You are on page 1of 16

Interface Description COM/TTX300/HART-EN Rev.

TTF300, TTH300
Temperature transmitter

HART protocol

Measurement made easy


Short product description
These instructions describe the communication-specific
properties of the TTX300-HART transmitter.

Further information
Additional documentation on TTF300, TTH300 is available to
download free of charge at www.abb.com/temperature.
Alternatively, scan this code:

TTF300 TTH300

Manufacturer
ABB Automation Products GmbH
Process Automation
Schillerstr. 72
32425 Minden
Germany
Tel: +49 571 830-0
Fax: +49 571 830-1806

Customer service center


Tel.: +49 180 5 222 580
Email: automation.service@de.abb.com

Change from one to two columns

2 COM/TTX300/HART-EN Rev. A | TTX300


Contents
1 Introduction ..................................................................... 4

2 Communication / HART TAG / device addressing......... 4

3 Configuration ................................................................... 4
3.1 Configuration types .............................................. 4
3.1.1 HART communication .......................................... 4
3.1.2 Configuration via the handheld terminal ................ 5
3.1.3 Configuration with Device Type Manager (DTM) ... 5
3.1.4 Configuration via EDD .......................................... 5
3.1.5 Configuration via the LCD indicator with the
operating buttons (optional).................................. 5
3.2 HART variables .................................................... 6

4 Parameter descriptions................................................... 7
4.1 Identify ................................................................. 7
4.2 Temperature measurement .................................. 7
4.3 Current output / mapping of measuring range ...... 9
4.4 Communication / HART ..................................... 10
4.5 Miscellaneous .................................................... 10
4.6 Upgrades for HART protocol rev. 7 and above ... 10

5 Double sensor input functionality / double sensor mode


....................................................................................... 11
5.1 2-HART measurement signals............................ 11
5.2 Redundancy / sensor backup ............................ 11
5.3 Sensor drift monitoring ....................................... 12

6 Sensor error adjustment ............................................... 14

7 D/A analog output balancing (4 mA and 20 mA trim) .. 14

8 Special functions ........................................................... 14


8.1 Output signal simulation ..................................... 14
8.2 Device reset ....................................................... 14
8.3 Factory reset...................................................... 14

TTX300 | COM/TTX300/HART-EN Rev. A 3


1 Introduction 3 Configuration
These instructions describe the communication-specific 3.1 Configuration types
properties of the TTX300-HART transmitter. The transmitter Transmitters can be configured as follows:
supports HART protocol rev. 5, and also HART protocol rev. 7 — Via HART protocol and handheld terminal (e.g. ABB
when using software version 01.03.00 or above. HART rev. 5 DHH800)
is preset using the factory settings and can be upgraded to — Via DTM in FDT frame applications (e.g. ABB DAT200)
HART rev. 7 by miniature switch. — Via EDD in EDD frame applications (e.g. HCF SDC625)
For general information concerning operation, sensor — Via fieldbus (PROFIBUS), if the higher-level remote I/O
configuration, connection or explosion protection, please refer system is HART-enabled (e.g. ABB S800 / S900)
to the operating and commissioning instructions.
For commissioning purposes, you will need a device driver in
EDD (Electronic Device Description) or DTM (Device Type
Manager) format.
You can download the relevant EDD and DTM files from
www.abb.com.
The way in which individual parameters are displayed,
arranged and referred to may vary between different frame
applications.
Fig. 1
1 Transmitter 2 Handheld terminal 3 HART modem
4 FDT / DTM technology 5 Grounding (optional)
6 Power supply unit (process interface)

2 Communication / HART TAG / 1) If required

device addressing
3.1.1 HART communication
For ease of identification, each HART device features a Communication with the transmitter takes place using the
configurable 8-digit HART TAG. All devices are supplied with HART protocol. The communication signal is modulated onto
the HART TAG "TI XXX" as standard. both wires of the signal line in accordance with the HART FSK
When storing HART TAG measuring point tags with more than "Physical Layer" specification, version 8.1 (08/1999). The
8 digits in the device, use the "Message" parameter, which electrical connection is provided at the + and – terminals of
supports up to 32 characters. the transmitter or by the power supply cable that is installed
HART rev. 7 also has a 32-digit HART Long TAG for improved on site. This makes remote configuration possible using a
device identification in large installations. The default HART power supply unit.
Long TAG is the same as the HART TAG when the device is
supplied.
In addition to the HART TAG, each device has a HART
address.
This address is set to zero by default, which means that the
device operates in HART standard communication mode
(point-to-point operation). When an address in the range 1 to
15 is used, the device switches to the HART "Multidrop"
mode. This operating mode enables users to connect up to
15 devices to a power supply unit in parallel.
In multidrop mode, an analog output signal that matches the
process temperature is not available. The output signal in
multidrop mode is a constant 3.6 mA and is used exclusively
for the power supply.
In multidrop mode, sensor or process data information is
available only as a HART signal.

4 COM/TTX300/HART-EN Rev. A | TTX300


3.1.2 Configuration via the handheld terminal 3.1.4 Configuration via EDD
Configuration with the handheld terminal normally takes place Configuration can also be performed within an EDD frame
at the factory before the transmitter is installed in an industrial application that is approved for use with the EDD.
plant.
1. Open the housing of the sensor head measuring inset. 3.1.5 Configuration via the LCD indicator with the
2. Carefully clamp both test tips of the separate operating operating buttons (optional)
control on the contacts in the slots in front of the + and – Configuration can be performed with an LCD using the four
terminals. control buttons on the front. Various submenus are available
3. Ensure that the test terminals are firmly seated. that allow you to change the configuration. For details of how
4. Complete the installation in accordance with Fig. 1. to use the LCD, please refer to the description in the operating
instructions.
NOTE
The test tips are connected without observing polarity. NOTE
Clamp the test tips to the (+) and (-) terminals. The In contrast to configuration based on the DTM or EDD, the
transmitter can also be configured via the HART protocol functionality of the transmitter can only be changed to a
during normal operation. limited extent with the LCD and control buttons.

3.1.3 Configuration with Device Type Manager (DTM)


Configuration can be performed within an FDT frame
application that is approved for use with the DTM. The bus
can be connected via FSK modem as well as HART + USB,
PROFIBUS + remote I/O, or HART Multiplexer.
Change from two to one column

TTX300 | COM/TTX300/HART-EN Rev. A 5


3.2 HART variables

Device Current Out


Variables Limits
Transducer Mapping 20 mA
R. J. Sensor 1
COMP Sensor 2 PV
Elec. temp. HART lout
Sensor 1
S1 elec.
LIN
S2 elec.
SV
S2 - S1 4 mA
Sensor 2 CALC S1 - S2 TV
Mean Value QV Range

A10262

Fig. 2

This figure illustrates how the measurement value is processed from the sensor input right through to the transmitter's current
output.
Change from one to two columns

As well as providing access to parameters and diagnostic Only the PV is mapped onto the current output, which means
data, a HART device has up to 4 dynamic variables, which can that it has an additional parameter in the form of the mapping
be read out by means of a command. Depending on the range.
configuration, the following measurement values are available
internally on the TTX300: In HART rev. 7 and above, it is also possible to access the
— Sensor 1 (temperature, resistance, voltage) status information on each of the aforementioned dynamic
— Sensor 2 (temperature, resistance, voltage) variables. See also the 4.6 "Upgrades for HART protocol rev. 7
— Difference between sensor 1 and sensor 2 (temperature, and above" on page 10 section.
resistance, voltage)
— Difference between sensor 2 and sensor 1 (temperature, NOTE
resistance, voltage) If the configuration is changed (by assigning variables), you
— Sensor 1 and sensor 2 redundancy (temperature, will need to check how the measurement value is
resistance, voltage) subsequently processed in the higher-level control system
— Average value of sensor 1 and sensor 2 (temperature, and make any necessary adjustments.
resistance, voltage)
— Electrical measured value, sensor 1 (resistance, voltage) With conventional 4 ... 20 mA operation, the PV is available
— Electrical measured value, sensor 2 (resistance, voltage) indirectly via the current output. Modern remote I/O systems
— Electronic unit temperature (temperature) (such as the ABB S800 / S900) also allow cyclic access to all
the subsidiary variables (SV, TV and QV). This enables support
The configuration functions in the EDD and DTM allow you to for more complex applications for which a measuring point
select up to 4 variables and assign them to the dynamic HART has to provide more information (e.g. absolute and differential
variables: temperatures), or cost-effective processing of two sensor
— Primary Variable, PV signals with a single transmitter.
— Secondary Variable, SV
— Tertiary Variable, TV
— Quarternary Variable, QV
Change from two to one column

6 COM/TTX300/HART-EN Rev. A | TTX300


4 Parameter descriptions
NOTE
Safety check is performed in accordance with the SIL Safety Instructions based on the SM/TTX200/TTX300/SIL document.

4.1 Identify

Parameter [DE] Parameter [EN] Description Safety instructions


Messstellenkennzeichen / Name TAG Measuring point name, 8 characters. The name that is
selected should be unique within the system.
Schreibschutz Write Protection All device parameters are write-protected. To unlock Must be locked to ensure safety
them, enter code 0110. Codes ≠ 0110 will lock the function.
device.
Softwareversion Software Revision Transmitter's firmware version in accordance with Check that the version is correct on
NAMUR recommendation, in the format XX.YY.ZZ. This the basis of the data sheet or
information can also be found on the transmitter's certificate.
name plate.
Hardwareversion Hardware Revision Transmitter's hardware version in accordance with Check that the version is correct on
NAMUR recommendation, in the format XX.YY. This the basis of the data sheet or
information can also be found on the transmitter's certificate.
name plate.
Hersteller Manufacturer Device manufacturer (ABB)
Gerätetyp Type Device type (TTX300 series)
Seriennummer Serial Number Serial number (transmitter assembly number). This
information can also be found on the transmitter's
name plate.
Beschreibung Description A user-defined text (optional) that is stored in the
device. E.g. additional information about the measuring
point.
Nachricht Message A user-defined text (optional) that is stored in the
device. E.g. information for maintenance personnel.

4.2 Temperature measurement

Parameter [DE] Parameter [EN] Description Safety instructions


Messart Measurement Mode PV measurement mode. Choice depends on the Check safety function
selections for
sensor types 1 / 2:
— Sensor 1
— Sensor 2
— Difference between sensor 1 and sensor 2
— Difference between sensor 2 and sensor 1
— Average of sensor 1 and sensor 2
— Sensor 1 and sensor 2 redundancy
— Electr. sensor 1
(sensor input signal in Ω or mV)
— Electr. sensor 2
(sensor input signal in Ω or mV)
— Electronic unit temperature
The setting specifies which measurement variable
affects the current output
(HART = "Primary Variable", PV).

TTX300 | COM/TTX300/HART-EN Rev. A 7


Parameter [DE] Parameter [EN] Description Safety instructions
Sensor 1 / 2: Sensortyp Sensor 1 / 2: Sensor type setting for sensor 1 / 2. All sensors Check safety function
Sensor Type specified on the data sheet or in the manual are
supported.
Sensor 1 / 2: Messbereich Sensor 1 / 2: Range Physical measuring range for sensor 1 / 2, depending
on type of sensor selected.
Sensor 1 / 2: Anschluss Sensor 1 / 2: Type of sensor connection (two-wire, three-wire, or Check safety function
Connection four-wire circuit).
Sensor 1 / 2: Vergleichstelle Sensor 1 / 2: Type of reference junction: Check safety function
Cold Junction No reference No compensation
Compensation (not used)

Internal (internal) Internal (measured inside


transmitter)
External (external) Stabilized externally using a
thermostat
Sensor 1 Measured using a
resistance thermometer on
channel 1 (only configurable
on channel 2)
Sensor 1 / 2: Sensor 1 / 2: The temperature of an externally stabilized reference Check safety function
Temperatur feste VG Temperature fixed junction is entered here in °C.
CJ
Sensor 1 / 2: Leitungswiderstand Sensor 1 / 2: Line resistance for sensor 1 / 2 if a resistance Check safety function
Line Resistance thermometer is being used or if the sensor type
selected is linear resistance measurement with a two-
wire circuit.
CvD Datensatz 1 ... 5 CvD Dataset 1 ... 5 Callendar-Van Dusen data set 1 / 2. Check safety function
Coefficients R0, A, B, C
Anwenderspezifische Kennlinie Fixed Point 1 ... 5 User-specific characteristic involving 32 pairs of Check safety function
1 ... 5 reference points (X1..32, Y1..32), strictly monotonic
increasing or decreasing.
Firmware version 01.01.03 and higher
Driftüberwachung: aktiv Drift Monitoring Activates sensor drift monitoring. Check safety function
active
Driftüberwachung: max. Max Sensor Value at which sensor drift is signaled if overshoot lasts Check safety function
Sensordifferenz Difference longer than the limit time period.
Driftüberwachung: Limit / Inhibit Time Time period during which the max. sensor difference is Check safety function
Sensordrift exceeded before sensor drift is signaled.
Limit-Zeitspanne

8 COM/TTX300/HART-EN Rev. A | TTX300


4.3 Current output / mapping of measuring range

Parameter [DE] Parameter [EN] Description Safety instructions


Einheit Unit For selecting the unit of measurement to be used for the PV Check safety function
measurement value (°C, °F, °R, K, user, mV, Ω, mA). This setting
also determines dependent parameters such as pressure sensor
limit values.
Messanfang Range Start Determines the sensor's lower range value (equivalent to 4 mA). Check safety function
Messende Range End Determines the sensor's upper range value (equivalent to 20 mA). Check safety function
Dämpfung Damping Damping of the primary variable using a first-order filter element. Check safety function
HI_HI Grenze HI_HI Limit Diagnostics are triggered if the value of the primary variable (PV)
exceeds this limit value.
HI Grenze HI Limit Diagnostics are triggered if the value of the primary variable (PV)
exceeds this limit value. The bit set within the diagnostics data
remains set even if the HI_HI limit is overshot.
LO Grenze LO Limit Diagnostics are triggered if the value of the primary variable (PV)
drops below this limit value. The bit set within the diagnostics
data remains set even if the LO_LO limit is undershot.
LO_LO Grenze LO_LO Limit Diagnostics are triggered if the value of the primary variable (PV)
drops below this limit value.
Verhalten bei Fehler Reaction on Failure Overrange Generates a high alarm signal in the event of a Check safety function
sensor or device error; can be configured from
20.0 ... 23.6 mA.
underranging Generates a low alarm signal in the event of a
sensor or device error; can be configured from
3.5 ... 4.0 mA.
Firmware version 01.01.03 and higher
Verhalten bei Wartungsbedarf Reaction on Analog alarm pulse signaling with configurable pulse width when Check safety function
Maintenance sensor maintenance is required (e.g. failure of a sensor in
required redundancy mode or overshooting of max. sensor drift difference).
— Off
— Pulse width: > 0 ... 59.5 seconds
— Continuous

The primary variable (PV) is mapped onto the current output linearly and within the range of 4 … 20 mA. The mapping limits
should be selected in accordance with the application concerned and do not have to lie completely within the sensor's physical
measuring range. It is also possible to assign warning and alarm limits to the PV. These are relevant from the point of
diagnostics, but will not affect the current output in any way.

lout

20 mA

4 mA

LO_LO LO HI HI_HI PV [°C]

Scalling range current out

Sensor range
A11131
Fig. 3

TTX300 | COM/TTX300/HART-EN Rev. A 9


4.4 Communication / HART

Parameter [DE] Parameter [EN] Description Safety instructions


HART TAG HART TAG Defines the HART TAG name. 8 characters,
alphanumeric
Addresse (Multidrop) Address (Multidrop) Specifies the communication type: Check safety function
Address = 0 corresponds to HART "Point-to-point
communication" operating mode, output signal
4 ... 20 mA.
Address = 1 ... 15 corresponds to HART "Multidrop"
operating mode, output signal a constant 3.6 mA.
Only the digital HART measured values are available.

4.5 Miscellaneous

Parameter [DE] Parameter [EN] Description Safety instructions


Werksreset Factory Reset Configuration data is reset to the factory setting: Safety function for potential risk. All
Pt100 three-wire circuit, 0 ... 100 °C, damping off, configuration and calibration data is
overrange. reset to the factory setting.
Calibration data (Trim high/low) and DAC adjustment
values are also reset to their factory settings.
Gerätereset Reset / Warm Start The device performs a restart (warm start). Parameters
and configuration data remain unchanged.

4.6 Upgrades for HART protocol rev. 7 and above


The following additional functions are supported in HART protocol rev. 7 and above:
— Reading of dynamic variables with additional status information.
— Reading and writing of the LONG TAG (32 bytes) for unambiguous device identification, even in large installations.
— Easier location of a device in the installation. The message "Squawk" is shown on the display of the device you are
searching for.
— Locking of changes to a device via the "Lock Device" HART command.
Change from one to two columns

10 COM/TTX300/HART-EN Rev. A | TTX300


5 Double sensor input functionality / "Maintenance required" diagnostic information can be signaled
double sensor mode in accordance with NE107 during normal operation with a
4 … 20 mA analog output by superimposing pulses.
5.1 2-HART measurement signals Depending on the fault signaling, positive 22 mA pulses are
As explained in the "Electrical connections" section of the superimposed on the 4 ... 20 mA signal in the case of a 22 mA
operating instruction, equivalent resistance sensors or overrange configuration and negative 3.6 mA pulses are
thermocouple sensors (or a combination of the two) can be imposed in the case of a 3.6 mA underrange configuration.
connected to the transmitter inputs. The following values can be configured via pulse width
Remote I/O systems such as the ABB S900 read out these parameters:
HART variables on a cyclic basis and provide them to the — A pulse width of 0.5 … 59.5 seconds (0.5 second
control system in the form of cyclic process data. increment)
The 4 … 20 mA analog output maps one sensor value only. — Continuous pulse
Users can choose to map sensor value 1 or sensor value 2, — No diagnosis notice via pulse on the analog output
the difference between the two, or the average. The value to
be mapped is specified during configuration of the transmitter, The stipulated pulse width refresh rate is 60 seconds.
e.g. via LCD indicator in the "Config Device" menu /
"Input/Output Assignment" submenu. Example:
If a pulse width of 10 seconds is set, the pulse width refresh
5.2 Redundancy / sensor backup rate of 60 seconds means that, after a 10-second pulse
Use two sensors and sensor redundancy mode to increase diagnostic alarm signal of e.g. 22 mA, the normal temperature
system uptime. signal of 4 … 20 mA is active at the output again for 50
If sensor 1 fails, the output signal switches to sensor 2 seconds.
seamlessly within the cyclic refresh rate. The next cycle begins with a 10-second diagnostic alarm
In addition, a "Maintenance required / Sensor wire break" signal and the standard 4 … 20 mA temperature signal is then
HART diagnosis notice is generated in accordance with Namur displayed at the output again for 50 seconds.
NE107.
If redundant sensor 2 fails, this merely generates a HART
signal diagnosis notice.
To minimize the effect on the output signal and increase
accuracy in case of a sensor wire break, the average of both
sensors is mapped to the analog output in redundancy mode
as long as both sensors are available.
Sensor or device failure fault signaling at the analog output
signal as required by Namur NE43 / NE107 ensures that the
transmitter is capable of signaling "Maintenance required"
diagnostic information via both a HART signal and an analog
signal, using overranging (22 mA) and underranging (3.6 mA).
Change from two to one column

TTX300 | COM/TTX300/HART-EN Rev. A 11


Grad / °C 4 Ia / mA

100 10 s 22 mA

90 c 60 s 60 s 60 s 60 s 20 mA
a b
50 s 50 s 50 s 50 s
80 12 mA

70

60

50

40

30 5

20

10 4 mA

0 min
0 1 2 3 4 5 6 7 8 9 10
A11132

Fig. 4: Alarm pulse signaling in redundancy mode for failure of the temperature progression for sensor 2
1 Temperature progression, sensor 1 ----------- 2 Temperature progression, sensor 2 3 4 … 20 mA output signal
4 Alarm, pulse1) 5 Break, temperature progression 2

1) Pulse alarm: off, on  configurable pulse width, continuous pulse

Change from one to two columns

5.3 Sensor drift monitoring To activate sensor drift monitoring, the transmitter must first
When two sensors are connected, an optional sensor drift be configured for the sensor types referred to above. The
monitoring function can be activated in redundancy mode, in maximum permissible sensor deviation must then be
2-HART measurement signal mode and during averaging. configured, e.g. max. 1 K.
Sensor drift monitoring and analog diagnostic signaling
(described in the previous section) can only be activated and Since sensor response times may be marginally different, it is
configured using a TTX300 DTM file or EDD-based tools. then necessary to set a limit time period during which the
sensor deviation must be continuously larger than the
Sensor drift monitoring can be activated with the following two maximum sensor drift differential value defined previously (1 K,
sensor types: for example).
— 2 x resistance thermometer (RTD), two-wire circuit If the transmitter records a greater sensor deviation during the
— 2 x resistance thermometer (RTD), three-wire circuit defined time period, a "Maintenance required" HART
— 2 x resistor (potentiometer), two-wire circuit diagnostic message is generated in accordance with NE107.
— 2 x resistor (potentiometer), three-wire circuit In addition, the device status "M" and the diagnosis code are
— 2 x thermocouple displayed below the measured value on the LCD indicator, to
— 2 x voltage indicate that the "Maintenance required" message has been
— 1 x resistance thermometer (RTD), two-wire circuit, and output.
1 x thermocouple "Maintenance required" diagnostic information concerning
— 1 x resistance thermometer (RTD), three-wire circuit, and sensor drift monitoring can also be superimposed on the 4 …
1 x thermocouple 20 mA signal as a pulse alarm signal and signaled in the same
— 1 x resistance thermometer (RTD), four-wire circuit, and way as if a sensor failure had occurred in redundancy mode
1 x thermocouple (see also the 5.2 "Redundancy / sensor backup" on page 11
section).

12 COM/TTX300/HART-EN Rev. A | TTX300


If drift monitoring is used for the same types of sensor (2 x The measured value from channel 1 (Pt100) is mapped to the
Pt100 or 2 x thermocouple), the average value calculated from transmitter output as a process variable.
the two sensors is mapped to the transmitter's output signal
as a process variable in redundancy mode. NOTE
If a thermocouple is used for Pt100 drift monitoring, the Pt100 Before configuring the maximum permissible sensor
sensor must be connected to channel 1 and the thermocouple deviation for drift detection, it is advisable to balance sensor
to channel 2. channel 2 with the value of sensor channel 1.

Change from two to one column

Grad / °C Ia / mA

100

90

80

5
70 4
a b
60 22 mA

1 20 mA
50
2 min
40 12 mA
60 s
30 c
f

20

10 4 mA

0 min
0 1 2 3 4 5 6 7 8 9 10
A11133

Fig. 5: Alarm pulse signaling for sensor drift overshoot


1 Temperature progression, sensor 1 ---------- 2 Temperature progression, sensor 2 3 4 … 20 mA output signal
4 Max. sensor drift difference (e.g. Δ > 1 °C) 5 Alarm, pulse1) f Sensor drift monitoring time period (e.g. 2 min.)

1) Pulse alarm: off, on  configurable pulse width, continuous pulse


Change from one to two columns

TTX300 | COM/TTX300/HART-EN Rev. A 13


6 Sensor error adjustment Prior to analog compensation, it is necessary to determine the
loop current values based on iterative entry of current values in
For sensor error adjustment, the sensor connected to the simulation mode; the higher-level I/O system displays exactly
transmitter must be brought to the lower range limit value 4000 mA or the lower range limit temperature, and 20000 mA
temperature / Trim low using a water quench or oven. It is or the upper range limit temperature. The current loop values
important to make sure the temperature is balanced and must be measured using an ammeter and recorded.
stable. The lower range limit value or 4000 mA +/- 16 μA must then
In the DTM, check that the proper adjustment temperature has be simulated in D/A analog output compensation mode using
been entered for the sensor before adjusting it. sensor simulation. Following this, the iteratively calculated
Based on the comparison of the adjustment temperature current value at which the higher-level system displays exactly
entered (setpoints) with the digital temperature measured by 4000 mA or the lower range limit value must be entered as a
the transmitter, the transmitter calculates the temperature compensation value. Proceed in a similar manner for the URL
deviation resulting from the sensor error. or 20000 mA.
During single-point adjustment, this calculated temperature The disadvantage of D/A analog output compensation is that
deviation results in an offset shift of the linear characteristic the HART signal present without correction prior to D/A
output by the linearization module. conversion differs from the analog output signal after D/A
Sensor error two-point adjustment results in a change to the conversion due to the incoming error correction of the higher-
offset and gradient due to the linear temperature value level system.
characteristic output by the linearization module.
A pure sensor offset error must be corrected using the "Trim
low" calibration function. By contrast, if the error is not a pure
sensor offset error, it can only be corrected using two-point
adjustment or two-point calibration. 8 Special functions
8.1 Output signal simulation
When output signal simulation mode is activated in the
TTX300's DTM via the path <Device> <Simulation>
7 D/A analog output balancing <Simulation>, it is possible to simulate an output signal in the
(4 mA and 20 mA trim) 3.5 ... 23.6 mA range regardless of the sensor value.

Output compensation is used to compensate for errors in the 8.2 Device reset
current input of the higher-level system. In the DTM, a device restart can be triggered via the path
Analog output compensation for the transmitter can be used <Device> <Tools> <Device Reset>. The type of reset that
to modify the loop current so that the desired value is follows is comparable with switching the supply voltage off
displayed in the higher-level system. and on again.
Error compensation for the higher-level system is possible at
the lower range value with 4 mA and/or 20 mA (single-point 8.3 Factory reset
error correction: offset or two-point error correction: offset + The DTM path <Device> <Tools> <Reset to Factory Setting>
linear gradient). can be used to restore the TTX300 configuration data to the
D/A analog output balancing can be accessed in the TTX300 factory setting (Pt100, three-wire circuit, 0 ... 100 °C, damping
DTM via the path <Device> <Calibration> <Output Balancing>. off, and overrange).

NOTE
The adjustment data (Trim high / low) and D/A compensation
values are also reset to their factory settings.

Trademarks
® HART is a registered trademark of FieldComm Group, Austin, Texas,

Change from two to one column


USA

14 COM/TTX300/HART-EN Rev. A | TTX300


Notes

TTX300 | COM/TTX300/HART-EN Rev. A 15


Contact us

COM/TTX300/HART-EN Rev. A 04.2015


ABB Limited Note
We reserve the right to make technical changes or
Process Automation
modify the contents of this document without prior
Howard Road, St. Neots notice. With regard to purchase orders, the agreed
Cambridgeshire, PE19 8EU particulars shall prevail. ABB does not accept any
UK responsibility whatsoever for potential errors or
possible lack of information in this document.
Tel: +44 (0) 870 600 6122
Fax: +44 (0)1480 213 339 We reserve all rights in this document and in the
Mail: enquires.mp.uk@gb.abb.com subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
utilization of its contents - in whole or in parts – is
ABB Inc.
forbidden without prior written consent of ABB.
Process Automation
125 E. County Line Road Copyright© 2015 ABB
Warminster PA 18974 All rights reserved
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183 3KXT200004R4001
Translation of the original instruction

ABB Automation Products GmbH


Process Automation
Schillerstr. 72
32425 Minden
Germany
Tel: +49 571 830-0
Fax: +49 571 830-1806

www.abb.com/temperature

You might also like