You are on page 1of 6

© Siemens 2021

Level measurement
Point level measurement
RF Capacitance switches
Pointek CLS100

■ Overview ■ Configuration
Installation

Standpipes

20 (0.79) max.
≥ 50 (2)

4
Wall restriction
Pointek CLS100 is a compact, 2-wire, inverse frequency shift ca-
pacitance switch for level and material detection in constricted
spaces, interfaces, solids, liquids, slurries, and foam; with the
ability to tune out buildup on probe.

■ Benefits
50 (2)
• Easy installation with verification by built-in LED min.
• Low maintenance with no moving parts
• Sensitivity adjustment
• Integrated cable or PBT enclosure versions available
• Intrinsically Safe, Dust Ignition Proof, and General Purpose 50 (2)
options available

■ Application
Pointek CLS100’s short insertion length of 100 mm (4 inch) and Pointek CLS100 installation, dimensions in mm (inch)
versatility in various applications and in vessels or pipes makes
it a good replacement for traditional capacitance sensors.
Its advanced tip-sensing technology provides accurate, repeat-
able switchpoint performance. The PPS (Polyphenylene sulfide)
probe [optional PVDF (Polyvinylidene Fluoride)] is chemically re-
sistant with an effective process operating temperature range
from -30 to +100 °C (-22 to +212 °F) (7ML5501), and
-10 to +100 °C (14 to 212 °F) (7ML5610). The fully potted de-
sign ensures reliability in a vibrating environment such as agi-
tated tanks up to 4 g. When used with a SensGuard protection
cover, the CLS100 is protected from shearing, impact, and abra-
sion in tough primary processes.
The Pointek CLS100 is available in three versions. The integral
cable version has a stainless steel process connection and
probe options of PPS or PVDF. The fully synthetic version has a
thermoplastic polyester enclosure with a PPS process connec-
tion combined with a PPS probe. The standard enclosure version
has a thermoplastic polyester enclosure with a stainless steel
process connection in combination with a PPS or PVDF probe.
• Key Applications: liquids, slurries, powders, granules, food
and pharmaceuticals, chemicals, hazardous areas

Siemens FI 01 · 2021 US Edition 4/11


© Siemens 2021

Level measurement
Point level measurement
RF Capacitance switches
Pointek CLS100

■ Technical specifications
Stainless steel process Fully synthetic process Stainless steel process Fully synthetic process
connection connection connection connection
(integral cable or (enclosure version (integral cable or (enclosure version
enclosure version) only) (7ML5610) enclosure version) only) (7ML5610)
(7ML5501) (7ML5501)
Mode of operation Sensor length (nominal) 100 mm (4 inch) 100 mm (4 inch)
Measuring principle Inverse frequency shift Inverse frequency shift Process connection Connection: 316L PPS process connection
capacitive level capacitive level material of probe/wetted stainless steel; and PPS sensor
detection detection parts 3) Process seal: FKM (Uni-Construction)
(optional FFKM);
Input Sensor: PPS
Measured variable Change in picoFarad Change in picoFarad (optional PVDF)4)
(pF) (pF) Connection (Enclosure Internal 5-point terminal Removable internal
Output version) block, 5-point terminal block,
½" NPT wiring entrance, ½" NPT wiring entrance,
Output signal M20 x 1.5 optional M20 x 1.5 optional
• Alarm output 4 ... 20/20 ... 4 mA 4 ... 20/20 ... 4 mA
Connection 4 conductors, 1 m Not applicable
2-wire loop 2-wire loop
4 • Switch output1) Solid-state: 30 V DC/30
V AC, max. 82 mA
Max. switching voltage:
60 V DC/30 V AC
(Integral cable version) (3.3 ft), 0.5 mm²
(22 AWG), shielded,
polyester jacket
Max. switching current:
1A Process connection ¾" NPT [(Taper), ¾" NPT [(Taper),
• Fail-safe mode Min. or max. Min. or max. ANSI/ASME B1.20.1] ANSI/ASME B1.20.1]
R 1" [(BSPT), R 1" [(BSPT),
Accuracy EN 10226/PT (JIS-T), EN 10226/PT (JIS-T),
JIS B 0203] JIS B 0203]
Repeatability 2 mm (0.08 inch) 2 mm (0.08 inch)
G 1" [(BSPP),
Rated operating EN ISO 228-1/PF (JIS-P),
conditions2) JIS B 0202]
Installation conditions Power supply
• Location Indoor/outdoor Indoor/outdoor Standard 12 ... 33 V DC 12 ... 33 V DC
Ambient conditions Intrinsically Safe 10 ... 30 V DC Not applicable
• Ambient temperature -30 ... +85 °C -10 ... +85 °C (Intrinsically Safe barrier
(-22 ... +185 °F) (14 ... 185 °F) required)
• Storage temperature -40 ... +85 °C -40 ... +85 °C Certificates and • General: CE, CSA, FM, • General: CSA, FM
(-40 ... +185 °F) (-40 ... +185 °F) approvals RCM
• Installation category I I
• Marine: Lloyds
• Pollution degree 4 4 Register of Shipping,
Medium conditions categories ENV1,
• Relative dielectric Min. 1.5 Min. 1.5 ENV2, and ENV5
constant εr Dust Ignition Proof
(barrier required):
• Process temperature -30 ... +100 °C -10 ... +100 °C CSA/FM Class II and III,
(-22 ... +212 °F) (14 ... 212 °F) Div. 1, Groups E, F, G
• Pressure (vessel) -1 ... +10 bar g -1 ... +10 bar g T4
(-14.6 ... +146 psi g), (-14.6 ... +146 psi g),
• Intrinsically Safe
nominal2) nominal
(barrier required):
• Degree of protection CSA/FM Class I, II, and
- Enclosure version IP68/Type 4/NEMA 4 IP68/Type 4/NEMA 4 III, Div. 1, Groups A, B,
- Integral cable version IP65/Type 4/NEMA 4 Not applicable C, D, E, F, G T4
• Cable inlet ½" NPT (M20 x 1.5 ½" NPT (M20 x 1.5 ATEX II 1 GD 1/2GD
optional) optional) EEx ia IIC T4 to T6
T107 °C
Design • Overfill protection:
Enclosure/Integral cable Fully synthetic version WHG (Germany)
version 1) When synthetic process connection version (7ML5610) is used in wet
Material locations, switching voltage of the relay is limited to 35 V DC/16 V AC.
• Body Thermoplastic polyester Thermoplastic polyester 2)
When operation is in areas classified as hazardous, observe restrictions
(Enclosure version) according to relevant certificate.
• Lid (Enclosure version) Transparent thermoplas- Transparent thermoplas- See also Pressure/Temperature curves on page 5/13.
tic polycarbonate (PC) tic polycarbonate (PC) 3) For caustic materials, consult a local sales person for alternative O-rings.
• Integrated cable body 316L stainless steel Not applicable For more information, please visit
(Integral cable version) http://www.usa.siemens.com/level.
4) When FFKM O-ring (Option A22) is selected, process temperature is
restricted to -20 °C (-4 °F).

4/12 Siemens FI 01 · 2021 US Edition


© Siemens 2021

Level measurement
Point level measurement
RF Capacitance switches
Pointek CLS100

■ Selection and ordering data Article No. Article No.

Pointek CLS100 RF Capacitance point level 7ML5501- Pointek CLS100 RF Capacitance point level 7ML5610-
switch, stainless steel process connection switch, PPS process connection
0 7777 0 7777
Detects level and interface in liquids, solids, slurries Detects level and interface in liquids, solids, slurries,
and foam. Compact, with 100 mm (4 inch) insertion, and foam. Compact, with 100 mm (4 inch) insertion,
adaptable sensitivity, with the ability to tune out adaptable sensitivity, with the ability to tune out
build-up on probe. build-up on probe.
Click on the Article No. for the online Click on the Article No. for the online
configuration in the PIA Life Cycle Portal. configuration in the PIA Life Cycle Portal.
Process Connection Process connection (PPS)
¾" NPT [(Taper), ANSI/ASME B1.20.1] A ¾" NPT [(Taper), ANSI/ASME B1.20.1] A
R 1" [(BSPT), EN 10226/PT (JIS-T), JIS B 0203] E (PPS probe body)
G 1" [(BSPP), EN ISO 228-1/PF (JIS-P), JIS B 0202] J R 1" [(BSPT), EN 10226/PT (JIS-T), JIS B 0203] B
(PPS probe body)
Approvals
General Purpose: CE, CSA, FM, RCM A Approvals
CSA/FM Class I, II, and III, Div. 1, C General Purpose: CSA, FM D
Groups A, B, C, D, E, F, G T4; ATEX II 1 GD ½ Versions/Options
GD EEx ia IIC T4 ... T6 T107 °C1)
CSA/FM Class II and III, Div. 1, Groups E, F, G1) G
Enclosure version, PPS process connection,
½" NPT cable inlet
1
4
Device version Enclosure version, PPS process connection, 2
Integral cable version (PPS probe) 1 M20 x 1.5
Enclosure version (PPS probe), ½" NPT cable inlet 3 Overfill protection
Integral cable version with PVDF probe body 5 Not required 0
Enclosure version with PVDF probe body 6 Required 1
(½" NPT cable inlet)
Enclosure version (PPS probe), M20 x 1.5 7 Further designs Order code
cable inlet
Enclosure version with PVDF probe body, 8 Please add "-Z" to Article No.
M20 x 1.5 cable inlet and specify Order code(s).

Overfill protection Stainless steel tag [70 x 13 mm (2.75 x 0.5 inch)]: Y17
Not required 0 Measuring-point number/identification
(max. 20 characters) specify in plain text
Required (WHG) 1
Material inspection Certificate Type 3.1 per C12
1) Barrier or Intrinsically Safe power supply required for Intrinsically EN 10204
Safe protection.
Operating Instructions
Further designs Order code Note: due to ATEX regulations one Quick start
Please add "-Z" to Article No. manual is included with every product. All literature
and specify Order code(s). is available to download for free, in a range of
languages, at
Stainless steel tag [70 x 13 mm (2.75 x 0.5 inch)]: Y17
Measuring-point number/identification http://www.siemens.com/processinstrumentation/documentation
(max. 20 characters) specify in plain text
Accessories Article No.
FFKM seal O-ring1) A22
SensGuard, ¾" NPT (PPS). 7ML1830-1DL
Material inspection Certificate Type 3.1 per C12 Only available for CLS100 with ¾" NPT thread.
EN 10204
INMETRO2) SensGuard, R 1" (BSPT) (PPS). 7ML1830-1DM
E34 Only available for CLS100 with ¾" NPT thread.
Operating Instructions Tag, stainless steel, 12 x 45 mm, (0.47 x 1.77 inch) 7ML1930-1AC
Note: due to ATEX regulations one Quick start one text line, suitable for enclosures
manual is included with every product. All literature 1) See Temperature restriction on page 4/14.
is available to download for free, in a range of
languages, at
http://www.siemens.com/processinstrumentation/documentation
1) See Temperature restriction on page 4/14.
2) Available only with Approvals option C.

Accessories Article No.


SensGuard, ¾" NPT (PPS). 7ML1830-1DL
Only available for CLS100 with ¾" NPT thread.
SensGuard, R 1" (BSPT) (PPS). 7ML1830-1DM
Only available for CLS100 with ¾" NPT thread.
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77 inch), 7ML1930-1AC
one text line, suitable for enclosures
Siemens Intrinsically Safe Barrier (DC powered), 7NG4124-0AA00
ATEX II 1 G EEx ia
½" NPT General Purpose Cable Entry IP68/IP69K 7ML1830-1JA
NEMA 6, -40 ... +80 °C (-40 ... +176 °F),
Dust Ignition Proof, cable size 6 ... 12 mm
(0.236 ... 0.472 inch)
M20 x 1.5 General Purpose Cable Entry IP68/IP69K 7ML1830-1JC
NEMA 6, -40 ... +80 °C (-40 ... +176 °F),
Dust Ignition Proof, cable size 7 ... 12 mm
(0.275 ... 0.472 inch)

Siemens FI 01 · 2021 US Edition 4/13


© Siemens 2021

Level measurement
Point level measurement
RF Capacitance switches
Pointek CLS100

■ Options
Optional SensGuard
Internal thread ¾" NPT
(1.26)

(1.26)
Process
32

32

Process connection
connection R 1" (BSPT)
¾" NPT
91 (3.6)

91 (3.6)
70 (2.75)

70 (2.75)

4 Optional SensGuard, dimensions in mm (inch)


1151-1153

4/14 Siemens FI 01 · 2021 US Edition


© Siemens 2021

Level measurement
Point level measurement
RF Capacitance switches
Pointek CLS100

■ Characteristic curves
Pressure/temperature curve CLS100
Threaded process connections (7ML5501)

Permitted operating pressures P

30 bar (435 psi)

20 bar (290 psi)

10 bar (145 psi)


Atmospheric
-22 ºF 14 ºF 100 ºF 200 ºF 300 ºF 400 ºF

-1 bar (-14.5 psi)


(-30 ºC) (-10 ºC) (38 ºC) (93 ºC) (149 ºC) (204 ºC) 4
-150 ºC -100 ºC -50 ºC 0 ºC RT 50 ºC 100 ºC 150 ºC 200 ºC
(-238 ºF) (-148 ºF) (-58 ºF) (32 ºF) (122 ºF) (212 ºF) (302 ºF) (392 ºF)
-29 ºC
Permitted operating temperature T
(-20 ºF)

Example:
Permitted operating pressure = 10 bar (145 psi) at 75 °C

Pointek CLS100 process pressure/temperature derating curves

■ Dimensional drawings
Integral cable version Enclosure version 80 (3.2)

Ground post Power LED (green) Cable inlet ½" NPT


36 (1.4) nominal* (optional M20 x 1.5)
Sensitivity trimpot
65 (2.6)
Power LED (green) 1
2

Cable relief 3
4

Sensor status
5

Output status LED (yellow)


Sensitivity trimpot LED (red) Terminal block
Cable Ø 5 (0.2) Sensor status Output status Ground lug
Trimpot cap LED (yellow) LED (red)
72.5 (2.9)
(2.0)
50

Process connection
Process connection
204 (8.0)
120 (4.7)

120 (4.7)
98 (3.9)
nominal

nominal
98 (3.9)

*Some G thread configurations deviate from this size.

Pointek CLS100, dimensions in mm (inch)

Siemens FI 01 · 2021 US Edition 4/15


© Siemens 2021

Level measurement
Point level measurement
RF Capacitance switches
Pointek CLS100

■ Circuit diagrams
Integral Cable Version - Non Intrinsically Safe only

LOW/HIGH Alarm
White Polarity as required
White
for
desired operation
Black

Red 12 ... 33 V DC

4/20 mA Loop Alarm


White

White

Black

Red
Rmax = Vsupply - 10 V
20 mA
V supply
12 ... 33 V DC

4 Solid State Switch Version


White
Solid state switch,
30 V DC/AC
White
(peak) 82 mA (max)
Black

Red V supply
12 ... 33 V DC

Enclosure and Fully Synthetic Version


Terminal operations Cable equivalent
mA current loop (+V or -V) Red wire
mA current loop (+V or -V) Black wire
ground Cable shield
Solid state switch/relay* White wire
Solid state switch/relay* White wire

* Switch/relay normally open in unpowered state


* Relay not available on Pointek CLS100 IS version (7ML5501)
Note:
When driving an inductive load (for example, an external relay), a protection diode
must be connected in the correct polarity to prevent possible switch damage due to
inductive spikes generated by switching the inductor (please refer to instruction
manual). Intrinsically Safe Models - please follow local regulations and area
classifications; refer to instruction manual for more details.

Pointek CLS100 connections

4/16 Siemens FI 01 · 2021 US Edition

You might also like