Models:
XHBQ(X)-D40GF
Attention
Please read this manual carefully before using the equipment
Beijing Holtop Artificial Environment Technology Co., Ltd.
Contents
Safety Considerations------------------------------------------------------------3,4
Unit Specifications----------------------------------------------------------------- 5
Dimensioned Drawings------------------------------------------------------------6
Installation Considerations------------------------------------------------------7,8
Electrical Installation--------------------------------------------------------------9
Wiring Diagrams------------------------------------------------------------------10
Commissioning Information------------------------------------------------------11
Controller Instruction-------------------------------------------------------------12
Maintenance ----------------------------------------------------------------------13
Safety Considerations
Please read the following safety instructions before installation. And ensure that the unit is installed
correctly.
Please observe all instruction in order to avoid any injury or damage to equipment or property.
Safety attentions
The following symbols indicate potential levels of caution.
Power cable and wires must be installed by To avoid condensation, insulation should be
a qualified electrical engineer. Improper fitted to fresh air ducts. Other ducting may
connection can cause over heating. Fire and also require insulation depending on dew
loss of efficiency. point conditions.
Insulation between the metal ducting and The cover of wiring box must be pressed
wall penetration must be installed if the down and closed to avoid dust and dirt
ducting penetrates metal wall cladding, to entering. Excess dust and dirt can cause
avoid risk of electric shock or current overheating of terminals and result in fire or
leakage. electric shock.
Use only approved installation hardware
and accessories. Failure to observe can Where the unit is positioned, at high level in
result in fire risk, electric shock and a hot humid situation. Please ensure
equipment failure sufficient ventilation is available
The outdoor ducts must be installed facing Correctly sized MCB must be fitted to the
downwards to avoid rain water entering. unit suitable earth leakage protection
Improper installation can cause water should also be installed to avoid risk of
leakage. electric shock or fire.
3
Safety Considerations
Safety Considerations
Acidic or alkali environments can cause Rated supply voltage must be maintained,
poisoning or a fire otherwise this may cause fire.
4
Specifications
5
Dimensioned Drawings
Wiring
接线盒
box
污风入口
污风出口
RA
SA flange size
出风口法兰尺寸 OA flange size
进风口法兰尺寸
EA
新风出口
新风入口
OA
OA
Model A B E F G I J K V V1 V2 W W1 W2 S S1 S2 U U1 U2 M N
XHBX(Q)-D40GF 2400 1700 2450 1660 900 830 395 320 350 375 400 500 525 550 500 525 550 600 625 650 14 16
Installation Considerations
Protect the unit to avoid dust or other obstructions entering the unit and accessories during installation,
or whilst in storage on site. Service ports should be installed to allow access for filter maintenance.
RA SA
EA SA
6
Installation Considerations
Installation Diagram
Fresh Air Duct
Supply Air
Return Air
Exhaust Duct
Exhaust Air Out
Fresh Air In
Return Air Supply Air
Insulation Discharge Duct
Physical Installation
1.Installer to prepare suitable threaded hangers with adjustable nuts and gaskets.
2.Install as shown by the image above. Installation must be level and securely fastened.
3.Failure to observe proper fixing could result in injury, equipment damage and excessive vibration.
Uneven installation will also effect damper operation.
4.The outlet of water drain should use the U shape trap
Nut
Gasket
Suspending Screw Pole
Suspending Part
Gasket
(Φ10-Φ12)
Nut
Ducting
1. Connection of unit vents and ducts should be taped or sealed to prevent air leakage, and should
comply to relevant guidelines and regulations.
2. The two outdoor vents should face downward toward the outside to prevent any rain water ingress.
(angle 1/100 1/50).
3. Insulation must be with the two ducts outside to prevent condensation.
Gradient1/100-1/50
坡度1/100-1/50
7
Installation Considerations
1. Be sure the ceiling height is no less than the Figures in above table B column.
2. Unit must not be installed close to boiler flues.
3. Following phenomenon should be avoided in the ducting installation.
As shown by drawing below, unit will produce dew or frost when saturation curve is formed from A to C.
Use pre-heater to ensure conditions are kept to right of the curve (B to B',to move C to C) to prevent
condensation or frost formation.
8. To avoid the outdoor exhaust air cycling back to indoor, the distance between the two vents installed
on the outside wall should be over 1000mm.
9.If heater is equipped to the unit, operation of heater should be synchronous with the unit, so that the
heater starts to work only when unit starts.
10.Duct muffler may be considered if user wants indoor noise to be minimized.
8
Electrical Installation
Power must be isolated during installation and before maintenance to avoid injury by electric shock. The
specifications of cables must strictly match the requirements, otherwise it may cause performance
failure and danger of electric shock or fire.
Power supply is AC 380V/50HZ/3 Phase. Open the cover of electrical box, connect the 2 wires (L/N/) to
the terminals and connect the cable of the control panel to the board according to the wiring diagram,
and join the control panel to the cable.
HDK-
XHBX(Q)-D40GF 5×4mm2 4×1.0mm2 16A 3A
09D
We do not accept any liability for any problems caused by the user’s self and non-authorized re-
engineering to the electrical and control systems.
9
Wiring Diagrams
XHBQ(X)-D40GF
Signal from
controller
Red
BLK
Org
W
N SA EA
L
Controller
10
Commissioning and Features
1. Check the cable and wire connections and commissioning.
2. XHBQ(X)-D40GF, please turn it on and make the trial operation one by one, and check the airflow
status.
3. It should be wiring fault if trial operation is abnormal. Shut down the appropriative breaker to re-
wire.
Loose or incorrect wiring connection can Don’t put fingers or objects into vents of
cause explosion or fire when the unit starts fresh air or exhaust air supply. Injury may
to work. Use only rated power voltage. be caused by the rotation of the impeller.
Don’t install, move or re-install the unit by Don’t change, disassemble or repair the
yourself. Improper action may cause unit unit by yourself. Improper action may cause
instability, electric shock or fire. electric shock or fire.
Running the unit continuously in an abnormal
status may cause failure, electric shock or Switch off the power and breaker when you
fire. clean the exchanger.
Features
1. Energy saving
Efficiently recover energy from air exchange (fresh air load), save cost on air conditioning.
2. Less equipment
Makes lower capacity air conditioner possible due to the energy saving.
3. Humidity adjustment
-In cooling, remove humidity of outdoor air and discharge fresh air with similar humidity to indoor.
-In heating, convert dry outdoor air to humidity and discharge fresh air with similar humidity to
indoor.
4. Comfort
Less temperature fluctuation from stable air exchange (exhaust and supply synchronously) in a close
room.
5. Quietness
Duct and the exchanger are sound-proof. They prevent noises between indoor and outdoor, which
keeps the public environment quite.
11
Controller Instruction
The control panel is sent together with the heat recovery ventilator, the body of which can be concealed
in the wall, and panel is exposed outside. User should prepare the cables, and the cables on the control
is for commissioning use.
Operation instructions
HDK-09D
ON/OFF:press button “ ”once for start, twice for stop. All settings are kept before it’s turning off.
Controller functions: It can control the supply fan and exhaust fan individually. Displaying the
indoor temperature, the status of supply fan and exhaust fan and the speed.
HDK-09D:press button“ ”once,and the lower sign“ ”begin to flash. At this time,
press button“▼”, the lower “ ”will disappear and the supply fan stops running; press button
“▲”, the lower “ ”will appear and the supply fan starts running. Press button“ ”one more
time, and the upper sign“ ” begin to flash. At this time, press button“▼”, the “ ”
will disappear and the exhaust fan stops running; press button“▲”, the “ ”will appear and
the exhaust fan starts running.
Press button“ ”to confirm the setting or wait for 5 seconds then will confirm automatically. After
that the sign“ ”will not flash any more.
12
Maintenance
Power must be isolated before installation and maintenance to avoid injury or electricsshock. Supply
power cables, main circuit breaker and earth leakage protection, must comply with national regulations.
Failure to observe could cause unit failure, electric shock or fire.
Standard filtration is supplied with this unit and must be used. Dust and dirt can accumulate in the heat
exchanger if filters are removed. (This can lead to failure or decreased performance). To ensure efficient
operation, regular cleaning or replacement of filters is required. Filter maintenance frequency will
depend on working environment and unit running time.
Fixed Part
Service Board
Cleaning the filter
Failure diagnose
User can use the unit after trial operation. Before contacting us, you can make self trouble shooting
following below chart in case of any failure.
1. Guarantee power is on
1. No electricity 2. Connect the breaker
Unit doesn’t work
2. Protection breaker is cut
13
Beijing Holtop Artificial Environment Technology Co., Ltd
Factory address: No. 158 Hanjiachuan Road, Haidian
District, Beijing, China