SERVICES : PREVENTIVE MAINTENANCE AND SERVICES AIRCONDITIONING MECHANICAL VENTILATION SYSTEM [NON-COMPREHENSIVE PACKAGE].

SCOPE OF SERVICES

No Equipment / Services Location Description Service Frequency Quantity

1 Air Cooled Split Unit Level 1, 2, 2A, 3, 6 & 7A Monthly Heat Exchanger Pump (HEX) Chilled Water Pump.
Inspect and clean the air filters. (24 months) 1) Hex-1 - 3 nos. 1) Chilled Water Pump capacity 70, model EHS 125-365 - 1 nos.
(375 RT x 3 nos, Total flow rate 169.20) 2) Chilled Water Pump capacity 70, model EHS 125-366 - 1 nos.
Inspect and clean the cooling coil when necessary. 3) Chilled Water Pump capacity 70, model EHS 125-367 - 1 nos.
Check compressor and refrigerant curcuit for proper operation tempreture Air Handling Unit (AHU).
conditiond. 1) AHU-HL1-3a, model YSM1-40x70 - 1 nos. Air Cooled Split Unit.
2) AHU-HL1-3b, model YSM1-50x70 - 1 nos. 1) Fire Control Room, capacity 28,000btu/hr/each - 2 nos.
Check refrigerant pressure once every three months. 3) AHU-HL1-4, model YSM1-40x80 - 1 nos. 2) SDF Room, capacity 18,000btu/hr/each - 2 nos.
4) AHU-HL2-7a, model YSM1-50x80 - 1 nos. 3) Police Office, capacity 22,000btu/hr/each - 2 nos.
Check crankcase heater where applicable. 5) AHU-HL2-7b, model YSM1-40x80 - 1 nos. 4) Telco Room, capacity 20,000btu/hr/each - 2 nos.
6) AHU-HL2-8, model YDM3-70x110 - 1 nos. 5) CCTV Room, capacity 14,000btu/hr/each - 2 nos.
Inspect unit controls. 7) AHU-HL3-14, model YSM1-30x50 - 1 nos. 6) Driver Room, capacity 20,000btu/hr/each - 2 nos.
Check compressor oil level where applicable. 8) AHU-HL3-15, model YSM1-50x80 - 1 nos. 7) Police Office, capacity 28,000btu/hr/each - 2 nos.
Check unloading mechanism where applicable. 9) AHU-HL4-21a, model YSM1-50x70 - 1 nos. 8) Management Office, capacity 40,000btu/hr/each - 2 nos.
10) AHU-HL4-21b, model YSM1-50x80 - 1 nos. 9) DCS Control Room, capacity 14,000btu/hr/each - 2 nos.
Visual check on condenser coils and cleans up when necesssary. 11) AHU-HL4-22, model YSM1-70x80 - 1 nos. 10) Surau (F), capacity 22,000btu/hr/each - 1 nos.
12) AHU-HL5-28a, model YSM1-50x80 - 1 nos. 11) Surau (M), capacity 28,000btu/hr/each - 1 nos.
Check thermostat setting. 13) AHU-HL5-28b, model YSM1-50x80 - 1 nos. 12) Dock loading bay, capacity 14,000btu/hr/each - 1 nos.
14) AHU-HL5-29, model YSM1-50x80 - 1 nos. 13) TOS Booth, capacity 14,000btu/hr/each - 1 nos.
Inspect control switchboard.
14) Ferry linkway entrance, ceiling casset unit - 3 nos.
2 Air Curtain Level 1, 2 & 3. Inspect control switch component. Monthly
Fan Coil Unit (FCU). 15) KTM linkway, ceiling casset - 15 nos
(24 months)
1) FCU HL2-7a-1, model YDFC 20 ST CB 4 - 1 nos.
To check the float valves operation.
2) FCU HL2-7a-8(F&B), model YCF 46-6 - 1 nos. Variace Refrigerant Flow (VRF) - Indoor
3 Chilled Water Fan Coil Unit. Retail shop lot llevel 1, 2, 3, & 4. Check and clean filters. Monthly 3) FCU HL2-7a-Taxi 1a&1b, model YCK 50 - 2 nos. MCC
(FCU). (24 months) 4) FCU HL2-7b-2, model YGFC 12 - 1 nos. 1) FCU-MCC, model S-280ME1E5 95,500btu/hr - 10 nos.
Check fan belt tension and adjust if necessary.
5) FCU HL2-7b-3, model YDFC 20 ST CB 3 - 2 nos. 2) FCU-MCC, model S-224ME1E5 76,400btu/hr - 4 nos.
Inspect fan motor. 6) FCU HL2-7b-7a&7b(F&B), model YCF 62-6 - 2 nos. HT Room
7) FCU HL2-7b-VIP(F&B), model YCF 46-6 - 1 nos. 1) FCU-HT, model S-224ME1E5 76,400btu/hr - 4 nos.
Check fan shaft bearings and motor bearings, lubricate when necessary. 8) FCU HL2-8-4(F&B), model YCF 30-6 - 1 nos. TX
9) FCU HL2-8-5(F&B), model YCF 46-6 - 1 nos. 1) FCU-TX, model S-280ME1E5 95,500btu/hr - 8 nos.
Check and clean the cooling coil and drain pan when necessary. 10) FCU HL2-8-6, model YDFC 18 ST CB 4 - 1nos. 2) FCU-TX, model S-73MF2E5A 25,000btu/hr - 1 nos.
11) FCU HL3-14-1(F&B), model YCF 62-6 - 1 nos. 3) FCU-TX model S-73MF2E5A - 1 nos.
Purge air trapped in cooling coil when necessary. 12) FCU HL3-14-16(F&B), model YCF 62-6 - 1 nos.
13) FCU HL3-14-2, model YDFC 29 ST CB 3 - 3 nos. Variance Refrigerant Flow (VRF) - Outdoor.
Check the operation of chilled water control valves and thermostat control. 14) FCU HL3-14-3, model YDFC 18 ST CB 4 - 3 nos. MCC
15) FCU HL3-14-4(F&B), model YCF 46-6 - 1n nos. 1) CU-MCC, model U-72ME2H7SP 614,300btu/hr - 2 nos.
4 Air Handling Unit (AHU) Level 1, 2, 3 & 4. Check and clean filters. Monthly 16) FCU HL3-15-7, model YDFC 14 ST CB 4 - 2 nos. HT Room
(24 months) 17) FCU HL3-15-8, model YDFC 14 ST CB 4 - 2 nos. 1) CU-FCU, model U-18ME2H7 153,600 - 2 nos.
Check fan belt tension and adjust if necessary.
18) FCU HL3-15-9, model YDFC 14 ST CB 4 - 2 nos. TX
Inspect fan motor. 19) FCY HL3-15-10, model YDFC 14 ST CB 4 - 2 nos. 1) CU-TX, model U-42ME2H7 402,700 - 2 nos.
20) FCU HL3-15-11, model YDFC 20 ST CB 4 - 1 nos.
Check fan shaft bearings and motor bearings, lubricate when necessary. 21) FCU HL3-15-12(F&B), model YCF 46-6 - 1 nos. Smoke Spill System.
22) FCU HL3-15-13(F&B), model YCF 46-6 - 1 nos. 1) SEF, model AXC 1250-12/14o-4(B) smoke spill axial 1250mm - 6 nos.
Check and clean the cooling coil when necessary. 23) FCU HL3-15-14(F&B), model YCF 36-6 - 1 nos. 2) SEF , model AXC 1250-12/25o-4(B) G smoke spill axial 1250mm - 1 nos.
24) FCU HL3-15-15(F&B), model YDFC 18 ST CB 3 - 2 nos. 3) SEF, model AXC 1250 12/26o-4(B) smoke spill axial 1250mm - 3 nos.
Check the operation of chilled water control valves and thermostat control. 25) FCU HL3-15-5(F&B), model DB 16-6 - 1 nos
26) FCU HL3-15-6(F&B), model YCF 46-6 - 1 nos. Pressurisation Fan
5 Chilled Water Pump Unit. Hex Pump Level 7 Lubricate pumps and motor when necessary. 27) FCU HL3-Food Court, model YCF 100-6 - 1 nos. 1) LPF, model AXC9A) 1250-12/18o-4(B)GV vane axial 1250mm - 1 nos.
28) FCU HL4-21a-1, model YDFC 18 ST CB 4 - 2 nos.
Check pumps mechanical seal and and tighten when necessary. 29) FCU HL4-21a-2a&2b, model YCF 100-6 - 2 nos. Kitchen Exhaust and fresh air System
30) FCU HL4-21a-3, model YDFC 14 ST CB 4 - 2 nos. 1) KEF, model AW60 DWDI cabinet centrifugal 609mm - 2 nos
Check water strainers and clean them when necessary.
31) FCU HL4-21a-Nursery, model YDFC 20 ST CB 4 - 1 nos. 2) KEF, model AW65 DWDI cabinet centrifugal 675mm - 4 nos.
Check pressure gauges and valves. 32) FCU HL4-21b-18(F&B), model YCF 46-6 - 1 nos. 3) KEF, model AW75 DWDI cabinet centrifugal 742mm - 1 nos.
Check for undue noise and vibration. 33) FCU HL4-21b-19(F&B), model YCF 100-6 - 1 nos. 4) KFAF, model AW55 DWDI cabinet centrifugal 550mm - 2 nos.
34) FCU HL4-21b-20(F&B), model YCF 100-6 - 1 nos. 5) KFAF, model AW60 DWDI cabinet centrifugal 609mm - 3 nos.
Check motor for undue tempreture rise.
35) FCU HL4-21b-4, model YGCF 10 - 1 nos. 6) KFAF, model AW65 DWDI cabinet centrifugal 675mm - 2 nos.
6 Water Treatment System Hex Pump Level 7 Check selnoid on/off valve is in good condition. Monthly 36) FCU HL4-21b-5(F&B), model YCF 30-6 - 1 nos.
Check pressure sensor is in good condition. (24 months) 37) FCU Hl4-22-8(F&B), model YDFC 14 ST CB 4 - 3 nos. Mechanical Ventilation System
Check wiring amp is in good condition. 38) FCU HL4-22-9(F&B), model YDFC 12 ST CB 4 - 2 nos. 1) EF, model AW sileo 350E4 propeller 350mm - 2 nos.
Application of chemical will be carried out by supplier. 39) FCU HL4-22-10, model YDFC 14 ST CB 4 - 2 nos. 2) EF, model AW sileo 450E4-K propeller 450mm - 2 nos.
40) FCU HL4-22-11, model YGFC 05 - 1 nos. 3) EF, model CDRE 315 cabinet in-line 315mm - 4 nos.
On site water analysis test will be carried out during service call. 41) FCU Hl4-22-12(F&B), model YCF 30-6 - 1 noa. 4) EF, model AXC 630-9/15o-4 axial 630mm - 2 nos.
42) FCU HL4-22-13(F&B), model DB 16-6 - 1 nos. 5) EF, model AXC 630-9/10o-4 axial 630mm - 1 nos.
Check and inspect each system and plant being treated. 43) FCU HL4-22-14(F&B), model YCF 62-6 - 1 nos. 6) EF, model VF-APK10 propeller 250mm - 2 nos.
A complete water analysis report will be sent. 44) FCU HL4-22-15(F&B) - 1 nos. 7) EF, model VF-APK6 propeller 150mm - 1 nos.
45) FCU HL4-22-16(F&B), model YCF 30-6 - 1 nos. 8) EF, model VF-APK12 propeller 300mm - 1 nos.
Check and report any irregularities related to the treatment program. 46) FCU HL4-22-17(F&B), model YCF 46-6 - 1 nos. 9) EF, model AW sileo 300E4 propeller 300mm - 2 nos.
47) FCU HL4-22-6(F&B), model YCF 30-6 - 1 nos. 10) EF, model AW sileo 400E4 propeller 400mm - 1 nos.
7 Heat Exchange Hex Pump Level 7 Check - Performance check for predicting maintenance requirement once Monthly 48) FCU HL4-22-7(F&B), model DB 16-6 - 1 nos.
every 1-2. (24 months) 49) FCU HL4-22-8(F&B), model YCF 46-6 - 1 nos.
Toilet Exhaust Fan
1) EF, model CDRE 450 cabinet in-line 450mm - 1 nos.
Cleaning of heat exchanger depends on water quality as a guideline, 4 Air Curtain 2) EF, model CDRE 400 cabinet in-line 400mm - 11 nos.
years a more accurate indication can obtained by using check. 1) Air curtain - 42 nos. 3) EF, model CDRE 355 cabinet in-line 355mm - 5 nos.

8 Mechanical Ventilation Fan Level 1 to Level 10 Note : Non - Comprehensive


Check for undue noise and vibration.
Check motor for undue tempreture rise.

Check fan shaft bearings and motor bearings, lubricate when necessary. Monthly
(24 months)
Chek fan belt tension and adjust if necessary.
Check thermostat control.
Inspect control switchboard component and cable lug for tightness
\