Ministry of Construction) for guidance and handling.
40
Machine Translated by Google
QCVN 09:2013/BXD
APPENDIX
(Refer)
PHYSICAL SPECIFICATIONS OF MATERIAL, STRUCTURE
1. Formula for determining thermistor and total heat transfer coefficient (U-value) of KCBC
n
bi
, 2 m .K/W
first
R o+1+= + h CHEAP
a
(first)
WOMEN first i
H BILLION
In there:
, hT - is the heat transfer coefficient of the outer and inner surfaces of the enclosure, respectively.
hN W/m2 .K ;
, W/m2 .K
first
U=
o
(2)
CHEAP
o
In there:
41
Machine Translated by Google
QCVN 09:2013/BXD
I. Asbestos materials
Concrete broken stone and crushed stone 2200 1.28 1.21 0.05
42
Machine Translated by Google
QCVN 09:2013/BXD
Table 1. (Continued)
43
Machine Translated by Google
QCVN 09:2013/BXD
Table 1. (Continued)
300 0.10 - -
400 0.12 - -
700 0.18 - -
800 0.20 - -
44
Machine Translated by Google
QCVN 09:2013/BXD
Table 1. (Continued)
Lime mortar plastered the outside of the wooden slats 1400 0.70 1.05 0.12
Lime mortar plastered in the wooden slats 1400 0.52 1.05 0.12
Lime mortar mixed with ore slag 1200 0.47 0.80 0.14
45
Machine Translated by Google
QCVN 09:2013/BXD
Table 1. (Continued)
XI. Metal
forty six
Machine Translated by Google
QCVN 09:2013/BXD
Table 1. (Continued)
Note:
1. Materials
first
White paper 0.20
4 slag 0.81
2. Wall face
47
Machine Translated by Google
QCVN 09:2013/BXD
Table 2. (Continued)
27 Wood 0.59
thirty first
Ordinary bamboo 0.60
48
Machine Translated by Google
QCVN 09:2013/BXD
Table 2. (Continued)
3. Roof face
forty six
Gray cement tile 0.65
49
Machine Translated by Google
QCVN 09:2013/BXD
Table 2. (Continued)
4. Painted surface
sixty one
Slag concrete 0.89
6. Translucent Materials
seventy three
1.2 mm . thick colorless organic glass 0.123
50
Machine Translated by Google
QCVN 09:2013/BXD
51
Machine Translated by Google
QCVN 09:2013/BXD
3. Some common exterior wall and roof structures and total heat resistance Ro is calculated
according to formula (1)
3.1. WALL
T1. Single wall (conventional thickness: 110 mm) baked clay solid brick
- Tipping plate = 15 mm
- Bricks ®Ets fired =105 mm
- Tipping plate = 15 mm
15 105 15
52
Machine Translated by Google
QCVN 09:2013/BXD
T2. Double wall (conventional thickness: 220 mm) baked clay solid brick
- Tipping plate = 15 mm
- Brick ®Et fired clay =105 mm
- Width of the spool = 10 mm
- Brick ®Et fired clay =105 mm
- Tipping plate = 15 mm
10
60
15 105 10105 15
Coefficient of Total
Layers of materials Meet or not meet the
STT thermal conductivity , thermistor
from the outside to the inside Thickness, m requirements compared to the standard
W/(mK) Ro, m2 .K/W
T3. Single wall (conventional thickness:110 mm) baked clay hollow brick
- Sprocket wheel = 15 mm
- Gch rçng =105 mm
- Tipping plate = 15 mm
15 105 15
53
Machine Translated by Google
QCVN 09:2013/BXD
T4. Calculation of double wall heat resistance (conventional thickness: 220 mm) fired clay hollow bricks
- Tipping plate = 15 mm
- Gg rçng =105 mm
- Width of the spool = 10 mm
- Gg rçng =105 mm
10
60
- Tipping plate = 15 mm
15 10510105 15
Total
Thermal
Layers of materials heat resistance Meet or not meet the
STT
from the outside to the inside Thickness, m Ro, requirements compared to the standard
conductivity, , W/(mK)
m2 .K/W
Ro>0.56 m2 .K/W
Hollow brick (ÿ = 1300) built with
light mortar (ÿ = 1400) 0.58 0.584 Qualified
2 or 0.220 or or or
Multi-hole bricks built with heavy 0.52 0.625 Pass and pass
54
Machine Translated by Google
QCVN 09:2013/BXD
T5. Brick wall, foam concrete block, single wall (conventional thickness: 110 mm)
- Tipping plate = 15 mm
- Blemishes are small =105 mm
- Tipping plate = 15 mm
15 105 15
Ro<0.56 m2 .K/W
2 Blocks of foam concrete 0.105 0.37 0.486
Unsatisfactory!
T6. Brick wall, foam concrete block, double wall (conventional thickness: 220 mm)
- Tipping plate = 15 mm
- Blec t<ng =105 mm
- Width of the spool = 10 mm
- Blemishes are small =105 mm
10
60
- Tipping plate = 15 mm
15 10510105 15
55
Machine Translated by Google
QCVN 09:2013/BXD
- Tipping plate = 15 mm
- Cement plate cutting = 50 mm
- Add polystyrol = 20 - 50 mm
- Cement plate cutting = 50 mm
- Tipping plate = 15 mm
15 502050 15
Coefficient
of
Layers of materials from the Thickness, Total Meet or not meet the
STT
outside to the inside m thermal conductivity , thermistor requirements compared to the standard
Note: The total heat resistance of the outer wall is calculated with the outer surface heat transfer coefficient hN= 25 W/ m2 .K and
the inner surface heat exchange coefficient hT= 7.692 W/ m2 .K – see table 3, Appendix.
56
Machine Translated by Google
QCVN 09:2013/BXD
3.2. ROOF
Ro < 1.0 m2 .K / W
2.
5 Pore air Ra = 0.22 m K/W 0.053 0.640
Unsatisfactory
57
Machine Translated by Google
QCVN 09:2013/BXD
M2. Roof structure with insulation layer of 105 mm thick hollow brick and slag concrete ÿ=1000 kg/
m3 thickness 150 mm Constructed like the M1 roof, but above the heat-resistant brick layer, there is an
additional layer of lightweight concrete - slag concrete ÿ =1000 kg/m3 - ÿ=0.41 W/(mK) 150 mm thick,
then the total heat resistance of M2 roof will be Ro=1,006 m2 .K/W – satisfactory.
first
Nem leaf brick 0.015 0.81
58
Machine Translated by Google
QCVN 09:2013/BXD
Conductivity
Note: The total heat resistance of the roof is calculated with the outside surface heat exchange coefficient hN= 25 W/ m2 .K and the system
the inner surface heat exchanger is hT= 5,882 W/ m2 .K – see table 3, Appendix.
59
Machine Translated by Google
QCVN 09:2013/BXD
TABLE OF CONTENTS
APPENDIX (Reference) Physical parameters of the material, construction and calculation of the thermal
1. The formula for determining the thermal resistance and total heat transfer coefficient (U-value) of KCBC.
3 Some common exterior wall and roof structures and total heat resistance Ro can be
60