You are on page 1of 6

Reactor Reactor Capacity T (final), T (intial), Heat Load Cycle

Sr.no. Code MOC (kg) degC degC (kJ) time


1 101 SS-316 8000 12 35 -270059.765 4
2 102 SS-316 6000 12 35 -202544.824 3

3 103 SS-316 6000 12 35 -202544.824 3


4 104 MS-GL 6300 12 35 -212672.065 3.15
5 105 MS-GL 5000 12 35 -168787.353 2.5

6 106 SS-316 4000 12 35 -135029.883 2


7 107 MS-GL 3000 12 35 -101272.412 1.5

8 108 SS-316 2000 12 35 -67514.9413 1


9 109 SS-316 1650 12 35 -55699.8266 0.825

10 110 SS-316 3000 12 35 -101272.412 1.5


11 111 MS-GL 3000 12 35 -101272.412 1.5
12 112 SS-316 4000 12 35 -135029.883 2
13 113 SS-316 5000 12 35 -168787.353 2.5

14 114 MS-GL 5000 12 35 -168787.353 2.5


15 115 SS-316 5000 12 35 -168787.353 2.5
16 116 MS-GL 3000 12 35 -101272.412 1.5
17 201 SS-316 8000 12 35 -270059.765 4
18 202 SS-316 8000 12 35 -270059.765 4
19 203 SS-316 8000 12 35 -270059.765 4
20 204 SS-316 5000 12 35 -168787.353 2.5
21 205 MS-GL 4000 12 35 -135029.883 2
22 206 SS-316 5000 12 35 -168787.353 2.5
23 207 SS-316 2500 12 35 -84393.6766 1.25
24 301 SS-316 1000 12 35 -33757.4706 0.5
25 302 MS-GL 1000 12 35 -33757.4706 0.5
26 303 SS-316 2000 12 35 -67514.9413 1
27 304 SS-316 4000 12 35 -135029.883 2
28 305 SS-316 5000 12 35 -168787.353 2.5
29 306 SS-316 6000 12 35 -202544.824 3
30 307 SS-316 2000 12 35 -67514.9413 1
31 308 SS-316 2000 12 35 -67514.9413 1
32 401 SS-316 6000 12 35 -202544.824 3
33 402 SS-316 6000 12 35 -202544.824 3
Solvent
Block A Block B Block C Recov
dH for water 20.92 20.92 20.92 20.92 kJ/kg

Total water required


at full load 112874.5 65352.66 37113.85 0 kg

Diversity 0.33 0.33 0.33 0.65


Actual water
consumption 37248.59 21566.38 12247.57 0

Actual water
consumption per
hour 17040.1 7455.044 8520.05 0 kg/hr

Actual water
consumption per
hour 17.04 7.46 8.52 0.00 m3/hr

Average cycle time 2.19 2.89 1.44 3.00 hrs

Cooling tower
capacity 28.16 12.32 14.08 0.00 TR

Total 54.55

Available 75
Efficiency 0.8
Component Cp (J/molK) dH vap (kJ/mol) mol wt Cp (kJ/kg/K) dH vap (kJ/kg)
Toluene 157 38 92.141 1.704 412.41
Acetic acid 39.1 60.052 2.043 651.10

MDC 84.93 1.188 330.40


Ethyl acetate 31.94 88.106 1.904 362.52
Water 4.182 2260

1.957 621.20
Reactor Reactor Capacity T (final), T (intial), Heat Load Cycle
Sr.no. Code MOC (kg) degC degC (kJ) time
1 101 SS-316 8000 12 35 -270059.765 4
2 102 SS-316 6000 12 35 -202544.824 3

3 103 SS-316 6000 12 35 -202544.824 3


4 104 MS-GL 6300 12 35 -212672.065 3.15
5 105 MS-GL 5000 12 35 -168787.353 2.5

6 106 SS-316 4000 12 35 -135029.883 2


7 107 MS-GL 3000 12 35 -101272.412 1.5

8 108 SS-316 2000 12 35 -67514.9413 1


9 109 SS-316 1650 12 35 -55699.8266 0.825

10 110 SS-316 3000 12 35 -101272.412 1.5


11 111 MS-GL 3000 12 35 -101272.412 1.5
12 112 SS-316 4000 12 35 -135029.883 2
13 113 SS-316 5000 12 35 -168787.353 2.5

14 114 MS-GL 5000 12 35 -168787.353 2.5


15 115 SS-316 5000 12 35 -168787.353 2.5
16 116 MS-GL 3000 12 35 -101272.412 1.5
17 201 SS-316 8000 12 35 -270059.765 4
18 202 SS-316 8000 12 35 -270059.765 4
19 203 SS-316 8000 12 35 -270059.765 4
20 204 SS-316 5000 12 35 -168787.353 2.5
21 205 MS-GL 4000 12 35 -135029.883 2
22 206 SS-316 5000 12 35 -168787.353 2.5
23 207 SS-316 2500 12 35 -84393.6766 1.25
24 301 SS-316 1000 12 35 -33757.4706 0.5
25 302 MS-GL 1000 12 35 -33757.4706 0.5
26 303 SS-316 2000 12 35 -67514.9413 1
27 304 SS-316 4000 12 35 -135029.883 2
28 305 SS-316 5000 12 35 -168787.353 2.5
29 306 SS-316 6000 12 35 -202544.824 3
30 307 SS-316 2000 12 35 -67514.9413 1
31 308 SS-316 2000 12 35 -67514.9413 1
32 401 SS-316 6000 12 35 -202544.824 3
33 402 SS-316 6000 12 35 -202544.824 3
Solvent
Block A Block B Block C Recov
dH for water 20.92 20.92 20.92 20.92 kJ/kg

Total water required


at full load 516647.8 299131.3 299131.3 0 kg

Diversity 0.3 0.3 0.3 0.65


Actual water
consumption 154994.3 89739.39 89739.39 0

Actual water
consumption per
hour 17726.3 7755.256 10404.57 0 kg/hr

Actual water
consumption per
hour 17.73 7.76 10.40 0.00 m3/hr

Average cycle time 8.74 11.57 8.63 3.00 hrs

Chilling tower
capacity 29.29 12.81 17.19 0.00 TR

Total 59.30 TR

Available 75
Efficiency 0.8
Component Cp (J/molK) dH vap (kJ/mol) mol wt Cp (kJ/kg/K) dH vap (kJ/kg)
Toluene 157 38 92.141 1.704 412.41
Acetic acid 39.1 60.052 2.043 651.10

MDC 84.93 1.188 330.40


Ethyl acetate 31.94 88.106 1.904 362.52
Water 4.182 2260

1.957 621.20

You might also like